Cascade Sequencer. Control Installation and Operation Instructions. Infinite Energy Boiler Manual. Also read and follow: CS-IOM-1

Similar documents
TABLE B Remote Wire Connection

Multi Boiler Guide. Kit #

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

PROGRAMMABLE 7-DAY THERMOSTAT

MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS

MODEL AC-SCC-5 INSTALLATION, OPERATION & MAINTENANCE MANUAL

B-40/B-41 Modulating Temperature Controller

MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS

prestige Control Application Supplement - ACVMax

TABLE B Remote Wire Connection

Control Application. Supplement - ACVMax

Service Manual Models:

SSIC INSTALLATION, OPERATION & MAINTENANCE MANUAL

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date:

INSTALLATION AND OPERATION MANUAL

prestige Control Application Supplement - TriMax

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

prestige Control Application Supplement - TriMax

CONVERSION TO PROPANE MANUAL M-Series Condensing Boiler. Wall-Mounted, Gas-Fired Boiler

Carbon Monoxide Transmitter

NR-20DU. Keep this manual near this remote controller for future reference whenever maintenance or service is required.

PEERLESS PUREFIRE Installation, Operation, and Maintenance Instructions Supplement - PF-460 NOTICE. Exhaust Vent/Air Intake Size

Service Manual Models:

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

ENVI Boiler Controller

PROGRAMMABLE 7-DAY RF THERMOSTAT

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

RK-HC-04 M2A Transmitter Operator s Manual

DOMESTIC HOT WATER Follow operational sequence

Model 60200FR Gas Primary Control Data Sheet

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ...

Product Manual SZ1009

prestige Control Application Supplement - Type 5 MCBA WARNING

CONDENSING, MODULATING, HOT WATER SUPPLY, POOL, AND HYDRONIC HEATING BOILERS

- Data Brochure Steam Control 279

ENERGY 200 Electronic Control for mono & bi- Compressor CHILLERS. User Manual

IMAX XTRA EL. 715kW FLOOR STANDING CONDENSING FEATURES AND BENEFITS

FXLF-9. High Efficiency Water Heaters and Boilers

K-Controller Brochure.qxp_ Controller Brochure 2/27/17 3:03 PM Page 4 Versa IC Platform

Models CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER

Service Manual Models:

BGH Series Hot Surface Ignition Control

USER'S INFORMATION MANUAL

RK-04 M2 Transmitter Operator s Manual

FXLF-4. High Efficiency Water Heaters and Boilers

Domestic Hot Water Heaters and Boilers FTIIIC-6

FTIIIC-10. Domestic Hot Water Heaters and Boilers

ECL Comfort 110, application 116

USER'S INFORMATION MANUAL

Installation & Operation Manual

- Data Brochure Universal Reset Module 422

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

Installation & Operation Manual

Service Manual. w/con X US Interface Models: WARNING

Now Available with PVC & Polypropylene Vent Configurations

Stainless Steel Condensing Boiler Connection Instructions To Additional Heating Devices

LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS

- Data Brochure Universal Reset Module 423

Up to 94.6% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL CONDENSING BOILERS OPERATING CONTROL FEATURING A BUILT-IN CASCADING SEQUENCER

- Data Brochure Boiler Control 274

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

USER'S INFORMATION MANUAL

Service Manual Models: Series 100 & 101

Copper-fin II/IIE Boiler and Water Heater Service Manual Models:

STREBEL S-CB + Cascade Kits

Highlights MBH 95% efficiency ENERGY STAR Qualified Low NOx emissions Space-saving design. 95% Efficient. Modulating Technology

Installation Guide. ECL Comfort 210, application A Table of Contents

Installation & User s Instructions

Installation Guide. ECL Comfort 310, application A Table of Contents

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

EW 40 Wireless Fan Control

Service Manual Models:

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

SUPPLY TO CENTRAL HEATING SYSTEM SUPPLY TO DHW TANK RETURN FROM CENTRAL HEATING SYSTEM RETURN FROM DHW TANK


Outdoor Armor Service Manual Models:

DOM-5. Domestic Hot Water Heaters & Boilers

Service Manual Models: 1.0, 1.3, and 1.5

VSL II QUICK START GUIDE

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater


User s Information Manual Lynx Direct-Vent Sealed Combustion Condensing Boiler Model LX-90, LX-120, LX-150

Installation & Operation Manual

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

Installation & Operation Manual

Electronic Pellet Burner Controller NPBC-V3M

Outdoor Reset IQ Option Card, p/n

CAUTION! Before putting the boiler into operation read this manual carefully. WARNING!

Product Manual SZ1022/SZ1031/SZ1035/

Operating Instructions. Temperature and Humidity EC Control. Model 35YV93

Safety & Installation Instructions

Project Name: Location: Engineer: Contractor: I. GENERAL

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8

prestige Control Application Supplement - Type 5 MCBA WARNING

Monitoring Software for NPBC-V3M-1 User Manual

Transcription:

CS-IOM-1 Cascade Sequencer Control Installation and Operation Instructions Also read and follow: Infinite Energy Boiler Manual Installer: Read the appliance Installation Manual, including this manual, before installing. Perform steps in the order given. User: This manual is for use only by a qualified heating installer. Qualified installer: qualified installer is an individual with specific, technical training in space heating systems, domestic hot water systems, fuel gas systems and electrical systems. This individual must have the legally required qualifications. Failure to comply with these provisions can cause a fire or explosion causing property damage, personal injury, or death. Installation and Alterations: Only a Qualified installer must carry out the installation and calibration of the heater. Never modify the heater or its flue gas carrying components in any way. This heater must be properly vented. Failure to follow these instructions could result in personal injury or death! Prior to any maintenance, disconnect the appliance s electrical power supply and shut off the inlet gas valve. Failure to follow these instructions could result in severe personal injury or death!

CONTENT OF THE KIT This kit is composed by: - a cascade sequencer code 62110095; - These instructions. 1 - INSTALLATION 1.1 - Piping Installation The 885HC cascade sequencer control shall be installed as shown in Figure 1.1. The master heater must be the closest to the low loss header because the master heater will be connected to the cascade general sensor. A maximum of 8 heaters can be connected in cascade. After installation, the heater nearest the low loss header will require hardware adjustments to become master heater #1 and the other heaters will require software changes to become dependent heaters. To do so, follow next sections. Figure 1.1 is only one example of a conceptual piping configuration; other piping configurations are possible. Contact your representative or manufacturer for optional configurations. Figure 1.1 - Conceptual Cascade Configuration 1 2 2 2 2 3 7 6 5 4 8 8 8 8 9 10 REF DESCRIPTION 1 885HC Cascade sequencer 2 Check valve 3 Cascade general sensor 4 Master heater #1 5 Dependent heater #2 6 Dependent heater #3 7 Dependent heater #4 up to #8 8 Heater pump 9 Low loss header 10 Heating pump 2

1.2 - Electrical Installation The electrical installation must be done as per Figure 1.2 or any other electrical installation suggested by the heater manufacturer. Figure 1.2 - Electrical installation MASTER HEATER (1) 3

Key of Figure 1.2 - Electrical Connections REF DESCRIPTION 101 Hot electrical supply 102 Neutral PE Ground 103 LWCO 104 LWCO 105 Heating pump Line (max 3A) 106 Heating pump Neutral (max 3A) Ground 107 DHW pump Line (max 3A) 108 DHW pump Neutral (max 3A) Ground 109 Alarm (NO) Volt free 110 Alarm (NO) Volt free 113 Local pump Line (max 3A) 114 Local pump Neutral (max 3A) Ground 8 Header sensor (HS) 9 Header sensor (HS) 10 Room thermostat (dry contact) 11 Room thermostat (dry contact) 12 Tank sensor 13 Tank sensor 14 Outdoor sensor (OS) 15 Outdoor sensor (OS) 16 Bus (Cascade sequencer) 17 Bus (Cascade sequencer) 18 RS 485 Modbus T+ 19 RS 485 Modbus T- 20 RS 485 Modbus GND 22 0-10 Vdc input (GND) 23 0-10 Vdc input (+) 24 Cascade header sensor 25 Cascade header sensor 28 Bus (cascade) 29 Bus (cascade) 30 Bus (Master) 31 Bus (Master) A Hot electrical supply B Neutral electrical supply C Ground Electrical supply D Low water cut OFF E Local pump (Max 3A) F Header temperature sensor G Room thermostat jumper H Cascate header temperature sensor L Ground M High Voltage terminals N 24 Vdc Voltage terminals P 885HC Cascade sequencer 4

1.3 - Adjust the S4 Switch on the 885IF Board 1. At top of heater remove junction box cover to gain access to the 885IF board (see Figure 1.3). 2. Move S4 switch from OFF position to ON position (see Figure 1.3). 3. Repeat the procedure on all heaters you want to connect in cascade. Figure 1.3-885IF Board and S4 Switch B S4 switch 1.4 - Adjust the Logic Address on Each Heater 1. On master heater #1, using two electrical wires each 2ft. long, connect the 885HC command to terminals 16 and 17. 2. Turn the on power to master heater #1. 3. Using the 885HC command set the Address to 1 (see Section 2.1). 4. Wait 2 minutes until the address is confirmed by # 1 appearing on the display. 5. Turn the power off to the master heater #1. 6. Disconnect the two wires from terminals 16 and 17 of the master heater #1. 7. Connect the two wires from the 885HC command to terminals 16 and 17 of the dependent heater #2. 8. Turn the power on to the dependent heater #2. 9. Using the 885HC command, set the Address to 2 (see Section 2.1); 10. Wait 2 minutes until the address is confirmed by #2 appearing on the display. 11. Turn the power off to the dependent heater #2. 12. Disconnect the two wires from terminals 16 and 17 of the dependent heater #2. 13. Repeat steps 7-12 for each dependent heater using progressive addresses 3, 4, 5, etc. 14. After setting the address on all dependent heaters return to master heater #1 and install the 885HC cascade sequencer to terminals 16 and 17. 020009.01.019 ON position OFF position (Must be on ON position) 1.5 - Adjust the 885HC Command for Boilers or Water Heaters 885HC command is set at the factory for boiler application, but not for water heater applications. When your system is in place, be sure parameters of the Sub Menu are set as shown in the list in Section 2.1. Select the column Boiler settings for boiler application; select the column Water Heater settings for water heater application. 1.6 - Adjust Parameter 2003 on All Dependent Heaters If parameter 2003 of the dependent heaters is not set to 0 (Zero), the cascade will not work. Follow section Installer s menu of the heater s installation manual to check this requirement on each dependent heater. 5

1.7 - Cascade General Settings for Parameters 3001, 3050, 2003 and S4 Switches Figure 1.4 - Model 199 Table Key of Figures 1.4, 1.5, 1.6 and 1.7 REF DESCRIPTION > MASTER Heater? 1 DEPENDENT Heater @ 2 DEPENDENT Heater up to 7 Figure 1.5 - Models 399 and 500 6

Figure 1.6 - Model 750 7

Figure 1.7 - Model 1000 8

2 - USE OF THE 885HC SEQUENCER Before any activity wait 40 seconds for communication between sequencer and heaters. The 885HC cascade sequencer has a basic screen shown below. Each button of the display controls a different function. Figure 2.1 - Control Panel By pressing button 10 of Figure 2.1 the bottom side of the display will change to show the status of the cascade. Display will show the number of heaters in the cascade, numbers 1, 2, and 3 (can be up to 8 ) and if they are in request for heating a flame icon appear below the number, or if they are in stand by a underscore icon appear below numbers. If there is an anomaly in the control a wrench icon will appear below numbers. 2.1 - Sub Menu Refer to Figure 2.1 when not otherwise specified. From the status screen the Sub menu can be entered by pressing and holding the HOME button (detail 9 ) for 8 seconds. When the Sub menu is displayed you can select a parameter by scrolling the list with the UP and DOWN buttons. When the parameter is selected, press the OK button (the dot of parameter selectioned will move on the value). Key of Figure 2.1 1 = Logic address 2 = Cascade setpoint 3 = Cascade temperature 4 = Status of the cascade 5 = OK button to confirm a change to a parameter 6 = Up button to scroll parameters or to increase a value 7 = Menu button to return to main menu 8 = Down button to scroll parameters or to decrease a value 9 = Home button to enter the menu 10 = Cascade button 11 = Outdoor temperature The parameter value will start to blinking. Now you can change the parameter value by using the UP and DOWN buttons. When the desired value is reached you can save it by pressing the OK button. Set each parameter following Figure 2.2 ( C) or 2.3 ( F). To leave the Sub Menu, press the Menu button. After any change, wait 40 seconds for screen to update status. Parameters displayed in this Sub Menu are showed in figures 2.2 and 2.3. 9

2.2 - Troubleshooting DESCRIPTION Display of the 885HC command does not light on Boiler address parameter is correctly set in all heaters but the same heaters reference is not shown on display. SOLUTION Check to be sure switch S4 is in the ON position (see Figure 1.3) Check that communication wires are correctly in place (see Figure 1.2 terminals 30 and 31 on master heaters and 28 and 29 on corresponding dependents. Dependent boiler seems to be operating independently. Verify that the unit is still present on the communication chain by looking at the sequencer's Cascade status menu. Changing the logic address on the heater, as per section 1.4, I m unable to see the update on the screen After changing the logic address, display can take up to 3 minutes to show the address on the screen. 10

Figure 2.2 - Parameters with C settings Parameter M.U. Range Factory settings Boiler settings Water Heater settings Customized value Boiler address / 0..16 0 0 - Stand Alone heater 1 - for Master 2 - for first dependent 3 - for second dependent 4 -...etc 1 - for Master 2 - for first dependent 3 - for second dependent 4 -...etc Temperature unit / C.. F / / / Cascade setpoint C 20..90 80 / / DHW ON..OFF / ON..OFF OFF ON only if you want to drive an indirect water heater Start delay time sec 0..1200 600 600 15 Stop delay time sec 0..1200 600 600 15 Start boiler diff C 8..20 2.5 2.5 2.5 Stop boiler diff C 8..32 1 1 1 Stop all boiler diff C 8..32 10 10 10 Max offset up C 8..28 10 10 10 Max offset down C 8..28 10 10 10 Rotation interval Days 1..10 5 5 5 P Value / 0..255 20 20 20 I Value / 0..255 120 120 120 D Value / 0..255 0 0 0 Slew rate / 1..255 5 5 5 System correction C 8..18 0 0 0 Mod delay factor min 0..60 4 4 0 OFF Figure 2.3 - Parameters with F settings Parameter M.U. Range Factory settings Boiler settings Water Heater settings Customized value Boiler address / 0..16 0 0 - Stand Alone heater 1 - for Master 2 - for first dependent 3 - for second dependent 4 -...etc 1 - for Master 2 - for first dependent 3 - for second dependent 4 -...etc Temperature unit / C.. F / / / Cascade setpoint F 68..194 140 140 140 DHW ON..OFF / ON..OFF OFF ON only if you want to drive an indirect water heater Start delay time sec 0..1200 600 600 15 Stop delay time sec 0..1200 600 600 15 Start boiler diff F 0,9..22,5 5 5 5 Stop boiler diff F 0..45 2 2 2 Stop all boiler diff F 0..45 18 18 18 Max offset up F 0..36 18 18 18 Max offset down F 0..36 18 18 18 Rotation interval Days 0..30 5 5 5 P Value / 0..255 20 20 20 I Value / 0..120 120 120 120 D Value / 0..255 0 0 0 Slew rate / 0..255 5 5 5 System correction F 0..18 0 0 0 Mod delay factor min 0..60 4 4 4 OFF 11

260 North Elm Street 7555 Tranmere Drive Westfield, MA 01085 Mississauga, Ontario L5S 1L4 Canada Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782 www.rbiwaterheaters.com