Installation instruction CTS 600 by Nilan VPL 15 VPL 15 Top VPL 25 Version: 5.02, 13-05-2011
Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Power supply... 4 Assembly of VPL 15/15T/25... 5 Condensation drain / water seal... 6 Ducting... 7 Heating surface, water... 8 Heating surface, electrical (retrofitting)... 10 Starting and set up of the CTS 600 control... 11 Starting... 11 Set up of the CTS 600 control... 11 Activating the service menu... 12 Heating surface... 13 Air exchange... 14 Defrost... 15 Temp. control... 16 Inlet control... 17 Room control... 18 Restart... 19 Preset... 20 Manual... 21 System dimension... 22 Accessories / spare parts... 23 Figure table Figure 1: CTS 600 control... 4 Figure 2: Mounting the VPL-Unit... 5 Figure 3: Condensation drain / water seal... 6 Figure 4: Insulation of ducting... 7 Figure 5: Connecting the heating surface, suggestion... 8 Figure 6: CTS 600 control... 11 Figure 7: Headlines in the servicemenu... 12 Figure 8: The "Heating surface" menu... 13 Figure 9: The "Air exchange" menu... 14 Figure 10: The "Defrost" menu... 15 Figure 11: The "Temp. control" menu... 16 Figure 12: The "Inlet control" menu... 17 Figure 13: The "Room control" menu... 18 Figure 14: The "Restart" menu... 19 Figure 15: The "Preset" menu... 20 Figure 16: The "Manual" menu... 21 Figure 17: System dimension... 22
Introduction Please control that the following documents have been delivered together with the unit: - Directions for assembly & use (this document) - CTS 600 directions - Electrical chart Should you have any questions on how to operate the system, contact your nearest Nilan dealer, who you can find at www.nilan.dk/dealers VPL 15/15T/25 is a ventilation unit with heat recovery. The unit can yield up to 325/700m 3 /h at 100Pa external back pressure. The unit can be equipped with different accessories e.g. hygrostat and filter box with pollen filter. Operating the unit is done with the CTS 600 control. The control has many functions such as menu based attendance, week programme, time controlled filter guard and adjustment of the velocity of the ventilator. (Directions for the CTS 600 control is described in another document delivered with the unit.) For accessories see page 23. We recommend that the system as well as the installation are adjusted/checked to ensure a healthy indoor climate and optimal operation. This document may be subject to change Side 3 of 23
Power supply Power supply including safety switch must be installed by an authorized electrician. The VPL 15/15T/25 unit must be connected according to the attached electrical chart. The unit is delivered with 1m test cable for the CTS 600 panel. The panel should be connected to the CTS 600 control in the unit with cable type 2x2x0.25mm 2 twisted in pairs. (Maximum length 50m). The CTS 600 panel must be placed dry and frost-proof. The panels integrated feeler prevents further cooling of the building if the primary heat-supply stops by stopping the ventilation if the panel feeler gets below a specific value. (Factory setting is 10 C; the value can be set from 1 C to 20 C.) Figure 1: CTS 600 control If a water post-heating element is installed, the control valve and circulation pump must be electronically connected as described in the provided wiring diagrams. This document may be subject to change Side 4 of 23
Assembly of VPL 15/15T/25 When mounting the VPL-unit future service and maintenance should be considered. There is required a minimum of open space in front and behind the unit of 600mm. The system s connection pieces and the pipes are connected with a flexible transition (flex pipes/sound flex pipes or the like). The system must be level due to the condense outlet. The condense outlet requires a clearance height of minimum 80-105 mm under the outlet connection piece. It is not necessary to re-insulate the system as it is delivered with a 20mm standard insulation. The system is low-noise and low-vibration. However, potential vibrations spreading from the system to the individual building parts must be taken into account. We recommend a minimum distance of 30 mm from building parts and other fixtures. To detach the system from the floor, we recommend that the system is placed on vibration absorbers as illustrated in figure 2 (See Accessories) 1 2 3 2 4 1: Vibration absorbers. 2: 22mm plywood/ chip board 3: Firm insulating batts 4: Wooden beam Figure 2: Mounting the VPL-Unit This document may be subject to change Side 5 of 23
Condensation drain / water seal The VPL unit is delivered with a 20mm condensation drain. (PVC, GF-fittings). The drain is placed under the discharge. The condensation drain should be carried with an even inclination of at least 1 cm per meter, frost-proof to the nearest outlet. The overflow from the safety valve should also be carried to the nearest outlet. To avoid frost problems it can be necessary to supply the condensation drain with a heating cable. It is the plumbers responsibility to secure the drain. When the system is running, there can be a vacuum of up to 500Pa (corresponding to 50mm water column) in the outlet. For this reason, the difference in height in the water seal must be minimum 50mm. This means that the first bend of the water seal must be at least twice as long in order for the system to be able to dispose of the condense water (see figure 3). The condensation drain must be airproof from the unit to the water seal in order for the condensation water to be let away from the unit. If the condensation drain is not airproof false air will be sucked in to the unit and the water will stay inside the unit. The water seal can dry out and avoid the water from running out of the unit. Therefore the water seal should be tested regularly and refilled with water if necessary. An elevated height of the water seal will reduce the need for refilling with water. Ø20 mm drain min. 50 mm. VPL min. 50 mm. min. 112,5 mm Figure 3: Condensation drain / water seal The water seal should be tested as described below. (the unit must be connected to the ducting and the front door should be closed): The condensation tray is filled with water and the unit is started at the highest ventilation step. The unit should run for a couple of minutes. Check that the condensation tray is empty when the test is finished. This document may be subject to change Side 6 of 23
Ducting We recommend that there are used ducts and fittings with rubber packing that meet sealing class B and that the connections between the unit and the ducting are made with 1 metre sound absorbing flexible transitions as regards sound reduction. The ducts should be shortened with a hacksaw or an angle grinder and laid out according to the working drawing. The ducts are typically laid out on the main beam of the truss frame and are secured with hole belts or they are being hanged in assembly belts. Please avoid any unnecessary area reductions and breaks of the ducting. The ducts should be insulated in some cases with the ordinary attic-insulation. All ducts should be insulated with 100mm mineral wool to avoid heat loss and condensation. This also applies for flexible transitions. It is recommended that the insulation is carried out with 2 layers of 50mm. If the ducts are laid out in an unheated room it will cause condensation problems if the unit are turned off for a longer period of time as the hot air from the heated room will rise to the ducts and cause condensation which can cause damp problems. Loft insulationmaterial Duct Granulate Figure 4: Insulation of ducting The discharge duct is leading the exhaust air away either above the roof or through the outer wall. It is important that the roof cowl has at least the same open space as the duct leading to the roof cowl. A reduction at this place will cause an unnecessary pressure drop which can lead to a reduced ventilation output. The holes for the inlet- and exhaust valves should be cut according to the mounting-frame for the prescribed valve. The frame for the valve must be secured with screws before placing the valve in the frame. The valves are placed in accordance with the size, construction and use of the room. As an example we would not recommend placing an inlet valve just above people with sedentary work because the inlet air in some cases would be experienced as a draught. This document may be subject to change Side 7 of 23
Heating surface, water Connecting the heating surface must be done by an authorized plumber. If the unit is placed outside or in a cold location the installation must frost secured. The heating unit is delivered as accessory and consists of: electrical box with LMC200-PCB, heating surface with temperature sensor T9 and frost-protection B3, actuator and regulating valve. The heating surface is to be installed in the inlet ducting just after the VPL unit. The heating surface must also be activated in the CTS 600 control as described on page 13. The mixing loop can be constructed as suggested below. The heating surface should be connected, scavenged and checked for any leakages before starting the unit. The dirt-catcher should be checked and cleaned after a thoroughly flushing of the system. 3 1 M 2 Heating surface Flow Air flow T9 Return B3 Note that the temperature sensor T9 and frost-protection B3 is placed at the heated side of the heating surface close to the return connection. See electrical chart. 1: Actuator and regulating valve: Danfoss AME 140/24V 0-10V signal, 2-way valve VZ2 Kv 0,4, (Nilan delivery) Kvs-value must be checked in accordance with supply. Differential pressure: 0,1 0,6bar There is calculated with a cooling of 20 C over the heating surface at a flow of 60 C. 2: Scavenging (not Nilan delivery) 3: Dirt-catcher (not Nilan delivery) Figure 5: Connecting the heating surface, suggestion This document may be subject to change Side 8 of 23
IMPORTANT regarding Danfoss Actuator type AME 140: Re-installing the actuator must be done as described below: 1. Disconnect the power supply and remove the cover of the actuator. 2. Liberate the gear by pressing down the button as the spindle is turned up (counter clockwise) 3. Re-install the actuator and turn on power. 4. DIP-switch nr. 1 should be moved to ON and then to. 5. The actuator is automatically calibrating for up to 6 minutes. (The LED is flashing when calibrating and is lit constantly when finished). 6. Re-install the cover of the actuator. The Danfoss Actuator type AME 140/24V should be placed in an environment of 0 C to 55 C. Electrical box with LMC200 PCB for heating surface: Power supply must be installed by an authorized electrician. The electrical box should be installed closed to the inlet branch of the unit. 230V power supply should be installed together with the ventilation unit. T9, temperature sensor of the heating surface, should be installed in the electrical box. T7, temperatur sensor of the inlet, should be let 3cm. into the inlet duct approximately 0,5m away from the ventilation unit. Danfoss Actuator should be connected to the clamps in the electrical box. B3 frost-protection should be connected to the CTS 600 PCB in the ventilation unit. See electrical chart. This document may be subject to change Side 9 of 23
Heating surface, electrical (retrofitting) Electrical heating surface should be installed in the ducting (Ø160/Ø200). When retrofitting an electrical heating surface it should be activated in the 600 control panel as described on page 15. Power supply must be installed by an authorized electrician. See electrical chart for the ventilation unit and electrical chart for LMC200 PCB A - H. This document may be subject to change Side 10 of 23
Starting and set up of the CTS 600 control Starting Before starting the VPL please check all functions as cooling, heating and heating surface if installed. Set up of the CTS 600 control In this passage we will go through the service menu of the CTS 600 control. For daily use of the CTS 600 control please see the CTS 600 directions. (delivered together with the VPL). Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on Figure 6: CTS 600 control This document may be subject to change Side 11 of 23
Activating the service menu Press q and at the same time for 10 seconds. The service menu is now available. Press q multiple times until the panel shows SERVICE. Press to enter the service menu. It is now possible to move around in the menu by using pq. The headlines of the service menu are shown below: SERVICE HEATING SURFACE Se side 13 AIR EXCHANGE Se side 14 DEFROST Se side 15 TEMP. Se side 16 Se side 17 ROOM Se side 18 Se side 19 PRESET Se side 20 MANUEL Se side 21 Figure 7: Headlines in the servicemenu This document may be subject to change Side 12 of 23
Heating surface The unit can be equipped with a heating surface. It is possible to retrofit a heating surface. The surface must be activated in the CTS 600 control in order to function together with the unit and for the frost-protection to be active. When installing a heating surface T7 is the temperature sensor in the inlet. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SELECT SURFACE WATERSUP AIR EXCHANGE DEFROST TEMP. ROOM KONTROL MANUEL DELAY 0 MIN Delay between start of ventilators and heating surface (0 60 minutes) SELECT WATERSUP SELECT EB SUP SELECT EL SUP SELECT Indstilling vælges ved anlæg uden eftervarmeflade Should be chosen when installing a heating surface for water. Controlled via 0-10 V signal LMC-200 PCB should be installed. Otherwise Alarm 90 slave I/O occurs. Should be chosen when installing an electrical heating surface, binary controlled (connection of steps via relays on CTS 600 PCB) Should be chosen when installing an electrical heating surface, controlled via 0-10 V signal LMC-200 PCB should be installed. Otherwise Alarm 90 slave I/O occurs. Figure 8: The "Heating surface" menu This document may be subject to change Side 13 of 23
Air exchange In the Air exchange menu it is possible to adjust 4 steps of ventilation speed (air volume). Inlet and exhaust is to be adjusted individually at each level. The inlet speed can be adjusted to a minimum and the exhaust can be adjusted to both a maximum and a minimum. It is possible to delay the starting of the fan in order to give time to the register to open. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HOTWATER AIR EXCHANGE MIN 0 The lowest permissible ventilation step for fresh air/inlet (0-2) DEFROST TEMP. EXHAUST MIN 1 EXHAUST MAX 4 The lowest permissible ventilation step for outlet/exhaust (1-2) ROOM >1< 23% >2< 40% The highest permissible ventilation step for outlet/exhaust (3-4). >3< 65% PRESET >4< 100% EXHAUST >1< 25% Each ventilation step can be set as a percentage of maximum fan speed. EXHAUST >2< 45% EXHAUST >3< 70% EXHAUST >4< 100% DELAY 2 MIN Delayed start of vent. This gives the valve time to open fully before the vents start (0-4 min.) Figure 9: The "Air exchange" menu This document may be subject to change Side 14 of 23
Defrost In the Defrost menu it is possible to chose how the unit should perform during defrosting of the evaporator in the exhaust. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE AIR EXCH LOW DEFROST TEMP. AIR EXCH USER AIR EXCH USER AIR EXCH Constant air flow during defrosting. ROOM Airflow stopped during defrosting (should be used when exhaust air temperature is less than 10 C). PRESET Figure 10: The "Defrost" menu This document may be subject to change Side 15 of 23
Temp. control In the Temp. control menu it is possible to chose a room temperature where the unit stops in order to avoid further cooling of the building if the primary heating shuts down. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST Indicates which sensor that needs to be the controlling one. PANEL T15 (Panel sensor). EXTERNAL T10 (to be installed in representative extraction fitting). SENSOR EXTERNAL TEMP. SENSOR PANEL SENSOR PANEL PRIORITY HP+EXT PRIORITY HP+EXT ROOM ROOM LOW 10 C PRIORITY HP EXTERNAL -1 C PRIORITY PRESET The unit stops at this room temperature (1-20 C) - - means that the function is unactive. - - should be chosen if the panel is placed in a cold environment. : ventilation without heatpump HP: ventilation only with heatpump activ HP+EXT: ventilation with heatpump and heating surface activ Figure 11: The "Temp. control" menu This document may be subject to change Side 16 of 23
Inlet control In the Inlet control menu it is possible to adjust the period of time before restart of the compressor. The Inlet control menu should only be adjusted by persons with knowledge of control engineering. (To restore factory settings, see page 19) indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HOTWATER AIR EXCHANGE DEFROST TEMP. GAIN 7.0%/ ROOM INTEGRAL 120s PRESET N- ZONE 2.0 C TMP- RAMP 0.10 /s The menu options are only accessible when the system has a postheating element KAP- RAMP 0.5%/s HEATPUMP RST 6m The minimum length of time (in minutes) the compressor must be stopped before restarting. Figure 12: The "Inlet control" menu This document may be subject to change Side 17 of 23
Room control In the Room control menu it is possible to adjust the regulator for controlling the room temperature. The Room control menu should only be adjusted by persons with knowledge of control engineering. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. Heat demand: Neutral Zone for start and stop of the evaporator: Desired room temperature (21 C) + N-ZONE (2 C) = 20 C for start of the evaporator, 22 C for stop of the evaporator ROOM N-ZONE 2.0 C Can be set from 0,5-10 C. PRESET Figure 13: The "Room control" menu This document may be subject to change Side 18 of 23
Restart The Restart menu enables you to set the unit to automatically restart in connection with highpressure/low-pressure alarms. indicates that the menu point flashes and can be set to another value The setting HP/LP in the Restart menu may not be used under normal conditions. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. ROOM PRESET HP/LP This function may not be used under normal conditions. (the function indicates that the unit should restart automatcally when high-pressure/lowpressure alarms occur.) Indicates that the unit should not restart automatically when highpressure/low-pressure alarms occur. Figure 14: The "Restart" menu This document may be subject to change Side 19 of 23
Preset indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. ROOM When standard is chosen all factory settings are reset. An eventual supplementary heating surface must be re-activated. A heating surface is NOT frost-protected until it is correctly installed and activated in the service menu. PRESET STANDARD PRESET PRESET Figure 15: The "Preset" menu This document may be subject to change Side 20 of 23
Manual In the Manual menu it is possible to test the functions of the unit manually. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST VEN+HEAT Manual test of ventilation & heat. Under test there are 50% signal to the heating surface TEMP. VENT+CPR Manual test of ventilation & compressor EXHAUST Manual test of exhaust ROOM Manual test of inlet PRESET FLAPS DEFROST Manual test of flaps Manual test of the defrost function. Manual test de-activated (normal working) Figure 16: The "Manual" menu This document may be subject to change Side 21 of 23
System dimension Right Front Left Figure 17: System dimension 1. Fresh air intake. 5. Compressor 9. Inlet fan 2. Exhaust 6. Condensator (hidden) 10. Exhaust fan 3. Inlet 7. Evaporator 11. Condensation drain 4. Discharge 8. Electrical connections Dimensions in mm: a b c d e f g h i j k l m n o p VPL15 650 680 400 200 200 90 410 90 410 Ø160 38 450 510 50 200 Ø20 VPL15T 550 600 635 50 95 190 140 140 160 160 160 160 - - - - VPL25 700 760 570 285 215 160 480 205 505 Ø250 44 505 540 25 85 Ø20 Weight in kg.: VPL15 VPL15T VPL25 Unit 54 50 65 Filterunit with Heat-pipe 30-40 This document may be subject to change Side 22 of 23
Accessories / spare parts VPL 15 Filter types Qty. Nilan item no. F5 (exhaust) 1 3953 F7 (inlet) 1 3952 VPL 15T Filter types Designation Qty Nilan item no. T-filter, comlete Ø160mm 1 8481 Filter for item no. 8481 Ø160mm 1 8504 VPL 25 Filterklasse Designation Qty. Nilan item no. T-filter, complete Ø250mm 1 8484 Filter for item no. 8484 Ø250mm 1 85063 Heating surface, water Unit Qty. Nilan item no. VPL 15 + VPL 15T 1 768893 VPL 25 1 768983 Heating surface, electrical Unit Output Qty. Nilan item no. VPL 15 + VPL 15T 0,9kW 1 76413 VPL 25 6,0kW 1 76423 Filterunit FU Unit Filter type Qty. Nilan item no. FU15H G3 1 3931 FU25H G3 1 3932 Heating Cable for condensate drain (frost protection) Unit Designation Nilan item no. VPL 15 VPL 15T VPL 25 Heating Cable (specify length when ordering) 2172 Vibration Unit Designation Qty Nilan item no. VPL 15 Sylomer (Green) 4 30451 VPL 25 Sylomer (Green) 6 30451 FU15H Sylomer (Green) 4 30451 FU25H Sylomer (Green) 4 30451 This document may be subject to change Side 23 of 23