Surface Temperature Tests on an LST Fan Convector

Similar documents
Electric radiator test

Electric radiator tests

Ultrasonic Clamp-On Flow Meter Testing

Furenflex RWV Advanced Liner

China Bathroom Study 2014

Water heating and solar thermal markets

Water heating and solar thermal markets

Domestic boilers, radiators and water heaters Turkmenistan

Pedestal Range. Installation and user manual. Kiosk. Trafalgar. Tube. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

Sargasso Range. Installation manual. Sargasso S. Issue 001 January 2018 ENGLISH UK IRL SmithsEP.co.uk

Hydroflame. Flame-effect fan convectors Installation and User Guide Elite and Classic Models. Contents

Energy services in North America 2014

LOW SURFACE TEMPERATURE RADIATORS

Space Saver. New easy guide. Connecting your Space Saver to a central heating system. Issue 001 February 2018 ENGLISH UK IRL SmithsEP.co.

CEE:3371 Principles of Hydraulics and Hydrology Project #2 Flow Measurement with a Weir

FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST

Space Saver. Installation and user manual SS3 SS5 SS7 SS9. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

Sargasso Range. Installation manual. Sargasso A. Issue 001 January 2018 ENGLISH UK IRL SmithsEP.co.uk

Signature, Sovereign, Sentry, Sentinel, Staccato Fan-Assisted Radiator. Installation & User Guide

Space Saver. New Easy Guide. Connecting your Space Saver to a central heating system BEFORE AFTER

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Cylinders for Domestic Purposes Heat Pumps

Australian Standard. Degrees of protection provided by enclosures (IP Code) AS IEC Ed 2.1:2001 AS 60529

Sargasso Range. A new range of radiant panels for heating commercial applications

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Space Saver. Installation and user manual. Issue 001 March 2018 ENGLISH UK IRL SmithsEP.co.uk. Issue March 2018 smithsep.co.

Heat Emitter Supplement To the Domestic Heating Design Guide

Attachment 1 TOWN OF NEW TECUMSETH. Manual for the Preparation of an Urban Design Report

Conventional Electric Space Heating Systems

LAB EQUIPMENT DETAILS

SECTION AIR COILS

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

RADIANT PANELS COMMERCIAL BUILDINGS INNOVATIVE VENTILATION & HEATING

Commercial Heating Domestic Heating

Sovereign Double CC/DD

TESTS OF ADSIL COATING

Australian Standard. Electroacoustics Sound calibrators AS IEC This is a free 7 page sample. Access the full version online.

REPORT. Condensing air heaters. Technology evaluation. Project report Maj 2013

ENSC 388: Engineering Thermodynamics and Heat Transfer

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

RADIANT PANELS COMMERCIAL BUILDINGS INNOVATIVE VENTILATION & HEATING

Warner Instruments, Inc Dixwell Avenue, Hamden, CT (800) / (203) (203) fax

Temperature Rises as Products Compete in the Heat. Market. Contact: Tim Page Press Release No: 20. Release date: Immediate Date: 11/11/09

(UK) Date : February 2016 NOTE: PLEASE LEAVE COPIES OF THESE INSTRUCTIONS AND ANY DRAWINGS WITH THE END USER.

Aegean Range. A new range of fan coils for heating and cooling commercial applications

Contact person RISE Date Reference Page Daniel Månsson P (13) Energy and circular economy

Introduction. There is no obligation to follow the methods or comply with the standards set out in this Technical Booklet.

Providing comfort for the built environment

NZQA unit standard version 1 Page 1 of 6. Install, maintain and repair of telecommunications optical fibre network infrastructure

Australian Standard. Fire hydrant installations. Part 1: System design, installation and commissioning AS

Technical-Report for SL Lamp 5 W

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production

Powrmatic PZN / PZN X Hot Water Heater

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Dryer Master Inc. Dryer Master AM 3. Product Manual

Australian Standard. Functional safety Safety instrumented systems for the process industry sector

Contact person Date Reference Page Björn Folkeson P (14) Energy and bioeconomy

SEAR II APPLICATION 9V899-A01D PREPARED FOR NICTD

Contact person Date Reference Page Daniel Månsson P07886B-rev2 1 (14) Energy and bioeconomy

MARCH 2012 ISSUE 2 DYNAMIC. The only electronically controlled Electric Radiator with dynamic looks, dynamic performance and dynamic efficiency.

TOPAZ ADIABATIC COOLER

H Y D R O C O U R S E T R E N C H H E A T I N G

DISPLACEMENT VENTILATION AND STATIC COOLING DEVICES

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Microtherm Heat Stress WBGT

AS/NZS 4012:1999 AS/NZS

Australian Standard. Automatic fire detection and alarm systems System design, installation, and commissioning AS

GREEN REFRIGERANT R-410A

o Clear instruction for operation o Measurement and control of o Stationary sensor for o Programming capabilities of o Countdown timer selectable

Radon Measurement Survey Report. McKnight School Service Center 417 Fifth Street Aurora, Illinois Prepared For:

Report No 288/ Part 1 of 2 This report consists of 22 pages. Maxitone ZAMT Type A Addressable Sounder. See Assessment Summary for details

AHU Air Handling Unit Fundamentals. j.ilangumaran

The electrical wattage needed by the circulator is:

Contact person RISE Date Reference Page. Daniel Månsson P (13) Energy and circular economy

AS/NZS 3190:2011 AS/NZS

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B

Radon Measurement Survey Report. Krug Elementary School 240 Melrose Avenue Aurora, Illinois Prepared For:

CLIMASTER ZCF AIR HANDLING UNITS

Electrical Safety Policy and Management System

NF X : Parts 1, 2, 3, 4 & 5

Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49. Report Number: EDR-5391 Rev. 0 06/15/05. Approved by: Signature: Date:

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

The Participant will select one of the two Approval Categories (below) and submit the appropriate documentation.

Appendix H. BGS BR211 Radon Report

NATURAL VENTILATION CONTROL SYSTEMS

evotouch Controller Installation evotouch

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Road Safety Impact Assessment

COMMERCIAL HVAC EQUIPMENT Coils: Direct Expansion, Chilled Water, and Heating

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

AS/NZS :2008

Bench Top Cooling Tower H893

Radon Measurement Survey Report. Oak Park Elementary School 1200 Front Street Aurora, Illinois Prepared For:

Radon Measurement Survey Report. Rollins Elementary School 950 Kane Street Aurora, Illinois Prepared For:

3500/61E & 3500/67E Temperature Monitor

LC2200 Level Controller Installation and Maintenance Instructions

Q1. The diagram shows an experiment to find out what happens to infrared waves when they strike different surfaces.

Contact person Date Reference Page Daniel Månsson P (13) Energy and circular economy

Welding Job Knowledge

Transcription:

Surface Temperature Tests on an LST Fan Convector BSRIA Report 59569/1 Edition 2 This report supersedes Report 59569/1 dated 29 July 2016 Carried out for Smiths Environmental Products Ltd. By Alf Russell 19 October 2016

Surface Temperature Tests on an LST Fan Convector Carried out for: Smiths Environmental Products Ltd. Blackall Industrial Estate South Woodham Ferrers Chelmsford Essex CM3 5UW Contract: BSRIA Report 59569/1 Edition 2 This report supersedes Report 59569/1 dated 29 July 2016. Date: 19 October 2016 Issued by: BSRIA Limited Old Bracknell Lane West, Bracknell, Berkshire RG12 7AH UK Telephone: +44 (0)1344 465600 Fax: +44 (0)1344 465626 E: bsria@bsria.co.uk W: www.bsria.co.uk Compiled by: Name: Alf Russell Title: Test Engineer BSRIA Test Checked by: Name: Tom Garrigan Title: Business Manager BSRIA Test Approved by: Name: Tom Garrigan Title: Business Manager BSRIA Test This report must not be reproduced except in full without the written approval of an executive director of BSRIA. It is only intended to be used within the context described in the text. BSRIA Page 3 of 16 BSRIA Report 59569/1 Edition 2

PREFACE PREFACE This report supersedes Report Number 59569/1 dated 29 th July 2016. The following amendment has been made: The model name has changed from Caspian Universal 120 to LST Caspian Universal 120. BSRIA Page 4 of 16 BSRIA Report 59569/1 Edition 2

SUMMARY SUMMARY A fan assisted LST convector was supplied by Smiths Environmental Products Ltd., and submitted for the assessment of surface temperatures against the NHS Estates guideline Safe Hot Water and Surface Temperatures (1998). Full details of the tests and product can be found in the main body of this report. The high fan speed dissipated heat away from the top grille well enough to maintain a grille temperature below 43 C with a water inlet temperature up to 84 C when in manual configuration. In low fan speed mode, a grille temperature of 43 C is exceeded with a water inlet temperature of 77 C in manual configuration. With the motorised valve set in LST mode and the normal operating condition established, the grille temperature is maintained below 43 C for a water inlet temperature of at least 86 C. At both fan speeds, with the unit in normal automatic LST mode, this unit can comply with the NHS Estates health guidance note: Safe Hot Water and Surface Temperatures, albeit giving a reduced output compared to a manual test. BSRIA Page 5 of 16 BSRIA Report 59569/1 Edition 2

CONTENTS CONTENTS 1 INTRODUCTION... 7 2 DESCRIPTION OF SAMPLE... 7 3 TEST FACILITY... 8 4 INSTRUMENTATION... 9 5 TEST RESULTS... 10 5.1 Surface temperatures...11 5.2 Results...11 6 CONCLUSION... 13 APPENDICES APPENDIX: A TEST ITEMS... 14 BSRIA Page 6 of 16 BSRIA Report 59569/1 Edition 2

INTRODUCTION 1 INTRODUCTION A fan assisted LST convector was supplied by Smiths Environmental Products, for assessment against the NHS Estates guideline, Safe Hot Water and Surface Temperatures published 1998. The work was requested by Smiths Environmental Products Ltd. and was carried out during the period 29 June to 5 July 2016. The sample was received in good condition on 27 June 2016. This report refers only to the item tested and no others. 2 DESCRIPTION OF SAMPLE The test sample consisted of a fan assisted LST convector and was supplied by Smiths Environmental Products Ltd. The sample was designated as follows: LST Caspian Universal 120 The sample was a fan assisted, LST convector, plumbed with top, bottom, same-end connectors, and was the largest size of a 3 model range of common height with varying length. Further details of the test sample can be found in Appendix A. BSRIA Page 7 of 16 BSRIA Report 59569/1 Edition 2

TEST FACILITY 3 TEST FACILITY The test facility consists of a test room 4.0 m (l) x 4.0 m (w) x 3.0 m (h), which is constructed to the requirements contained in BS EN 442-2 : 2014 for radiator testing, i.e. five water cooled surfaces and one insulated surface against which the test radiator is installed. Usually when steady state conditions are achieved the appliance output is determined from measurements of the water flow rate and inlet/outlet water temperature difference. A standard rated output test consists of three test points. For all appliances a first test is carried out with a water supply temperature that produces a mean water temperature of 70 C with the water flow rate such that for radiators the inlet/outlet water temperature difference is 10 C. Two further tests are carried out at the water flow rate established in the first test but with different supply water temperatures. For all standard radiator tests the enclosure air temperature is controlled to maintain 20 C at the inner room reference point, which is 0.75 m from the floor in the centre of the room. In this instance, when in LST mode, the fan convector used four internal sensors to control the operation of an internal 2 port valve and the fan, such that the 2 port valve did not open until water at 35 o C+ was present, the heated air did not exceed 43 o C and if the air temperature dropped below 32 o C the fan shut down to avoid cold draughts. Three sensors had fixed set points and one (leaving air) was adjusted to 39 o C. The unit was therefore constantly modulating the output by means of the 2 port valve and did not maintain the steady state that would be required to conduct a standard rated output test. Similarly the position of the 2 port valve and bypass in LST mode meant that while the measured total water flow through the unit remained relatively stable, it was not possible to determine what proportion was going through the coil or the bypass at any one time. An initial test was therefore conducted with the 2 port valve locked manually open (not LST mode) to obtain an estimate of the flowrate necessary to achieve a nominal 10 o C drop with a supply of 86 o C, as requested by Smiths with fan set at high speed (8.6VDC). This test was conducted in the manner of a standard rated output test, but outside the normal tolerances used for radiators. This provided a minimum datum flow rate to be used during the tests in LST mode. The unit was then set to automatic operation, low speed (4.5VDC) with the nominal 86 o C supply temperature and the water temperatures, flow rate and surface temperatures logged at 100 second intervals. BSRIA Page 8 of 16 BSRIA Report 59569/1 Edition 2

INSTRUMENTATION 4 INSTRUMENTATION TEST RECORD SHEET TP21/7 : TEST EQUIPMENT / INSTRUMENTS Contract Number Test Engineer FM59569A Phil Stonard Instrument No. Calibration expiry date Weigh scales (water flow rate) 2026, 2027 23/03/17 Resistance thermometer (air) reference & radiant shield 329 13/08/16 Resistance thermometers (water) reference 1485-1488 21/08/16 Digital logging system (6½ digits) 266 21/08/16 Digital barometer 455 09/12/16 Electronic timer within PC 1 526 21/10/16 Steel rule (0-300mm) 218 01/03/17 Retractable steel rule (0-8m) 683 01/03/17 Digital caliper (0 300mm) 2057 04/02/18 Spring balance (0 100Kg res.) 393 01/04/17 Comments: None Test Engineer Phil Stonard BSRIA Page 9 of 16 BSRIA Report 59569/1 Edition 2

TEST RESULTS 5 TEST RESULTS TEST REPORT Date of Test: 29-06-2016 Manufacturer: Smiths Environmental Model Reference: LST Caspian Universal 120 Test Reference Number: 59569A1PS Type of Heater: Fan assisted convector Pipework Connections: T.B.S.E. HEATER DIMENSIONS Overall Height: (mm) 660 Overall Length: (mm) 1195 Overall Depth: (mm) 245 Convector Height: (mm) 50 Convector Depth: (mm) 200 Height above floor: (mm) 110 Distance from wall: (mm) 0 Radiated heat factor Sk 0.00 Barometer exponent np 0.40 MEAN TEST VALUES TEST 1 TEST 2 TEST 3 Room air temperature 0.75m: ( o C) 24.5 21.0 24.2 Flow rate (g/s) 78.4 79.1 73.2 Flow enthalpy (J/g) 316.9 233.9 346.1 Return enthalpy (J/g) 250.7 191.6 267.5 Flow temperature ( o C) 75.7 55.9 82.7 Return temperature ( o C) 59.9 45.8 63.9 Output (W) 5186.7 3350.3 5753.8 Mean water temperature ( o C) 67.8 50.8 73.3 Temperature difference ( o C) 43.3 29.9 49.1 Barometric pressure (mbar) 1000.4 1001.1 1001.5 Corrected output (W) 5212.7 3366.2 5780.1 Estimated output (W) 5108.1 3383.5 5868.5 PERFORMANCE EQUATION Output (W) = K M (mean water temperature - room air temperature) ^n From test results K M = 78.1764 n = 1.1091 VARIATION OF OUTPUT WITH TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE o C HEAT OUTPUT W 20 2168 30 3400 40 4677 50 5991 60 7333 Note: Estimated output only. Fan set to high with manual output. This extracted test data does not comply with the tolerances set by EN442 or EN16430 and is for manufacturer's guidance only. BSRIA Page 10 of 16 BSRIA Report 59569/1 Edition 2

TEST RESULTS 5.1 SURFACE TEMPERATURES Position of surface temperature thermocouples 1 2 3 4 5 6 7 8 Note: Drawing not to scale 5.2 RESULTS The following chart shows surface temperatures plotted against inlet water flow temperatures with 2 port valves set to manual (open). Tabular data is shown for both manual and LST configurations. This enables comparison with the NHS Estates Health Guidance Note, Safe hot water and surface temperatures, which states the maximum surface temperature of space heating devices should not exceed 43 C when the system is running at the maximum design output BSRIA Page 11 of 16 BSRIA Report 59569/1 Edition 2

Surface Temperature ( C) SURFACE TEMPERATURE TESTS ON AN LST FAN CONVECTOR TEST RESULTS Average Surface Temperatures at High Fan Speed (8.6v) (Manual Output) Top Cover Top Grille Front below Grille Inlet ( C) TC01 ( C) TC02 ( C) TC03 ( C) TC04 ( C) TC05 ( C) TC06 ( C) TC07 ( C) TC08 ( C) 55.9 25.4 24.9 24.1 31.8 29.6 28.6 27.5 26.2 75.7 30.9 29.9 28.7 40.5 37.0 35.7 33.8 32.1 82.7 31.4 30.5 29.4 42.0 38.4 37.1 34.5 33.0 slope 0.234868 0.217505 0.204988 0.390313 0.337797 0.328571 0.27589 0.263335 intercept 12.44348 12.88303 12.74711 10.20901 10.86772 10.3446 12.23279 11.61594 Estimated Surface Temperatures for an Input Temperature of 86 C Top Cover Top Grille Front below Grille Inlet ( C) TC01 ( C) TC02 ( C) TC03 ( C) TC04 ( C) TC05 ( C) TC06 ( C) TC07 ( C) TC08 ( C) 86.0 32.6 31.6 30.4 43.8 39.9 38.6 36.0 34.3 Estimated Inlet Water Temperature for a Maximum Surface Temperature of 43 C Top Cover Top Grille Front below Grille Inlet ( C) TC01 ( C) TC02 ( C) TC03 ( C) TC04 ( C) TC05 ( C) TC06 ( C) TC07 ( C) TC08 ( C) 84.0 32.2 31.2 30.0 43.0 39.2 37.9 35.4 33.7 50 LST Caspian Universal 120 45 43 40 35 30 25 TC01 ( C) TC02 ( C) TC03 ( C) TC04 ( C) TC05 ( C) TC06 ( C) TC07 ( C) TC08 ( C) 20 50 55 60 65 70 75 80 85 90 Inlet Water Temperature ( C) The above chart is based on data from 59569A1PS. This test was run with the fan speed set to high (8.6VDC) and the motorised valve set to manual. The flow rate during this test varied between 73 and 79 g/s. As the LST mode was disabled, this is not for the unit in its normal operating mode, but to establish a target water flow rate for use in subsequent tests. BSRIA Page 12 of 16 BSRIA Report 59569/1 Edition 2

CONCLUSION Two single water temperature tests were conducted with the fan speed set to low, at nominal water inlet temperatures of 77 o C and 86 C and in manual and LST mode for comparison. Single temperature test at 50 C - Motorised valve on manual, fan set to low (4.6v) Top Cover Top Grille Front below Grille Inlet ( C) TC01 ( C) TC02 ( C) TC03 ( C) TC04 ( C) TC05 ( C) TC06 ( C) TC07 ( C) TC08 ( C) 77.2 34.0 32.6 31.8 48.2 43.4 43.9 38.1 36.2 Single temperature test at 86 C - Motorised valve on auto, fan set to low (4.6v) Top Cover Top Grille Front below Grille Inlet ( C) TC01 ( C) TC02 ( C) TC03 ( C) TC04 ( C) TC05 ( C) TC06 ( C) TC07 ( C) TC08 ( C) 85.9 25.9 24.8 23.8 32.2 29.9 27.4 27.5 25.8 In the first of these two tests the water flow rate was 94 g/s. In the second test the overall water flow rate was 100 g/s. However, as the motorised valve was set to auto on the second test, it was impossible to determine the percentage of water directed through the bypass and emitter, at any one time. 6 CONCLUSION The high fan speed dissipated heat away from the top grille well enough to maintain a grille temperature below 43 C with a water inlet temperature up to 84 C when in manual configuration. In low fan speed mode, a grille temperature of 43 C is exceeded with a water inlet temperature of 77 C in manual configuration. With the motorised valve set in LST mode and the normal operating condition established, the grille temperature is maintained below 43 C for a water inlet temperature of at least 86 C. At both fan speeds, with the unit in normal automatic LST mode, this unit can comply with the NHS Estates health guidance note: Safe Hot Water and Surface Temperatures, albeit giving a reduced output compared to a manual test. The LST Caspian Universal is available in three lengths: model 120 (1195mm), model 90 (895mm) and model 60 (595mm). The model tested was the longest, 1195mm. As these units are identical in every way bar length, it is logical to assume that the surface temperatures, on all three models, would be maintained below 43 C in normal, automatic, operating conditions. BSRIA Page 13 of 16 BSRIA Report 59569/1 Edition 2

APPENDIX: A TEST ITEMS APPENDIX: A TEST ITEMS TEST RECORD SHEET TP21/1: TEST ITEMS Contract number FM59569A Sheet number 1 of 1 Date of receipt Test Engineer initials Full description of test item 27/06/2016 PS A fined tube emitter with two axial fans assembled in a steel case with inlet and outlet grilles. 660 x 1195 x 245mm Test item reference number 59569A1AR Comments:- Automatic control of LST function by means of 2 port valve & integral sensors. Test Engineer Phil Stonard BSRIA Page 14 of 16 BSRIA Report 59569/1 Edition 2

APPENDIX: A TEST ITEMS TEST RECORD SHEET TP21/2 : PRODUCT INFORMATION BSRIA test reference number 59569A1PS Client Smiths Environmental Products Ltd Manufacturer Smiths Environmental Products Ltd Product reference number LST Caspian Universal 120 Product style Fan convector Material of construction Steel, aluminium and copper tubing Date of receipt 27/06/2016 Product or packaging markings Type and size Test start date 01/07/2016 Weight (dry) (kg) N/A Water content (kg) N/A DIMENSIONAL MEASUREMENTS Measurement Parameter Overall height 660 Overall depth 245 Measured value (mm) Manufacturer s stated value (mm) EN 442-2 dimensional tolerance Overall length 1195 See Comments Convector height 44 Convector depth 203 Pass / Fail Emitter configuration Emitter overall length (mm) 1050 Emitter finned length (mm) 950 2 rows, 4 tubes Distance between centres (mm) 20 (row 1 2) Tube diameter (mm) 22 (connectors) Emitter height from floor (mm) 480 Fin thickness (mm) 0.2 Fin pitch (mm) 2.4 Additional information Comments : Not required for LST surface temperature measurement. T.B.S.E. with automatic control of LST function by 2 port valve & integral sensors TEST ENGINEER Phil Stonard BSRIA Page 15 of 16 BSRIA Report 59569/1 Edition 2

APPENDIX: A TEST ITEMS LST Caspian Universal 120 BSRIA Page 16 of 16 BSRIA Report 59569/1 Edition 2