Immersion heating type IN 16.. PTB 99 ATEX 1009 U May 1999 thuba Ltd. CH-4015 Basle Telefon +41 061 307 80 00 Telefax + 41 061 307 80 00 headoffice@thuba.com www.thuba.com
Manual PTB 99 ATEX 1009U 2 Immersion Heater Type IN 16.. Target group: Experienced electricians as defined by ElexV and properly instructed personnel. Contents: 1. Safety rules 2. Conformity with standards 3. Technical data 4. Installation 5. Maintenance 1. Safety rules The immersion heater is used for heating liquids and gas/air mixtures. The immersion heater may be used only for heating combustible and noncombustible liquids with a flash point 55 C in open systems that are not heated above their flash point. It is not suitable for use in Zone 0. The immersion heater is designed for attachment to vessels, apparatus and piping systems by means of a flange connection. The safety precautions taken for the heating of closed systems must be reviewed by an expert. During operation, do not leave this instruction Manual or other objects in the junction box. Operate the immersion heater for its intended duty in undamaged and clean condition, and only where the resistance of the enclosure material to the ambient conditions is assured. The junction box s minimum protection of IP 54 applies only in the case of correct assembly in compliance with EN 60 529: 1991. No modifications to the immersion heater are allowed. The manufacturer has adapted the immersion heater to the specific requirements during project planning and/or has established the temperature class and other duty conditions by routine thermal testing prior to initial start-up taking local and
Manual PTB 99 ATEX 1009U 3 operating circumstances into account; the temperature class and other duty conditions may not be changed thereafter. The manufacturer has designed the control system as an integral part of the immersion heater installation in terms of safety and type aspects in accordance with EN 50 019:1994. The heating of liquids is permissible only if there is sufficient cover ( 50 mm). This requirement can be fulfilled with a level detector or comparable precautionary measures. In the case of installations with flowing liquids, the flow monitor provided is an integral part of the installation. Modifications to it are also forbidden. Whenever work is done on the immersion heater installation, be sure to observe the national safety and accident prevention codes as well as the safety rules that follow in this Instruction Manual, which are stated in italics like this paragraph! 2. Conformity with standards The immersion heater complies with the requirements of EN 50 014:1997, EN 50 018: 1995 and EN 50 019:1996. It was developed, manufactured and tested in accordance with state-ofthe-art engineering practice and EN 29 001. 3. Technical data Explosion protection EEx de IIC T1...T6 EC Type Test Certificate PTB 99 ATEX 1009U Junction box enclosure material stainless steel or polyester, depending on the version Enclosure protection type IP 54 (to IEC Publication 529) Admissible ambient temperatures 20 C to +40 C
Manual PTB 99 ATEX 1009U 4 Marking 0102 II 2 G 3.1 Electrical data Maximum figures for the power circuits: Rated voltage e.g. max. 750 V (see rating plate) Rated current e.g. max. 63 A (depending on version) Max. conductor cross-section e.g. 16 mm² (depending on version) Maximum figures for the control circuits: Rated voltage e.g. max. 250 V (see rating plate) Rated current e.g. max. 16 A (depending on version) Max. conductor cross-section e.g. 2.5 mm² (depending on version Type code IN 16.. Heating rod diameter 08 8.5 mm 10 10 mm 12 12.8 mm 14 14 mm 16 16 mm 63 63 mm
Manual PTB 99 ATEX 1009U 5 4. Installation For installation/operation, the provisions of ElexV and the Equipment Safety Law apply, as do generally accepted engineering practice (EN 60079-14) and this Instruction Manual. The immersion heater is designed for attachment to vessels, apparatus and piping systems by means of a flange connection only. It is inadmissible to undertake modifications to the operation of the immersion heater. Only the manufacturer may carry out such modifications. A wiring diagram is provided with every immersion heater. It provides information on utilization of the junction box terminals by the power and control circuits and should be observed without fail. Be sure to observe the figures stated on the rating plate and any other information provided by the manufacturer. Supplementary documentation from the manufacturer should be observed and taken into account whenever changes are made (e.g. replacement of a control contactor). The cable and conductor entry glands in the junction box are made of plastic or metal. Take care to bring in the cables and conductors through these glands in such a way that selfloosening will be prevented and permanent sealing of these cable and conductor entry glands is assured. Depending on the heater version, the conductor cross-sections are carried to the respective terminals as indicated in the wiring diagram. 4.1 Temperature The temperature class is established during the type testing or during the thermal testing that takes local and operating conditions into account and is subject to approval by an expert. It is absolutely necessary to observe the maximum ambient temperature. In this connection, take nearby sources of heat into account in order to ensure safe operation of the control and monitoring equipment. The connection head of any immersion heater is subject to temperature limitations. Use the heater only for its intended
Manual PTB 99 ATEX 1009U 6 purpose, and do not exceed the maximum admissible temperature. At the same time, make sure that the heat from the connection head can be dissipated unhindered. The thermostat reset elements in the junction box may be actuated only after the cause of tripping has been rectified and normal operating conditions have been restored. Prior to initial start-up and during operation, make sure that the parts of the immersion heater in contact with the medium are fully covered by liquid. They should be covered by no less than 50 mm of liquid at all times. 4.2 Equipotential bonding The internal and external potential terminals are provided for reliable connection of the equipotential bonding conductor. They are laid out for a maximum connection cross-section of 16 mm² (depending on the version). 5. Maintenance The provisions of ElexV 9, ElexV 13 and EN 60079-17 applicable to maintenance/overhaul/testing must be observed. When performing maintenance work, pay special attention to checking those parts that govern the equipment s type of protection.