VEKA ver C Supply air unit

Similar documents
eco TOP INSTALLATION AND MAINTENANCE MANUAL

eco PREMIUM ENERGY RECOVERY UNIT» INSTALLATION AND MAINTENANCE MANUAL

VEKA ver C SUPPLY AIR UNIT IINSTALLATION AND MAINTENANCE

MODBUS RS485. » Technical instructions. Air Comfort. Housing ventilation

Heat recovery unit RDKS. Technical instructions for installation, operation and maintenance

HEAT RECOVERY UNIT MINIMASTER RDKS INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

HEAT RECOVERY UNIT VILLAMASTER RDAF INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS

MODBUS RS485 TECHNICAL INSTRUCTIONS

Manual for the integration in BMS/GTC

Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX

recooler HP EQKR HEAT PUMP

TopMaster Air Handling unit. Technical data

IPSUM OPTIMIZATION SYSTEM» DEMAND CONTROLLED VENTILATION OVERVIEW

Z24 Wireless Zone Controller Professional Installation Guide

SAVE VTR 500. Installation and Service. Document in original language A001

VEKA Integrated Control

Natural Ventilation Controller with 24vDC drive NVC-1204

SAVE VSR 150/B. Installation and Service. Document in original language A001

Topvex SR03, SR04, SR06 Compact Air Handling Unit

REMOTE CONTROL FOR CHILLER MYCHILLER

SAVE VTC 200. Installation and Service. Document in original language A002

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later

AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS

BLAUAIR AUTOMATIC CONTROL SYSTEM

SIRe Competent Air Curtains Water With quick guide. SIReAC. For wiring diagram, please see p Original instructions

Instructions for the fan motor control system, SILVER C

Topvex SF02-SF12 Air Handling Unit

Halton SAFE / 7.14 user guide and installation instructions

READ AND SAVE THESE INSTRUCTIONS

Natural Ventilation Controller with 24vDC drive NVC-1204

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel

Installation Guide. ECL Comfort 210, application A Table of Contents

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Sensor Control Panel

Networkable Fan Coil Controller Specification and Installation Instructions

ggg Air Handling Unit RT 700/1000S-EC-RS INSTALLATION OPERATION & CONTROL PANEL MAINTENANCE & SERVICE

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

TopMaster Air Handling Unit

INSTALLATION AND OPERATION MANUAL

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

AIR HANDLING UNITS RIS P EKO 3.0. New range - 5 sizes, 20 models! Efficient EC. E f f i c i e n c y up to 94%! E x t r e m e l y low height! fans!

Built-on speed controller for GMPM plug fan with permanent magnet motor

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

TPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

SYX660 Commissioning Guide V Page 1 of 55

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h

CLEVER CONTROL Version: V3

USER MANUAL. OPTIMA 312 ES960C circuit board

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

D-TECT 3 IP. GJD260 IP Motion Detector

AirTrak. Digital Control System. User Manual. Touchscreen Systems

Corrigo E. Second generation which contains all applications and languages

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses

Instructions for the fan motor control system with integrated wiring terminals SILVER C

MCD User Manual

DAP III Zone Master User s Guide

5, SE GÅNGHESTER,

ESAR SMOKE CONTROL DAMPER» TECHNICAL CATALOGUE

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

C-series Controllers for air handling systems

ST 53.1 User s manual

ENTOUCH ONE USER GUIDE

SYX66x Commissioning Guide V Page 1 of 61

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

Swegon Home Solutions CASA. R2 Smart. Installation, commissioning and maintenance instruction. R2_a_EN-t

Installation and User Instructions

SAVE VTR 250/B. User Manual. Document in original language A001

INSTALLATION AND OPERATION MANUAL

Installation and Service

XC1008D -XC1011D- XC1015D and VGC810

eq PRIME » ENERGY EFFICIENCY AND FLEXIBILITY STRAIGHT OUT OF THE BOX AIR COMFORT AIR TREATMENT AIR HANDLING UNITS

DC 60 & DM 60 displays

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

C User manual

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

SIRe Advanced Air Curtains Electric With quick guide. SIReAA GB DE FR For wiring diagram, please see last pages. ES

Modbus RTU RS485 Manual

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Application description

GreenCon On/Off Room Thermostat

LCF Touch Modbus Datasheet Application Security Advice Caution

Pre-programmed room controller with communication

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

D-TECT 2 IP. GJD230 IP Motion Detector

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

Sauter flexotron 800 ventilation Manual

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

SIRe Advanced Air Curtains Water Ambient, no heat

EXPERT TRI-STAR. Temperature controller. User s Manual

Transcription:

Air omfort Air Treatment VEKA ver VEKA ver Supply air unit» Integrated ontrol Equipment uro

2 Supply air unit VEKA Integrated ontrol Equipment uro Innehåll 1.. Electrical connections Page 1.1 Motors... 3 1.2 Electrical Post heater... 3 1.3 Main supply... 3 1.4 onnection of control panel...4 2. onnection of external components 2.1 Electrical Post heater... 5 2.2 Post heater, hot water... 5 2.3 ooling coil, water... 5 2.4 ooling coil, DX... 5 2.5 Damper... 5 2.6 Temperature sensors... 5 2.7 Extended/Forced Ventilation... 6 2.8 Fire protection function... 6 2.9 Summary alarm... 6 2.10 External exhaust fan... 6 2.11 Filter guard... 6 3. Wiring diagram...7 4. ontrol panel, operations, commissioning Page 4.1 General... 10 4.2 Home screen... 11 4.3 Sub menus...13 4.4 Date and time, language...14 4.5 Advanced Settings for installers and service personnel...15 4.6 ommissioning Wizard... 16 4.7 Schedules... 19 5. ontrol functions 5.1 Heating and ooling...22 5.2 Temperature controls...22 5.3 Freeze protection...23 5.4 Fan control...23 6. ommunication 6.1 Modbus, RS485...24 6.2 Modbus, TP/IP...24 6.3 Webserver...24 7. Parameter list...25 8. DeclaraTION OF conformity...30

Integrated ontrol Equipment uro Supply air unit VEKA 3 1. Electrical connections 1 NY BILD! 2 4 3 1. ontrol board 2. Transformer 230/24 V 3. Terminals 4. Fuse, 24 V, 4 A 1.1 Motors Size Power, kw urrent, A Voltage, V 20 0,77 kw (0,385 kw x 2) 5 A (2,5 A x 2) 1 x 230 V 30 1,50 kw (0,75 kw x 2) 6,6 A (3,3 A x 2) 1 x 230 V 1.2 Electrical post heater Size Power, kw urrent, A Voltage, V 20 9 13 3 x 400 V 20 15 22 3 x 400 V 20 21 30 3 x 400 V 30 24 35 3 x 400 V 1.3 Main supply The main supply cable must be fitted with an external safety switch located close to the unit. Ambient temperature 0-40. Main supply 1 x 230 V. Fuse 10 A.

4 Supply air unit VEKA Integrated ontrol Equipment uro 1. ELETRIAL ONNETIONS 1.4 ONNETION OF ONTROL PANEL The control panel is connected when delivered from factory and provided with a magnet for easy handling. For wall mounting see below. 5. onnect the cable to the back of the display as shown above. Note. Please do not touch the electronics. 6. Push back the display in the enclosure. 1. Open the control panel using a screwdriver. NOTE! The control panel is only for indoor use. 2. Lift the display out of the enclosure. 3. Push the connection cable through a suitable hole and if needed make an outlet for the cable in the side of the cover. 4. Mount the enclosure directly on the wall.

Integrated ontrol Equipment uro Supply air unit VEKA 5 2. onnection of external components Use the control box on the outside of the unit to connect all external accessories. For information about how to connect available accessories see below. 2.1 Electrical post heater Duct mounted. Separate supply 3 x 400V. onnect alarm, start and control signal to the control box. The unit is preconfigured for electrical post heater. omponent Designation onnection Remark P1/SK1 1-2 Start signal Heating - NO Electrical ALM P1 25-26 1) Alarm, overheating (N) heater 21-22 SV1 TRL ontrol signal 0-10 V Y - M Supply 3 x 400 V Not from the unit 1) onnects directly to the control board. 2.2 Post heater, hot water irculation pump (P1) and valve actuator (SV1) connects according to table below. omponent Designation onnection Remark P1/SK1 Pump supply 1 - N - PE Heating (230 V max 2A 2) ) irculation pump P1 P1/SK1 Heating 2-3 NO - L1 Loop only with circulation pump ALM P1 25-26 1) Voltfree alarm input (NO, configurable) Valve actuator SV1 SV1 TRL 21-22 - 23-24 Y - M - G - GO 1) onnects directly to the control board. 2) The current consumption for P1 and P2 is limited to 2 A. A separate safety switch for the pump is needed if it is a long distance between the pump and the AHU. 2.3 ooling coil, water irculation pump (P2) and valve actuator (SV2) connects according to table below. omponent Designation onnection Remark P2/DX Pump supply 4 - N - PE ooling (230 V max 2A 2) ) irculation pump P2 P2/DX ooling 5-6 NO - L1 Loop only with circulation pump ALM 39-40 P2/DX Voltfree alarm input (NO, configurable) Valve actuator SV2 SV2 TRL 25-26 - 27-28 Y - M - G - GO 1) onnects directly to the control board. 2) The current consumption for P1 and P2 is limited to 2 A. A separate safety switch for the pump is needed if it is a long distance between the pump and the AHU. 2.4 ooling coil, DX The unit can manage cooling DX, 1-step. Note that the coil is not included in the delivery of the unit. For configuration see control functions. omponent Designation onnection Remark DX-cooling, P2/DX ooling 4-5 - NO Start: 10 % Stop: 0 % 1-step ALM P2/DX 39-40 1) Voltfree alarm input (NO, configurable) 1) onnects directly to the control board. 2.5 Spjäll On/off actuator with spring return, 15 Nm, 24 VA. omponent Designation onnection Remark Damper ST1 29-30 G - GO Exhaust air damper if used is connected in parallel (Maximum 2 dampers) 2.6 Temperature sensors The unit is provided with: Supply air sensor GT1, delivered separately. Duct mounting. able not included. Room temperature sensor GT2 (accessory) is supplied when the unit is configured for room temperature control. The room sensor is intended for wall mounting and needs to have good air circulation and not direct sun light. able not included. Outdoor air sensor GT3 (accessory) is supplied when the unit is configured for outdoor air compensation. Duct mounting. able not included. Frost protection sensor GT5 is supplied when hot water coil is used. Immersion sensor. omponent Designation onnection Remark Supply air sensor GT1 46-47 1) Duct mounting Room temperature GT2 sensor 50-51 1) Wall mounting Outdoor air sensor GT3 48-49 1) Duct mounting Frost protection sensor 1) onnects directly to the control board. GT5 52-53 1) Immersion sensor

6 Supply air unit VEKA Integrated ontrol Equipment uro 2. onnection of external components 2.7 Extended / forced ventilation For external electronic timer, push button, PIR or other volt free contact. Electronic timer and/or PIR if ordered is supplied separately. When using a push button the time has to be set in the control panel. 2.8 FIRE PROTETION FUNTION External fire alarm to stop the unit can be connected to terminals in the control box. Smoke detectors and fire dampers cannot be connected directly to the air handling unit, a separate fire system is needed. omponent Designation onnection Remark Timer 1 TMR1 13-14 1) Timer 2 TMR2 15-16 1) 1) onnects directly to the control board. omponent Designation onnection Remark Fire protection funcion FIRE 35-36 1) Voltfree contact (N) Looped at delivery 1) onnects directly to the control board. Function of aux. inputs Timer 1 (T1) and Timer 2 (T2) can be selected according to the following tables. Timer Function 1 (default) Timer 1 Timer 2 Manual/Automatic Mode 0 0 Trickle 1 0 Normal 0 1 Boost 1 1 Timer Function 2 Timer 1 Timer 2 Manual/Automatic Mode 0 0 Trickle 1 0 Boost 0 1 Stop 1 1 Timer Function 3 Timer 1 Timer 2 Manual/Automatic Mode 0 0 Normal 1 0 Boost 0 1 Stop 1 1 Timer Function 4 Timer 1 Timer 2 Stop 0 0 Manual/Automatic Mode 1 0 Stop 0 1 Boost 1 1 Timer Function 5 Timer 1 Timer 2 Stop 0 0 Manual/Automatic Mode 1 0 Stop 0 1 Normal 1 1 2.9 Summary alarm The alarm output can be configured to indicate A-alarms or both A- and B-alarms. omponent Summary alarm Designation onnection Remark ALM 11-12 1) Voltfree contact Maximum load 24 V, 200 ma 1) onnects directly to the control board. 2.10 External exhaust fan External exhaust fan (FF) with frequency converter connects according to the following table. omponent Designation onnection Remark 64-65 External ontrol signal 1) Y - M exhaust fan Alarm 23-24 1) Voltfree contact, (NO, configurable) 1) onnects directly to the control board. 2.11 Filter guard Filter guard (GP1) connects according to the following table. omponent Designation onnection Remark Filter guard GP1 17-18 1) Voltfree contact (NO) 1) onnects directly to the control board.

G 24 V G0 G 24 V G0 Integrated ontrol Equipment uro Supply air unit VEKA 7 3. Wiring diagram T1 230 V 24 V ontrol Board DO9 ontrol Board DO10 Supply ontrol Board 230 V 24 V Sid 2 TF Brown Blue Yellow/Green TF Brown Blue Yellow/Green P1/SK1 Start SK1 Blue Brown P2/DX Start 2) Loop only with circulation pump DX Supply fan (2 parallel) Alt. 1 Start Electrical Heater Alt. 1 Start DX ooling Outside unit Not in Fläkt Woods delivery Q1 2 1 4 3 6 5 External Safety Switch (Accessory) Alt. 2 irculation pump Heating (max 2 A totaly) Alt. 2 irculation pump ooling Main supply 1 x 230 V, 50 Hz Fuse Protection 10A (Electrical heater has separate supply) ontrol Board Digital Outputs (D0) Summary Alarm (Max 24 V, 0,2 A) 12 DO4 11 104 DO8 Reläkort 105 29 G G0 30 Shut-off damper ST1 Analogue Outputs (A0) ontrol Signal Supply Fan TF 66 Y Ref A01 67 M Modbus RS485 A B RS485 64 ontrol Signal External Fan TF Y A02 65 M Alt. 2 ontrol Signal Electrical Heater Alt. 1 Actuator Heating Ethernet TP/IP Ethernetcard 62 A03 63 21 22 Y M 21 Y G 23 22 M G0 24 ontrol Panel uro Touch 58 A05 59 SV2 Actuator ooling 25 Y G 27 26 M G0 28

8 Supply air unit VEKA Integrated ontrol Equipment uro 3. Wiring diagram ontrol Board Digital Inputs (DI) External Timer 1 TMR1 NO 13 25 DI1 DI7 14 26 NO Alt. 1 Alarm P1 Heating N Alt. 2 Alarm Electrical Heat. NO 15 39 NO External Timer 2 TMR2 DI2 16 DI10 40 Alarm irculation pump P2/DX cooling Supply Filter Alarm GP1 NO 17 23 DI3 DI10 18 24 NO Alarm External Exhaust Fan FF N N 35 21 Fire Alarm DI8 DI5 Alarm Supply Fan TF (Fan 1) 36 22 N Alarm Supply TF (Fan 2) Analogue Inputs (AI) B Vit 46 52 Vit B Supply Air Temp. GT1 M Brun AI1 47 AI4 53 Brun M GT5 Freeze Protection Sensor Outdoor Air Temp. GT3 B M Vit Brun 48 AI2 49 B Vit 50 Room Temp. GT2 M Brun AI3 51 24 V Terminals 2 3 N 2 3 N 5 6 N 1 1 4 4 External connections diagram 230 V 25 L1 N 5 6 N 21 22 23 24 25 26 27 28 29 30 1) 2) Safety Switch (iaccessory) Main Supply 1 x 230 V, 50 Hz Fuse Protection 10 A (Electrical Heater has separate supply) Alt. 1 Supply P1, 230 V Alt. 2 MStart electrical heater. Volt free contact P1/SK1 START 1) Loop only with P1, Alt. 1 Max 2A in total Alt. 1 Supply P2, 230 V Alt. 2 Start DX-cooling. Volt free contact P2/DX START 2) Loop only with P2, Alt. 1 Y M SV1 TRL, Valve actuator Heating G GO Y M SV2 TRL, Valve actuator ooling G GO G GO ST1, Shut-off damper

Integrated ontrol Equipment uro Supply air unit VEKA 9 3. Wiring diagram External connections diagram 24 V onnects directly to the control board NO 11 12 NO 13 12 NO 15 16 NO 17 18 NO ALM, Summary Alarm (Max. 24V, 0.2 A) TMR1, Ext. Timer input 1 TMR2, Ext. Timer input 2 GP1, Supply Filter Alarm FF Ext. LExhaust Fan Alarm P1, Alarm Input Heating FIRE, Fire Alarm Inout (Looped at delivery) GT1, Supply temp. Sensor 23 24 NO 25 26 P2, Alarm Input ooling N 35 36 NO 39 40 B M 46 47 B M 48 49 B M 50 51 B M 52 53 Y M 64 65 Ref A B 68 69 70 Timer function 1 (Default) TMR 1 TMR 2 Low speed 1 0 Normal speed High speed 0 0 1 1 For other time functions, see manual. When using electrical heater, the sensor has to be fitted after the heater GT3, Outdoor air temp. sensor GT2, Room temp. sensor GT5, FFreeze Protection sensor FF, External Exhaust Fan, ontrol signal MODB, Modbus RS485

10 Supply air unit VEKA Integrated ontrol Equipment uro 4 ontrol panel, operations, commissioning 4.1 General HMI This section provides an introduction to the touchscreen LD control panel, also known as the Human Machine Interface, or simply, HMI. The HMI serves two main purposes: To provide information about the current operational state of the unit. To allow the unit to be setup and configured. Touch Screen Tips To select an item, touch the center of the icon or option. Do not press too hard, the touch screen is sensitive enough to pick up light, firm touches. Use the tip of your finger or the back of a pencil to touch the required option. Be careful not to touch any other options. leaning the Screen Disconnect the power cord. Gently wipe the screen with a soft, dry non-abrasive cloth. If the marks remain, moisten the cloth slightly with a detergent that is de signed for LD or mobile screens and wipe the screen gently from top to bottom. Never use other detergents, as these may contain ammonia or other additives. IMPORTANT: Never spray, or pour liquids directly on to the screen. Do not clean the screen while the system is on. onventions used within this manual The following buttons and symbols are universal and available on many menu pages. Home key, to return to the Home Screen. Back button, to cancel and return to the previous page. onfirm button to confirm and proceed. hanging a value: Option 1: Press the arrow keys to increase or decrease the value. Option 2: Press the displayed number to numerically adjust the value. Using the Unit Powering On Use the number buttons to enter a value. onfirm with or cancel with. Values that can only be read, but not written, are displayed without a surrounding window. Values that can be both read and written, are displayed with a surrounding window. Some submenus has several pages. Touch the upper or the lower part of the scroll list to navigate between pages. Each time power is applied, the unit will run through a series of internal system tests which take approximately 20 seconds to complete. Once the internal system tests have been completed, the HMI will always display the Home screen. The unit will be in Manual Mode the first time that power is applied. Home Screen From the Home screen it is possible to determine how the unit is operating as well as navigating to further screens to configure the unit to suit the demands of the end system. From the Home Screen, it is possible to: Navigate to further configuration screens to setup system parameters. Manually adjust the fan speed. Determine the operating status of the product. Interrogate and acknowledge system alarms.

Integrated ontrol Equipment uro Supply air unit VEKA 11 4. ontrol panel, operations, commissioning 4.2 Home screen Status line Post-heater active ooling active urrent set point value lock 18 11:08 Alarm No alarm Alarm B Alarm A Operating status Manual mode Automatic mode Timer 1 Timer 2 Timer 1/Timer 2 Stop Operating modes Shut down time Trickle or low speed Normal or medium speed Boost or high speed

12 Supply air unit VEKA Integrated ontrol Equipment uro 4. ontrol panel, operations, commissioning 4.2 Home screen, cont. Shortcut to set the temperature set point Shortcut to ommissioning Wizard Shortcut to set the time and date Alarm See section 4.3.. Select operating mode See section 4.3. Stop ManuAl Automatic User Settings See section 4.3. Trickle or low speed Normal or medium speed Boost or high speed Press each field to select the operating mode. Only active in Manual Mode.

Integrated ontrol Equipment uro Supply air unit VEKA 13 4. ontrol panel, operations, commissioning 4.3 Sub menus Operating Modes The operating status icon present on the Home Screen displays the current operating mode. To change the operating mode, press the large fan icon located on the Home Screen. The unit has three operating modes selectable through the Operating Modes screen: Stop Mode: In this mode, the unit will stop both the supply and the extract fans. Manual Mode: In this mode, the unit can be manually adjusted on the Home Screen to run at three different speeds. Automatic Mode: In this mode, the unit will be automati cally controlled using internal sche dules and timers, O 2 demand control, PIR sensors, etc. Alarm Screen The alarm icon on the Home Screen indicates the status of any system alarms: No alarm Alarm B Alarm type B are deemed non-critical and do not stop the unit ventilation. Alarm type A are deemed critical and will Alarm A cause the unit to stop ventilating. Press the icon to enter the Alarm Screen. User Settings Temperature status The temperature set point is used to determine when the post-heater (if fitted) starts to warm the supply air entering the property. The temperature set point can be adjusted to any temperature between 15 and 35, factory setting is 19. Temperatures and output signals are read only values. Fan Status From the Fan Status screen it will be possible to view parameters such as supply and exhaust fan speeds, %. Air Quality Not for VEKA. System Overview Version ontrol Panel IP Octet 1 Bootloader ontrol Panel IP Octet 2 Version ontrol ard IP Octet 3 Bootloader ontrol ard IP Octet 4 Unit type VEKA Schedules Example 1: No alarm Example 2: Active alarms learing Alarms To clear an individual alarm, press the Ack button. To clear all the Alarms press the Ack All button on top of the screen. It may not always be possible to clear the status of an alarm as the source of the alarm may immediately trigger the status to return. For example, it will not be possible to clear a faulty temperature sensor alarm until the sensor itself has been repaired or replaced. Read only. For more information see section Schedules, section 4.7. Advanced settings See section Advanced settings, section 4.4. Alarm history

14 Supply air unit VEKA Integrated ontrol Equipment uro 4. ontrol panel, operations, commissioning 4.4 Date and time, language Settings To enter the settings menu: Date/time 1. Set the date and press the onfirm button. 1. Push the gear cog button. 2 Set the time and press the onfirm button 2. Push the spanner button. hoose Language 3. In this menu you set the date, time and language. It is also possible for installers and service personnel to log in and access additional parameters. 1. hoose the appropriate language flag and press the onfirm button. Note, further language flags are available after pressing the right arrow icon. Not all translations are available.

Integrated ontrol Equipment uro Supply air unit VEKA 15 4. ontrol panel, operations, commissioning 4.5 Advanced Settings for installers and service personnel Settings for installers and service personnel This section provides an overview to the more advanced operations that are available from the Home Screen via the passcode protected Advanced Settings option. Numerous system parameters can be adjusted through the Settings Screen; however, only those that are relevant and appropriate to the scope of the HMI User Manual will be described. It is strongly recommended to avoid the adjustment of any system parameters not outline within this section. Access to the Settings Screen is passcode protected to prevent system critical parameters from being accidentally adjusted to values that could compromise the correct operation of the unit. Therefore, extreme caution should be observed when adjusting Advanced Settings parameters. Login Advanced settings requires the Login passcode, 0000, to be entered. 1. Enter the correct passcode and press the onfirm button.

16 Supply air unit VEKA Integrated ontrol Equipment uro 4. ontrol panel, operations, commissioning 4.6 OMMISSIONING WIZARD There are two ways to start the wizard. 1. Press the question mark on the start screen. The question mark is not shown if the wizard has been started earlier. 2. hoose 2. Run ommissioning Wizard under Settings/Login Press 2.1 Start to get a step by step guidance through the settings needed during commissioning, or go directly to a specific menu to change a single value.

Integrated ontrol Equipment uro Supply air unit VEKA 17 4. ontrol panel, operations, commissioning Menu 2.2 refers to external exhaust fan if any. Option 2 - Use the numerical keypad, confirm with. option 1 option 2 There are two ways to change the fan speeds: Option 1 Press Trickle, Normal, Boost, the use ±1 or ±10 buttons Option 2 Press the values within the boxes adyescent to Trickle, Normal or Boost, then use the numerical keypad. When completed, press the confirm button to proceed to next step. Option 1 - Use ± buttons Make the appropriate settings for the supply fan.

18 Supply air unit VEKA Integrated ontrol Equipment uro 4. ontrol panel, operations, commissioning Enter desired temperature setpoint value. If using outdoor temperature compensation or room control also set the minimum and maximum temperature for the supply air. To end the commissioning wizard press the red cross button. Press the to continue to schedules. See section 9.7

Integrated ontrol Equipment uro Supply air unit VEKA 19 4. ontrol panel, operations, commissioning 4.7 Schedules The controller has three types of internal time schedules: Weekly, Single date and Date period. First, program the weekly schedule with the required times. Then use any single date programs and the period to enter exceptions. Each schedule also needs to be activated. This is done by pressing the grey tick button. A green tick indicates that the schedule is active. Priority When several enabled applications overlap, the following applies: Lowest priority Weekly 1 Weekly 8 Single date 1 Single date 4 Date period 1 Highest priority Date period 4 Weekly-schedule (1-8) By using a weekly schedule the unit can be programmed to operate at trickle, normal and boost speed alternatively stop. Example 1 Below is an example of a weekly schedule configured to run the fans at normal speed from 08.00 to 18.00 Monday to Friday. At all other times, the fans are turned off. Day Time Fan speed Monday 8 18 Normal Tuesday 8 18 Normal Wednesday 8 18 Normal Thursday 8 18 Normal Friday 8 18 Normal Other time Stop Only Weekly 1 should be activated.

20 Supply air unit VEKA Integrated ontrol Equipment uro 4. ontrol panel, operations, commissioning 4.7 Schedules, cont. Example 2 Below is an example of a weekly schedule configured to run the fans at normal speed from 08.00 to 18.00 Monday to Thursday, from 08.00 to 17.00 on Friday and 10.00 to 14.00 on Saturday. At all other times, the fans are turned off. Example 3 Below is an example of a weekly schedule configured to run the fans at normal speed from 08.00 to 18.00 Monday to Friday. At all other times, the fans are configured to run at trickle speed. At trickle speed the temperature set point will be decreased by two degrees. Day Time Fan speed Monday 8 1 8 Normal Tuesday 8 18 Normal Wednesday 8 18 Normal Thursday 8-18 Normal Friday 8-17 Normal Saturday 10 14 Normal Other time Stop Day Time Fan speed Temperature set point Monday 8 18 Normal 0 Tuesday 8 18 Normal 0 Wednesday 8 18 Normal 0 Thursday 8 18 Normal 0 Friday 8 18 Normal 0 Other time Trickle (Low) 2 1 Weekly 1 Fan speed Normal Temp set point Rel 0 1 Weekly 1 Fan speed Trickle Temp Setpoint Rel -2 From Mon To Fri Daily 08:00 18:00 From Mon To Sun Daily 00:00 23:59 2 Weekly 2 Fan speed Stop Tem Setpoint Rel 0 2 Weekly 2 Fan speed Normal Temp Setpoint Rel 0 From Fri To Fri Daily 17:00 18:00 From Mon To Fri Daily 08:00 18:00 3 Weekly 3 Only Weekly 1 2 should be activated. Fan speed Normal Temp Setpoint Rel 0 From Sat To Sat Daily 10:00 14:00 Only Weekly 1 3 should be activated.

Integrated ontrol Equipment uro Supply air unit VEKA 21 4. ontrol panel, operations, commissioning 4.7 Schedules, cont. Single date schedule (1-4) A single date schedule is defined as a one-off schedule that automati cally starts and finishes on the same date. Note!! Remember to enable the desired time channels by pressing Example The unit must be switched off on 6 June. Date period schedule (1-4) A date period schedule is defined as a one-off schedule that is configured to run between any two dates. Example The unit must be switched off between 24 December and 26 December.

22 Supply air unit VEKA Integrated ontrol Equipment uro 5. ONTROL FUNTIONS 5.1 HEATING AND OOLING The unit is configured differently regarding to heating and cooling, see below. HEATING No heater Electrical post heater Hot water coil OOLING No cooling Water DX, On/Off ontrol function The control function works as follows: Regardless of control mode the unit tries to achieve the desired setpoint. This is done by the unit depending on the needs, demand for heat recovery, heating or cooling. Built into the system is also a dead zone. The dead zone function (usually 2 ) acts as a temperature zone between heat recovery and cooling where neither calls for heat recovery or cooling. ontrol signal, % 100 50 Heating Sequence control Figure 1. The figure shows the controller s output signals to the various components at different temperatures. The zone between T1 and T2 is called the dead zone. ooling T0 T1 T2 T3 Temperature, 5.2 Temperature controls VEKA has two temperature control options, supply air, and room control. In addition it is possible to use outdoor temperature compensation. This control mode cannot be combined with room control. To obtain other control modes, first the controller must be changed from standard mode to cascade mode. Then control mode is selected by changing the cascade reference to room control (0) or outdoor temperature compensation (1). Below is a description of the different control modes. Supply air control To maintain a constant supply air temperature, the controller works with the setpoint and the supply air temperature. Based on these parameters, the current heating and cooling sequences are controlled. Room control Room control gives the best control of temperature in a specific room and is used when only one unit serves this room. This method works best for larger premises. This enables the unit to regulate the supply air temperature in a way that maintains the room temperature at a desired level. Limitation of the supply air temperature (min. temp. and max. temp.) ensures that the supply air temperature is maintained within the set range. Default parameters for room control 1. ontroller = 2 Selects cascade control 2. ascade reference = 0 Selects room control 3. ascade A = 0.5 When the sensor gets colder than given setpoint value 4. ascade B = 0.5 When the sensor gets warmer than given setpoint value 5. Min. temp. = 15 Sets lowest supply air temperature 6. Max. temp. = 25 Sets highest supply air temperature Example 1. Setpoint = 18 2. Room temperature = 22 This means that the new calculated setpoint for the supply air controller is: alculated setpoint = setpoint + (setpoint room air temperature) x cascade B = 18 (18 22) x ( 0.5) = 16.

Integrated ontrol Equipment uro Supply air unit VEKA 23 5. ONTROL FUNTIONS Outdoor temperature compensation The setpoint temperature for supply air can be adjusted up or down depending on the outdoor temperature. By setting a higher set point value both on cold winter days and hot summer days indoors comfort is improved. In summer, this will increase energy savings. Outdoor temperature compensation can not be combined with room control. Default parameters for outdoor temperature compensation 1. ontroller = 2 Selects cascade control. 2. ascade reference = 1 Selects outdoor temperature compensation. 3. ascade A = 0,05 When the sensor gets colder than given setpoint value. 4. ascade B = 0.03 When the sensor gets warmer than given setpoint value. 5. Min. temp. = 15 Sets lowest supply air temperature. 6. Max. temp. = 25 Sets highest supply air temperature. Setpoint +30 +25 +20 +15 20 15 10 Outdoor temperature compensation 5 0 5 10 15 20 25 30 35 Outdoor temperature, Example 1 1. Setpoint = 18 2. Outdoor air temperature = 2 This means that the new calculated setpoint for the supply air controller is: alculated setpoint = setpoint + (setpoint outdoor air temperature) x cascade A = 18 + (18 (-2)) x 0.05 = 19 Example 2 1. Setpoint = 18 2. Outdoor air temperature = 28 This means that the new calculated setpoint for the supply air controller is: alculated setpoint = setpoint + (setpoint outdoor air temperature) x cascade B = 18 (18 28)) x 0.30 = 21. 5.3 Freeze protection Warning! Do not change these parameters unless it is absolutely necessary. If the unit is misconfigured the water coil can freeze up and cause water damage to property. Freeze protection is used during low outdoor temperatures to prevent the coil from freezing. When the unit is stopped, the temperature in the water coil is maintained at the setpoint to keep the unit warm. If there is a risk of freezing in the water coil the valve is controlled to open. If the temperature drops below the limit value an A-alarm is obtained, which then stops the unit. 5.4 Fan control 3-speed control (trickle, normal, boost). To change fan speed use schedules, external timer or PIR.

24 Supply air unit VEKA Integrated ontrol Equipment uro 6. ommunication The unit can communicate with a Building Management System (BMS) via Modbus (RS485 and TP/IP). No other protocols are supported. 6.1 MODBUS, RS485 See table below for connection of Modbus. For more information, see the separate Modbus ins omponent Terminal onnection Note Modbus, RS485 Modbus 47 48 49 REF - A - B 6.2 MODBUS, TP/IP The unit has a built-in Ethernet card for connection to a LAN. onnect the Ethernet cable (RJ45) to the connector on top of the unit. 6.3 WEBSERVER There is a built-in webserver in the uro control system. This makes it possible to read and change parameters via a web browser. To read or change the IP-address, enter menu 8.1.

Integrated ontrol Equipment uro Supply air unit VEKA 25 7. Parameter list Incorrect parameter settings may cause malfunction and freezing damage in hot water coil. Therefore all settings has to be made by persons with necessary knowledge. Temperature Status Parameter Type of value 1) Range Unit Default value omments Supply air R 40-100 Outdoor air R 40-100 Extract air R 40-100 Freeze protection R 40-100 For unit with Hot Water oil Set point R/W 15-35 19 Summer / Winter mode R Summer / Winter Output signal, Post Heater R 0-100 % Output signal, Pre Heater R 0-100 % Not for VEKA Output signal, Heat Recovery R 0-100 % Not for VEKA Output signal, ooling R 0-100 % ontrol mode/alculated Set point R 15-35 Fan status Parameter Type of value 1) Range Unit Default value omments Supply Fan, speed R 0 or 15-100 % Exhaust Fan, speed R 0 or 15-100 % Air quality Parameter Type of value 1) Range Unit Default value omments O 2 value R 0-2000 ppm Not for VEKA System overwiev Parameter Type of value 1) Range Unit Default value omments Software version, ontrol panel R Bootloader version, ontrol panel R Software version, ontrol board R Bootloader version, ontrol board R Unit type R VEKA IP Octet 1 R 0-255 Actual IP address, accessory IP Octet 2 R 0-255 IP Octet 3 R 0-255 IP Octet 4 R 0-255 Schedules Parameter Type of value 1) Range Unit Default value omments Schedules R Active schedules, read only 1) R/W = Read and write value, R = Read only value

26 Supply air unit VEKA Integrated ontrol Equipment uro 7. Parameter list Settings Parameter Type of value 1) Range Unit Default value omments Set Date and Time R/W Set Language R/W Swedish Login R/W 0000-9999 0000 For installers and Service personnel Settings For installers and Service personnel 1. Schedule See section 4.7. 2. ommissioning Wizard See section 4.6. 3. Timer ontrol Timer control R/W 1-6 1 See section 2.7 Timer Release Delay R/W 0-9999 min 0 4. Fan ontrol 4.1 Fan settings Boost Running Timer R/W Yes / No No Boost Running Time R/W 0-9999 min 120 Startup Time R/W 0-32767 s 15 Shut Down Time R/W 0-32767 s 0 300 sec for unit with Electrical heater Fireplace R/W 0-360 min 30 Not för VEKA 4.2 OP / AV Not för VEKA 5. Heating / ooling 5.1 Pre Heater Not for VEKA 5.2 Heating/ooling Temperature control option R/W 1-2 1 1 = Standard, supply air control. See section 5.2 2 = ascade control See section 5.2 Minimum Supply temp R/W 15-35 15 Maximum Supply temp R/W 15-35 25 ooling sequence R/W Yes/No No ooling DX R/W Yes/No No Dead zone ooling R/W Yes/No Yes Dead zone R/W 0-25 2 Block cooling in Winter R/W Yes/No Yes Block heating in Summer R/W Yes/No Yes Post Heater R/W Yes/No Yes ascade reference R/W 0-1 0 0 = Extract air control 1 = Outdoor air compensation ascade A R/W 10-10 0,5 ascade B R/W 10-10 0,5 Relative / Absolute temperature R/W rel/abs rel Relative or absolute temperatures in Schedule 5.3 Night ooling Not for VEKA 5.4 Defrosting Not for VEKA 5.5 ooling Recovery Not for VEKA 5.6 Summer / Winter mode urrent season mode R Summer / Winter Automatic/Manual mode R/W Auto / Manuellt Auto Manual Summer / Winter mode R/W Summer / Winter Winter 1) R/W = Read and write value, R = Read only value

Integrated ontrol Equipment uro Supply air unit VEKA 27 7. Parameter list Parameter Type of value 1) Range Unit Default value omments 5.7 Frost protection See section 5.3 Pump stop R/W Yes/No Yes No = Pumps always running Pump Stop mode R/W 1) R/W = Read and write value, R = Read only value Summer / Winter Heating / ooling Heating / ooling onstant temp Hot Water oil R/W 0-50 25 Low limit running temp, Set point R/W 0-50 12 Frost Protection Alarm, Set Point R/W 0-50 7 6. Air quality 6.1 O 2 ontrol Not for VEKA Heating/ooling = Heating pump is running when there is a heating demand. ooling pump is running when there is a cooling demand. Summer/Winter = Heating pump is running when the unit is in winter mode. ooling pump is running when the unit is in summer mode. Exercise of pumps every day at 12.00-12.05. 7. Alarm onfiguration 7.1 Alarm Settings Dirty Filter alarm time R/W 0-600 days 0 Set to 0 to deactivate the filter alarm A and B on first Relay R/W Yes / No Yes Enable temperature alarm R/W Yes / No Yes Temperature alarm R/W -10 - +10 5 Activate test of RHE belt R/W Yes / No No Not for VEKA 7.2 Alarm cathegorys Fire Alarm R/W A/B A External function Sensor Error Supply air R/W A/B A Sensor Error Outdoor air R/W A/B A Sensor Error Extract air R/W A/B A Sensor Error Frost Protection R/W A/B A For unit with Hot Water coil Sensor Error Defrost R/W A/B B Not for VEKA Sensor Error AI10 R/W A/B B Not for VEKA Supply Fan Error R/W A/B A Not for VEKA Extract Fan Error R/W A/B A Not for VEKA Dirty Filter Alarm R/W A/B B Not for VEKA Preesure switch RHE R/W A/B B Not for VEKA RHE Failure R/W A/B B Not for VEKA Filter Alarm Supply R/W A/B B Filter Alarm Extract R/W A/B B Not for VEKA Electrical Heater Error R/W A/B B Pump Heater Malfunction R/W A/B B Frost Protection R/W A/B B Alarm ooling R/W A/B B Pump ooling Malfunction R/W A/B B Temperature alarm R/W A/B A RHE belt alarm R/W A/B A Not for VEKA

28 Supply air unit VEKA Integrated ontrol Equipment uro 7. Parameter list Parameter Type of value 1) Range Unit Default value omments 7.3 Alarm Delays Fire Alarm R/W 0-9999 s 2 External function Sensor Error Supply air R/W 0-9999 s 5 Sensor Error Outdoor air R/W 0-9999 s 5 Sensor Error Extract air R/W 0-9999 s 5 Sensor Error Frost Protection R/W 0-9999 s 5 For unit with Hot Water coil Sensor Error Defrost R/W 0-9999 s 5 Not for VEKA Sensor Error AI10 R/W 0-9999 s 5 Not for VEKA Supply Fan Error R/W 0-9999 s 2 Not for VEKA Extract Fan Error R/W 0-9999 s 2 Not for VEKA RHE Failure R/W 0-9999 s 2 Not for VEKA Filter Alarm Supply air R/W 0-9999 s 60 Filter Alarm Extract air R/W 0-9999 s 60 Not for VEKA Electrical Heater Error R/W 0-9999 s 2 Pump Heater Malfunction R/W 0-9999 s 2 Frost Protection R/W 0-9999 s 2 Alarm ooling R/W 0-9999 s 2 Pump ooling Malfunction R/W 0-9999 s 2 Temperature alarm R/W 0-9999 min 10 RHE Belt Alarm R/W 0-9999 s 60 Not for VEKA 7.4 ontact function DI1 Timer 1 R/W NO/N NO DI2 Timer 2 R/W NO/N NO DI3 RHE Rotation Guard R/W NO/N NO Not for VEKA DI4 Defrost pressure switch R/W NO/N NO Not for VEKA DI5 Filter Alarm Supply air R/W NO/N NO DI6 Filter Alarm Extract air R/W NO/N NO Not for VEKA DI8 Fire Alarm R/W NO/N N DI9 ooker Hood R/W NO/N NO Not for VEKA DI7 Alarm Heater R/W NO/N NO N with Electrical Heater DI10 Alarm cooling R/W NO/N NO 8. onfigure 8.1 IP Address R/W Static / Dynami Dynamic Subnet mask R/W Gateway R/W Static = Manual Dynamic = Automatic via DHP 8.2 Menu configure Log to USB R/W Yes / No No Only for troubleshooting Unit Type R eo Top Auto logout time R/W 0-32767 min 10 Threshold Heater R/W 0-100 % 0 For Installers and Service Personnel Threshold ooling R/W 0-100 % 0 For Installers and Service Personnel Threshold Heat Exchanger R/W 0-100 % 0 For Installers and Service Personnel Threshold External Fan R/W 0-100 % 5 For Installers and Service Personnel 8.3 Screen saver Screensaver R/W On/Off On Timeout R/W min 10 8.4 Modbus BMS Modbus Slave Address R/W 0-255 2 Baudrate R/W 9.6, 19.2, 38.4 19,2 Parity R/W None, Even, Odd None Data bits R/W 7,8 8 Stop bits R/W 1,2 1 1) R/W = Read and write value, R = Read only value

Integrated ontrol Equipment uro Supply air unit VEKA 29 7. Parameter list Parameter Type of value 1) Range Unit Default value omments 8.5 Mac address Mac address R 8.6 Reset 8.6.1 Soft reset Reset All values are reset except adjusted air flows and setpoints 8.6.2 Factory reset Reset All values are reset 8.7 Login settings Auto Logout R/W Yes/No Yes Set Password 1 R/W To change password 8.8 About Software Version ontrol Panel R Software Version ontrol Board R Bootloader version ontrol Board R 9. Save settings Saves adjusted values Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 10. Load settings Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Upload saved adjusted values from ontrol Panel 11. Save settings to SD opies saved values to SD Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 12. Load settings from SD Loads saved values from SD Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 13. Test For Service Personnel 13.1 Inputs 13.2 Outputs 14. Logout 1) R/W = Read and write value, R = Read only value

30 Supply air unit VEKA Integrated ontrol Equipment uro 8. Declaration of onformity Bilaga II A Försäkran om maskinens överenstämmelse Declaration of onformity med EG:s Maskindirektiv / with the EU Directive for Machinery, 2006/42/E EG:s EM Direktiv / with the (EM) Directive, 2014/30/EU EG:s Lågspänningsdirektiv LVD / with the Low Voltage Directive(LVD), 2014/35/EU EG:s Direktiv för energirelaterade produkter / EU Directive for Energy related Products ErP 2009/125/E Tillverkaren Fläkt Woods AB Manufacturer Fläktgatan 1 551 84 Jönköping Försäkrar härmed att: Herewith declares that: Produkten Typ / Type: Ventilationsaggregat / Ventilation Unit Product Fabrikat / Manufacturer: Fläkt Woods AB Varunamn / ommercial name: VEKA Maskinen är konstruerad och tillverkad i enlighet med följande standarder, i tillämpliga delar: The machine is designed and manufactured in accordance with the following standards, in relevant parts. EN ISO 12100 EN 60204-1 EN 61000-6-2 EN 61000-6-3 Maskinsäkerhet Allmänna konstruktionsprinciper Riskbedömning och riskreducering Safety of machinery General principles for design- Risk assessment and risk reduction Maskinsäkerhet Maskiners elutrustning, Del 1: allmänna fordringar Safety of machinery; electrical equipment of machines; general requirements Elektromagnetisk kompatibilitet (EM) - Del 6-2: Generella fordringar - Immunitet hos utrustning i industrimiljö Electromagnetic compability (EM) - Part 6-2: Generic standards Immunity standard for industrial environments. Elektromagnetisk kompatibilitet (EM) - Del 6-3: Generella fordringar - Emission från utrustning i bostäder, kontor, butiker och liknande miljöer. Emission standard for residential, commercial and light-industrial environments. För produkten har riskanalys upprättats enligt krav i Maskindirektivet. / A risk analysis has been made according to requirements of the Directive for Machinery. Behörig Authorized Att sammanställa teknisk dokumentation: To prepare technical documentation: Ann-Sofie Andersson Konstruktion / Design Fläkt Woods AB, Housing Gesällgatan 17 745 39 Enköping Försäkran gäller endast om installation av aggregatet skett enligt Fläkt Woods instruktioner och förutsatt att inga ändringar gjorts på aggregatet. The declaration applies only to the installation made according to Fläkt Woods instructions and assuming no changes made to the unit. Enköping 2016-08-31 Matthias Junker, Produktionschef / Operations Manager, Fläkt Woods AB, Enköping Fläkt Woods AB Postal Address Street Address Telephone Telefax Reg. no: Fläkt Woods AB Fläktgatan 1 Nat 036-19 30 00 Nat 036-19 31 40 556239-2463 S-551 84 Jönköping Int +46 36 19 30 00 Int +46 36 19 31 40 Reg. office: Sweden Jönköping 99679967SE_GB_VEK_ Declaration of onformity(2a)201608.doc

FWG-VEKA ver ontrol equipment-gb-2016.09.27 9965GB opyright 2016 Fläkt Woods Group We bring better air to life www.flaktwoods.com VEKA ver 9965GB 20160927 With over a century of innovation and expertise to share with our customers, Fläkt Woods is a global leader in Air Technology products and solutions. We specialize in the design and manufacturing of a wide range of products and solutions for Air Movement, Air Treatment, Air Distribution, Air Management and Air Diffusion with focus on two major benefits Air omfort and Fire Safety. With market presence in 65 countries we are in a unique position to be a local supplier and an international partner in our customer s projects. Our product brands such as SEMO, eq, eq Prime, JM Aerofoil, Econet, Veloduct, Optivent, Optimix, Econovent and leanvent are well-known and trusted by customers all over the world to deliver high quality and energy efficient solutions.» To learn more about our offering and get in contact with your nearest sales representative please visit www.flaktwoods.com