INSTALLATIONSANVISNING INSTALLATION MANUAL INSTALLATIONS ANLEITUNG. LD-64 Profibus

Similar documents
INSTALLATIONSANVISNING INSTALLATION MANUAL INSTALLATIONS ANLEITUNG LD-64F

4120 Fire Alarm Network Reference

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting. Features. Operation.

Engineering Guideline. pac- Carriers Type Universal

EOTec 2C32 Installation Guide

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual

T3/E3 Fiber Optic Line Drivers

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for 4120 Network. UL, ULC, CSFM Listed; FM Approved* Features

Engineering Guideline. pac-carriers Type SIEMENS ET-200M Fail-safe signal modules

4 Channel Contact Closure SFP DIN Fiber Link System

RC801/803/ B 16E1 Fiber-Optic Multiplexer (Rev. M) User Manual. Raisecom Technology Co., Ltd. (04/2005)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

MT-RJ Optical Fiber System Field Testing

4-Channel Contact Closure Fiber Link Card System

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

21-light Remote Annunciator. Owner s Manual

SACE PR021/K SIGNALLING UNIT

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

Simplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed*

AUTO SWITCH ALARM PS1 PS2 CH2 MANUAL REMOTE HISTORY ALARM ONLINE AUTO MANUAL SELECT SWITCH RESET

Single Channel Video Receive Unit with two Bi-directional Data Channels and one Bi-directional Alarm Channel for a Multimode Fibre Link

VPS3 Installation Manual

Panel Mounted Fault Annunciator Series

IF-L/RF Protection Switch

1.7. Insulation fault evaluators EDS460/490 EDS461/491

5.1 Safety instructions for system configuration and explosion protection. Zone-specific conditions for system configuration

M2500 Engine Controller Installation Manual

REA 105 Arc Protection Module. Operator s Manual

EOTec 2000 ControlNet Fiber Optic SHR/DSHR Communications Modules* With Support for Single and Dual Channel Self-Healing Rings

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

Universal fault annunciator for panel mounting

Single phase solid state contactors ENG. User Manual DATA MANAGEMENT CONTROLS PROCESS AUTOMATION

Dual System with 2x Independent Channels each of :

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Engineering Guideline. pac-carriers Type for TRICON system TRICONEX TMR PLC

PROFIBUS Optical Bus Terminal (OBT) SIMATIC NET. PG/PC - PROFIBUS PROFIBUS Optical Bus Terminal (OBT) Introduction 1. Components of the product

On the job around the clock 24/7: Fire detection systems

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Window facia fault annunciators

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Four channel video link For low cost video transmission

Panel Mounted Fault Annunciator Series

IQ-Sense. 2/2 Introduction. 2/3 IQ-Sense photoelectric sensors. 2/5 IQ-Sense ultrasonic sensors. 2/6 4 IQ-Sense sensor module for ET 200S

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

UEZ 2000/1 LSN, UEZ 2000 LSN, Intrusion Control Centers

RS485 MODBUS Module 8AI

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O. Assembly

Single Channel Video Transmit Unit with one Bi-directional Data Channel and two Uni-directional Alarms for a Multimode Fibre Link

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Fratech Multipath-IP

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

User manual. ABB i-bus EIB. Zone Terminal MT/S Intelligent Installation System ABB STOTZ-KONTAKT

8-port Unmanaged Industrial Ethernet Switch Hardware Installation Guide

Instruction Manual Model L2 RF Switch

Insulation fault evaluator EDS460-DG

Interface and EOL Modules 8

5000 INSTALLATION GUIDE

HRX Technical Manual. Version 1.2

RION ORION TELECOM NETWORKS INC. E2, 2Mbps x 4 Opti-Multiplexer Integrated E2, OLTE and Multiplexer. Product Brochure & Data Sheet TELECOM NETWORKS

ECO N DATE DESCRIPTION OF CHANGE CHG

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

FIRERAY 5000 range USER GUIDE

M7100 Pressure Transducer

PROFIBUS-PA Display RID 261 PROFIBUS-PA

STATUS ALARM HISTORY ALARM RESET

U86B. Urea Dosing SPECIFICATIONS FEATURES APPLICATIONS

FLAME AMPLIFIER MODULE 3001

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

Analog Input Module IC670ALG630

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

600 Range Dialer Installation Manual. Version 1.0

PTE0705 Electric Fence Monitor

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Instruction Manual Model Backup Switch, 1 for 8

G4 Pulsed Fiber Laser

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

SPACE DETECTOR SP Presentation

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

CCU Family of Modules

OPERATION / INSTALLATION

FCX-11AB5-3XX-XX 155Mbps BIDI SFP TRANSCEIVER(100Km)

P2267 NETWORK INTERFACE

VM-3000 SERIES INTEGRATED VOICE EVACUATION SYSTEM

Instruction Manual SCD24. Read this document prior to installation. Contents

Analog Annunciator Unit SACO 16 A3. Product Guide

HD COMMUNICATOR. Features & Benefits: Unique continuous Redundant Routing capacity. Up to 20km reach on a single copper pair.

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

IT system floor-standing distribution

Parameterisable compact fault annunciator with permanent display

Transcription:

LD-64 Profibus INSTALLATISANVISNING INSTALLATI MANUAL INSTALLATIS ANLEITUNG Galvanic Isolation 6073-2031 Transient Protection Balanced Transmission CE Approved Westermo Teleindustri AB 2001 REV. B Fiberoptiskt redundant modem Profibus, RS-485 Fibre-optic redundant modem Profibus, RS-485 Glasfaser redundante Leitungsteiler Profibus, RS-485 www.westermo.se

Specifications LD-64 Profibus Transmission Interface 1 Interface 2 Data rate Indicators Temperature range Humidity Dimension Weight Mounting Power supply alternatives Model description Asynchronous, full/half duplex or simplex EIA RS-485 / ITU-T V.11 Profibus standard 9-position D-sub alt. 5-position screw block Fibre optical 4 ST-connections 9.6, 19.2, 93.75, 187.5, 500, 1 500 kbit/s PWR, TD, ERR, RD, Tx1, Rx1, Tx2, Rx2 5 50 C ambient temperature 0 95% RH without condensation 55x100x128 mm (WxHxD) 0.4 kg On 35mm DIN-rail LD-64HV PROFIBUS LD-64LV PROFIBUS Power supply 95 240V AC ± 5% / 12 45V AC ± 5% / 110 240V DC ± 5% 12 55V DC ± 5% Frequency 48 62 Hz / 48 62 Hz / Fuse, F1 1 A T / 1 A T 1 A T / 1 A T Wickmann Wickmann Power consumption 30 ma 3 W Transient protection Power/Line Yes/ Yes/ Isolation, RMS Power supply 3 750 V 3 750 V LEDs for indication on LD-64 Profibus PWR: Indicates that the unit has power. ERR Indicates interruption on any fibre channel. TD: Indicates recevied data on Profibus/RS-485 side. RD: Indicates transmitting data on Profibus/RS-485 side. Rx1: Indicates received data on fibre channel 1. Rx2: Indicates received data on fibre channel 2. Tx1: Indicates sending data on fibre channel 1 from Profibus/RS-485 side. Tx2: Indicates sending data on fibre channel 2 from Profibus/RS-485 side. 12 6073-2031

Functional description LD-64 Profibus LD-64 offers redundant fibre optic communication between equipment with RS-485 interface. The unit is specially developed for Profibus and uses a Profibus standard 9-position D-sub for connection with RS-485. Possibility to connect to a 5-position screw block is also available. The fibre optic interface uses ST-connectors and both multi mode and single mode fibre versions are available. The maximum transmission distance is calculated from the available power budget of the modems and the attenuation of the cable, splice joints and connectors. Distances up to 25 km can be reached using single mode fibres. The LD-64 units are used in a ring connection and one unit is configured via switches as the master. The redundant logical system will control the flow of the data during fault conditions. If a break is detected on a fibre or pair of fibres the data will be re-routed. This operation will take approximately 4 ms and all data transmitted during this period will be lost and will need to be resent. The unit has indications for dataflow and also fault alarm outputs for each fibre optical channel which for example can control an external relay. The alarm outputs will be activated as long as the fault persists. As with all other Westermo products the LD-64 Profibus provides a high level of galvanic isolation on the power supply side through transformers and also on the alarm side through optocouplers. LD-64 Profibus can be used at all standard Profibus transmission speeds up to 1.5 Mbit/s and all operating parameters are set-up via DIP switches easily accessable under the lid on the top of each unit. LD-64 Profibus is available in low (LV) and high voltage (HV) versions. LD-64LV supports power supplies 12 45V AC ± 5% and 12 55V DC ± 5%. LD-64HV supports power supplies 95 240V AC ± 5% and 110 240V DC ± 5%. 6073-2031 13

Description of redundancy LD-64 Profibus is connected through two parallel fibre optical rings, ring 1 and ring 2. The ring topology introduces the possibility for the units to handle a fault on a fibre or a fibre pair and still maintain communication. The units will automatically change the communication path when a fault is detected. This change can take up to 4ms and all data sent during this time needs to be resent since the modems do not have any possibility to databuffer. One modem in the ring needs to be configured as master through switches inside the unit. The master controls the data and prevents data to be resent through the ring. The master is also used for monitoring of the fibre rings since all faults detected in the rings will be sent to the master. This gives possibility to monitor the complete system through the master unit. The other modems in the ring needs to be configured as slaves and will be transparent during normal communication. LD-64 Profibus is equipped with alarm signals which is used for indication of fibre interruptions. Each unit is equipped with two alarm ports, one for each fibre channel. These ports are marked as and on the unit. A fault will close the circuit between indications C and E on respective port. The alarm outputs can for example be used for connection of an external relay. See connection and examples on page 19 20. There is also a led indication for fibre interupption. This makes it easy to locate an interupption. An interruption will be detected by the closest unit which will indicate a receiver alarm and also send the error further to the master unit which will indicate a corresponding fault for the ring. For correct function the fibre optic rings needs to be connected correct between each modem Ring 1: Tx1 Rx2 Tx1 Rx2 etc. Ring 2: Tx2 Rx1 Tx2 Rx1 etc. 14 6073-2031

Below follows a number of different fault situations which shows the different alarm outputs. Link 1 x LD-64 Slave 1 LD-64 Master LD-64 Slave 2 LD-64 Slave 3 The receiver Rx2 at the master modem detects an interruption on ring 1. Alarm output indicates at the master unit. Link 2 Link 1 LD-64 Slave 1 LD-64 Master LD-64 Slave 2 LD-64 Slave 3 x The receiver Rx2 on slave modem 3 detects an interruption on ring 1. Alarm signal indicates at slave modem 3 and also at the master unit. Link 2 Link 1 LD-64 Slave 1 LD-64 Master LD-64 Slave 2 LD-64 Slave 3 x Link 2 The receiver Rx1 on slave modem 3 detects an interruption on ring 2. Alarm signal indicates at slave modem 3 and also at the master unit. x Link 1 LD-64 Slave 1 LD-64 Master LD-64 Slave 2 LD-64 Slave 3 x Link 2 The receiver Rx1 on slave modem 3 and receiver Rx2 on slave modem 1 detects interruptions. Alarm signal indicates on slave modem 3 and indicates on slave modem 1. Both and indicates at the master unit. LD-64 Slave 1 LD-64 Master LD-64 Slave 2 Link 1 LD-64 Slave 3 Link 2 6073-2031 Slave modem 3 stops working due to lack of power or other reason. Receiver Rx2 on slave modem 1 and receiver Rx1 on slave modem 2 detects interruptions. Alarm signal indicates on slave modem 1 and indicates on slave modem 2. Both and indicates on master modem. 15

Power budget Min. budget Typ. budget Unit Unit Fibre 820 nm 1300 nm single mode 50/125 10.7 db 8.1 db 62.5/125 14.5 db 11.6 db 100/140 20.6 db 9/125 6.3 db Fibre 820 nm 1300 nm single mode 50/125 16.6 db 14.6 db 62.5/125 18.6 db 15.1 db 100/140 25.9 db 9/125 12.3 db Min. budget states the minimum guaranteed power budget. Experience shows however that the typical value is in the range of the indicated Typ. budget. Attenuation in fibre cable The values below can differ depending on quality and manufacturer of the fibre optic cable. Fibre Attenuation at 820 nm Attenuation at 1300 nm Attenuation at single mode (1300 nm) 50/125 µm 3.0 db/km 1.0 db/km 62.5/125 µm 3.5 db/km 1.2 db/km 100/140 µm 4.0 db/km 9/125 µm 0.5 db/km Attenuation in connectors Attenuation in splice 0.2 0.4 db Fusion 0.1 db Mecanical 0.2 db 16 6073-2031

Switch settings LD-64 Profibus S1:1-9 :1-5 Selection of master/slave Selection of retiming S1 Slave S1 Retiming activated S1 Master S1 Retiming inactivated Please note that only one master can be used per system Retiming implies that the incoming data on fibre side will be retimed to an exact bitlength depending on configured transmission speed. This gives the possibility to connect an increased number of units in serie. Selection of data rate / Number of units Data rate Number of units S1 9.6 kbit/s 20 S1 19.2 kbit/s 20 S1 93.75 kbit/s 20 S1 187.5 kbit/s 20*) S1 500 kbit/s 20*) S1 1 500 kbit/s 20*) *) Active retiming Number of units is depending on the data rate and the total system, retiming (see S1:2) increases the number of possible units but also introduces a delay in the system. "Number of units" means a typical value that can be changed depending on the structure of the total system. 6073-2031 17

Selection of termination with fail-safe Selection of termination resistor No termination Termination cable type A (220Ω) Termination Termination cable type B (150Ω) The fail-safe function forces the received signal to inactive state when the connected transmitter is in tri-state (transmitter inactive). See cable types page 19 Selection of transmitted power channel 1 Selection of transmitted power channel 2 Low Low High High Factory settings S1 18 6073-2031

Connections LD-64 Profibus Line connection Connections Designation 9-pos D-sub pin no. 5-pos screw block pin no. Description T/R-P 3 8 Line connection P T/R-N 8 7 Line connection N VP 6 9 +5V supply DGND 5 6 Signal ground Cable types Designation Impedance Capacitance Resistance Conductor area Cable type A 135 165Ω (3 20MHz) <30pF/m <110Ω/km 0,34 mm 2 (22AWG) Cable type B 100 130Ω (>100kHz) <60pF7m 0,22 mm 2 (24AWG) Connection example Profibus DP/FMS Profibus DP/FMS 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 Connection to screw block-terminal Connection to 9-pos D-sub Power connections Connection LD-64LV Profibus 2-position screw-terminal Connection LD-64HV Profibus 3-position screw-terminal Screw no. Power supply Connection Power supply 1 Low voltage 2 + Low voltage L N O High voltage + High voltage Protective earth 6073-2031 19

Fibre optic connection Note! Always connect channel 1 to channel 2 RX1 RX2 LD-64 Profibus TX1 TX2 RX1 RX2 LD-64 Profibus TX1 TX2 RX1 RX2 LD-64 Profibus TX1 TX2 Profibus-DP/FMS Profibus-DP/FMS Profibus-DP/FMS 9 8 7 6 5 4 3 2 1 Transmitter (Tx1) Receiver (Rx1) Transmitter (Tx2) Receiver (Rx2) Alarm connections (Opto Link Monitor) Upon failure the circuit between the contacts C and E is closed. Please note that the maximum allowed voltage/current is 30 V / 80 ma. The alarm connection can for example be used to control an external relay. 9 8 7 6 5 4 3 2 1 Relay + Max 30 V, 80 ma In this example only channel 2 is connected. Under normal operation channel 1 and channel 2 should be connected. 20 6073-2031

OWN COMMENTS 6073-2031 21

1 2 3 4 5 6 7 8 9 R+ R- T+ T- T+ T- R+ R- CHANNEL 3 PWR DCD2 DCD3 DCD4 RD TD CHANNEL 4 CHANNEL 2 POWER R+ R- T+ T- 12-36V DC 1 2 3 4 5 - + 1 2 3 4 5 6 7 8 9 R+ R- T+ T- T+ T- R+ R- CHANNEL 3 PWR DCD2 DCD3 DCD4 RD TD CHANNEL 4 CHANNEL 2 POWER R+ R- T+ T- 12-36V DC 1 2 3 4 5 - + 1 2 3 4 5 6 7 8 9 R+ R- T+ T- T+ T- R+ R- CHANNEL 3 PWR DCD2 DCD3 DCD4 RD TD CHANNEL 4 CHANNEL 2 POWER R+ R- T+ T- 12-36V DC 1 2 3 4 5 - + 1 2 3 4 5 6 7 8 9 R+ R- T+ T- T+ T- R+ R- CHANNEL 3 PWR DCD2 DCD3 DCD4 RD TD CHANNEL 4 CHANNEL 2 POWER R+ R- T+ T- 12-36V DC 1 2 3 4 5 - + Application example Westermo Teleindustri AB SE-640 40 Stora Sundby, Sweden Phone +46 16 42 80 00 Fax +46 16 42 80 01 E-mail: info@westermo.se Westermo Web site: www.westermo.se Westermo Data Communications Ltd Unit 14 Talisman Business Centre Duncan Road Park Gate, Southampton SO31 7GA Phone: +44(0)1489 580 585 Fax.:+44(0)1489 580586 E-Mail: sales@westermo.co.uk Web: www.westermo.co.uk Westermo Data Communications GmbH Goethestraße 67, 68753 Waghäusel Tel.: +49(0)7254-95400-0 Fax.:+49(0)7254-95400-9 E-Mail: info@westermo.de Web: www.westermo.de Subsidiaries Westermo Data Communications S.A.R.L. 9 Chemin de Chilly 91160 CHAMPLAN Tél : +33 1 69 10 21 00 Fax : +33 1 69 10 21 01 E-mail : infos@westermo.fr Site WEB: www.westermo.fr Westermo Teleindustri AB have distributors in several countries, contact us for further information. 6073-2031 01.11 Mälartryck AB, Eskilstuna, Sweden