AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH WITH ADDITIONAL TEMPERATURE SWITCH

Similar documents
AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH. Manual Number: LX-SPDT A

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH. Manual Number: LX-DualSP A

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH WITH ADDITIONAL TEMPERATURE TRANSMITTER

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM FX SERIES FLOW SWITCH WITH ADDITIONAL TEMPERATURE SWITCH. Manual Number: FXTX2116-1

FLT93 Installation, Operation and Troubleshooting Guide

Electronic Flow Switches

Instruction Manual. Princo Model L3522. Point Level Controllers with LEVEL SENTRY. Rev 2, June 2013

GAS MONITOR Model Model

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual

RK CO 2 Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

CT-7 Series Toxic Gas Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

Sapphire. Ultrasonic Point Level System User Guide P/N Part of Thermo Fisher Scientific. Revision C

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

RK-02 Multi Point Detector Operator s Manual

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

Once the sensors are mounted and connected to the EGI-RLC-MM, each sensor needs to be adjusted as follows:

Installation, operation & service manual. AlarmScout 961/962 line powered

RK/ RK Oxygen Detector Operator s Manual

INTRODUCTION / TABLE OF CONTENTS

Thermo Flo With Compact Junction Box AT17, AT18, AG17 & AG18 Series Manual

Gas Fired Humidifier. SKG Series Combustion Field Adjustment Instructions. SKG Combustion Field Adjustment Instructions

RK Combustible Gas Transmitter Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual

Instruction Manual WARNING

TEMPERATURE CONTROLLERS

CR7075 Two-Stage Lighting Controller

Once the sensors are mounted and connected to the EGI-RLC-MM, each sensor needs to be adjusted as follows:

RK-05 Carbon Monoxide Transmitter Operator s Manual

Ultrasonic Point Level Switches

RK Multi Point Detector Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

T7079A,B Solid State Remote Temperature Controllers

Installation, Operation & Maintenance Manual

Quick Start Manual July pointek CLS100

CH cleaning head Sensor cleaning accessory operated by compressed air

FAN POWERED VAV TERMINALS

MST, INC. MODEL 2002 CARBON MONOXIDE MONITOR (AMBIENT-TYPE) OWNER S MANUAL

RK / RK Methane Detector Operator s Manual

Ultrasonic Switches. Features & Benefits

Public Safety DAS Annunciator Panel

RK/ RK Carbon Monoxide Detector Operator s Manual

III. 99 Washington Street Melrose, MA Phone Toll Free Visit us at OPERATING INSTRUCTIONS

ENERVEX ADC100 DRAFT CONTROL

ADC150 Automatic Draft Control

RK/ RK Oxygen Detector Operator s Manual

Controllers. Instruction Manual WARNING

MICRO GROW GREENHOUSE SYSTEMS, INC ZEVO DR., SUITE B-1, TEMECULA, CA PHONE (951) FAX (951) Growmate Growmate Plus

VEHICLE EXHAUST DETECTOR

Instruction Manual Model A

LAKEWOOD INSTRUMENTS MODEL 353 ORP/MILLIVOLT CONTROLLER

RES-210 (-211, -220, -221) / RES-420

Familiarization with the Training System

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Water Leak Detector. Installation and Troubleshooting. Overview

RK-03 Hydrogen Detector Operator s Manual

INSTALLATION, OPERATION INSTRUCTIONS FOR FLOW SWITCHES 62-9FS & FS

5245 / Thermotouch 4.3dC. Dual Control Thermostat. Installation & User Guide

Operations Manual. Motion Detector Module Model ZS10

MST, INC. MODEL 2002 OXYGEN MONITOR (AMBIENT-TYPE) OWNER S MANUAL

Duct and Rough Service Carbon Monoxide Sensor

TABLE OF CONTENTS Flow Detect 1000 Specifications 3 Description 4 Principle of Operation 4 Detection Through Walls 4 Sensing Beam Shape 4 Installation

RK/ RK Combustible Gas Detector Operator s Manual

CP CP

PACKAGED UNITS KITS AND ACCESSORIES 10/2009 INSTALLATION INSTRUCTIONS FOR SMOKE DETECTOR KITS USED WITH KC/KG/KH & LCH/LGH UNITS

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

SC2000 CONTROLLER INSTALLATION AND OPERATION MANUAL

MBCE-110/230UV Flame Sensor Module

Exercise 2-4. Heat Exchangers (Optional Exercise) EXERCISE OBJECTIVE DISCUSSION OUTLINE. Description of a brazed plate heat exchanger DISCUSSION

Installation and Operations Manual

Thermal Dispersion Flow, Level, Granular Solids & Temperature Switch

5800 Refrigerator Compressor Capacitor/Relay Kit

Switch-Pro. AU13 & AZ13 Series Owner s Manual. w/ Compact Relay Controller

MODEL AC-SCC-5 INSTALLATION, OPERATION & MAINTENANCE MANUAL

PUTTING A WATER FILTRATION OR WATER SOFTENER SYSTEM IN BYPASS

CabLite Luminous Auto Light Control Installation Manual

SMOKELESS INDOOR GRILL & INDUCTION STATION WITH TRIVET

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

RK Transmitter Technical Notice

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL

Hi-Temp Bath Installation and Operation Manual

Ultraviolet Monitoring System. Part Numbers UV/MS-1 V3 UV/MS-2 V3. Installation And Operations Manual

T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat

CX-29. Section 1 General Description. Section 2 Installation. Besam Switching Network & Bi-Directional Door Sequencer Installation Instructions

IMPORTANT BATTERY SAFETY INSTRUCTIONS, READ FIRST

TT /97 WARNING WARNING WARNING INSTALLATION INSTRUCTIONS

RESISTRON. Replacing RES-102/RES-420. Replacement Instructions. Comparison of RES-102 / RES-420. Dimensions. Temperature indication (actual value)

Sitron s CF Line of Flow Switch Monitors

DIGITAL CAP THE MAXX PRESS OPERATOR S MANUAL

Square D Clipsal Outdoor Light-Level Sensor

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS

Remote NAC Power Supply D7038

AirTrak. Digital Control System. User Manual. Touchscreen Systems

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ASTRO FF14 FRICTION FEEDER SERVICE MANUAL

Transcription:

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH WITH ADDITIONAL TEMPERATURE SWITCH Manual Number: LXTX-SPDT-2117-2-A 1185L Park Center Dr. Vista CA 92081 1-760-727-7273 1-800-910-6689 1-760-727-7151 Fax www.ameritrol.com 1

OVERVIEW This unique instrument is both a liquid level switch and a temperature switch. Both the liquid level and temperature switch points are independently adjustable as well as the corresponding relay energization. The LX series is an electronic point level switch that can be used for simple wet/dry applications or interface applications that are otherwise difficult to detect for other technologies. LX level switches can be used to detect the interface from air/gas and liquids, air/gas and foam, foam and liquids, liquid to liquid interfaces such as oil and water, and solids in a liquid. The device senses the thermal conductivity of the product surrounding the probe. The greater the thermal conductivity the lower the resulting signal output. For example: Air has a low thermal conductivity and a high signal output and water has a high thermal conductivity and low signal output (see table in Operation section). Some users may find it beneficial to perform a bench calibration before installation. This can be accomplished by obtaining a small sample of the product (assuming the product is safe to handle) and immersing the level sensor into and out of the product while following the steps listed in the Calibration section outlined below. The additional temperature switch is designed to detect the increase or decrease of temperature. Please refer to attached wiring diagram for DIP switches and relay energization switch settings (S1 & S2). The level switch factory default settings are configured for liquid level and relays energized when wet. To change from factory default to relay energized when dry: Reverse red slide switch (S1). The application settings switch for temperature is configured as Switches 1 and 2 are off and switches 3 and 4 are on. The temperature switch factory default is configured for relay energized below set point. To change from factory default relay energization to relay energized above set point: Reverse red slide switch (S2). Power input and relay rating are written on the board. The potentiometer referred to in this manual is a 25 turn multi-turn potentiometer. The potentiometer cannot be damaged by overturning in either direction. INSTALLATION Conduit Recommendation: Do not place level/temperature switch at low point of conduit, because moisture can collect at the low point. A conduit seal may be beneficial in preventing moisture from entering the enclosure and damaging the electronics. SIDE MOUNTED- This point level/temperature switch can be mounted directly into the tank or vessel or in a stand pipe parallel to the vessel. It is recommended that the probe extend into the stand pipe or vessel when used with highly viscous products. A half coupling or thread-o-let attached to the side of the tank or vessel will allow proper insertion. The flats on the sensor can be placed in any orientation but should remain constant once calibration has been done. TOP MOUNTED- The level/temperature switch can be top mounted directly to the tank or vessel. It is recommended a potting Y be used on the conduit connection to prevent moisture/condensation from filling the enclosure. The flats on the sensor are for reference only and should remain constant after calibration WIRING- See attached drawing for wiring details. 2

OPERATION The level switch operates by primarily detecting the thermal conductivity of the product surrounding the probe. Air and gases are poor conductors of heat and will create the largest signal output from the sensor. A liquid is a greater conductor of heat than air and will provide a lower output. The following table lists typical product types and their relative output. High Signal Output Field Adjustable Set-Point Low Signal Output AIR FOAM OIL/ORGANIC EMULSION WATER SOLIDS IN LIQUIDS The field adjustable set-point can easily be set to detect interfaces between products with different thermal conductivities. The relay output can be field selected to be energized when the sensor head is wet or dry. The factory default is for the relay to be energized when wet and can be changed by switching the relay energization switch (S1) as shown on the attached wiring diagram. CALIBRATION STARTUP 1. Power the instrument and allow 3 minutes for the sensor head to reach equilibrium. 2. Remove the housing cover observing the safety precautions associated with the area in which the unit is mounted. LIQUID LEVEL SWITCH CALIBRATION The instrument is factory set to detect a wet (water) / dry condition with relay energized when wet. For other applications and relay energization follow steps that correspond with your relay energization requirement. In applications where it is difficult to change the product level, the following calibration steps may be performed before installation. This can be accomplished by immersing the level sensor into and out of a product sample while following the steps listed in the Calibration section outlined below. This is not necessary, but may be easier in certain situations. RELAY ENERGIZED WHEN WET (factory default) It is assumed that the user will have the relay energized when wet (or in product with low signal output) and will alarm (relay de-energize) when dry (or in product with higher signal output). Please refer to attached wiring diagram for relay energization switch setting. Adjust the potentiometer (R22 on the wiring diagram) on the circuit board until the red LED changes state, as 3

If the LED is on: Turn the potentiometer clockwise. If the LED is off: Turn the potentiometer counterclockwise. Once the red LED on/off location is determined, turn the potentiometer as If the sensor is currently exposed to a product that provides a high output, (as described in operation section) turn the potentiometer clockwise (per product listed below) past the point the red led turns off as Air to Liquid (water): 4 turns Air to Liquid Organics/hydrocarbons: 2 turns Liquid Organics/hydrocarbons to Water: 1 turn Emulsion to Water: 1 turn If the sensor is currently exposed to a product that provides a low output (as described in operation section), turn the potentiometer counterclockwise (per product listed below) past the point the red led turns on as Liquid (water) to Air: 2 turns Liquid Organics/hydrocarbons to Air: 2 turns Water to Liquid Organics/hydrocarbons: 1 turn Clean liquid to Solids in liquid: 1/2 turn RELAY ENERGIZED WHEN DRY (field change of relay energization switch) It is assumed that the user will have the relay energized when dry (or in product with higher signal output) and will alarm (relay de-energize) when wet (or in product with low signal output). Please refer to attached wiring diagram for relay energization setting. The relay energization switch (red slide switch: S1) will need to be changed from the factory default setting. Adjust the potentiometer (R22 on the wiring diagram) on the circuit board until the red LED changes state, as If the LED is on: Turn the potentiometer counterclockwise. If the LED is off: Turn the potentiometer clockwise. Once the red LED on/off location is determined, turn the potentiometer as If the sensor is currently exposed to a product that provides a high output, (as described in operation section), turn the potentiometer clockwise (turns per product listed below) past the point the red led turns on as Air to Liquid (water): 4 turns Air to Liquid Organics/hydrocarbons: 2 turns Liquid Organics/hydrocarbons to Water: 1 turn Emulsion to Water: 1 turn If the sensor is currently exposed to a product that provides a low output (as described in operation section), turn the potentiometer counter clockwise (per product listed below) past the point the red led turns off as Liquid (water) to Air: 2 turns Liquid Organics/hydrocarbons to Air: 2 turns Water to Liquid Organics/hydrocarbons: 1 turn Clean liquid to Solids in liquid: 1/2 turn 4

TEMPERATURE SWITCH CALIBRATION The temperature switch uses the liquid level switch reference sensor as its primary sensor. Typically the temperature switch is set at the factory per customer specifications. To field calibrate expose the sensor to desired temperature set-point and adjust as shown below. Power the instrument and adjust as TO DETECT AN INCREASE IN TEMPERATURE (FACTORY DEFAULT): It is assumed that the user will have the relay energized below the set-point and will alarm (relay de-energize) on increasing temperature. Please refer to attached wiring diagram for relay energization programming. Adjust the potentiometer (R8 on the wiring diagram) on the circuit board until the red LED changes state, as If the LED is on: Turn the potentiometer clockwise. If the LED is off: Turn the potentiometer counterclockwise. Locate the point where the relay just turns on and the unit is calibrated. TO DETECT DECREASE IN TEMPERATURE: It is assumed that the user will have the relay energized above the set-point and will alarm (relay de-energize) on decreasing temperature. Please refer to attached wiring diagram for relay energization programming. The relay energization switch (red slide switch: S2) will need to be changed from the factory default setting. Adjust the potentiometer (R8 on the wiring diagram) on the circuit board until the red LED changes state, as If the LED is on: Turn the potentiometer counterclockwise. If the LED is off: Turn the potentiometer clockwise. Locate the point where the relay just turns on and the unit is calibrated. Technical service hours are Monday Friday from 8:00 AM to 4:30 PM Pacific Standard Time 5