KOG LN. Low Noise Chilled Water Cassettes Models 09, 12 & to 6.10kW to 5.10kW. 330 to 920 m3/h

Similar documents
KOG LN. Low Noise Chilled Water Cassettes Models 30 & 45

Refrigerant R407C CW-AR. 2.4 to 3.1kW. Water Source Heat Pumps - Vertical Mounting Version Models 07 to to 2.7kW

X X Packaged Air Conditioners - Vertical Units Air Cooled Models (AR) Water Cooled Models (AO) Refrigerant R407C to 18.

SYSEFTYS - SYSHRW THE. Water Source Heat Pumps Range N E W. Water cooled. Refrigerant R407C. from 2.1 to 30.0 kw. from 2.7 to 38.1 kw. models.

ELFODuct MP. Technical Bulletin. New generation horizontal and vertical built-in water-source ductable terminal for medium and large systems

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

CATALOG WATER SOURCE HEAT PUMPS

Packaged air conditioners vertical units

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

CASSETTE UNIT. Comfort Circle

HT V2 HT Split

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

THIN PROFILE CENTRIFUGAL FAN COIL UNITS SLIM

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX

Cassette units Model Comfort Circle. - heating - cooling - ventilation

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

consumption ECM motors NEW Low energy Cassette Fan Coil Units YHK ECM YHK

SkyStar SK-ECM. Cassette Fan Coil Unit with EC Brushless Electronic Motor and Inverter Board

SABIANA ENVIRONMENTAL COMFORT. Air Conditioning Futura Fan Coil Units ICIM

SPECIFICATIONS CWC - 2P / 4P CWC 020 CWC 030 CWC 040 CWC 050 CWC 070 CWC

FCX FAN COIL SILENT & EFFICIENT. Floor, ceiling & ducted installation Applicable with VMF management system, Plasmacluster filter option

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

CWX 6 - CWX 8 - CWX 10 CASSETTE TYPE TERMINAL UNIT

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

System architecture. Air treatment Index

Blower-YEFB-020-3R-1maxVel

DUCTED UNITS EBH EDS INTEGRATED COMFORT SYSTEMS

technical data Fan coil unit FWB small duct unit

QTS SELECTION TECHNICAL BOOKLET

Carisma Fly Carisma Fly-ECM. Made in. Italy. High Wall Fan Coil. Air Conditioning ENVIRONMENTAL COMFORT

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT

UniTrane Terminals. High Wall Fan Coil: W-Line Ducted Fan Coil: D-Line Blower coil: B-Line. Product Presentation September 2016

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSWALL. Wall mounted fan coil units

EHH SERIES DRAW THROUGH FAN COILS CFM

KLIMA Active Chilled Beams

Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing Create value to design better

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

SkyStar SK. Cassette Fan Coil Unit with Asynchronous Motor

Carisma Fly. Made in. Italy. Wall-mounted Fan Coil. Air Conditioning ENVIRONMENTAL COMFORT.

OMNIA RADIANT FAN COIL WITH RADIANT HEATING PANEL THE FAN COIL FEATURING 3 HEATING MODES

> Refrigerant R-410A. Uniflair LE TDER-TUER kW. Energy-saving units with backward-curved fans. Perimeter cooling for medium/large data center

ELFODuct MP. Technical Bulletin. New generation horizontal and vertical built-in water-source ductable terminal for medium and large systems

CHILLED BEAM CASSETTE IQ STAR LYRA

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

COMFORT HYDRONIC TERMINALS

WATER TO AIR DUCTABLE INDOOR HORIZONTAL HEAT PUMP

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

EXPAIR. Use. Precision air handling cabinets. Reducted footprint Dual-wall construction

42AM. Air heaters PRODUCT SELECTION DATA

50CO. Close Control Unit. Wide range of chilled water cabinets. Compact and attractive design. EC motor for energy savings. Auto-adaptive control

UCS UCS/M UCS/H UCS900

Advance Split

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

NEW. SkyStar SkyStar ECM. Cassette Fan Coil Units. consumption ECM motors. Low energy. Air Conditioning ENVIRONMENTAL COMFORT

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

Компрессорно-конденсаторные агрегаты. Chiller. AQH DCI 20 to 30. Air Cooled Water Inverter Heat Pump Engineering Data Manual. 20 to 30 kw.

QZHW Fan Coil Unit. Key features. Specifications

The technical and dimensional data reported in this manual may be modified in view of any product improvement.

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

Precision air handling cabinets Ciatronic MICRO/EXPAIR

NEW GREEN TECHNOLOGY

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

EEDEN technical data. Fan coil units FWV-FWL-FWM FWD FWB FWC FWF FWT

Centrifugal air heaters hot water or electrical supply

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

Application guide. ARMONIA ARMONIA EC 1,3-11 kw. Chilled water cassette Chilled water cassette - EC motor ARMONIA-AGU-1010-E

MAGISTER. Compact and attractive design Energy savings with EC motor and self-regulating control. Easy to install. Use. Chilled water operation

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

COMFORT APPLICATION HYDRONIC TERMINALS ELEGANCE AND DESIGN FOR YOUR RESIDENTIAL COMFORT

Air treatment units 0932EN October 2017 Dehumidifier unit for radiant systems Flush-mounting installation in false ceilings

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

QFDK "ägir II" chilled water cassette

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

KELVIN Clim F497. Kelvin air conditioning

FAN COIL UNITS LASER / LOW BODY / CONCEALED

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

Technical Manual. New Water Cassette. Series BREZZA DOUBLE

MODEL: ACWD CEILING CONCEALED Chilled Water Fan Coils Unit

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

Product Specifications. Vertical Floor Consoles By First Co.

INDUSTRIAL AIR CURTAIN. IndAC 2

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

Neosys Product catalogue

QZB "Standard" comfort fan coil

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

TECHNICAL DATA. F.H. Biddle B.V. P. O. Box 15, NL-9288 ZG Kootstertille,The Netherlands. Tel: Fax:

ART-U 1-4 kw. Design fan coil unit with a minimum depth of 10 cm only and BLDC motor. Fan coil ART-U PLUS. Design-driven innovation NEW

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

PYXIS U PYXIS U. rcgroupairconditioning

TopVent Design Handbook

Transcription:

KOG LN Low Noise Chilled Water Cassettes 09, 12 & 18 1.70 to 6.10kW 1.58 to 5.10kW 330 to 920 m3/h

KOG LN 9 / KOG LN 12 / KOG LN 18 Design Features Introduction The new low noise chilled water cassettes 09 LN to 18 LN offer a comfortable air conditioning with improved acoustic performance. Their design and their small dimensions allow them to fit harmoniously into the standard ceiling tiles of 600 x 600 mm size. These new cassettes have been specially designed for an easy and fast installation, as well as for a great ease of maintenance with a complete access to internal components through the return air grille. The chilled water cassettes are available in 3 sizes (K09OG LN, K12OG LN & K18OG LN) and in 3 versions (2-pipe, 2-pipe/2-wire and 4-pipe). Features and benefits As a result of new motor staging, the noise level has been reduced by 4 to 6 dba at low speed. The casing to be fitted into the false ceiling has a low profile (287 mm thick). Its dimensions as well as the incorporation of electrical box and control valves (optional) inside the unit, make its installation compatible with standard false ceiling tiles (600 x 600 mm size). The casing is made from galvanized steel sheet with thermal and acoustical insulation, eliminating condensations on the casing and providing low sound levels. The grille of RAL 9016 colour combines discharge and return with air filter; discharge manually ajustable on all four sides with possibility of closing one or two faces of discharge, return at the center. The coils are composed of copper tubes and aluminium hydrophilic fins ensuring a better condensate drainage and a better protection against corrosion. The coils of sizes K09OG LN and K12OG LN have 2 rows for 2-pipe and 4-pipe systems. Those of size K18OG LN have 3 rows for 2-pipe and 4-pipe systems. Prepunched holes for connection with fresh air intake and connection with a stub duct to treat air of adjacent room. In this case, it becomes necessary to provide a decompression in the adjacent room to allow air return on the cassette. Easy and quick access, by simply removing the front grille, to the internal components such as the coil, the fan-motor assembly, the condensate pump, the optional regulating valve(s) and the electrical box. All connections : water, electrical, condensate drain and air vent cock are located at the same side, on the exterior of the unit. Sliding electrical box is easily accessible after removing two screws. Electrical box has a junction block provided for quick connection on terminals without screws and a multi-output autotransformer supplied for eventual change of fan speeds (on site). Condensate pump supplied as standard, can be easily reached and removed by only one screw; electrical connection by pin type connector. The condensate pump provides a manometric lift up to 600 mm. The pump is, in addition, equipped with a high security level control system : it is concerning a 3-level detection float ("On", "Off" to avoid permanent operation, and "Alarm"). Control valves (factory-supplied option) mounted inside the casing to limit the works on site and the installation costs. Flexible hoses for connection on units with or without control valves. Filtration Cleanable synthetic type air filter (55 % arrestance, G1 class) accessible after opening the return grille. Fan-motor assembly Centrifugal turbine with direct drive. Motor resiliently mounted and equipped with internal thermal safety device. It can be dismounted by 3 screws and disconnection from electrical supply cable by pin type connector. The chilled water cassettes sizes K09OG LN, K12OG LN and K18OG LN can be supplied with 2 types of motor : The standard AC motor of direct drive type having 6 speeds, 3 of them are factory pre-wired. The motor is suitable for nominal voltage of 230 V / 1~ / 50 Hz and is equipped with a built-in normally closed thermal protection of automatic reset type. The EC motor of high efficiency and low electrical consumption type for a significant energy saving. The motor is suitable for 0-10 V input, ensuring variable speed capability. It is fitted with ECospeed3 interface card (supplied as standard) for a 3-speed optimized running. Electrical connection Fast connection on terminals without screws. Two cable glands are provided on the casing wall allowing to block the supply and control cables. Supply voltage : 230 V / 1~ / 50 Hz + Earth. Available accessories and options IRYS Diffuser the modern design of the IRYS diffuser combines aesthetics and a flat appearance to meet the architectural constraints: Perfect integration into the standard false ceiling, exterior dimensions 595x595. Metallic diffuser which keep colors over time. Epoxy paint RAL 9003 Air diffusion with Coanda effect: Air diffusion in 360 avoiding any dead air zones OR air diffusion in 180. When the air is blown from a point near the ceiling, the air stream is pressed against the ceiling and has an improve air throw. IRYS Diffuser uses this principle of air diffusion "Coanda effect" in order to ensure a homogeneous distribution of the air in the room with a high induction rate and reduced temperatures stratification (less than 1 C). Definition of a comfort zone which eliminates air flow phenomena and temperature stratification (speed of air below 0.15m/s). Air throw: The air throw is the distance between the cassette and the points where the speed of the spread air (approximately 0.2 m/s) is not longer felt by the human body. The IRYS diffuser possesses the blowing reach of air over of 5m in HS. Easy maintenance: Quick access to the filter. Access to internal components. Easy cleaning thanks to a perfectly smooth surface. Electric heater for use with 2-pipe/2-wire system It is composed of heating elements located inside the tubes of heat exchanger and is thermally protected against abnormal rises in temperature by two thermostats : automatic reset thermostat and manual reset one. Supply voltage : 230 V / 1 ph / 50 Hz + earth. Control valves Motorized valves, 2 ways and 3 ways with by-pass, factory-fitted option and incorporated inside the unit for 2-pipe and 4-pipe systems. Controls TRM-VP (kit), TRM-FA (kit), TAE 20 (kit), TAE 20 + SEH (kit), Aqu@Simp, Aqu@Net and IR remote control. 1

2 KOG LN 9 / KOG LN 12 / KOG LN 18 Advantages of Chilled Water Cassettes LN with EC motor Energy class with standard motor More efficient FCEER FCCOP K09OG LN K12OG LN K18OG LN K09OG LN K12OG LN K18OG LN 2-pipe 4-pipe 2-pipe 4-pipe Less efficient Energy class with EC motor More efficient FCEER FCCOP 2-pipe 4-pipe 2-pipe 4-pipe Less efficient 3-speed control interface for EC motor Aqu@Net Interface card 3 speeds EC motor 0 to 10 V ECoSpeed3

KOG LN 9 / KOG LN 12 / KOG LN 18 3 designation K12OGLN. 2P. EC. SYS. 1800W. N. NIU. 3W. I180 + FH 1 2 3 4 5 6 7 8 9 10 REP. Description 1 Size K09OGLN : KOG LN size 9 K12OGLN : KOG LN size 12 K18OGLN : KOG LN size 18 2 Coil 2P : 2 pipes 4P : 4 pipes 3 Fan type Blank : AC fan EC : EC fan 4 Brand SYS : SYSTEMAIR 5 Electric heater Blank : Without heater 1500W : Capacity 1500W 1800W : Capacity 1800W 2400W : Capacity 2400W 6 Regulation Blank : Terminal block D : Aquanet FCC controller 2 pipes/ without valve/cooling only E : Aquanet FCC controller 2 pipes/valve/ cooling only F : Aquanet FCC controller 2 pipes/ without valve/heating only G : Aquanet FCC controller 2 pipes/valve/ heating only H : Aquanet FCC controller 2 pipes/valve/ heating only/change over J : Aquanet 2 pipes/without valve/ heating only/change over L M N P Q : Aquanet FCC controller 4 pipes/valve : Aquanet FCC controller 2 pipes/ cooling only/electric heater : Aquanet FCC controller 2 pipes/ without valve/reversible cycle/ Change over : Aquanet FCC controller 2 pipes/valve/ reversible cycles/change over : Aquanet FCC controller 2 pipes/valve/ reversible cycle/change over/ electric heater 7 Option Aquanet NIU : µbms compatible communication board NIU for Aquanet eniu : Modbus communication board eniu for Aquanet 8 Valve Blank : Without valve 2W : 2 way valve 3W : 3 way valve 9 Facade Blanck : Standard plastic I360 : IRYS COANDA 360 I180 : IRYS COANDA 180 10 Option FH IR : Fuse holder : IR for Aquanet FCC controller NOECO : Without Ecospeed3 C/O : Change over

4 KOG LN 9 / KOG LN 12 / KOG LN 18 Technical Data KOG LN with AC motor Capacites - 2 pipe Cooling (1) K09OG LN K12OG LN K18OG LN S1/S2/S3 S1/S2/S3 S1/S2/S3 Total cooling capacity W 1580/1870/2250 2280/2570/3450 2770/3650/4530 Sensible capacity W 1230/1470/1750 1680/2020/2850 2120/2900/3780 Water flow l/h 280/330/400 400/450/600 480/640/790 Water pressure drop kpa 6/9/12 8/11/18 8/11/16 Heating (2) Heating capacity W 2100/2500/3100 2700/3200/4500 3300/4600/5700 Capacites - 4 pipe Cooling (1) Total cooling capacity W 1580/1870/2250 2280/2570/3450 2770/3650/4530 Sensible capacity W 1230/1470/1750 1680/2020/2850 2120/2900/3780 Water flow l/h 280/330/400 400/450/600 480/640/790 Water pressure drop kpa 6/9/12 8/11/18 8/11/16 Heating capacity W 1700/1900/2200 2200/2500/3330 3300/3950/4470 Heating (3) Water flow l/h 160/180/210 200/220/290 290/340/380 Sound levels - 2 pipe Water pressure drop kpa 3/4/5 7/9/13 19/27/31 Sound power level db(a) 34/40/52 34/40/50 41/49/57 Sound pressure level(*) db(a) 26/32/42 26/32/42 33/41/49 NR db(a) 20/27/37 20/27/37 28/35/43 Sound levels - 4 pipe Sound power level db(a) 34/40/50 34/40/50 43/49/57 Sound pressure level(*) db(a) 34/50/34 26/32/42 33/41/49 NR db(a) 26/42/26 20/27/37 28/35/43 Fans Number 1 1 1 Air flow - 2 pipe m³/h 330/450/720 330/450/720 410/580/830 Air flow - 4 pipe m³/h 330/450/720 330/450/720 410/580/830 Electrical data Power supply V/Ph/Hz 230V/1~/50Hz Absorbed power - 2 pipe W 20/30/50 20/30/50 30/46/71 Absorbed power - 4 pipe W 20/30/50 20/30/50 30/46/71 Electrical heater W 1500 1800 2400 Water connections type Gas male threaded 2 pipe or 4 pipe "Cooling" pouce 1/2" 1/2" 3/4" 4 pipe "Heating" pouce 1/2" 1/2" 1/2" Dimensions plastic facade Casing mm 571 x 571 x 287 571 x 571 x 287 571 x 571 x 287 diffuser mm 625 x 625 x 40 625 x 625 x 40 625 x 625 x 40 Casing mm 571 x 571 x 293 571 x 571 x 293 571 x 571 x 293 IRYS facade diffuser mm 595 x 595 x 34 595 x 595 x 34 595 x 595 x 34 Weight 2 pipe kg 26 28 29 4 pipe kg 27 28 29 (1) Nominal conditions : Air : 27 C/19 C wet bulb (nominal air flow in high speed). Chilled water : 7 C/12 C. (2) Nominal conditions : - In 2-pipe configuration : air : 20 C (nominal air flow in high speed); hot water : entering temperature 50 C (nominal water flow obtained in cooling mode). - In 4-pipe configuration : air : 20 C (nominal air flow in high speed); hot water : 70 C / 60 C. (3) Water pressure drops given for the corresponding nominal water flow on cassettes without control valves. (*) The sound pressure levels Lp are based on (NR) characteristic of a room having volume of 100m 3 with reverberation time of 0.5 seconds and a distance of 1 meter.

KOG LN 9 / KOG LN 12 / KOG LN 18 5 Technical Data KOG LN with EC motor Capacites - 2 pipe Cooling (1) K09OG LN K12OG LN K18OG LN S1/S2/S3 S1/S2/S3 S1/S2/S3 Total cooling capacity W 1590/1890/2270 1960/2220/2970 2790/3680/4560 Sensible capacity W 1240/1490/1770 1580/1910/2690 2140/2930/3810 Water flow l/h 280/330/400 340/384/513 480/640/790 Water pressure drop kpa 6/9/12 7/10/16 8/11/16 Heating (2) Heating capacity W 2100/2500/3100 2450/2910/4090 3300/4600/5700 Capacites - 4 pipe Cooling (1) Total cooling capacity W 1590/1890/2270 2290/2590/3470 2790/3680/4560 Sensible capacity W 1240/1490/1770 1690/2040/2870 2140/2930/3810 Water flow l/h 280/330/400 400/450/600 480/640/790 Water pressure drop kpa 6/9/12 8/11/18 9/11/16 Heating capacity W 1700/1900/2200 2200/2500/3335 3300/3950/4470 Heating (3) Water flow l/h 160/180/210 200/220/290 290/340/380 Sound levels - 2 pipe Water pressure drop kpa 3/4/5 7/9/13 17/24/28 Sound power level db(a) 34/40/50 37/40/50 40.5/49/57 Sound pressure level(*) db(a) 26/32/42 26/32/42 33/41/49 NR db(a) 20/27/37 20/27/37 28/35/43 Sound levels - 4 pipe Sound power level db(a) 34/40/50 34/40/50 40.5/49/57 Sound pressure level(*) db(a) 26/32/42 26/32/42 33/41/49 NR db(a) 20/27/37 20/27/37 28/35/43 Fans Number 1 1 1 Air flow - 2 pipe m³/h 330/450/720 330/450/720 410/580/830 Air flow - 4 pipe m³/h 330/450/720 330/450/720 410/580/830 Electrical data Power supply V/Ph/Hz 230V/1~/50Hz Absorbed power - 2 pipe W 8/11/26 8/11/26 9/23/41 Absorbed power - 4 pipe W 8/11/26 8/11/26 9/23/41 Electrical heater W 1500 1800 2400 Water connections type mâle fileté gaz 2 pipe or 4 pipe "Cooling" pouce 1/2" 1/2" 3/4" 4 pipe "Heating" pouce 1/2" 1/2" 1/2" Dimensions plastic facade Casing mm 571 x 571 x 287 571 x 571 x 287 571 x 571 x 287 diffuser mm 625 x 625 x 40 625 x 625 x 40 625 x 625 x 40 Casing mm 571 x 571 x 293 571 x 571 x 293 571 x 571 x 293 IRYS facade diffuser mm 595 x 595 x 34 595 x 595 x 34 595 x 595 x 34 Weight 2 pipe kg 26 28 29 4 pipe kg 27 28 29 (1) Nominal conditions : Air : 27 C/19 C wet bulb (nominal air flow in high speed). Chilled water : 7 C/12 C. (2) Nominal conditions : - In 2-pipe configuration : air : 20 C (nominal air flow in high speed); hot water : entering temperature 50 C (nominal water flow obtained in cooling mode). - In 4-pipe configuration : air : 20 C (nominal air flow in high speed); hot water : 70 C / 60 C. (3) Water pressure drops given for the corresponding nominal water flow on cassettes without control valves. (*) The sound pressure levels Lp are based on (NR) characteristic of a room having volume of 100m 3 with reverberation time of 0.5 seconds and a distance of 1 meter.

6 KOG LN 9 / KOG LN 12 / KOG LN 18 Electrical Data KOG LN with AC motor K09OG LN.2P K12OG LN.2P K18OG LN.2P With BE Without BE With BE Without BE With BE Without BE Nominal current A 6.7 0.3 8 0.3 10.8 0.4 Fuse rating gg A 10 1 ** 10 1 ** 16 1 ** Fuse rating ASE/VDE** A 16 2 16 2 16 2 Power supply 230V/1~/50Hz Cable section* mm 2 3G1.5 3G1 3G2.5 3G1 3G2.5 3G1 Electric heater capacity W 1500 / 1800 / 2400 / K09OG LN.4P K12OG LN.4P K18OG LN.4P Nominal current A 0.3 0.3 0.4 Fuse rating gg A 1 1 1 Fuse rating ASE/VDE** A 2 2 2 Power supply 230V/1~/50Hz Cable section* mm 2 3G1 3G1 3G1 BE : Electric heater. * Minimum section to be adapted according to local regulations and norms. ** am or circuit breaker curve C. KOG LN with EC motor K09OG LN.2P K12OG LN.2P K18OG LN.2P With BE Without BE With BE Without BE With BE Without BE Nominal current A 6.7 0.31 8 0.31 11.4 0.46 Fuse rating gg A 10 1 ** 10 1 ** 16 1 ** Fuse rating ASE/VDE** A 16 2 16 2 16 2 Power supply 230V/1~/50Hz Cable section* mm 2 3G1.5 3G1 3G2.5 3G1 3G2.5 3G1 Electric heater capacity W 1500 / 1800 / 2400 / K09OG LN.4P K12OG LN.4P K18OG LN.4P Nominal current A 0.31 0.31 0.46 Fuse rating gg A 1 1 1 Fuse rating ASE/VDE** A 2 2 2 Power supply 230V/1~/50Hz Cable section* mm 2 3G1 3G1 3G1 BE : Electric heater. * Minimum section to be adapted according to local regulations and norms. ** am or circuit breaker curve C. Standard fan motor electrical data Fan speed K09OG LN K12OG LN K18OG LN Absorbed current (A) Absorbed power Absorbed current (A) Absorbed power Absorbed current (A) S1 0.08 20 0.08 20 0.13 30 S2 0.12 30 0.12 30 0.20 46 S3 0.21 50 0.21 50 0.31 71 S4 / / / / / / EC fan motor electrical data Fan speed K09OG LN K12OG LN K18OG LN Absorbed Absorbed Set Absorbed Absorbed Set Absorbed current (A) power Voltage (V) current (A) power Voltage (V) current (A) Absorbed power Absorbed power Set Voltage (V) S1 0.10 8 3.77 0.10 8 3.77 0.15 9 4.45 S2 0.14 11 4.39 0.14 11 4.39 0.27 23 6.03 S3 0.31 26 6.17 0.31 26 6.17 0.40 41 7.53 S4 / / / / / / 0.46 52 8.20

KOG LN 9 / KOG LN 12 / KOG LN 18 7 Electrical Data Electric heater The electric heater of the cassettes is composed of heating resistances placed inside the tubes of the heat exchanger. These resistances are heat protected against any abnormal temperature rise by two thermostats equipped with a "positive safety" device (mechanical or thermic destruction of the capillary switches off the heating permanently) : K09OG LN K12OG LN K18OG LN Capacity W 1500 1800 2400 OO OO a thermostat with automatic reset, a thermostat with manual reset. Acoustical Data KOG with AC motor Data based on units 2 tubes Value for plastic facade with/without fresh air intake and IRYS facade without fresh air intake (*) The sound pressure levels Lp are based on (NR) characteristic of a room having volume of 100m 3 with reverberation time of 0.5 seconds and a distance of 1 meter. KOG with EC motor Acoustical power per octave band (db(a)) Speeds 125 250 500 1000 2000 4000 8000 K09OG LN K12OG LN K18OG LN Data based on units 2 tubes Value for plastic facade with/without fresh air intake and IRYS facade without fresh air intake Lw Global db(a) (*) The sound pressure levels Lp are based on (NR) characteristic of a room having volume of 100m 3 with reverberation time of 0.5 seconds and a distance of 1 meter. Lp* db(a) S1 26.4 27.3 28.6 23.1 25.5 18.2 9.2 34.0 26 20 S2 30.3 34.2 35.4 31.9 27.5 21.5 11.7 40.0 32 27 S3 37.1 43.9 47.4 45.9 44.0 33.4 22.7 52.0 42 37 S1 26.4 27.3 28.6 23.1 25.5 18.2 9.2 34.0 26 20 S2 30.3 34.2 35.4 31.9 27.5 21.5 11.7 40.0 32 27 S3 37.1 43.9 47.4 45.9 44.0 33.4 22.7 50.0 42 37 S1 29.9 35.0 36.1 32.6 32.9 24.1 8.1 41.0 33 28 S2 39.5 40.8 43.3 42.4 40.6 33.4 19.0 49.0 41 35 S3 49.7 48.4 50.0 50.1 48.9 46.2 32.2 57.0 49 43 Acoustical power per octave band (db(a)) Speeds 125 250 500 1000 2000 4000 8000 K09OG LN K12OG LN K18OG LN Lw Global db(a) Lp* db(a) S1 26.4 27.3 28.6 23.1 25.5 18.2 9.2 34.0 26 20 S2 30.3 34.2 35.4 31.9 27.5 21.5 11.7 40.0 32 27 S3 37.1 43.9 47.4 45.9 44.0 33.4 22.7 50.0 42 37 S1 26.4 27.3 28.6 23.1 25.5 18.2 9.2 37.0 26 20 S2 30.3 34.2 35.4 31.9 27.5 21.5 11.7 40.0 32 27 S3 37.1 43.9 47.4 45.9 44.0 33.4 22.7 50.0 42 37 S1 29.9 35.0 36.1 32.6 32.9 24.1 8.1 40.5 33 28 S2 39.5 40.8 43.3 42.4 40.6 33.4 19.0 49.0 41 35 S3 49.7 48.4 50.0 50.1 48.9 46.2 32.2 57.0 49 43 NR* NR*

8 KOG LN 9 / KOG LN 12 / KOG LN 18 Thermal Performance - 2 pipe KOG LN with AC motor Speeds Humid air flow (m 3 /h) Water flow (l/h) WPD (kpa) Cooling Pt Ps Heating Pc K09OG LN.2P K12OG LN.2P K18OG LN.2P S1 (Eurovent) 330 280 6 1580 1230 2100 S2 (Eurovent) 450 330 9 1870 1470 2500 S3 (Eurovent) 720 400 12 2250 1750 3100 S1 (Eurovent) 330 400 8 2280 1680 2700 S2 (Eurovent) 450 450 11 2570 2020 3200 S3 (Eurovent) 720 600 18 3450 2850 4500 S1 (Eurovent) 410 480 8 2770 2120 3300 S2 (Eurovent) 580 640 11 3650 2900 4600 S3 (Eurovent) 830 790 16 4530 3780 5700 KOG LN with EC motor Speeds Humid air flow (m 3 /h) Water flow (l/h) WPD (kpa) Cooling Pt Ps Heating Pc K09OG LN.2P K12OG LN.2P K18OG LN.2P S1 (Eurovent) 330 280 6 1590 1240 2100 S2 (Eurovent) 450 330 9 1890 1490 2500 S3 (Eurovent) 720 400 12 2270 1770 3100 S1 (Eurovent) 330 340 7 1960 1580 2450 S2 (Eurovent) 450 384 10 2220 1910 2910 S3 (Eurovent) 720 513 16 2970 2690 4090 S1 (Eurovent) 410 480 8 2790 2140 3300 S2 (Eurovent) 580 640 11 3680 2930 4600 S3 (Eurovent) 830 790 16 4560 3810 5700 S4 920 884 20 5100 4225 6100 Performances based on : ² ² Summer : air 27 C/19 C (wet bulb) and chilled water 7/12 C. ² ² Winter : air 20 C, entering water température 50 C, water flow identical to cooling mode.. Pt : Total cooling capacity. Ps : Sensible cooling capacity. Pc : Heating capacity. WPD : Water pressure drop Standard wiring of the 3 speeds. Other speed combinations available upon request.

KOG LN 9 / KOG LN 12 / KOG LN 18 9 Thermal Performance - 4 pipe KOG LN with AC motor K09OG LN.4P K12OG LN.4P K18OG LN.4P Speeds Humid air flow (m 3 /h) Cooling Pt Ps Water flow (l/h) WPD (kpa) Heating Pc Water flow (l/h) S1 (Eurovent) 330 1580 1230 280 6 1700 160 3 S2 (Eurovent) 450 1870 1470 330 9 1900 180 4 S3 (Eurovent) 720 2250 1750 400 12 2200 210 5 S1 (Eurovent) 330 2280 1680 400 8 2200 200 7 S2 (Eurovent) 450 2570 2020 450 11 2500 220 9 S3 (Eurovent) 720 3450 2850 600 18 3330 290 13 S1 (Eurovent) 410 2770 2120 480 8 3300 290 18.8 S2 (Eurovent) 580 3650 2900 640 11 3950 340 26.6 S3 (Eurovent) 830 4530 3780 790 16 4470 380 31 WPD (kpa) KOG LN with EC motor K09OG LN.4P K12OG LN.4P K18OG LN.4P Speeds Humid air flow (m 3 /h) Cooling Pt Ps Water flow (l/h) WPD (kpa) Heating Pc Water flow (l/h) S1 (Eurovent) 330 1590 1240 280 6 1700 160 3 S2 (Eurovent) 450 1890 1490 330 9 1900 180 4 S3 (Eurovent) 720 2270 1770 400 12 2200 210 5 S1 (Eurovent) 330 2290 1690 400 8 2200 200 7 S2 (Eurovent) 450 2590 2040 450 11 2500 220 9 S3 (Eurovent) 720 3470 2870 600 18 3335 290 13 S1 (Eurovent) 410 2790 2140 480 9 3300 290 17 S2 (Eurovent) 580 3680 2930 640 11 3950 340 24 S3 (Eurovent) 830 4560 3810 790 16 4470 380 28 S4 920 5100 4225 884 20 4600 404 30 WPD (kpa) Performances based on : ² ² Summer : air 27 C/19 C (wet bulb) and chilled water 7/12 C. ² ² Winter : air 20 C, entering water température 50 C, water flow identical to cooling mode.. Pt : Total cooling capacity. Ps : Sensible cooling capacity. Pc : Heating capacity. WPD : Water pressure drop Standard wiring of the 3 speeds. Other speed combinations available upon request.

10 KOG LN 9 / KOG LN 12 / KOG LN 18 Air throw I180 S1 S2 S3 K09OG LN AC Airflow m 3 /h 330 450 720 Throw m 4.2 5.7 9.1 K12OG LN AC Airflow m 3 /h 330 450 720 Throw m 4.2 5.7 9.1 K18OG LN AC Airflow m 3 /h 410 580 830 Throw m 5.2 7.3 10.5 I360 S1 S2 S3 K09OG LN AC Airflow m 3 /h 330 450 720 Throw m 3.5 4.8 7.6 K12OG LN AC Airflow m 3 /h 330 450 720 Throw m 3.5 4.8 7.6 K18OG LN AC Airflow m 3 /h 410 580 830 Throw m 4.3 6.1 8.8 K12OG LN - I360 0 1 2 3 V1 4 V2 5 6 7 V3 8 9 10métres K12OG LN - I180 0 1 2 3 V1 4 5 V2 6 7 8 V3 9 10 métres K12OG LN - I360 0 1 2 3 4 5 6 7 V3 8 9 10 métres 40cm 30 20 10 0 K12OG LN - I180 1.0m/s<V 0.5m/s<V<1.0m/s 0.2m/s<V<0.5m/s 0 1 2 3 4 5 6 7 8 V3 9 10 métres 40cm 30 20 10 0 1.5m/s<V 1.0m/s<V<1.5m/s 0.5m/s<V<1.0m/s 0.2m/s<V<0.5m/s

KOG LN 9 / KOG LN 12 / KOG LN 18 11 Water Pressure Drops K09OG LN 50 C 40 D 30 A kpa B 20 10 0 100 200 300 400 500 600 l/h Curve A : Curve B : Curve C : Curve D : Pressure drop of heating circuit with control valve (4-pipe system). Pressure drop of heating circuit without control valve (4-pipe system). Pressure drop of cooling circuit with control valve (2 and 4-pipe systems). Pressure drop of cooling circuit without control valve (2 and 4-pipe systems). K : Glycol coefficient Twm ( C) % Glycol 10 20 30 40 50 3 1.135 1.234 1.385 1.53 1.85 5 1.13 1.23 1.38 1.51 1.77 10 1.12 1.22 1.37 1.47 1.66 15 1.11 1.19 1.36 1.46 1.64 20 1.1 1.18 1.35 1.44 1.59 25 1.09 1.17 1.33 1.43 1.57 30 1.08 1.16 1.31 1.42 1.56 35 1.07 1.15 1.29 1.41 1.54 40 1.06 1.14 1.28 1.4 1.52 45 1.05 1.13 1.25 1.37 1.49 50 1.04 1.12 1.22 1.34 1.47 55 0.99 1.1 1.2 1.31 1.44 60 0.94 1.09 1.19 1.28 1.42 Twm : Average temperature of the mixture. Pwo : Pure water pressure drop. Pw : Brine water pressure drop. Pw : K x Pwo. % Glycol Tse ( C) 10 20 30 40 50-25 yes -20 yes yes -15 yes yes -10 yes yes yes -5 yes yes yes yes 0 yes yes yes yes yes 5 yes yes yes yes yes Tse : Outdoor dry bulb temperature.

12 KOG LN 9 / KOG LN 12 / KOG LN 18 Water Pressure Drop K12OG LN 50 C 40 A 30 B kpa D 20 10 0 100 200 300 400 500 600 700 l/h Curve A : Pressure drop of heating circuit with control valve (4-pipe system). Curve B : Pressure drop of heating circuit without control valve (4-pipe system). Curve C : Pressure drop of cooling circuit with control valve (2 and 4-pipe systems). Curve D : Pressure drop of cooling circuit without control valve (2 and 4-pipe systems). K18OG LN 70 60 A B C 50 40 kpa 30 20 D 10 0 100 200 300 400 500 600 700 800 900 1000 l/h

KOG LN 9 / KOG LN 12 / KOG LN 18 13 Operating Limits Use of chilled water Lower limits plastic facade IRYS facade Thi 13 13 Indoor temperature C Tsi 17 17 Water temperature C Twe 5 6 Higher limits plastic facade IRYS facade Thi 22 24 Indoor temperature C Tsi 32 27 Water temperature C Twe 18 18 Thi : Tsi : Twe : Indoor wet bulb temperature. Indoor dry bulb temperature. Entering water temperature. Use of hot water Thi 22 Maximum indoor temperature C Tsi 32 Maximum entering water temperature C Twe 70 (1) (2) Thi : Tsi : Twe : Indoor wet bulb temperature. Indoor dry bulb temperature. Entering water temperature for 2 or 4-pipe systems. Water connections Fresh air intake Fresh air flow should not exceed 12 % of nominal air flow (see table below). An antifreeze thermostat, switching off the external fan at +5 C, must be used on fresh air intake during winter period. A filter, fan and insulated air duct are to be provided on site. (1) : For reversible 2-pipe system with extra electric heater energized, maximum Twe is 35 C. (2) : For applications with water temperature higher than 70 C, consult factory. 9 LN 12 LN 18 LN Contents l 1,3 1,3 2 Maximum operating pressure bar 5 5 5 Test pressure bar 24 24 24 Couplings (2-pipe system) Ø 1/2" gas male 1/2" gas male 3/4" gas male mm 15-21 male 15-21 male 20-27 male Couplings (4-pipe system) KOG LN with AC motor Ø 1/2" gas male 1/2" gas male mm 15-21 male 15-21 male K09OG LN K12OG LN K18OG LN 2P 4P 2P 4P 2P 4P Nominal air flow in high speed m 3 /h 720 720 720 720 830 830 Maximum fresh air flow m 3 /h 86.4 86.4 86.4 86.4 99.6 99.6 KOG LN with EC motor K09OG LN K12OG LN K18OG LN 2P 4P 2P 4P 2P 4P Nominal air flow in high speed m 3 /h 720 720 720 720 830 830 Maximum fresh air flow m 3 /h 86.4 86.4 86.4 86.4 99.6 99.6 The new air must be preprocessed to prevent any risk of condensation on the product. 1/2" gas male (heating) 3/4" gas male (cooling) 15-21 male (heating) 20-27 male (cooling)

14 KOG LN 9 / KOG LN 12 / KOG LN 18 Dimensional Data (mm) KOG LN 2 pipe 620 571 327 270 276 (IRYS) 7 8 9 B A 12 11 Ø 200 10 Ø 100 6 287 293 (IRYS) 571 510 3 4 30 625 595 (IRYS) 40 34 (IRYS) C 5 2 1 30 legend 1 False ceiling 7 Condensate drain (Ø15) 2 T-shaped rod (false ceiling) 8 3 Coil 9 4 Fan 10 5 Suction grille 11 6 Electrical connection 12 Air vent Water leaving gas male coupling (refer to table "water connections") Water entering gas male coupling (refer to table "water connections") Port for fresh air succion (ready to punch out) Opening for ducted air distribution into the adjacent room (ready to punch out) 625 595 (IRYS) K09OG LN.2P K12OG LN.2P K18OG LN.2P A 39 39 50 B 119 119 130 C 126.5 126.5 106.5 KOG LN 2 pipe 620 571 327 270 276 (IRYS) 7 8 9 B1 A 12 B2 E 11 Ø 200 10 Ø 100 6 287 293 (IRYS) 571 510 3 4 30 625 595 (IRYS) 40 34 (IRYS) C D 5 2 1 30 legend 1 False ceiling 7 Condensate drain (Ø15) 2 T-shaped rod (false ceiling) 8 3 Coil 9 4 Fan 10 5 Suction grille 11 Water leaving gas male coupling (refer to table "water connections") Water entering gas male coupling (refer to table "water connections") Port for fresh air succion (ready to punch out) Opening for ducted air distribution into the adjacent room (ready to punch out) 6 Electrical connection 12 Chilled water air vent 625 595 (IRYS) K09OG LN.4P K12OG LN.4P K18OG LN.4P A 39 39 39 B1 119 119 130 B2 119 119 132 C 76.5 76.5 85.5 D 50 50 50 E 39 39 50

Notes KOG LN 9 / KOG LN 12 / KOG LN 18 15

16 KOG LN 9 / KOG LN 12 / KOG LN 18 Notes

Systemair AC SAS route de Verneuil, 27570 Tillières-sur- Avre Tél. 02 32 60 61 00 Fax 02 32 32 55 13 www.systemair.fr Systemair EDM KOG1-S-4GB/05.16 - Supersedes EDM KOG1-S-3GB/02.15 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. may 2016