TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

Similar documents
PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

PLL Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

TMC Temperature Monitoring Control Temperature Range -30 to 250 F (-35 to 120 C)

HWE-SS DIGI-El i t e Hydronic Single-Stage Boiler Control

SMC. Snowmelt Control. Installers and Users Installation and Operation Manuals

INSTALLATION/OPERATING INSTRUCTIONS HEAT-TROL Elite Series. HWE-Motorized Valve

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Beacon 800 Gas Monitor Operator s Manual

INSTALLATION/OPERATING INSTRUCTIONS SEQUENCING PANELS

Remote Relay Module (RRM)

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

E340 BOILER CONTROL INSTALLATION MANUAL

INSTALLATION/OPERATING INSTRUCTIONS BCP-3. Hot Water Reset Control For up to 3 Boilers. How the BCP-3 operates... 1:4 1:3 1:2 1:1.

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Remote Sensor Module: EB-RSM-01

INSTALLATION & OPERATION MANUAL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

Installation Manual. THM-0100 Setpoint Thermostat Version THM HBX Control Systems Inc.

Beacon 110 Gas Monitor Operator s Manual

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

User's Manual H-VC5. Chore-Logic. H-VC5 User manual. Version HPS 11/11/2006 User manual 1.02 ST50737MA 3/07. Page 1

Chore-Tronics Load Cell Indicator

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

be liable for any other loss or damage, whether direct, indirect, incidental or consequential.

RC-2000 Thermostat Installation Instructions

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.

RAM3 Remote Alarm Module

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

WIRING DIAGRAMS R410A MODELS PAC 2OAC/2OACH CAC OWC PWC

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

B-40/B-41 Modulating Temperature Controller

Conductivity Network Sensor

INSTRUCTION MANUAL P Heating and 1 Cooling

Pump-Down Controller MODEL 4052

Quest Power Electric Heat EHS 31 Pro

AV17 Series Switch-Tek Manual Direct and Remote Drum Mount Float Alarm 17 SEPT 08 Rev A

WIRING MODEL 20 Low Water Cut-Off and Pump Control MAXIMUM PRESSURE: 20 PSI INTERNAL WIRING BLUE WHITE UPPER PROBE (FEED OFF) FEED PROBE (FEED ON) ALL

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Interrupted Ignition Series Oil Primary Control

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Beacon 410A Gas Monitor Operator s Manual

Owner s Manual Phoenix FireBird

Installation, Operation & Service Manual

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Pump-Up Controller MODEL 4062

RATIO:GUARD Model E-1S EC Monitor

INSTALLATION AND OPERATION INSTRUCTIONS. Hydronic Multi-Stage Boiler Control

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Spa Control System OWNER S MANUAL

Centro-Matic Automated Lubrication Systems System Controls

FreezeAlarm. General Description FA-D /FA-D-AAB. Applications. Features. Specifications. Dimensions

Product Manual SZ1144

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

SEC 2000 Millenium Infrared Gas Detector

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

SC Installation, Operation & Application Guide

Product Manual SZ1145

PAC-2750 ELECTRIC COOLING FAN CONTROLLER

LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL

SYSTEM CONTROL KIT Model: CK-41P

MaxLite LED Round Pendant Highbay Series

Fan Speed. Auto Swing. Timer. Power. Mode. Fan. Only. Saver. Temp. Dry. Fan. Speed. Auto Swing. Timer. Power. Mode. Saver. Only. Temp.

MBCE-110/230FR Flame Sensor Module

Freeze Alarm. General Description VD-6300-MCS / VD-6301-MCS. Applications. Features. Specifications. Dimensions

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

CurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00

- User Brochure tekmarnet 4 Setpoint Control 161

INSTRUCTION MANUAL P Heating and 2 Cooling with Humidification and De-humdification

Static Pressure Control

RK-04 M2 Transmitter Operator s Manual

SEISCO SUPERCHARGER EXTENDER/BOOSTER INSTALLATION GUIDE & OWNERS MANUAL

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

R E N HI ITI CUSTOM AN LO +12v ADJUSTMENT

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

1022 R/T Remote Monitor

OPERATION & INSTALLATION MANUAL

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Humidity Monitor model 01080

7-Day. Digital Thermostat. residential. & 2-cool

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

prestige Control Application Supplement - TriMax

Auto Opening with Pressure Readout 15 x15 & 16 x20 Heat Transfer Machines

MaxLite LED Vapor Tight Linear Fixture

Installation, Configuration and User Manual

ATMOX MAXX System THE Complete Moisture Control System for Crawlspaces. User s Guide

ECC-1 user manual and installation guide

Digital Refrigerator/Freezer Thermometer model 00986

Transcription:

Installation and Operation Manual Temperature and Pressure Monitoring for Heating and Cooling Applications Temperature Monitoring Control VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK MENU/SET INPUT RATINGS: 120VAC 60HZ, 16 VA Control Module Warning This Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety control. All equipment must have its own certified limit and safety controls required by local codes. The installer must verify proper operation and correct any safety problems prior to the installation of this Heat-Timer control.

Content Layout 3 Operating Concept 4 Status Mode 4 Package Component and Accessories 5 Solenoid Valve Table 5 Control Installation 5 Mounting the Enclosure 5 Wiring 6 Wiring the Power 6 Wiring the Solenoid Valve 6 Wiring the Alarm 6 System Sensor 7 Sensor Table 7 System Temperature Sensor 7 Pressure System Sensor 7 Remote Reset 8 Wiring 4-20mA Remote Set Point 8 Buttons and Navigation Menus 8 LEDs 8 Menu 9 Startup Menu 9 Input Type 9 Control Mode 9 4mA and 20mA Set Point 9 heat Mode 10 Solenoid Valve 10 Setting the to Factory Default 10 Default Display 10 Operating Menu 10 Set Point 10 Maintenance 10 System Trim 10 Troubleshooting 11 and ETV Piping- Temperature 12 Wiring- Temperature 13 Wiring- Pressure 14 Warranty 15 Specifications 16 2 Installation and Operation Manual

Layout LED Indicates actuator modulation 2-Line Display shows current status RESET/BACK: Goes back one menu level. Reset Alarms : Scrolls through the menu or changes values. MENU/SET: Enters the menu or accepts value. VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK MENU/SET INPUT RATINGS: 120VAC 60HZ, 16 VA Maximum 15A for All Circuits Control Module CAUTION: Risk of Electric Shock. More than one disconnect switch may be required to de-energize the equipment before servicing Use Copper Conductors and Flexible Conduit Only. Wire all circuits as Class I or Electric Light and Power circuits. Output EMS Press PWR System Remote Alarm Alarm Valve 4-20mA 4-20mA L N + - Pwr Temp Reset + Sig 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RS485 120VAC to power 2 Alarm Outputs Solenoid Valve Relay EMS 4-20mA Remote Set Point Pressure Sensor with Power Sourcing Remote Reset System Temperature Sensor Installation and Operation Manual 3

VALVE OPEN ALARM INPUT RATINGS: 120VAC 60HZ, 24 VA System= Alarm at= RESET /BACK 148 o F 150 o F MENU/SET POWER INPUT RATINGS: 120VAC 60HZ, 24 VA SYSTEM= TARGET= BACK 148 o F 150 o F MENU/SET Operating Concept The displays and monitors the system temperature or pressure and provides two alarm outputs if the System Sensor reaches a critical point. The alarm condition can only be cleared by pressing the RESET button. The is ideal for domestic hot water systems. When the domestic water temperature rises above the selected set point, the will enter the Alarm Mode. The will control a solenoid valve. In the Alarm Mode, the solenoid valve will close the flow of hot water to the domestic system. To open the solenoid valve and let the hot water back into the system, two things must happen: the domestic water temperature must fall below the critical point, and the RESET button must be pressed. ETV Control Module ETV Control Module Tempered Cold NC Solenoid Hot HOT WATER SOURCE Typical uses of the include: Domestic Hot Water (DHW) alarm Freeze condition alarms Refrigeration system alarms Hydronic heating systems high temperature alarms and control for solenoid valve to disable the heating system Space temperature alarm systems Status Mode The operation has two status modes: Normal: In this mode, the System Sensor (temperature or pressure) is not in a critical zone. Critical zone is when the sensor reading is above the Set Point in Heating or below the Set Point in cooling. The solenoid valve will be open and its LED will be on. Alarm LED and Alarm relays will be de-energized. Alarm: The will automatically enter this mode whenever the System Sensor reading enters the critical zone. The will then close the solenoid valve (regardless of the Solenoid Valve type selected from the Startup menu). The Valve Open LED will be off and the Alarm LED will be blinking. All alarm outputs will be energized. Warning To Exit the Alarm Mode, the System Sensor must be out of the critical zone and the RESET button must be pressed. Status Mode Normal Alarm Sensor Value Out of critical area Within critical area Activation Solenoid Valve Alarm Status LED Relay LED Sensor reading is out of critical zone. Open On Off Off RESET button was not pressed. Sensor reading is within critical zone. Close Off On Blinking 4 Installation and Operation Manual

Package Component and Accessories The comes pre-packages with a temperature sensor (904220-00) and a ½ NPT well (904011-00). The is designed to operate a solenoid valve. The solenoid valve must be ordered separately. Solenoid VALVe Table Solenoid Part # Size C v Differential (PSI) Opening Min Max Default Opening Power VAC/ Watts Safe Working Pressure (PSI) Opening Valve Time (Sec) Closing Valve Time (Sec) 920520-00 ½ 4.6 4 142 N. C. 120 / 14 225 0.04 0.35 920521-00 ¾ 9.3 4 142 N. C. 120 / 14 225 0.04 1.00 920522-00 1 12.3 4 142 N. C. 120 / 14 180 0.30 1.00 920523-00 1-¼ 21 4 142 N. C. 120 / 14 180 1.00 2.50 920524-00 1-½ 28 4 142 N. C. 120 / 14 180 1.50 4.00 920525-00 2 46.7 4 142 N. C. 120 / 14 180 5.00 10.00 Control Installation Each control consists of four primary enclosure components. The Enclosure Display Module: contains the display, buttons, LEDs, and electric wiring terminals. It has two screws to hold it to the base. The wiring terminals are of the plug-in type to ease installation and removal. The Enclosure Base: contains the holes to mount and hold the control against the wall or any flat surface. All other enclosure components mount onto the base. The Enclosure Base bottom section contains the wiring chamber with bottom knockouts for all input and output wiring connections. The Enclosure Wiring Cover: seals the wires from the external environment. It has two screws to hold it to the base. In addition, it has a hole that can be used with a padlock to secure the enclosure. The Enclosure Top Cover: seals the top of the Display Module. It is screwed to the Display Module from the inside. Mounting the Enclosure Select a location near the equipment to be controlled. The surface should be flat, wide, and strong to support the Control. Keep the control away from extreme heat, cold, or humidity. Remove the Enclosure Wiring Cover by removing the two screws holding it to the base. Remove the Enclosure Display Module with the Enclosure Top Cover by removing the 2 middle screws. It is easier to remove necessary knockouts before mounting the Enclosure Base. Screw the Enclosure Base to the surface using the upper and lower mounting holes on the back of the enclosure. Replace the Enclosure Display Module and the middle mounting screws. Do not replace the enclosure wiring covers until all wiring is done. When purchasing a padlock for the Bottom Enclosure Wiring Cover, the maximum shank diameter should not exceed ¼. Enclosure Base Enclosure Top Cover Enclosure Top Cover Latches Mounting Holes Display Mounting Screws Mounting Holes Enclosure Wiring Cover Mounting Holes Enclosure Display Module Enclosure Screws to Hold Wiring Wiring Cover Cover to base Hole for Optional Padlock Installation and Operation Manual 5

Wiring Wiring the Power (Terminals 1, 2) Bring the 120VAC 60 Hz power wires through the enclosure left bottom knockout. Connect the hot line to terminal 1 marked L. Connect the neutral line to terminal 2 marked N. The installation of the provided metal Grounding Plate is needed when using conduit. Heat-Timer recommends the installation of a power switch and a surge-suppressor before the power line connection for safety and ease of service. 120 VAC L N PWR L N 1 2 Warning Class 1 voltage wiring must use a different knockout and conduit from any Class 2 voltage wiring. Wiring the Solenoid VALVe (Terminals 7, 8) The solenoid valve requires an external power source. The does not provide power to the solenoid valve. A separate power source must be wired in series with the solenoid as per the illustration on the right. The solenoid output relay can operate up to 1 Amp pilot duty or 6 Amp resistive load. If additional load is required, use a relay. The can operate a solenoid valve that is normally open or normally closed. The option to select which type of valve must be set in the Startup menu. See Solenoid Valve on page 10. Regardless of the solenoid valve s normal status (N.O. or N.C.), the Valve Open LED will light up when the valve is open. Alarm 3 4 Output Alarm Valve 5 6 7 8 L 120 VAC N Solenoid Valve Wiring the Alarm (Terminals 3, 4 or 5, 6) The has two Alarm output relays. It does not provide power to the alarm outputs. A separate power source must be wired in series with the alarm. Each of the Alarm output relays can operate up to 1 Amp pilot duty. The Alarm output will be active whenever the System Sensor has risen (or fallen if in the cooling mode) out of range. Even if the sensor reading returns to normal, the alarm will not clear until the manual Reset button has been pressed. See Status Mode on page 4. The alarm power should be switched through the output terminals. These are either terminals 3 and 4 or terminals 5 and 6. The Alarm LED will blink whenever the is in Alarm Mode. To exit the Alarm Mode, the System Sensor reading must not be in the critical zone and the RESET button must be pressed. PWR Alarm L N 1 2 3 4 To EMS Alarm input Output Alarm Valve 5 6 7 8 L 120 VAC N Vis-U-Alarm 6 Installation and Operation Manual

System Sensor The is capable of accepting either a pressure transducer or a temperature sensor as the system input. Select the proper Input Type from the Startup menu as the control will only measure the input terminals designated by the Input Type. In addition, it will adjust the sensor range based on the transducer selected from the Input Type menu. See Input Type on page 9. Sensor Table STANDARD Temp. SENSOR Part # 904220-00 904250-00 SENSOR TYPE Temperature F or C SET POINT Default TRIM 0 F to 250 F 70 F -5 to +5 13, SENSOR TERMINALS Press. 904310-00 Pressure 30 PSI 0.0 to 30.0 PSI 10.0 PSI -5 to +5 11, 12 Press. 904312-00 Pressure 100 PSI 0 to 100 PSI 30 PSI -5 to +5 11, 12 Press. 904311-00 Pressure 200 PSI 0 to 200 PSI 60 PSI -5 to +5 11, 12 System Temperature Sensor (Terminals 13, 14) Set the Startup menu Input Type to F or C. See Input Type on page 9. The provided temperature sensor (904220-00) must be inserted into the provided 3/8 ID 1/2 NPT immersion well (HT #904011-00). Install the System Sensor well between the boiler output and the hot water input to the 3-way motorized valve. The sensor wires can be extended up to 500 using a shielded 2-conductor cable (Belden #8760 or equivalent (#18/2)). Connect the shield to terminal 14. Do not connect the shield at the sensor end. Do not run sensor wires in the same conduit or in close proximity to line voltage wiring. Class 2 voltages must enter the enclosure through a different knockout from any Class 1 voltage wiring. Sensor Inserted in Well or Electric Light and Power circuits. EMS Press 4-20mA 4-20mA System Remote + - Pwr Temp Reset + Sig 9 10 11 12 13 14 15 16 Shield RS485 System Temperature Sensor 2-Conductor Shielded Cable Well Warning On a sensor fault (reading is SHORT or OPEN), the will enter the Alarm Mode. Pressure System Sensor (Terminals 11, 12) provides Excitation Voltage to the Transducer Pressure Transducer must be ordered Separately. Set the Startup menu Input Type to 30 PSI, 100 PSI, or 200 PSI. See Input Type on page 9. Attach a 1/4 brass isolation tube (pigtail) to the steam header (Straight HT# 135020-00 or Angle HT #135021-00). Fasten the transducer to the pigtail. See Sensor Table on page 7. The sensor wires can be extended up to 500 by splicing with 18 gauge shielded or twisted pair wire. When shielded cable is used, connect the shield to Earth Ground. Do not run sensor wires in conduit with line voltage or in close proximity to line voltage wiring. Class 2 voltages must enter the enclosure through a different knockout from any Class 1 voltage wiring. The sensor s BLACK wire should be connected to terminal (Pwr + 11). The sensor s RED wire should be connected to terminal (Sig 12). Shield Ground Conduit Only. Wire all circuits as Class I or Electric Light and Power circuits. EMS Press 4-20mA 4-20mA System Remote + - Pwr + Sig Temp Reset 9 10 11 12 13 14 15 16 BLACK Connect Transducer to 1/4" pigtail RED RS485 Cut the Green, White, and ClearTube Pressure Transducer Installation and Operation Manual 7

Remote Reset (Terminals 15, 16) These terminals accept a remote dry-contact input to switch the control to Normal Mode if the sensor reading is out of the critical range. The Remote Reset input has the identical function as pressing the RESET button. EMS Press 4-20mA 4-20mA System Remote + - Pwr Temp Reset + Sig 9 10 11 12 13 14 15 16 Wiring 4-20mA Remote Set Point (Terminals 9, 10) This feature can be used whenever it is desirable to set the set point from a remote location. The Control Mode must be set to EMS 4-20mA to utilize this capability. See Control Mode on page 9. The DOES NOT SOURCE POWER to the 4-20mA terminals. The EMS/BMS systems must source the excitation voltage. See Wiring 4-20mA Remote Set Point on page 8. Any signal that is less than 2mA or greater than 22mA will display Fault at the set point. In this case, the will enter the Alarm Mode. Buttons and Navigation Menus The has four buttons. MENU/SET: This button function varies. When in the Default Screen, pressing the MENU/SET button views the MENU. When in the menus and settings, this button accepts the selected entry or setting value. : When in the menus, pressing the and buttons will scroll through the menu options. When in a specific setting, they are used to change its value. I.e., change the Set Point or Trim. RESET/BACK: When in Alarm Mode and if the sensor was in the critical range, pressing the RESET button will not cause any change. However, if the sensor was out of the critical range, pressing the RESET button will switch the system to the Normal Mode. See Status Mode on page 4. When in the menus, the BACK button will bring the user back one menu level until the user reaches the default screen. RESET /BACK Remote Reset EMS Press 4-20mA 4-20mA System Remote + - Pwr + Sig Temp Reset 9 10 11 12 13 14 15 16 (-) to EMS (+) EMS/BMS Sources Excitation Voltage Remote Set Point System= Alarm At= 128 o F 130 o F MENU/SET LEDs The has a two LED lights: VALVE OPEN: This LED will be on whenever the control is NOT in Alarm Mode. In this case the control will allow flow through the valve. When the control enters the Alarm Mode, this LED will be off and no flow will pass through the valve. ALARM: The Alarm LED will blink whenever the control is in Alarm Mode or the sensor is in the critical range. Upon exiting both situations and pressing the RESET button, this LED will turn off. See Status Mode on page 4. VALVE OPEN ALARM 8 Installation and Operation Manual

-- MODE -- HEAT COOL Set Point Menu SYSTEM STARTUP PRESS SET -- CONTROL MODE -- Set Point EMS 4-20mA -- INPUT TYPE -- F C 30PSI 100PSI 200PSI --SOLENOID VALVE-- N C N O EMS 4-20mA -- EMS 4mA -- 80 o F Default Screen SYSTEM= Alarm At= 168 F 170 F -- EMS 20mA -- 180 o F BACK MENU/SET ------MAIN------ SetPnt 70 F <Maintenance> <Startup> <Info> -- SET POINT -- 70 o F > 170 o F -- MAINTENANCE --- Trim = +0 F -- SENSOR TRIM -- +0 o F > +1 o F Startup Menu Input Type Options: Temperature ( F, C), Pressure (30, 100, 200) PSI Default: F Menu Button:/<System Startup>/Input Type The will measure only the sensor input terminals associated with the Input Type. In addition, the pressure transducer used must match the Input Type. See Sensor Table on page 7. Control Mode Options: Set Point, EMS 4-20mA Default: Set Point Menu Button:/<System Startup>/Input Type/Control Mode The new can accept an alarm Set Point either by setting it in the menus or through a remote EMS set point. Use the Set Point option to allow setting the value directly in the. Use the EMS 4-20mA option when a remote 4-20mA set point can be sent from a BMS/EMS system. The control will measure up to 2mA above and below the full range. Anything below 2mA or above 22mA will display FAULT and will activate the Alarm Mode. 4mA and 20mA Set Point (Available when Control Mode = EMS 4-20mA) 4mA Set Point Adjustable from 0ºF/-18ºC to 150ºF/66ºC, 0 PSI Default: 80ºF/27ºC 20mA Set Point Adjustable from 0ºF/-18ºC to 250ºF/121ºC, Max PSI Default: 180ºF /82ºC Menu Button:/<System Startup>/Input Type/Control Mode/EMS 4mA /EMS 20mA These menus ares used to match the signal scale (supplied by EMS). See Wiring 4-20mA Remote Set Point on page 8. The Pressure Input Types will use the maximum and minimum transducer values as the 4mA and 20mA set points. -- INPUT TYPE -- F C 30PSI 100PSI 200PSI -- CONTROL MODE -- Set Point EMS 4-20mA -- EMS 4mA -- 80 o F -- EMS 20mA -- 180 o F Warning Any signal below 2mA or above 22mA will display a Fault Set point and will cause the to enter the Alarm Mode. Installation and Operation Manual 9

heat Mode Options: Heat, Cool Default: Heat Menu Button:/<System Startup>/Input Type/Control Mode/ Mode The is designed to work in a heating or a cooling system. The Heat option triggers the alarm and closes the valve whenever the System Sensor value exceeds the set point. The Cool option triggers the alarm and closes the valve whenever the System Sensor value drops below the set point. Solenoid VALVe Options: N.C., N.O. Default: N.C. Menu Button:/<System Startup>/Input Type/Control Mode/ Mode / Solenoid Valve The can operate either a Normally Open (N. O.) or a Normally Close (N. C.) solenoid valve. Depending on the option selected, the control will manage the valve relay to keep the valve open during normal operation and keep it close when in the Alarm Mode. See Solenoid Valve Table on page 5. The Valve Open LED will be on whenever the control is in normal operation. Setting the to FACTOry Default To reset the control to its original factory defaults, power down the control. Hold down the RESET/BACK and buttons while powering the control up until the "Resetting to Factory Defaults" message appears. This is followed by the Startup menu. -- MODE -- HEAT COOL --SOLENOID VALVE-- N C N O Resetting to Factory Defaults RESET /BACK MENU/SET Default Display The default display will show the current System temperature/pressure and the Alarm at temperature/ pressure (Set Point). If no button was pressed for 2 minutes when in any of the menu options, the control will revert to the Default Display. When the control is in Alarm Mode, the Alarm at Display line will alternate between the Set Point value and the message In Alarm. Operating Menu Set Point (Available when Control Mode = Set Point) Options: Varies based on Input Type. See Sensor Table on page 7. Menu Button:/Set Point This is the critical temperature or pressure setting at which the will trigger the alarm at. If the Control Mode is set to EMS 4-20mA, the set point will be a read only value. Maintenance System Trim Options: Varies based on Input Type Menu Button:/<Maintenance>/Trim The Heat-Timer pressure and temperature sensors are very accurate and normally require no calibration. However, sometimes it may be desirable to make small adjustments to match other instruments. See Sensor Table on page 7. System= Alarm at= 148 F 150 F System= 152 F In Alarm Set Point: 70 F 140 F -- SENSOR TRIM -- +0 o F > +1 o F 10 Installation and Operation Manual

Troubleshooting No Display Check the power to the. It requires 120VAC power to terminals 1 and 2. Turn the power off and back on to restore the display. Make sure that the Fuse on the back of the board is working by checking it with a continuity meter. If no continuity, replace with 20 mm 2.5 amp fuse Fuse Temperature Sensor Reads OPEN or SHORT If the sensor reads Open, short the sensor input terminals. The display should read Short. If it doesn t, the may be damaged. If it does, either the sensor is damaged or its wiring is not continuous. If the sensor reads Short, remove the wires from the input terminals. The display should read Open. If it doesn t, the may be damaged. If it does, the sensor is damaged and needs to be replaced. Incorrect Temperature Sensor Reading Remove the sensor wires from the input terminals. The display should change to read Open. If it doesn t, the may be damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the Temperature Sensor Chart. If the difference is within 5 F adjust the sensor Trim. Otherwise, replace the sensor. Temperature Sensor Chart TEMPERATURE F C Value (in Ohms) TEMPERATURE Value F C (in Ohms) 30-1 17264 TEMPERATURE Value F C (in Ohms) 90 32 3667 TEMPERATURE Value F C (in Ohms) 180 82 583 OPEN 150000 35 2 14985 100 38 2914 190 88 489-30 -34 117720 40 4 13040 110 43 2332 200 93 412-20 -29 82823 45 7 11374 120 49 1879 210 99 349-10 -23 59076 50 10 9944 130 54 1524 220 104 297 0-18 42683 55 13 8714 140 60 1243 230 110 253 10-12 31215 60 16 7653 150 66 1021 240 116 217 20-7 23089 70 21 5941 160 71 842 250 121 187 25-4 19939 80 27 4649 170 77 699 SHORT 100 Incorrect Pressure Sensor Reading First, make sure that the pressure transducer installed matches the Input Type selected from the Startup Menu. See Input Type on page 9. Then, check if the reading is within the Trim range, adjust it using the System Trim. Check the transducer wiring. No excitation voltage is needed as the sources the power to the transducer. See Pressure System Sensor on page 7. If the reading is Short, remove the wires from the sensor terminals. The display should change to read Open. If it does not, the may be damaged. Otherwise, if it does, then the pressure transducer is damaged and needs to be replaced. Pressure Sensor Chart INPUT (in ma) 0-30 0-100 0-200 2 Open 4 0 0 0 4.08 1 4.16 1 2 4.53 1 INPUT (in ma) 0-30 0-100 0-200 5.07 2 5.6 3 10 20 7.2 6 20 40 8.8 9 30 60 10.4 12 40 80 12 15 50 100 INPUT (in ma) 0-30 0-100 0-200 13.6 18 60 120 15.2 21 70 140 16.8 24 80 160 18.4 27 90 180 20 30 100 100 22 Short No Alarm Output Check to make sure that the is in Alarm Mode by watch the Alarm LED. If it was, then check the wiring to the alarms. Note that, the does not source power to the output relays. An external power source must be used. See Wiring the Alarm on page 6. Installation and Operation Manual 11

ETV VALVE OPEN POWER ALARM System= 148 o F SYSTEM= 148 o F Alarm at= 150o F TARGET= 150 o F BACK MENU/SET INPUT RATINGS: 120VAC 60HZ, 24 VA ETV Control Module Tempered ETV / Piping Cold Water Circ. Pump (Continuous Running) Tempered Water Circulating Return Settings: Input Type: Temperature F or C Control Mode: Set Point Mode: Heat and ETV Piping- Temperature ETV Sensor Sensor RESET /BACK MENU/SET INPUT RATINGS: 120VAC 60HZ, 24 VA Control Module Cold NC Solenoid Hot 32 Min Vertical Drop HOT WATER SOURCE Alert Since each installation is unique, Heat-Timer Corp. is not responsible for any installation related to any electrical or piping diagram generated. The provided illustrations are to demonstrate the control operating concept only. 12 Installation and Operation Manual

Wiring- Temperature VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK MENU/SET INPUT RATINGS: 120VAC 60HZ, 16 VA Maximum 15A for All Circuits Control Module CAUTION: Risk of Electric Shock. More than one disconnect switch may be required to de-energize the equipment before servicing Use Copper Conductors and Flexible Conduit Only. Wire all circuits as Class I or Electric Light and Power circuits. Output EMS Press PWR System Remote Alarm Alarm Valve 4-20mA 4-20mA L N + - Pwr Temp Reset + Sig 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RS485 120 VAC L N Vis-U-Alarm Remote Reset Solenoid Valve Shield System Temperature Sensor Alert Since each installation is unique, Heat-Timer Corp. is not responsible for any installation related to any electrical or piping diagram generated. The provided illustrations are to demonstrate the control s operating concept only. Settings: Input Type: Temperature F or C Control Mode: Set Point Mode: Heat Installation and Operation Manual 13

Wiring- Pressure VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK MENU/SET INPUT RATINGS: 120VAC 60HZ, 16 VA Maximum 15A for All Circuits Control Module CAUTION: Risk of Electric Shock. More than one disconnect switch may be required to de-energize the equipment before servicing Use Copper Conductors and Flexible Conduit Only. Wire all circuits as Class I or Electric Light and Power circuits. Output EMS Press PWR System Remote Alarm Alarm Valve 4-20mA 4-20mA L N + - Pwr Temp Reset + Sig 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RS485 120 VAC L N BLACK RED Vis-U-Alarm Ground Shield Remote Reset Solenoid Valve Connect Transducer to 1/4" pigtail Cut the Green, White, and ClearTube Pressure Transducer Alert Since each installation is unique, Heat-Timer Corp. is not responsible for any installation related to any electrical or piping diagram generated. The provided illustrations are to demonstrate the control operating concept only. Settings: Input Type: Control Mode: Mode: Pressure 30, 100, or 200 PSI Set Point Heat 14 Installation and Operation Manual

Warranty WARRANTIES AND LIMITATIONS OF LIABILITY AND DAMAGE: Heat-Timer Corporation warrants that it will replace, or at its option, repair any Heat-Timer Corporation manufactured product or part thereof which is found to be defective in material workmanship within one year from the date of installation only if the warranty registration has been properly filled out and returned within 30 days of the date of installation. Damages to the product or part thereof due to misuse, abuse, improper installation by others or caused by power failure, power surges, fire, flood or lightning are not covered by this warranty. Any service, repairs, modifications or alterations to the product not expressly authorized by Heat-Timer Corporation will invalidate the warranty. Batteries are not included in this warranty. This warranty applies only to the original user and is not assignable or transferable. Heat-Timer Corporation shall not be responsible for any maladjustments of any control installed by Heat-Timer Corporation. It is the users responsibility to adjust the settings of the control to provide the proper amount of heat or cooling required in the premises and for proper operation of the heating or cooling system. Heat-Timer Corporation shall not be required to make any changes to any building systems, including but not limited to the heating system, boilers or electrical power system, that is required for proper operation of any controls or other equipment installed by Heat-Timer Corporation or any contractor. Third Party products and services are not covered by this Heat-Timer Corporation warranty and Heat-Timer Corporation makes no representations or warranties on behalf of such third parties. Any warranty on such products or services is from the supplier, manufacturer, or licensor of the product or service. See separate Terms and Conditions of Internet Control Management System ( ICMS ) services, including warranties and limitations of liability and damages, for ICMS services. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED AND HEAT-TIMER CORPORATION SPECIFICALLY DISCLAIMS ANY AND ALL WARRANTIES OF MERCHANTABILITY FOR A PARTICULAR PURPOSE. UNDER NO CIRCUMSTANCES SHALL HEAT-TIMER CORPORATION, ITS AUTHORIZED REPRESENTATIVES, AFFILIATED OR SUBSIDIARY COMPANIES BE LIABLE FOR SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES, EXCEPT AS SPECIFICALLY STATED IN THESE TERMS AND CONDITIONS OF SALE. THE SOLE REMEDY WITH RESPECT TO ANY PRODUCT OR PART SOLD OR INSTALLED BY HEAT-TIMER CORPORATION SHALL BE LIMITED TO THE RIGHT TO REPLACEMENT OR REPAIR F.O.B. FAIRFIELD, NJ. HEAT-TIMER CORPORATION SHALL NOT BE LIABLE OR RESPONSIBLE FOR LOSS OR DAMAGE OF ANY KIND RESULTING FROM DELAY OR INABILITY TO DELIVER FOR ANY REASON, INCLUDING BUT NOT LIMITED TO FIRE, FLOOD, LIGHTNING, POWER FAILURE OR SURGES, UNAVAILABILITY OF PARTS, STRIKES OR LABOR DISPUTES, ACCIDENTS AND ACTS OF CIVIL OR MILITARY AUTHORITIES. 03122010 Installation and Operation Manual 15

Specifications Operating Temperature.......................................... 20 F/-6 C to 120 F/49 C Voltage Input:..................................................... 120 VAC 60 Hz Maximum Input Rating:................................................. 16 VA Max Fuse:......................................................... 20 mm 0.5 Amp Output Relays................................... 2 Alarms and 1 Solenoid Valve (Relays are SPST) Output Relay Rating:................ 1 Amp inductive, 6 Amp resistive at 120 VAC 60 Hz, 15A total for all circuits Display:........................................ Back Lite 2 Line Alphanumeric LCD Display Display Units:............................. Fahrenheit (ºF) and Celsius (ºC), 30 PSI, 100 PSI, 200 PSI Operating Mode......................................................Heat or Cool Set Point:............................................... See Sensor Table on page 7. Solenoid Valve Options:..................................... Normally Open or Normally Close LED:..................................................... 1 Valve Open, 1 Alarm Inputs:.................................... System Temperature, System Pressure, Remote Reset Remote Set Point................................ Accepts 4-20mA set point as pressure or temperature Buttons:.......................................... 4 (RESET / BACK,,, MENU/SET) Dimensions:................................................. 8 ⅝ W x 10 H x 3 ½ Weight:............................................................2 pounds 20 New Dutch Lane, Fairfield, NJ 07004 Ph: (973) 575-4004 Fax: (973) 575-4052 http://www.heat-timer.com