Typologies of Hybrid Ventilation in Schools

Similar documents
Residential ventilation concepts based on the idea of displacement airflow distribution

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Thermal Comfort with Convective and Radiant Cooling Systems

Vertical Distribution of Air Temperatures in Heated Dwelling Rooms

Ventilation Strategies for Healthy IEQ and Energy Efficiency

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

The impact of thermal loads on indoor air flow

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Human response to thermal environment in rooms with chilled beams

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

ACTIVE VENTILATION SYSTEMS

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Space Air Diffusion II

ICSV14. Cairns Australia 9-12 July, Noise reduction of handheld vacuum cleaners according to geometric optimization of air passages

Smoke Master SMIA Compact pressurisation and smoke exhaust system

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Figure 1: Low energy dwellings testsite

Villa Bagatelle Technical Report

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Improving Single-Sided Room Ventilation by Using a Ceiling Fan

lindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

American Society of Heating, Refrigerating and Air-Conditioning Engineers

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

Air distribution for clean rooms. Clever and flexible.

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

KLIMA Active Chilled Beams

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing

EFFECTS OF COMBINING SMART SHADING AND VENTILATION ON THERMAL COMFORT

ENERGY EFFICIENCY BRIEF REPORT

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

nzeb office building

Hot-air heating of family houses with accumulation of energy in the floor

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Displacement Ventilation

Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

UniTrane U-Line ductable water terminals Optimum efficiency with a sound reduction bonus

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

The Corbioli House is a single-family house situated

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Computer Models For Fire and Smoke

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

CLIMATE SEPARATION SOLUTION. SensAir

Center for the Built Environment October 2013

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

AR/IA 241 LN 231 Lecture 6: Passive Cooling

Ceiling air diffuser INDULTHERM INDULTHERM-e

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

C o o l i n g a n d h e a t i n g s y s t e m s

Numerical study of heat pipe application in heat recovery systems

2013 innovation. Room-by-room demand controlled heat recovery ventilation

CLIMATE SEPARATION SOLUTION. SensAir

ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

A Method of Heat Exchange Structure Optimization of the Cricoid Plastic Parts

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Compression of Fins pipe and simple Heat pipe Using CFD

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Air Excellent AE55SC. Technical Datasheets

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

Passive building in Hot and Humid Climates

Air Excellent AE45SC. Technical Datasheets

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system

Demand-controlled Ventilation Leading edge products for demand-controlled ventilation

AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS

Technical Selection. elevent ceiling diffusers. Swirl, Jet, Louvred and Curved ceiling diffusers

ASSEMBLY HALL AIR DISTRIBUTION

Halton Vario Design Guide

Slimline 150 & 300 Exceptionally low energy consumption. High Efficiency, Low Profile Heat Recovery Range

HEX390. Balanced Pressure Ventilation with Heat Recovery. for healthy indoor air

Primo Hotel. General. Indoor climate units for hotel rooms

Diffuse Ceiling Ventilation Zhang, Chen; Yu, Tao; Heiselberg, Per Kvols; Pomianowski, Michal Zbigniew; Nielsen, Peter Vilhelm

Lecture 18 Auditorium Acoustics

ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

Healthy, comfortable and energy-efficient ventilation

Development of a Compact High Efficiency Cooling Device for the PA8000 Processor*

Heating and cooling ceiling systems Suspended ceiling systems. Heating Cooling Fresh Air Clean Air

CASE STUDY REGARDING ENERGY EFFICIENCY OF A VENTILATION SYSTEM WITH RECUPERATIVE HEAT RECOVERY

Transcription:

Typologies of Hybrid Ventilation in Schools Peter van den Engel Delft Technological University, the Netherlands Corresponding email: p.vd.engel@deerns.nl SUMMARY This article is the result of a study on how to close the gap between architects and a building service consultant. Closing is necessary in order to be able to create both a better indoor climate and an interesting architectural environment. Especially for schools with natural air supply some basic physical principles of draught prevention should be checked in an early stage of the design or commissioning process. Air supply designs for the most common architectural problems should be easily available. Most of the presented design options have been evaluated with measurements and CFD-simulations. For schools with natural air exhaust (overpressure system) the results of an on-site test are presented. This system can be applied even in existing schools with single glass windows and a monumental façade. INTRODUCTION In The Netherlands and other European countries the air change rate in schools increases in order to prevent health problems of students. The minimum air supply in The Netherlands is 7 l/s (= ca. 25 m 3 /h) per student. Due to the high occupancy (generally 1 person at 2 m 2 = 3.5 l/sm 2 ) prevention of draught needs much attention. Architects need ready-to-use ventilation design concepts for schools because of: - A lack of knowledge of draught prevention, - Individual architectural opinions, - A low budget. A research project is starting in The Netherlands to design options of natural, mechanical or hybrid ventilation. These systems for new or refurbished schools will be presented in a comprehensive way in a Dutch design guide and can be integrated in a REHVA-guide dealing with healthy schools in the near future. In this guide higher air change rates will be discussed as well: 35 m 3 /h and 45 m 3 /h per student = 4.9-6.3 l/sm 2. Hybrid ventilation may have different meanings. Generally it comprises a low pressure natural ventilation system which can be supported by fans when necessary. However, a combination of natural air supply with mechanical exhaust or natural air exhaust with mechanical supply can be considered as hybrid as well. Sometimes the building service consultant has to make design proposals for the architect. On the other hand architects can stimulate the creativity of a building service consultant to find a specific solution for a specific problem.. METHODS The methods used during my study and subjects discussed with architects are: a. Research of physical principles b. Architectural research c. Airflow measurements

a. Research of physical principles The research provides a variety of options to deal with air flows and heat transfer: - Mixing of cold air Mixing of cold air with the surrounding warm air in order to prevent draught, without or with a false ceiling. Research at the Delft Technological University [1] shows that it is possible to prevent draught ( 3.5 ls/m 2 ) by means of natural air supply without a ceiling. When the air is supplied just beneath the ceiling with an Archimedes-number of 0,001 (figure 1, II) the DR-value will be maximal 20%. However, it is possible to have an acceptable thermal comfort as well with other Archimedes numbers when the air will be supplied with a wide air inlet with the same size as the width of the room. When the velocity is low (figure 1, I) or very high (figure 1, III) the air velocity above the floor will increase. Concrete core and (floor) heating can - to a certain extend - compensate draught-risks by higher local operative temperatures near the floor. I II III Figure 1: Air supply options without a false ceiling. The integration of the air inlet at the ceiling needs much attention [2, 4], because of the fact that the narrow inlet-slit should be close under the ceiling. In case of a false ceiling there are more possibilities of draught prevention and integration of an air inlet into the façade is more easy [4]. - An outlet via a double window There is no information of the combined performance of an air outlet and a double window. The thermal qualities of the window and air flows are analyzed with CFD-simulations. The outlet system is tested in a police academy in Apeldoorn by measuring the air flow and pressure differences during the heating season. - Heating systems The most common heating systems are a radiator under windows, floor or concrete core heating and preheating of air of an air inlet. It is very important to understand the difference of the convection flow characteristic of radiator heating and floor heating. This has been evaluated with CFD-simulations (Phoenics, Flair). b. Architectural research Two systems are discussed: 1. Systems of natural air supply, mechanical exhaust and several combinations with ceilings for three different façade typologies (positions of windows). After analysing the most general typologies of façades, design principles for architects are developed to support their design processes.

2. A system of natural air exhaust via a double window and mechanical air supply for existing monuments. A design option has been developed for an existing building in which physical, aesthetic, practical and economic requirements are combined. c. Airflow measurements and CFD-simulations The presented natural air supply and natural exhaust systems have been measured or simulated. The performance of the outlet system has been evaluated with the following equations: The maximum air velocity through a vent with a very low air resistance is [1]: Where U max = the maximum air velocity (m/s), the volumetric mass of air (kg/m 3 ). U P = 2 ρ max (1) P = the pressure difference in (Pa) and ρ is For instance, the maximum air velocity at 4 Pa and 20 o C will be 2.6 m/s. The measured air velocity of the system can be divided by the maximum air velocity. This is the airflowefficiency, ε airflow (-): U measured airflow = U max ε (2) The air velocity is measured with a hot wire anemometer (Envic AFT-1D, 0-10 m/s, 3% tolerance) in the opening of the air exhaust system. The pressure difference is measured at both sides of the window (SETRA 267, +50 - -50 Pa, 1% tolerance). The measurements have a sample time of 1 minute. RESULTS a. Physical principles In case of a false ceiling there are other options to prevent draught (figure 2). In this situation the warm air from the room en heath from the concrete ceiling is used to warm up the supplied cold air. The false ceiling has a large surface so there is more time for the cold air to mix with the warm air. > 200 mm Figure 2. Presentation of some physical principles of draught prevention and promotion of mixing of cold and warm air flows, making use of a common -air inlet.

e = mc 2 Figure 3. Presentation of the physical principles and comfort qualities of the system of figure 2. Draught is prevented by the false ceiling. Cold downward air flows from the air inlet are prevented by a spoiler connected to the air inlet. Experience shows that a lot of discussions with architects are necessary to integrate this option in their specific design. Generally it is necessary to make draught problems visible for architects underline the draught-problem (figure 4). local discomfort e = mc 2 Figure 4. Presentation of local thermal discomfort of the system of figure 7b. b. Architectural research Some of the most common systems of natural air supply used by architects in The Netherlands are presented with the following figures: I I A B Figure 5. a) Air supply close to the ceiling, b) Air supply in combination with a false ceiling

II II A B Figure 6. a) Air supply between the window and the ceiling, b) Combination with a false ceiling III III A B Figure 7. a) Air supply above a window, b) Combination with a false ceiling An example of how architects try to integrate this knowledge in their design details is presented in figure 8: Figure 8: Two examples of air inlets details from different Dutch architects. The supplied air can be transported via the zone above a false ceiling (system III B, figure 7). c. Airflow measurements and CFD-simulations Results are design options of: - A self regulating natural air exhausts system. - False ceilings, related to thermal and acoustic parameters. - Different heating systems: Concrete core or radiator heating and options of preheating supplied air. An example of a self regulating natural air exhausts system is given below:

For a monumental building - the police academy in Apeldoorn - an air outlet system has been tested. In this case the air outlet of a self regulating vent is combined with a double window system (figure 9). Some advantages are: - reduction of the amount of ducts in the building - reduction of fan energy - prevention of downdraught by increasing the temperature of the glass at the inner side - reduction of infiltration of cold outdoor air CFD-simulations show that a high position of the outlet is most favourable to prevent downdraught: the temperature of the window at the room side rises and the cold air between the windows cannot flow back into the room. Figure 9: Presentation of the principle of a self-regulating air outlet (system 1, table 1) and a picture with the outlet at the upper side of the window. The self regulating system prevents the wind to influence the airflow too much. Moreover, when the air supply fan is shut off, the heat loss due to ventilation is small (figure 10 and table 1). Air velocities and pressures of system 1 (data 17-25 november 2005) Air velocity (m/s) 2,4 2,2 2 1,8 1,6 1,4 1,2 1 0,8 0,6 0,4 0,2 0-10 -5 0 5 10 15 20 25 Pressure (Pa) Figure 10: Measurement results of air outlet system 1

Table 1. Comparison of two natural air outlet-systems (1.72 m long, opening ca. 1.38 m long) with a repulse valve combined with a double window system. The measurements of system 1 and 2 are executed at the same time in a different window in the same classroom (Apeldoorn, 17-25 November 2005) System 1 System 2 Air velocity (m/s) Pressure difference (Pa) Flow (m 3 /h) Air flow efficiency (-) System Air velocity (m/s) Pressure difference (Pa) Flow (m 3 /h) Air flow efficiency (-) average 1,89 5,49 282 62 % 1,50 6,20 207 standard 0,13 0,73 19 0,11 0,72 15 deviation maximum 2,28 21,07 340 1,86 27,91 256 minimum 0,06 2,01 9 0,05 2,10 7 47 % Tab1e 1 shows a better efficiency of system 1 compared to system 2. The main reason is that the area of the smallest opening in system 1 is larger than of system 2 and the aerodynamic properties of system 1 are better than system 2. However, even the efficiency of system 1 can be improved avoiding sharp edges of the inlet, outlet and bends and creating a smooth channel without disturbances that can create eddies. In that case an air flow efficiency of more than 83% can be reached [5]. False ceilings, related to thermal and acoustic parameters: To have the right reverberation time and good speech intelligibility it is necessary to create 25% absorption on the whole inner surface of a class room. For reasons of air quality the floors need a smooth surface and a large part of the walls and the ceiling should be available for acoustic materials. Acoustic elements can diffuse fresh air. They should not hinder the heat transfer and cleaning of these elements should be possible. At his moment there is a database of design options and a calculation model is developed to predict the acoustical properties of a classroom [6]. Floor or radiator heating and CFD-simulations: Floor heating Radiator heating Figure 11: Comparison of convection flows of natural air supply, combined with a false ceiling and different heating systems (derived from CFD-simulations). Figure 11 shows that it is much easier for radiator heating than for floor heating to prevent downdraught from natural air supply and to promote the mixing of cold and warm air above a false ceiling. In case no radiator is available, heating of the ceiling - like concrete core heating - is necessary as well. However, at the opposite side of the façade there is always the risk of downdraught. This can be reduced by creating - for instance- a air permeable ceiling at the opposite side of the façade.

DISCUSSION When natural air supply and natural exhaust-systems are compared both systems have different opportunities and can be energy effective. In table 2 some of the characteristics of both systems are compared: Table 2: Comparison natural air supply and natural exhaust Air flow Heat recovery Heating and cooling Fan energy Natural air Max. 3.5 Heat pump on air Heating and cooling Very low supply l/sm 2 exhaust with water Natural exhaust 3.5-6.3 l/sm 2 Aquifer preheats and cools the supplied air Heating with water and air, cooling with air Low This table shows that larger air flows can be supplied with a system of natural exhaust than with a system of natural air supply without creating a draught risk. This is possible by using the right air inlet-systems and using the corridor as an outlet as well. By preheating natural supplied air, larger air flows might be possible, but this has not been tested up to now. 1. For architects and other designers it is very important to have a compact database of images and knowledge to show comfort-problems and optional solutions. 2. An integral approach of all the important indoor physical parameters is necessary even for common design problems. ACKNOWLEDGEMENT The author wishes to thank Theo Peters and Linda van Helvoort-Mascini for their assistance with measurements and data-processing and the companies Trox and Buva for developing natural outlet-prototypes. REFERENCES 1. Engel, P.J.W. van den. Inducing vents and their effect on air flow patterns, thermal comfort and air quality. 1995. Indoor air, An Integrated Approach. International workshop Australia. Handbook Elsevier Science (edited by L. Morawska, N.D. Bofinger and M. Maroni), pp 277-280. 2. Engel, P.J.W. van den. Inducing air via the façade for better comfort. 1993. Proceedings of the 6th International Conference on Indoor Air Quality and Climate - Indoor Air '93, Vol 5, pp 163-168. 3. Engel, P.J.W. van den, Zoon W.A.C. Opportunities of hybrid ventilation in existing builings. Proceedings of the 21th Conference of Passive and Low Energy Architecture (PLEA 2004), pp 355-358. 4. Engel, P.J.W. van den. 2005. Healthy climate in schools due to Ventilation and slab heating. Proceedings of Clima 2005, Lausanne. 5. Engel, P.J.W. van den. Development of a floor ventilation channel (research report Ubbink, the Netherlands). 1996. 6. Linde, J. van der. Engel, P. van den. Nijs, L. Speech intelligibility in classrooms with concrete core activation ( Spraakverstaanbaarheid in klaslokalen met betonkernactivering ). TVVLmagazine 2006-6