an ISO9001 company APPLICATION NOTES FOR TGS2611 Application Notes for Methane Gas Detectors using TGS2611

Similar documents
an ISO9001 company APPLICATION NOTES FOR TGS2610 Application Notes for LP Gas Detectors using TGS2610

an ISO9001 company TECHNICAL INFORMATION FOR TGS813 Technical Information for Combustible Gas Sensors

an ISO9001 company TECHNICAL INFORMATION FOR TGS813 Technical Information for Combustible Gas Sensors

TGS for the detection of Carbon Monoxide

DISCONTINUED PRODUCT. For reference only SMOKE DETECTOR WITH INTERCONNECT FEATURES. ABSOLUTE MAXIMUM RATINGS (Voltages are referenced to V SS

IR25 Dual Gas Series Datasheet

Replaced by A5367CA. DISCONTINUED PRODUCT SMOKE DETECTOR WITH INTERCONNECT AND TIMER FEATURES

Danfoss gas detection units

Danfoss gas detection unit Type GD Heavy Duty

Gas Detection Sensor type GDA, GDC, GDHC, GDHF, GDH REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Danfoss gas detection units

IR15 Dual Gas Series Datasheet

Lamp Supply (Recommended)

Web Site: Forums: forums.parallax.com Sales: Technical:

IR15TT-R Miniature Infrared Gas Sensor for Monitoring Carbon Dioxide and Methane up to 100% Vol.

Ozone Gas Sensor. (Model:MQ131 High Concentration) Manual. Version: 1.4. Valid from: Zhengzhou Winsen Electronics Technology Co.

DP86 Constant Voltage with Fitting

DAWN Electronics, Inc.

2015 Amphenol Advanced Sensors. Jinton Industrial Park, Wujin, Changzhou, Jiangsu, China. Web:

Operation and Maintenance Manual

FIS SMART SENSOR U (Draft 1) June 25, 2001

HTF3000LF PVH-3.3 TEMPERATURE AND HUMIDITY MODULE

TECHNICAL DATA MQ-2 GAS SENSOR

Smoke Sensor. (Model:MQ-2) Manual. Version: 1.4. Valid from: Zhengzhou Winsen Electronics Technology Co., Ltd

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0

M7100 Pressure Transducer

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

Safe Operation Manual. Honeywell IQ Force Gas Detector

-smartgas- A new low cost infrared gas sensor for domestic and automotive applications

Analog Room Pressure Monitor RPC Series

The MiCS-5524 is a compact MOS sensor.

D5100 Industrial Differential Pressure Transducer

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller

Standard SPECIFICATIONS FEATURES APPLICATIONS

OEM REFRIGERANT GAS SENSORS for Leak Detection & Measurement

DIGITAL INDICATOR JIR-301-M

Advanced Ultraviolet Burner Controller

Requirements of refrigerant leak detector and alarm for air conditioning and refrigeration equipment

IR1xxx Series 1, IR2xxx Series 1 Miniature Infrared Gas Sensors for Hazardous Areas and Intrinsic Safety in Mining

This instruction manual explains the use of three models listed on the left.

CT-930CH, CT-930LPCH and CT-940CH TABLE OF CONTENTS

MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION

IR1 Single Gas Series Datasheet

IRceL CH4 Methane (CH 4

VQ600 Datasheet. Pellistor Gas Sensor for Hazardous Areas (Fixed Systems) FEATURES TECHNICAL SPECIFICATION OPERATION

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Basic Board Mount Pressure Sensors: NBP Series Uncompensated/Unamplified 60 mbar to 10 bar [1 psi to 150 psi]

Catalytic Gas Sensor. (Model: MC113/ MC113C) Manual. Version: 1.3. Valid from: Zhengzhou Winsen Electronics Technology Co.

SMART Dust Sensor. Amphenol Advanced Sensors SM-PWM-01C. Application Note. Features

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

MS4525 SPECIFICATIONS

MICROpeL 75 Combustible Gas Sensor Part Number: PM

MEMS Carbon Monoxide Gas Sensor. (Model No.:GM-702B) Manual. Version: 1.1. Valid from: Zhengzhou Winsen Electronics Technology Co.

E PIR Motion Detector. Features. General Description. Applications. Single Sensor Application Circuit

The MiCS-4514 is a compact MOS sensor with two fully independent sensing elements on one package.

A5364. Ionization Smoke Detector with Interconnect

6-1 Installing Batteries 6-2 Automatic Circuit/Reset Feature 6-3 Feature Sensitivity Adjustment

Instruction Manual STATIC ERASER TOP FAN. Table of Contents

Datasheet: K-22 LO Sensor

CMF, CMX & CMA series

Ammonia Gas Sensor. (Model:MQ137) Manual. Version: 1.4. Valid from: Zhengzhou Winsen Electronics Technology Co., Ltd

O3TH. Ozone Detector c/w Indicator for Temperature/Humidity. Automatikprodukter. Features. Technical Data. Description. Ordering Codes. Dec.

INSTRUCTION MANUAL FOR RIKEN PORTABLE TOXIC GAS MONITOR

TOCOS. Guidelines & Precautions. For Using Trimmer Potentiometers. Guidelines for Circuit Design. Guidelines for Production Processes

RK / RK Methane Detector Operator s Manual

Warranty Registration

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

SIARGO MEMS FLOW SENSING PRODUCTS MEMS Mass Flow/Clog Sensors VC Siargo Ltd. ISO 9001 ISO OHSAS 18001

Model C-380. Instruction Manual. Refrigerant Leak Detector. reedinstruments

CARBON MONOXIDE CO SS SOLID STATE ELECTROCHEMICAL SENSORS

MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR

Data Sheet Sensor: IRA-S210ST01 Lens: IML-0685 / IML Sensor : IRA-S210ST01 Lens : IML-0685/0688. Pyro Electric Infrared Sensor Fresnel Lens

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

HM1520LF Relative Humidity Module

Mercury Vapor Monitor VM-3000

NGD8800 USER S MANUAL

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

GasAlert. Introduction. WWarning. Table 1. GasAlert Models. Gas Monitored

D5100 Industrial Differential Pressure Transducer

TILT SENSOR SWITCH. Item No. RBS Description Ball-Contact Version 13 Page 1 of 7 Publish Date May 29, 2018

Two-Channel Gas Controller

Sensor unit MC2 with analog output for Freon gases and refrigerants

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

MS1471 SPECIFICATIONS. PC Board Mountable Pressure Sensor 0-60 mv Output Gage and Absolute Low Cost

LI-830 and LI-850 Gas Analyzers. For Continuous Monitoring Applications

LI-830 and LI-850 Gas Analyzers. For Continuous Monitoring Applications

Key Features. General Description

Technical data sheet TDS0060

02/11/2015

NIDS Dust sensor ED-N-DS-1408

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100

Hydrocarbon Gas Detector

SEC Millenium Carbon Dioxide Gas Detector

MS4525DO SPECIFICATIONS FEATURES APPLICATIONS

FIS30XXseries Gas sensor module SPECIFICATIONS

GAS LEAK DETECTORS FOR METHANE AND LPG P11 - P12

RK-05 Carbon Monoxide Detector Operator s Manual

Sub psi SPECIFICATIONS

MSP100 Pressure Transducer

HOA1888 Series. Infrared Assemblies Wide Gap Transmissive Sensor. MICRO SWITCH Sensing and Control

Transcription:

Application Notes for Methane Gas Detectors using TGS2611 an ISO9001 company The TGS2611 methane gas sensor has been presorted into groupings which will allow users to simplify the manufacturing process for methane gas detectors. This brochure offers example application circuits and important technical advice for designing and manufacturing gas detectors which use classified TGS2611 sensors. Page Introduction...2 Detector Circuit Design Basic Circuit with Temperature Compensation...2 Selecting a Load Resistor...2 Compensation for Internally Generated Heat...3 Heater Breakage Detection Circuit...3 Sensor Malfunction Detection Circuit...3 Prevention of Intermittent Alarming...4 Alarm Prevention during Warmup...4 Alarm Delay Circuit...5 Application Circuit...5 Manufacturing Process Handling and Storage of Sensors...5 RL Selection...5 PCB Assembly...5 Sensor Assembly...5 Final Assembly...6 Preheating of Final Assembly...6 Gas Test...6 Storage of Finished Products...6 Anticipated Performance at 10%LEL of Methane...6 Precalibrated Sensor Module...7 Appendix...8 See also Technical Brochure Technical Information on Usage of TGS Sensors for Toxic and Explosive Gas Leak Detectors. IMPORTANT NOTE: OPERATING CONDITIONS IN WHICH FIGARO SENSORS ARE USED WILL VARY WITH EACH CUSTOMER S SPECIFIC APPLICATIONS. FIGARO STRONGLY RECOMMENDS CONSULTING OUR TECHNICAL STAFF BEFORE DEPLOYING FIGARO SENSORS IN YOUR APPLICATION AND, IN PARTICULAR, WHEN CUSTOMER S TARGET GASES ARE NOT LISTED HEREIN. FIGARO CANNOT ASSUME ANY RESPONSIBILITY FOR ANY USE OF ITS SENSORS IN A PRODUCT OR APPLICATION FOR WHICH SENSOR HAS NOT BEEN SPECIFICALLY TESTED BY FIGARO. TGS2611J00 is a UL recognized component in accordance with the requirements of UL2075. Please note that component recognition testing has confirmed long term stability in 60ppm of methane; other characteristics shown in this brochure have not been confirmed by UL as part of component recognition. Revised 08/03 1

To facilitate ease in manufacturing gas detectors, both Figaro TGS2611J00 and TGS2611B00 methane gas sensors are individually marked with an ID number (see Figure 1) indicating a factory presorted classification which corresponds to narrow ranges of sensor resistance in methane. When the sensor s ID number is properly used, the calibration process can be greatly simplified, eliminating long preconditioning time and the complicated handling of calibration gas. 1. Detector Circuit Design 11 Basic circuit with temperature compensation Figure 2 shows an example of a basic circuit for gas detection, including temperature compensation for variations caused by ambient temperature fluctuations. Typical values for the circuit components are as follows: RL : refer to Table 1 RTH : 4.7kΩ (±3%), B=3977 (±5%) RA : 11.5kΩ (±1%) RB : 4.32kΩ (±1%) RC : 8.25kΩ (±1%) The values for components related to temperature compensation should be chosen so that Vref is onehalf of the Vc value at standard temperature (20 C). The Vref curve should approximate the temperature dependency curve of the VRL when compensation is properly done. 12 Selecting a load resistor (RL) To optimize resolution of the output signal at the desired alarming concentration, it is necessary to adjust the resistance of the load resistor (RL). It is recommended that RL be selected at a value which is equal to the sensor s resistance (Rs) at the alarming concentration (i.e. Rs/RL = 1.0). Please refer to the brochure General Information for TGS Sensors for more details. Since the ID number corresponding to sensor resistance in methane gas is indicated on the sensor cap, the load resistor value can be selected according to Table 1. For example, for an alarm setting at 10% LEL, when using a sensor having an ID number of 7, the RL value should be set at 1.27kΩ. By using the recommended RL, the VRL value at the alarming point typically will be 2.5V, which is equal to half of the circuit voltage (Vc). D.C. input Voltage regulator 78M05 TGS2611 984AA #07 TGS2611J00 TGS2611B00 Fig. 1 Sensor markings 4 1 Vc = 5.0 ± 0.2V TGS 2611 RL Sensor code 3 Lot # 2 ID # RA RB RC TGS2611 314AE #07 VREF VRL Fig. 2 Basic circuit with temperature compensation RTH Alarm signal Comparator Sensor RL( kω) with ± 1% tolerance ID# 5% LEL 10% LEL 15% LEL 20% LEL 01 0.976 0.715 0.590 0.511 02 1.07 0.787 0.649 0.562 03 1.18 0.866 0.715 0.619 04 1.30 0.953 0.787 0.681 05 1.43 1.05 0.866 0.750 06 1.58 1.15 0.953 0.825 07 1.74 1.27 1.05 0.909 08 1.91 1.40 1.15 1.00 09 2.10 1.54 1.27 1.10 10 2.32 1.69 1.40 1.21 11 2.55 1.87 1.54 1.33 12 2.80 2.05 1.69 1.47 13 3.09 2.26 1.87 1.62 14 3.40 2.49 2.05 1.78 15 3.74 2.74 2.26 1.96 16 4.12 3.01 2.49 2.15 17 4.53 3.32 2.74 2.37 18 4.99 3.65 3.01 2.61 19 5.49 4.02 3.32 2.87 20 6.04 4.42 3.65 3.16 21 6.65 4.87 4.02 3.48 22 7.32 5.36 4.42 3.83 23 8.06 5.90 4.87 4.22 24 8.87 6.49 5.36 4.64 Table 1 Recommended RL by sensor ID Note: Lower explosion limit (LEL) of methane = 50,000ppm Revised 08/03 2

13 Compensation for internally generated heat Depending on the design of the case and the PCB, there is often a difference between the temperature near the thermistor s placement in the detector and the ambient temperature. Therefore it is recommended to measure the actual temperature difference between the inside and the outside of the detector and select the value of RC according to Table 2. When RC is selected in this manner and used in the basic circuit (Figure 2), the result would be that Vref=1/2 Vc. T ( C) Rc ( kω) 0 8.25 5 7.68 10 7.15 15 6.65 20 6.34 T= (temp near themistor)(temp outside detector) Table 2 Effect on selection of Rc by temperature differential inside and outside of detector 14 Heater breakage detection circuit Figure 3 shows an example of how breakage of the sensor s heater wire and/or heater element can be detected. By adding RE (3.57Ω±1%) into the circuit and monitoring VRE, a malfunction can be considered to have occurred when VRE (0.2V typ.) drops to near 0V. Please note that a circuit voltage (Vc) of 5.2V should be applied to a circuit which incorporates a heater malfunction detection circuit. Vc=5.2V 78M05 56mA (typ.) RE 0.2V (typ.) 0.05~0.1V Heater breakage signal Figure 3 Heater breakage detection circuit (RE = 3.57Ω±1%) 15 Sensor malfunction detection circuit Breakage of lead wires to the sensor s electrodes and/or sensor element can be detected by using a circuit such as that shown in Figure 4. This involves replacing RC with RC1 and RC2, selecting their values so that RC1/RC2 35. Since VRL is normally greater than 70mV in any atmospheric conditions, by comparing VRL to a reference voltage of 70mV, breakage of the lead wires and/ or sensor element can be considered to have occurred if VRL drops below 70mV. VC RC1 RC2 RA RTH RB VREF VRL 70mV (typ.) Sensor breakage signal Figure 4 Sensor malfunction detection circuit (RC1/RC2 35) Revised 08/03 3

16 Prevention of intermittent alarming When gas concentration fluctuates right at the alarming threshold, dropping just below and rising just above, the detector would intermittently alarm in short bursts. In order to prevent the nuisance of intermittent alarming, a circuit such as that shown in Figure 5 can be used. By adding RD to the original circuit, a Schmidt trigger circuit which includes a comparator can be created (the value of RD should be set at 2030 times that of Rc). As a result, a range for the alarming threshold is created. An alarm is then generated when the upper range of the threshold is breached and the alarm signal would cease after the signal drops below the lower end of the threshold range, thus eliminating frequent intermittent alarming. VC VRL RA RB VREF RC RTH Figure 5 Circuit for prevention of intermittent alarming (RD/RC = 20~30) RD Alarm signal 17 Alarm prevention during warmup As described in Sec. 26 of Technical Information for TGS2611, when energizing the sensor after an unpowered period, the sensor s resistance (Rs) drops sharply for the first few seconds after energizing, regardless of the presence of gases, before recovering to a stable level. This initial action may cause activation of an alarm during the first few moments of energizing since VRL would exceed Vref. To prevent this from happening, a circuit modification such as that shown in Figure 6 may be used. After powering the detector, sensor output (VRL) should be set to zero for a predetermined period (2.5 minutes is recommendedthe timer function should be created by selecting the proper combination of C3 and R11). In order to restrict current to the sensor during this period, the recommended value of RF should exceed 5kΩ. VC RL RF VRL 2.5 min. time delay circuit Figure 6 Circuit for alarm prevention during warmup (RF > 5kΩ) R9 R10 R11 C3 D5 Revised 08/03 4

18 Alarm delay circuit To prevent false alarms caused by transient interference gases such as alcohol in cooking vapors, a delay circuit modification such as that shown in Figure 7 can be used. The alarm signal generated by this circuit should be connected to the comparator in the basic circuit (see Figure 1). The recommended timer period for alarm delay is 15 secondsthe timer function should be created by selecting the proper combination of C4 and R15. VC Alarm signal R8 R12 Tr R13 15 sec. time delay circuit D6 R14 R15 R9 C4 R10 IC3 Delayed alarm signal 19 Application circuit An application circuit which incorporates all of the advice included in Secs. 11 through 18 can be seen in Appendix 1. Figure 7 Alarm delay circuit 2. Manufacturing Process (see Fig. 8) 21 Handling and storage of sensors Prior to usage, sensors should be stored at room temperature in a sealed bag containing normal clean air. During manufacturing, sensors should be handled in a clean air environment and at room temperature. Clean air refers to air free of contaminants, excessive dust, solvent vapors, etc. Room temperature should be 20~25 C. 22 RL selection Choose the proper resistor for RL by referring to the ID number of the sensor and Table 1. 23 PCB assembly Flux should be sufficiently dried before sensors are assembled onto the PCB to avoid any contamination of the sensor by flux vapors. 24 Sensor assembly Manual soldering of the sensor to the PCB is strongly advised. Solders composed of Sn63:Pb37 or Sn60:Pb40 with nonchloric resin flux (MIL: RMA Grade; for example, Almit KR 19) are recommended for usage. 25 Final assembly Avoid any shock or vibration which may be caused by air driven tools. This may cause breakage of the sensor s lead wires or other physical damage to the sensor. Investigation Acceptance of classified sensor RL selection NG Acceptance of components PCB Assembly PCB Test Final Assembly (PCB, casing etc.) Preheating ( 48 hours) OK OK Figure 8 Manufacturing process flowchart *3 NG Sensor and RL Assembly (manual soldering) Gas Test Packing Storage Shipping Repair Quality control sampling *Alarm concentration *Long term stability Revised 08/03 5

26 Preheating of final assembly To stabilize the detector assembly before gas testing, the minimum period for preheating final assemblies should be 48 hours at room temperature (20~25 C). Be certain to maintain clean atmospheric conditions for preheating. 27 Gas test Test all finished products in the target gas under normal operating conditions. Keep the atmospheric conditions in the chamber stable, utilizing a userdefined standard test condition which is based on applicable performance standards and on anticipated usage for detectors. Remove any traces of smoke, adhesives, gases, or solvents from the chamber. NOTE: Without testing after final assembly, detectors have no guarantee of accuracy or reliability. 28 Storage of finished products Detectors should be stored in a clean air environment at room temperature. Avoid storage in dirty or contaminated environments. Cautions listed in Sec. 61.3 of General Information for TGS Sensors should also be observed. 3. Anticipated Performance at 10%LEL of Methane When using the classified TGS2611 with Figaro s recommended RL for 10%LEL (Table 1) and temperature compensated circuit design (Figure 2), typical alarm tolerances for 10%LEL of methane such as those shown in Figure 9 are expected. Each RL classification contains a range of tolerance as exemplified by the alarming range labelled as standard conditions (i.e. these conditions are wellcontrolled). When factoring in the additional effects of environmental extremes and the allowable variation in circuit conditions, the resulting alarming range would be typified by the range labelled as operating conditions. However, in actual usage, alarm thresholds may vary since the threshold is also affected by factors such as the tolerances of the thermistor and/or other components, load resistor value, test conditions, and heat generation inside the detector enclosure. As a Figure 9 Expected performance of methane detectors with classified TGS2611 & recommended RL for 10% LEL (refer to Table 3 for test conditions) Temperature and humidity Circuit condition Conditioning to test under operating conditions at recommended circuit condition Standard conditions Operating conditions Standard conditions Operating conditions prior under std test conditions 3 4 5 6 7 8 9 10 15 20 25 30 Alarming point (%LEL) 20± 2 C, 65± 5%RH 10 ~ 40 C, 30~95%RH V c=5.0± 0.01V DC V H=5.0± 0.05V DC V c=5.0± 0.2V DC V H=5.0± 0.2V DC 48 hours Table 3 Test conditions for measuring performance of methane detectors as shown in Figure 9 Revised 08/03 6

result, Figaro neither expressly nor impliedly warrants the performance shown in Figure 9. If a large difference between the expected and actual performance of detectors is noticed, please consult with Figaro. Precalibrated sensor module Figaro has available a precalibrated methane sensor module NGM2611 (see Fig. 10). This module includes the classified TGS2611 sensor, a matched load resistor, and a factory preset temperature compensation circuit, all on a small PC board. The NGM2611 module is calibrated for a typical set point at 10% LEL, achieving performance as indicated in Figure 9 by simply plugging it into a main PC board. Please refer to the brochure Product Information for NGM2611 for detailed information. Figure 10 Precalibrated sensor module NGM2611 Important Reminder Without testing alarm threshold after final assembly, detectors have no accuracy or reliability guarantee. Figaro USA Inc. and the manufacturer, Figaro Engineering Inc. (together referred to as Figaro) reserve the right to make changes without notice to any products herein to improve reliability, functioning or design. Information contained in this document is believed to be reliable. However, Figaro does not assume any liability arising out of the application or use of any product or circuit described herein; neither does it convey any license under its patent rights, nor the rights of others. Figaro's products are not authorized for use as critical components in life support applications wherein a failure or malfunction of the products may result in injury or threat to life. FIGARO GROUP HEAD OFFICE Figaro Engineering Inc. 1511 Senbanishi Mino, Osaka 5628505 JAPAN Tel.: (81) 727282561 Fax: (81) 727280467 email: figaro@figaro.co.jp OVERSEAS Figaro USA Inc. 3703 West Lake Ave. Suite 203 Glenview, IL 600251266 USA Tel.: (1) 8478321701 Fax.: (1) 8478321705 email: figarousa@figarosensor.com Revised 08/03 7

Appendix 1 Example application circuit for gas detector using classified TGS2611 Power Supply (AC10V / 80mA) ~ Initial delay: approx. 2.5 minutes Alarm delay: approx. 15 seconds IC 1 D 1~4 C 1 C 2 3 4 1 2 SENSOR RL R 1 R 8 R 11 D 6 R 15 D 7 R 2 R TH R 9 R 7 D 5 R 14 R 3 R 12 Tr 1/4 R 6 IC 2 R 4 2/4 R 10 R 5 C 3 3/4 R 13 C 4 1/2 IC 3 2/2 Malfunction signal 4/4 (Active "L") (Note: "L" output also occurs during initial delay) No. name Model No./ Specification Maker No. name Model No./ Specification Maker No. name Model No./ Specification Maker Sensor Gas sensor TGS2611 Figaro R9 Resistor D1 Rectification S5566G RTH NTC thermistor 4.7kΩ, B=3977 Phillips R10 Resistor D2 Rectification S5566G RL Resistor See Table 1), 1%, 1/8W ( R 1 1 Resistor 470kΩ, 5% 1/8W D3 Rectification S5566G R1 Resistor 3.57Ω 1%, 1/2W, R 2 1 Resistor D4 Rectification S5566G R2 Resistor 11.5kΩ 1%, 1/8W, R 3 1 Resistor D5 Small signal 1S1588 R3 Resistor 4.32kΩ 1%, 1/8W, R 4 1 Resistor 1kΩ, 5% 1/8W D6 Small signal 1S1588 R4 Resistor 7.87kΩ, 1% 1/8W R15 Resistor 470kΩ, 5% 1/8W D7 Small signal 1S1588 R5 Resistor 226Ω, 1% 1/8W C1 Electrolytic capacitor 470µ F/25V Tr NPN transistor 2SC2603 Mitsubishi R6 Resistor C2 Electrolytic capacitor 10µ F/10V IC1 Voltage regulator MC78M05CT Motorola R7 Resistor 200kΩ, 5% 1/8W C3 Electrolytic capacitor 470µ F/10V, 10% IC2 Comparator LM339 Motorola R8 Resistor C4 Electrolytic capacitor 47µ F/10V, 10% IC3 Comparator LM393 Motorola Alarm signal (Active "L") Revised 08/03 8