AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE

Similar documents
Code Technology Committee Meeting #31 March 31-April 1, 2015 Care_WTC Recommendations/Elevators

Status Update K-tag WG 12/8/2011

Following are code change proposals submitted through Adhoc Health from General study group and related changes. General. Position.

CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B

Fxx - 13 K-66 Smoking Regulations (New)

AdHoc Committee on Healthcare Meeting #14 April 1-2, 2015 AHC Group A Changes (Agenda Item 5.0)

ICC code change proposals are being reviewed, evaluated, prioritized, and desired results determined by the BHMA Task Group working on the proposals.

AHC MEETING #4 PART I ROUND 1 ISSUES CODE CHANGES

E25 (D) Automatic controls for general means of egress lighting

AHC Meeting #7 July 12-13, Occupancy WG Report

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

2000 to 2012 Hospital K-tag crosswalk matrix for hospitals 2000 Tag #

Emergency Planning for Institutional Facilities

Summary. Code Technologies Committee has submitted 6 public comments: FS42-15, EB58-15, G9-15, G33-15, G200-15, P34-15

AHC Meeting #7 July 12-13, Fire Safety WG Report. A Cycle Approved Code Changes

Code Technologies Committee Report Elevator Lobby Group A changes: Elevator Lobby

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

SAF-BCF SECOND REVISIONS WITH STATEMENTS

First Revision No NFPA [ Section No ]

BCAC Egress Work Group

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

Code Technologies Committee Report Fire Rated Glazing Group A changes: Fire rated glazing

ICC Committee on Health Care Hospitals and Nursing Homes Group A Draft Proposals Revised Copyright 2017 International Code Council, Inc.

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Public. Mike Free Health. State of Alabama Department of

CTC Meeting #27 JUNE 17 18, 2013 NIST report on the Charleston sofa store fire

Public Health Fax: Web Site:

Report on First Revisions with Statement June 2014 NFPA 101

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

AHC MEETING # 4 K-TAG CODE CHANGE PROPOSALS (Covers all Work Groups)

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

DEALING WITH FIRE SAFETY

FIRE/SMOKE BARRIER FUNDAMENTALS

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

NFPA 101 Life Safety Code Culture change 2012

Defend In Place 2012 IFC Overview of Institutional Occupancies

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Agency for Health Care Administration

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

IRC - BUILDING - ELECTRICAL - ELECTRICAL TAC

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Chapter 2: Definitions

Code Technology Committee Area of Study Balanced Fire Protection Roof Vents

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Agency for Health Care Administration

U.S. Codes & Standards for Energy Storage Systems. Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group

Life Safety Code Comparison

Purpose of the Act. Learning Objectives. Latest with DOJ. Latest with DOJ. Texas Registered Accessibility Specialists Association

Agency for Health Care Administration

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

ICC CODE TECHNOLOGY COMMITTEE Area of Study Labeling of Fire Rated Glazing

Residential Care Facilities Requirements

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

International Code Council

2015 Recommended Building Code with Amendments. The Executive Committee of the Central Iowa Code Consortium does ordain as follows:

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

FIRE AND SAFETY PROJECT REVIEW REPORT

2012 International Fire Code Errata (Portions of text and tables not shown are unaffected by the errata)

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

For additional information regarding R-3.1 residential care facilities please contact (951)

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

Agency for Health Care Administration

Residential Based Care Facility Guidelines

ICC CODE CORNER 2015 International Fire Code

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

FAQs - Codes and Listings

Iowa (2) Delete section and insert in lieu thereof the following new section:

Agency for Health Care Administration

Code Technology Committee 2006/2007 Cycle Area of study Carbon monoxide alarms Public comments

Date: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 PRELIMINARY CODE REVIEW. International Plumbing Code Edition

Building Standards Advisory Promoting construction of safe, healthy, habitable buildings

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

SP07: Coordinating New Door Assembly Installation with Access Control Systems

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

The New Life Safety Code & Texas Responds with New Small House Nursing Design Standards

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

SECTION 915 CARBON MONOXIDE DETECTION

Agency for Health Care Administration

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Transcription:

AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE This report includes 6 code change proposals from the Adhoc Health Care, Means of Egress committee developed for Group B changes. Other proposals are currently wrapped into the proposal for new Section 1105 that appears in the General Committee report. Code Section Comments IFC 605.12 Electrical system maintenance IFC/IBC IFC 907.2.6.2 (IBC [F] 407.8, 907.2.6.2) Coordinate language for automatic fire detection IFC 1030.2.1 Security devices and egress locks coordination with lock changes to Group A IFC 1030.3.1 Maintain clear width of aisle, corridors and ramps IFC 1104.7 Door size will be incorporated into new Section 1105 proposal IEBC 805.10 Level II or Level III alteration requires check for refuge area

605_12 - F321 -Williams.docx 605.12 (new), 605.12.1(new) Proponent: John Williams, CBO, Chair, ICC Ad Hoc Committee on Health Care Add new text as follows: IFC 605.12 Electrical systems maintenance. Electrical components, equipment and systems shall be maintained in compliance with the provisions of NFPA 70. IFC 605.12.1 Group I-2 maintenance. Group I-2 electrical components, equipment systems shall also be maintained in accordance with the provisions of NFPA 99. Reason: Existing electrical systems are required to comply with NFPA 70 by the Center for Medicare/Medicaid Services (CMS) in order for a facility to receive federal reimbursement funds. Providing the code language for Group I-2 occupancies will ensure the required electrical systems are maintained per NFPA 70. All meeting materials and reports are posted on the AHC website at: http://www.iccsafe.org/cs/ahc/pages/default.aspx.

907_2_6_2 -F312A -Williams.docx IFC 907.2.6.2 (IBC [F] 407.8, 907.2.6.2) Proponent: John Williams, CBO, Chair, ICC Ad Hoc Committee on Health Care Revise as follows: IBC [F] 407.8 Automatic fire detection. An automatic smoke detection system shall be installed in corridors in nursing homes, long-term care facilities, detoxification facilities and spaces permitted to be open to the corridors by Section 407.2 shall be equipped with an automatic fire detection system. The system shall be activated in accordance with Section 907.5. Hospitals shall be equipped with an automatic smoke detection system as required in Section 407.2 and 407.4.3. Exceptions: 1. Corridor smoke detection is not required where sleeping rooms in smoke compartments that contain sleeping units where such units are provided with smoke detectors that comply with UL 268. Such detectors shall provide a visual display on the corridor side of each sleeping room and unit and shall provide an audible and visual alarm at the care provider s station attending each unit. 2. Corridor smoke detection is not required where sleeping room in smoke compartments that contain sleeping units where sleeping unit doors are equipped with automatic door-closing devices with integral smoke detectors on the unit sides installed in accordance with their listing, provided that the integral detectors perform the required alerting function. 907.2.6.2 (IBC [F] 907.2.6.2) Group I-2. An automatic smoke detection system shall be installed in corridors in nursing homes, long term care facilities, detoxification facilities and spaces permitted to be open to the corridors by Section 407.2. The system shall be activated in accordance with Section 907.4. Hospitals shall be equipped with an automatic smoke detection system as required in Section 407. Exceptions: 1. Corridor smoke detection is not required in smoke compartments that contain sleeping units where such units are provided with smoke detectors that comply with UL 268. Such detectors shall provide a visual display on the corridor side of each sleeping unit and shall provide an audible and visual alarm at the care provider s station attending each unit. 2. Corridor smoke detection is not required in smoke compartments that contain sleeping units where sleeping unit doors are equipped with automatic doorclosing devices with integral smoke detectors on the unit sides installed in accordance with their listing, provided that the integral detectors perform the required alerting function. Reason: The proposed language in IBC 407.8 and IBC/IFC 907.2.6.2 coordinates with the proposed language automatic smoke detection system requirements in IBC 407.4.3 submitted by the Adhoc Health Care committee during Group A hearings. The intent is also to make the language consistent between the two sections.

907_2_6_2 -F312A -Williams.docx All meeting materials and reports are posted on the AHC website at: http://www.iccsafe.org/cs/ahc/pages/default.aspx

1030_2_1 F308B-Williams.docx IFC 1030.2.1 Proponent: John Williams, CBO, Chair, ICC Ad Hoc Committee on Health Care and Carl Baldassarra, P.E., FSFPE, Chair, ICC Code Technology Committee Revise as follows: IFC 1030.2.1 Security devices and egress locks. Security devices and locks affecting means of egress shall be subject to approval of the fire code official. Special locking arrangements including, but not limited to access controlled egress doors, security grills, mechanical locks and latches and all electronic locks and systems that restrict, control or delay egress shall be installed and maintained as required by this chapter. Reason: The Adhoc Health Care committee and ICC Code Technologies Committee co-sponsored code changes to update terminology for several of the different locking systems address in the IBC. This change in terminology would make the maintenance provisions in the IFC consistent with the terminology changes. All meeting materials and reports are posted on the AHC website at: http://www.iccsafe.org/cs/ahc/pages/default.aspx Insert standard CTC paragraph

1030_3_1 F304 -Williams.docx IFC 1030.3.1(new) Proponent: John Williams, CBO, Chair, ICC Ad Hoc Committee on Health Care and Carl Baldassarra, P.E., FSFPE, Chair, ICC Code Technology Committee Add new text as follows: IFC 1030.3.1 Group I-2. In Group I-2, the required clear width for aisles, corridors and ramps that are part of the required means of egress shall comply with Section 1018.2. The facility shall have a plan to maintain the required clear width during emergency situations. Exception: In areas required for bed movement, equipment shall be permitted in the required width where all the following provisions are met: 1. The equipment is low hazard and wheeled. 2. The equipment does not reduce the effective clear width for the means of egress to less than 5 feet (1525 mm). 3. The equipment is limited to: 3.1. Equipment and carts in use; 3.2. Medical emergency equipment; 3.3. Infection control carts; and 3.4. Patient lift and transportation equipment. 4. Medical emergency equipment and patient lift and transportation equipment, when not in use, is required to be located on one side of the corridor. 5. The equipment is limited in number to a maximum of one per patient sleeping room or patient care room within each smoke compartment. Reason: The new language in Section 1030.3.1 is to be placed in the International Fire Code as a procedural requirement. It is recognized that the 8-0 wide corridor in an institutional occupancy where beds are moved is to remain at 8-0 in width. The language recognizes and identifies the fact that certain movable pieces of equipment will be present in the corridor during normal operations of the patient care units and seeks to restrict the types and number of such pieces of equipment and the restrictions the equipment may impose on the means of egress. The language also recognizes that during emergencies facilities must have an emergency management plan that address the steps that must be taken by the facility and responding staff to ensure that the required 8-0 wide corridor is kept clear of movable obstructions. The terminology is consistent with NFPA 101. Board of Directors to evaluate and assess contemporary code issues relating to hospitals and ambulatory healthcare facilities. The AHC is composed of building code officials, fire code officials, hospital facility engineers, and state healthcare enforcement representatives. The goals of the committee are to ensure that the ICC family of codes appropriately addresses the fire and life safety concerns of a highly specialized and rapidly evolving healthcare delivery system. This process is part of a joint effort between ICC and the American Society for Healthcare Engineering (ASHE), a subsidiary of the American Hospital Association, to eliminate duplication and conflicts in healthcare regulation. Since its inception in April, 2011, the AHC has held 5 open meetings and over 80 workgroup calls which included members of the AHC as well as any interested party to discuss and debate the proposed changes. All meeting materials and reports are posted on the AHC website at: http://www.iccsafe.org/cs/ahc/pages/default.aspx. Insert standard CTC paragraph

1104_7-F313 -Williams.docx 1104.7 Proponent: John Williams, CBO, Chair, ICC Ad Hoc Committee on Health Care Revise as follows: IFC 1104.7 Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 28 inches (711 mm). Where this section requires a minimum clear width of 28 inches (711 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 28 inches (711 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. In Group I-2 and Ambulatory care facilities, doors serving as means of egress from patient treatment rooms or patient sleeping rooms shall provide a clear width of not less than 32 inches (813 mm). Means of egress doors in an occupancy In Group I-2, doors serving as means of egress and used for the movement of beds shall provide a clear width not less than 41.5 inches (1054 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. The height of doors shall not be less than 80 inches (2032 mm). Exceptions: 1. The minimum and maximum width shall not apply to door openings that are not part of the required means of egress in occupancies in Groups R-2 and R- 3. 2. Door openings to storage closets less than 10 square feet (0.93 m 2 ) in area shall not be limited by the minimum width. 3. Width of door leafs in revolving doors that comply with Section 1008.1.4.1 shall not be limited. 4. Door openings within a dwelling unit shall not be less than 78 inches (1981 mm) in height. 5. Exterior door openings in dwelling units, other than the required exit door, shall not be less than 76 inches (1930 mm) in height. 6. Exit access doors serving a room not larger than 70 square feet (6.5 m 2 ) shall be not less than 24 inches (610 mm) in door width. Reason: Doors in hospitals, nursing homes, and similar occupancies have historically required doors to be a minimum of 32-inches in clear width due to the nature of the occupants within the buildings. The BOCA Basic Building Code in 1975 and the Uniform Building Code prior to 1979 both started requiring doors providing a clear width of 32-inches. The Americans with Disabilities Act Accessible Guidelines (ADAAG) of 1994 and the 2010 ADA Standards for Accessible Design, along with the Unified Federal Accessibility Standards (UFAS) also require a minimum of 32-inches clear because of the width necessary to maneuver a wheelchair through a door opening. Adding Ambulatory Care Facilities to the rule does not add any additional restrictions further than the IBC for door sizing. All meeting materials and reports are posted on the AHC website at: http://www.iccsafe.org/cs/ahc/pages/default.aspx.

1104_7-F313 -Williams.docx

805_10-EB314A -Williams.docx EBxx-12/13 IEBC 805.10-805.10.3 (new) Proponent: John Williams, CBO, Chair, ICC Ad Hoc Committee on Health Care Add new text as follows: IEBC 805.10 Refuge areas. Where alterations affect the configuration of an area utilized as a refuge areas, the capacity of the refuge area shall not be reduced below that required in Section 805.10.1 through 805.10.3. IEBC 805.10.1 Smoke compartments. In Group I-2 and I-3 occupancies, the required capacity of the refuge areas for smoke compartments in accordance with Section 407.5.1 and 408.6.2 of the International Building Code shall be maintained. IEBC 805.10.2 Ambulatory care. In ambulatory care facilities required to be separated by Section 422.2 of the International Building Code, the required capacity of the refuge areas for smoke compartments in accordance with Section 422.4 of the International Building Code shall be maintained. IEBC 805.10.3 Horizontal exits. The required capacity of the refuge area for horizontal exits in accordance with Section 1025.4 of the International Building Code shall be maintained. Reason: When a space is being altered the designer needs to check that an alteration does not conflict with the area being used as a refuge area from an adjacent compartment. There is a correlative change proposed for IBC Chapter 34/IEBC Chapter 4. All meeting materials and reports are posted on the AHC website at: http://www.iccsafe.org/cs/ahc/pages/default.aspx. Insert standard CTC paragraph