VRV IV i-series heat pump

Similar documents
Keep looking you ll never find me. VRV IV heat pumps for indoor installation

Replacement VRV Quick & quality replacement for R-22 and R-407C systems

Water cooled VRV IV W-series

VRV IV S-series heat pump

VRV IV heat recovery Best efficiency and comfort solution

Concealed ceiling unit with medium ESP

6/8/2016 THE INVISIBLE VRV. VRV-i

Concealed ceiling units

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer

VRV IV 360 efficiency

Air Conditioning. Technical Data. Multi model application EEDEN MXS-E

Product Line Introduction. Karl Zhang Technical support engineer

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling

Air Conditioning. Technical Data EEDEN RXS-F8

PRODUCT LINEUP VRF. For LIGHT COMMERCIAL & RESIDENTIAL, COMMERCIAL

FUJITSU VRF 2016/17 PRODUCT CATALOGUE VRF MULTI SPLIT VRF VENTILATION

Fully Flat Cassette Design & Genius in one

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FXMQ-MB

Air Conditioning. Technical Data EEDEN RZQG-L8/7V1

VENTILATION. Effective heat exchange and fresh air ventilation

New rooftop series UATYQ-ABAY1 AFC2Y1 AFC3Y1. Extensive option package included in all models. ErP. years warranty. compliant 2018

Introducing the new Sky Air A-series with ultra-efficient Bluevolution R-32 technology. Our mission Achieve the lowest environmental impact

Air Conditioning. Technical Data EEDEN AZQS-BV1

Air Conditioning. Technical Data. VRV IV S-series heat pump EEDEN16-200_2 RXYSQ-TV1

COOLflow 4E PRODUCT RANGE

3 rd Generation of VRV. The professional solution for your professional project

Air Conditioning. Technical Data. Pair, Twin, triple, double twin EEDEN RZQ-C

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

Ventilation. Technical Data. Outdoor air processing unit, ventilation and air processing EEDEN FXMQ-MF

High temperature hydrobox for VRV

Digital Inverter 4 series 8 & 10HP

where innovation meets creativity

VRV+AHU System DAIKIN NEW STANDARD SERIES UNIT MODEL AHUR-CA/SA

Air conditioners Heating & Cooling

recooler HP EQKR HEAT PUMP

Air Conditioning. Technical Data. VRV IV S-series compact heat pump EEDEN RXYSCQ-TV1

Air Conditioners Heating & Cooling

mini-cassette W MULTI SPLIT R410A & VRF SERIES AUTO MODEL MDH13HLS MDH13HLS

Optimised for high ambient operation (up to 55 C ambient) EWAD-MZ. Air cooled chiller

Air Conditioning. Technical Data EEDEN RZQSG-L(8)Y1

Air Conditioning. Technical Data EEDEN RZQSG-L(3/8)V1

AHU Plus. DX Air Handling Units

TABLE OF CONTENTS RMXS-E8V1B

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-C

Air Conditioners Heating & Cooling

Air conditioners Cooling only

Air Conditioning. Technical Data. High temperature hydrobox for VRV EEDEN HXHD-A8

Daikin Applied UK Technically better... D-AHU Modular R. Air handling units. Compact air handling unit with heat recovery wheel

MRVIII-C MRVIII-C. 4 way air return heat exchanger design. Two stages heat exchanger design. Double EEV design. Special Heat Exchanger Design

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

COMMERCIAL AIR CONDITIONERS. R410A All DC Inverter VRF V5 X Series 50/60Hz

Daikin offers the widest range in DX ventilation in the market. With a variety of ventilation solutions from small heat recovery ventilation to large

. Creating Maximum Comfort

THE CARRIER COMFORT LINE

DC inverter VRF presentation

DAIKIN FBQ DUCTED SERIES HEATING & COOLING SYSTEMS. DC DUCT-CONCEALED Up to 17.5 SEER / Up to 10.6 HSPF Up to 13.0 EER

FTQ SERIES DUCTED HEAT PUMP SYSTEMS. INDOOR AND OUTDOOR UNITS Up to 20 SEER / Up to 12 HSPF / Up to 14.5 EER INVERTER, VARIABLE SPEED COMPRESSOR

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling

Air Conditioning. Technical Data. VRV IV heat recovery EEDEN14-200_4 REYQ-T

Ventilation. Product catalogue 2019 for professionals

EEDEN technical data ERHQ AA

AIR HANDLING UNITS ASSET REFERENCE: DESIGN AHU 1 AHU 2

Commercial Air Conditioners 2017/2018. VRF 50/60Hz. V5 X Series

Europe s first light commercial cassette system using R-32 refrigerant. Our mission The lowest environmental impact

FCQH-D8 / RZQ-D3V1/D9V1

Daikin leads the way:

Integrated VarIable refrigerant flow ahu/pau (r410a)

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Hitachi Air Conditioning. Engineered for tomorrow. VRF Systems Ventilation GENERAL CATALOGUE

Air Conditioners Heating & Cooling

Ducted inverter reverse cycle air conditioning

The natural fit, all-in-one. Daikin Altherma monobloc heat pump for the installer

Sky Air. Product catalogue for installers Your business is our concern

INVERTER SCROLL. LG Electronics Distributed by. Copyright 2017 LG Electronics. All rights reserved.

SUPERB TECHNOLOGY FOR SUPERB INTERIORS

Air conditioners Heating & Cooling

Air Conditioners Heating & Cooling

Ventilation Product catalogue 2017 for professionals

VZ Chiller series. Water cooled inverter chiller. The highest peak in chiller technology

Multi Air Conditioning System for Buildings

NEW DAIKIN FTQ SERIES HEATING AND COOLING SYSTEMS. MULTI-POSITIONAL AIR HANDLER Up to 16 SEER / Up to 10.4 HSPF / Up to 12.5 EER

Air Conditioning. Technical Data. Concealed ceiling unit EEDEN FDXM-F

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

Index. Toshiba Solutions. Absolute comfort

EWAD-TZB. Screw inverter chiller. High efficiency chiller for comfort and process cooling

Launching of new SET-FREE Outdoor Units - RAS-FSXN1E Series (8-54HP)-

Product catalogue Air handling units. Easy and flexible solutions for any ventilation requirements

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

DESIGN & TECHNICAL MANUAL

Air Conditioners Heating & Cooling

VRF D4 PLUS System. Highlights. Digital Scroll Series. Dealer information. Commercial Air Conditioner Business Units Midea Group

For small and medium-sized food retailers. Conveni-Pack. The integrated solution for refrigeration, heating and air conditioning

your comfort. our world. Altherma Flex Type Renewable heat pump system for every environment

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Compact Design For Light Commercial Buildings. Benefit Points SMALL OFFICES HOTELS NEW SHOPS, RESTAURANTS. 1. Compact & Quiet design

VARIABLE REFRIGERANT FLOW (VRF) FULL LINE CATALOG

Transcription:

VRV IV i-series heat pump for indoor installation unique patented concept Air curtain Biddle Air curtain for VRV (CYV) 22 Indoor units VRV type indoor units Control systems Ventilation Heat Reclaim ventilation (VAM/VKM) AHU connection kit VRV IV standards: Variable refrigerant temperature Customize your VRV for best seasonal efficiency & comfort VRV configurator Software for simplified commissioning, configuration and customisation Night quiet mode Full inverter compressors Low noise function Sine wave DC inverter DC fan motor E-pass heat exchanger I demand function Manual demand function For detailed explanation of these functions refer to vrv iv technologies tab 76

Invisible Consider a wider range of properties because Seamless integration into the surroundings as only outdoor installation is not a factor Open for business sooner because getting building permits is simplified No need for a roof installation or back alley the grille is visible Outdoor Unit Product Range installation Quiet Highly suited to densely populated areas such as city centres thanks to their low operating sound Lightweight parts can be installed by two people < Dedicated modes reduce sound further to comply with inner-city noise regulations Heat exchanger sound not louder than a normal conversation Compressor sound not louder than a refrigerator 77

Unique split outdoor unit for indoor installation Compact and easy to hide, the compressor can be installed at floor level, in a back office, storage room, technical area or in a kitchen, while the heat exchanger can be installed in a false ceiling space. This means that the air conditioning system is completely invisible and does not take up expensive commercial floor space. Unrivalled flexibility thanks to the fact that the outdoor unit is split into two parts 1 1. The heat exchanger can be installed in a false ceiling space. 2 1 2 2. The compressor is compact and easy to hide, this element can be installed at floor level, in a back office, storage room, technical area or in a kitchen. This means that the air conditioning system is completely invisible and does not take up expensive commercial floor space. VRV Indoor units Heat exchanger unit Max. 70 m Max. 30 m Compressor unit 78

Outdoor Unit Product Range Invisible air suction and air discharge 79

The problem solver for many installation issues Example 1 High flexibilty The other way around: install the modules where if fits your customer, not where it is the best fit for the outdoor unit If there is no flat roof or backgarden available for installation of the outdoor unit, VRV IV i-series offers the solution. The suction and exhaust can be installed at the façade or at the rear of the building as the inverter fans allows ESP to be adjusted to the length of the ductwork. The compressor module can be installed up to 30 m from the heat exchanger unit in a storage room,... 80 Flexible installation thanks to inverter fans

Example 2 Shorter pipe runs to the indoor units reduces installation costs compared to rooftop or back alley installation Back alley or rooftop needs very long piping lengths Long installation time Additional cost Capacity loss VRV IV i-series can be installed close to the indoor units Quicker installation Lower cost No capacity loss Outdoor Unit Product Range short distance Example 3 No need for bulky and expensive sound countermeasures To comply with city regulation countermeasures are needed for standard units Expensive sound cages might be needed to reduce sound (standard outdoor unit sound = 50~60 dba) Inside installation using expensive floor space With VRV IV i-series you easily comply with city regulation without additional measures Operation sound 47 dba (flexible to install in corridor, shop area, ) or lower with attenuator No floor space is used as units can be installed in false ceiling, against the wall, Reduced floor space More floor space sound Expensive counter measures No additional measures needed Other VRF VRV IV i-series cage Other VRF VRV IV i-series technical aera stock = stock kitchen kitchen SHOP SHOP 81

Patented V-shape heat exchanger for best surface to volume ratio 8 patents Optimised air flow and temperature distribution Best performance for defrost (tested in high humidity down to -20 C). Patented perforated and insulated partition plate Reduces conductivity and prevents cold bridges Only 400mm high Fits easily in any false ceiling Standard delivered filter with the unit to prevent dirt from entering the heat exchanger Super efficient centrifugal fans Over 50% efficiency increase compared to sirocco fan Patented backward- curved blade technology More pressure increase 82

Compressor unit with rotating switchbox Flexible and easy to install Flexibility by back and top refrigerant connection possibility Rotating switchbox For easy access to all compressor parts Outdoor Unit Product Range Only 77 kg Tube-in-tube subcool heat exchanger This patented heat exchanger increases the capacity of the system by ensuring optimal state of refrigerant in the heat exchanger module. This in turn increases overall efficiency. No drain connection needed Thanks to natural evaporation Minimized cold surface to reduce dew formation Fast and easy installation Non welded bottom casing Avoids any corrosion risk Small footprint Maximizes useable floor space (600 x 550 mm) Can easily be mounted in a storage room, back office, 83

SB.RKXYQ-T VRV IV heat pump for indoor installation The invisible VRV Unique VRV heat pump for indoor installation Unrivalled flexibility because the unit is split up into two elements: the heat exchanger and the compressor Heat exchanger unit SB.RKXYQ5T VRV Indoor units Max. 70 m Max. 30 m Compressor unit Highly suited to densely populated areas thanks to the low operation sound and seamless integration into surrounding architecture as only the grille is visible Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature, VRV configurator and full inverter compressors Lightweight units (max. 97kg) can be installed by two people Unique V-shape heat exchanger results in compact dimensions (h/e unit only 400mm high) allowing false ceiling installation, while ensuring top efficiency ʯ ʯ Super efficient centrifugal fans (over 50% efficiency increase compared to sirocco fan) Small footprint compressor unit (600 x 550 mm) maximizing useable floor space Contains all standard VRV features 8HP launch 2nd half 2016 Outdoor system SB.RKXYQ 5T 8T System Compressor unit RKXYQ5T RKXYQ8T Heat exchanger unit RDXYQ5T RDXYQ8T Capacity range HP 5 8 Cooling capacity Nom. 35 CDB kw 14.0 22.4 Heating capacity Nom. 6 CWB kw 14.0 22.4 Max. 6 CWB kw 16.0 - Power input - 50Hz Cooling Nom. 35 CDB kw 4.38 - Heating Nom. 6 CWB kw 3.68 - Max. 6 CWB kw 4.71 - EER at nom. capacity 35 CDB kw/kw 3.20 - COP at nom. capacity 6 CWB kw/kw 3.80 - at max. capacity 6 CWB kw/kw 3.40 - Maximum number of connectable indoor units 10 (1) (1) Indoor index connection Fan 84 Min. 62.5 100 Nom. - - Max. 162.5 260 External static Max. Pa 150 150 pressure Nom. Pa 60 - Operation range Cooling Min.~Max. CDB -5~46-5~46 Heating Min.~Max. CWB -20~15.5-20~15.5 Temperature Min. CDB 5 5 around casing Max. CDB 35 35 Piping connections Between Compressor Liquid OD mm 12.7 12.7 module (CM) and heat Gas OD mm exchanger module (HM) 19.1 22.2 Between Compressor Liquid OD mm 9.5 9.52 module (CM) and indoor units (IU) Gas OD mm 15.9 19.1 Total piping length System Actual m 140 300 (1) Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%). Outdoor unit module compressor module heat exchanger module RKXYQ5T RKXYQ8T RDXYQ5T RDXYQ8T Dimensions Unit Height/Width/Depth mm 701/600/554 701/760/554 397/1,456/1,044 397/1,456/1,044 Weight Unit kg 77 100 97 107 Fan Type - - Centrifugal Centrifugal Air flow rate Cooling Nom. m³/min - - 55 - Discharge direction - - Discharge duct Discharge duct Sound power level Cooling Nom. dba - - - - Sound pressure level Cooling Nom. dba 47 56 47 - Refrigerant Type R-410A R-410A R-410A R-410A Charge kg 2 4 - - TCO₂eq 4.2 8.4 - - GWP 2,087.5 2,087.5 - - Power supply Phase/Frequency/Voltage Hz/V 3N~/50/380-415 3N~/50/380-415 1N~/50/220-240 1N~/50/220-240 Current - 50Hz Maximum fuse amps (MFA) A 16-10 - *Note: blue cells contain preliminary data

Detailed technical drawings RDXYQ-T RDXYQ5T7V1B 63 62 5 239 4 1044 705 Suspension position 239 149 255 5 4 45 9 (4x) View A 397 26 298 1456 1498 Suspension position 67 1196 99 6 8 7 A 117 25 27 102 716 3 2 1 659 716 9 Hook 9 Hook 8 Service door 8 Service door 7 Air discharge side 7 Air discharge side 6 Air suction side 6 Air suction side 5 Wiring intake (low voltage wiring) 4 Wiring intake (high voltage wiring) 5 Wiring intake (low voltage wiring) 3 Drain outlet 4 Wiring intake (high voltage 2 Gas pipe wiring) connection port 1 Liquid pipe connection port 3 Drain outlet No. Part name 2 Gas pipe connection port 1 Liquid pipe connection port No. Part name Transmission wiring connection Power supply connection Transmission wiring connection VP25 Power Ø supply 19.1 brazing connection VP25 Ø 12.7 brazing connection Remark Ø 19.1 brazing connection Ø 12.7 brazing connection Remark 2D098826 RKXYQ-T RKXYQ5T7Y1B 600 4x O17 Foundation bolt hole 554 149 45 9 (4x) View A 1456 1498 Suspension position 1196 8 6 7 117 99 25 A Outdoor Unit Product Range 27 102 3 2 1 659 2D098826 7 118 57 View A 101 Indoor unit 3 57 54 8 701 6 4 Heat exchanger unit 5 1 337 365 2 88 120 55 59 516 Pitch of foundation bolt holes 15 426 Pitch of foundation bolt holes A 85 8 Handle 7 Pipe routing hole 6 Wiring intake (low voltage wiring) 5 Wiring intake (high voltage wiring) 4 Gas pipe connection port 3 Liquid pipe connection port 2 Gas pipe connection port 1 Liquid pipe connection port No. Part name Knockout hole. Transmission wiring connection Power supply connection Ø 15.9 brazing connection Ø 9.5 brazing connection Ø 19.1 brazing connection Ø 12.7 brazing connection Remark 3D098827 85

Detailed technical drawings RDXYQ-T RDXYQ5T7V1B Air discharge side 50 or more Air suction side RKXYQ-T RKXYQ5T7Y1B 10 or more 10 or more 10 or more 500 or more 10 or more 10 or more 100 or more 100 or more 500 or more 3D098834 Front view Top view 86 3D098835