Thermal Modelling for the Motor in Semi-hermetic Screw Refrigeration Compressor under Part-load Conditions

Similar documents
The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Purdue e-pubs. Purdue University

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Low GWP Refrigerants for Air Conditioning Applications

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Dynamic Simulation of Liquid Chillers

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Numerical Simulation of a New Cooling System for Commercial Aircrafts

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Sub-Critical Operation of the CO2 Expander/ Compressor

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Screw Compressor For Ammonia-Water Heat Pump Lubricated By The Process Mixture

Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid Refrigerant Injection

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Study of R161 Refrigerant for Residential Airconditioning

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

System Modeling of Gas Engine Driven Heat Pump

Development of Large Refrigerant Compressors

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Experimental Study on the Performance of Twisted Capillary Tube

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Air-Cooled Heat Exchanger Performance for R410A

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Optimization of Compressors used in Air Conditioning Units

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Diagnosing Troubles in Refrigeration Units with Screw Compressors

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

R32 Compressor for Air conditioning and Refrigeration applications in China

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Design And Analysis Of Centrifugal Pump

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

High Efficiency R-134a Compressor for Domestic Refrigerator

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance of CO2 Cycles with a Two-Stage Compressor

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Comparison of the High Side vs

Efficiency of Non-Azeotropic Refrigerant Cycle

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Compressor Capacity Control: A New Direction

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Experimental and Numerical Study on a Dryexpansion Shell-and-Tube Evaporator Used in Wastewater Source Heat Pump (WWSHP)

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 Thermal Modelling for the Motor in Semi-hermetic Screw Refrigeration Compressor under Part-load Conditions Wenqing Chen wqchen@hotmail.com Jiubing Shen Zhilong He Huagen Wu Ziwen Xing Follow this and additional works at: https://docs.lib.purdue.edu/icec Chen, Wenqing; Shen, Jiubing; He, Zhilong; Wu, Huagen; and Xing, Ziwen, "Thermal Modelling for the Motor in Semi-hermetic Screw Refrigeration Compressor under Part-load Conditions" (2012). International Compressor Engineering Conference. Paper 2075. https://docs.lib.purdue.edu/icec/2075 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

1246, Page 1 Thermal Modeling for the Motor in Semi-hermetic Screw Refrigeration Compressor under Part-load Conditions Wenqing CHEN*, Jiubing SHEN, Zhilong HE, Huagen WU, Ziwen XING School of Energy and Power Engineering, Xi an Jiaotong University, Xi an, 710049, China Phone: 86-29-82675258, Fax: 86-29-82663783, E-mail: wqchen@hotmail.com * Corresponding Author ABSTRACT Semi-hermetic screw refrigeration compressor is mostly driven by a three phase asynchronous induction motor with its squirrel cage rotor attached to the shaft of the compressor helical male rotor. The motor is cooled by low temperature refrigerant coming from evaporator before it is inspired into compressor suction port. In order to investigate cooling effects of the motor and performance of the compressor under part-load conditions, a lumped parameter model describing heat transfer characteristics inside the motor and a part-load model of screw refrigeration compressor are developed. Heating effects at compressor suction end are taken into account and nodes representing refrigerant inside the motor cooling passages are modeled separately. Due to the decreasing refrigerant mass flow rate and motor efficiency, temperature rise of refrigerant through the motor increases and stator winding temperature curve goes up when the compressor load drops by suction volume variation. 1. INTRODUCTION Development of high efficiency double-side asymmetric profile, maturity of rapid precision machining technology and introduction of oil injection make twin screw refrigeration compressor have various advantages, such as stable operation, high efficiency, reliable and compact structure. Semi-hermetic screw refrigeration compressor is widely utilized in industrial and commercial refrigeration systems. In the semi-hermetic arrangement, the squirrel cage rotor of three phase asynchronous induction motor is directly attached to the shaft of compressor helical male rotor, refrigerant gas flows through the motor and absorbs heat dissipation due to motor losses before it is inspired into compressor suction port, refrigerant and oil leakage through the shaft seal occurring in the open-type arrangement can be avoided in addition to more compact compositions. Temperature rise is an important parameter to evaluate performance of the motor, it is directly related to the motor lifetime, output power and efficiency. With increasing requirements for energy efficiency and cost reduction, as well as the imperative to fully exploit new topologies and materials, temperature estimate inside the motor is increasingly essential (Boglietti et al., 2009). Besides, semi-hermetic screw refrigeration compressor is frequently operated under part-load conditions to meet the load variation caused by different seasons and applications. When the compressor is under part-load conditions, mass flow rate of refrigerant through the motor decreases, so does the motor efficiency because its output power deviates from the rated one, then the motor may not be cooled sufficiently and the superheat degree of refrigerant at the compressor suction port would rise, adversely affecting the reliable continued operation and performance of the semi-hermetic screw refrigeration compressor. Consequently, it is of great importance to study heat transfer characteristics inside the motor and investigate their influences on performance of the semi-hermetic screw refrigeration compressor under part-load conditions, which can be helpful for motor selection, arrangement of cooling passages and improvement of part-load efficiency.

1246, Page 2 2. THERMAL ANALYSIS OF THE MOTOR In order to make sure sufficient motor cooling effect and minimize temperature rise and pressure drop of refrigerant through the motor, coolant channels inside the motor should be arranged according to distribution of motor losses. Losses inside the three phase asynchronous induction motor can be divided into iron losses, ohmic losses and stray load losses by the induced mechanism. Therefore there are three flow domains for motor cooling in the semihermetic screw refrigeration compressor shown in Figure 1, stator cooling ducts, inner gap and rotor cooling holes. stator cooling ducts inner gap helical rotors slide valve suction end endwindings slot windings suction filter caged rotor discharge end bearings internal gas-oil separator rotor cooling holes suction end bearings discharge end Figure 1: Schematic of semi-hermetic screw refrigeration compressor (exaggerated inner gap) 2.1 Thermal equivalent circuit Thermal equivalent circuit, the most common approach of the lumped parameter method, has become the main tool used by many researchers involved in thermal analysis of electrical machines (Okoro, 2005). As shown in Figure 2, the motor is geometrically divided into a series of lumped elements, each element is indicated by a thermal node storing thermal information like heat generation and thermal capacity and interconnecting to neighboring nodes through a linear mesh of thermal resistances, average temperature of the element is represented by the node temperature. The circular nodes represent motor solid components, whereas the square ones indicate refrigerant gas in coolant channels. Combining and solving ordinary differential energy conservation equations of all the thermal nodes, steady temperature distribution inside the motor can be obtained. Heat generation is equivalent to current source in electrical circuit, including electrical losses, heating effects at compressor suction end, friction and gas-flow losses. Electrical losses are derived by electromagnetic analysis and then applied to the corresponding thermal nodes. Friction losses are caused by rotor rotation and mainly generated in inner gap, space around rotor end-rings and rotor cooling holes. Gas-flow losses are associated with tangential acceleration of refrigerant gas in inner gap and rotor cooling holes. Friction and gas-flow losses are significant only at high rotation speeds (higher than 20000 r min -1 ) ( Saari, 1998) while the rotation speed is usually lower than 6000 r min -1 for the motor in semi-hermetic screw refrigeration compressor, so they are ignored in this paper. Heating effects of oil back from suction end bearings, bearing losses and by-pass flow venting back through the by-pass port when the compressor is under part-load conditions by movement of a slide valve, are dependent on rotation speed, by-pass flow state, oil temperature and flow rate as F 5 3 TSref Moilcoil Toil 0.15 u 10 Mbp, oilcoil Tbp, oil Mbp, ghbp, g 10 (1) d where c oil represents oil specific heat capacity, M oil and Toil indicate oil mass flow rate and temperature difference back from suction end bearings respectively, F is bearing load, d and u represent diameter and peripheral velocity at the circle connecting centers of bearing balls respectively, M bp, oil and T bp, oil denote mass flow rate and

temperature difference of by-pass oil flow, while Mbp, g and h, denote mass flow rate and specific enthalpy of bypass refrigerant gas respectively. bp g 1246, Page 3 T env T env T env T env left-side endcap 1 9 9 5 10 refrigerant at stator cooling ducts middle frame stator yoke 11 10 refrigerant at stator cooling ducts middle frame stator yoke 11 right-side frame refrigerant left-side at entry end-windings 2 slot windings 13 12 stator teeth slot windings 13 12 stator teeth right-side end-windings refrigerant at exit 3 refrigerant at inner gap 14...... refrigerant at inner gap 14 7 6 4 left-side end-ring 15 rotor windings 15 rotor windings 8 right-side end-ring 16 rotor yoke shaft 17 refrigerant at rotor cooling holes 18 16 rotor yoke shaft 17 refrigerant at rotor cooling holes 18 Figure 2: Thermal equivalent circuit of the motor in hermetic refrigeration compressor Thermal storage represents the ability of storing heat energy and resisting temperature rise in a certain region, it is disabled for the thermal equivalent circuit when the semi-hermetic screw refrigeration compressor is under steady operation. Thermal resistance denotes heat transfer intensity between neighboring nodes. For the motor in semihermetic screw refrigeration compressor, only heat conduction and convection are considered, whereas heat radiation is so weak that it can be neglected (Boglietti et al., 2006). Conduction thermal resistance between motor solid components is equal to the path length divided by product of the path area A and the material s thermal conductivity : TR cond (2) A Convection thermal resistance is equal to one divided by product of the surface area A and convection heat-transfer coefficient : 1 TR conv (3) A 2.2 Modeling of refrigerant In semi-hermetic screw refrigeration compressor, most of the heat generated from motor losses is removed by refrigerant gas due to the forced open cooling circuit, and there is a rather high temperature rise for refrigerant when it arrives at compressor suction end. The irreversible flow direction makes that temperature of downstream flow is always higher than that of upstream flow and refrigerant gas moves with heat from a node to the next one, heat does not flow simply from higher temperature nodes to lower temperature nodes as happening in solid components. Hence, heat exchange between refrigerant elements must be analyzed separately to get reliable calculated results of temperature distribution inside the motor with forced open cooling circuit. It is assumed that refrigerant through the motor is incompressible with constant properties and the heating of refrigerant gas is linear, then refrigerant temperature rise for the ith section in a flow passage can be written as T R (4) Rq is thermal resistance of refrigerant defined as 2 q i

1 Rq (5) 2Mc i p 1246, Page 4 Φi is sum of heat absorbed in node i, M i is mass flow rate of refrigerant gas passing node i. Then it can be concluded that: temperature rise at refrigerant node i relative to earth is equal to sum of two products, the first is 2R q multiplied by heat absorbed by refrigerant before node i and the second is R multiplied by heat absorbed at node i : i1 i q j q i j1 T 2R Φ R Φ (6) 3. PART-LOAD MODEL OF SCREW COMPRESSOR The working process of screw refrigeration compressor under part-load conditions is a rather complicated variable mass thermodynamic process, where the effects of two-phase flow leakage, oil injection, heat transfer and capacity control have to be taken into account. The model is developed based on energy conservation in the working chamber d mu de de dq dw (7) i o the item on the left side means increment of internal energy, the right four items in order are energy carried in by inflow, energy carried out by outflow, heat removed from refrigerant and power consumed in the working chamber. Continuity equation and other additional relations, such as heat-transfer calculation and refrigerant properties, are also employed. Then capacity control process has to be simulated to make up a complete model describing working process of screw refrigeration compressor under part-load conditions. Suction volume variation, achieved by the slide valve motion, is still the main method widely employed for capacity control in the twin screw compressor. A by-pass port appears between the slide valve and slide stop when the compressor is under part-load conditions, and the normal compression process is postponed due to the by-pass process. In screw refrigeration compressor, oil is usually injected into the working chamber at the preliminary stage of compression soon after suction and the oil port position does not change with movement of the slide valve. Therefore the by-pass process partly overlaps with the oil injection process, and the flow through the by-pass port should be treated as two-phase flow since much oil has been injected into the working chamber. The mass flow rate of gas-oil mixture through the by-pass port can be expressed by (Lin, 2003) CaSA 2lP m 1x x l g mg xm ml 1x m (8) 2 3 g g g 1.48625 9.26541 44.6954 60.6150 l l l 4 5 g g 5.12966 26.5743 l l where a is the void fraction, x is the ratio of refrigerant in the gas-oil mixture, C is the flow coefficient. 4. RESULTS AND DISCUSSION For the sake of model validation, experimental study on temperature distribution inside the motor and performance of semi-hermetic screw refrigeration compressor under part-load conditions by slide valve motion is implemented. Main parameters of the semi-hermetic screw refrigeration compressor are listed in Table 1. Several K-type thermocouples are immersed into stator windings; refrigerant thermodynamic states at motor entry and compressor suction port are measured. q

1246, Page 5 Table 1 Main parameters of the semi-hermetic screw refrigeration compressor Parameter Value Parameter Value Refrigerant R22 Number of stator cooling ducts 5 Voltage (V) 380 Cross angle of each stator cooling duct (deg) 48 Supply frequency (HZ) 50 Stator outer radius (mm) 150 Number of motor poles 2 Frame inner radius (mm) 162.5 Rated power (kw) 67 Number of rotor cooling holes 3 Length of stator core (mm) 241 Radius of rotor cooling holes (mm) 4 Inner gap length (mm) 1.0 Compressor maximum displacement (m 3 h -1 ) 237 Volumetric efficiency and power consumption of the compressor at different slide valve positions with an evaporation temperature of -5ºC and a condensation temperature of 35ºC are shown in Figure 3. The superheat degree on the suction line is 12ºC. Figure 4 presents temperature curve of stator windings, temperature rise and pressure drop of refrigerant under part-load conditions. It can be observed that measured and calculated results are in good agreement with each other, indicating that the model developed in this paper is reasonable for thermal analysis of the motor in semi-hermetic screw refrigeration compressor under part-load conditions. Figure 3: Performance of the compressor by suction volume variation For windings in stator slots, the axial thermal conductivity is almost the same as it is for copper, while the radial thermal conductivity is far lower because of the presence of different insulation layers. As a result, most of the heat transformed from stator copper losses is removed from stator stack area to end-windings, turning end-windings into the hottest points inside the motor. However, it can be relieved to some extent for end-windings closed to motor entry by the prior cooling with the refrigerant just coming from suction pipe. Consequently, the temperature curve of stator windings along the axial direction should be declining firstly from end-windings closed to motor entry (denoted as left side) and then rising to the highest point at end-windings closed to compressor suction port (denoted as right side). As the compressor load drops, both refrigerant mass flow rate and power consumption decrease (Figure 3), but the decrement rate of power consumption becomes smaller at lower load positions due to the larger proportion of irreversible losses (Chen et al., 2011). Moreover, motor efficiency will decline because the output power of the motor is much smaller than the rated power. As a result, stator winding temperature increases and temperature difference between the left side and right side end-windings decreases as shown in Figure 4 (a). Due to the larger

1246, Page 6 power consumption when the compressor is fully loaded, stator winding temperatures are higher than that under 75% and 50% load positions. Heating effects of the oil and refrigerant gas venting back from the by-pass port, combined with the less mass flow rate, make the temperature rise of refrigerant increase sharply and suction pressure drop go down while the compressor loads down as shown in Figure 4 (b). (a) Stator winding temperature curve (b) Temperature rise and pressure drop of refrigerant Figure 4: Measured and calculated results inside the motor by suction volume variation 5. CONCLUSIONS Based on the lumped parameter method, thermal equivalent circuit of the motor in semi-hermetic screw refrigeration compressor has been developed, where heating effects at compressor suction end are taken into account and refrigerant inside the motor cooling passages is modeled separately. The part-load model of screw refrigeration compressor has been also established. Combining the validated models, temperature distribution inside the motor and performance of the semi-hermetic screw refrigeration compressor under part-load conditions can be calculated. The comprehensive model developed in this paper can be used for motor selection, cooling passage arrangement and efficiency improvement of semi-hermetic screw refrigeration compressor under part-load conditions in the following work. When the semi-hermetic screw refrigeration compressor load drops by slide valve motion, both the stator winding temperature and temperature rise of refrigerant through the motor increase, the compressor should not run under too low load positions.

1246, Page 7 REFERENCES Boglietti A., Cavagnino A., Staton D. and Shanel M., 2009. Evolution and Modern Approaches for Thermal Analysis of Electrical Machines. IEEE Transactions on Industrial Electronics, vol. 56, p. 871-882. Okoro O.I., 2005. Steady and transient states thermal analysis of a 7.5-kW squirrel-cage induction machine at ratedload operation. IEEE Transactions on Energy Conversion, vol. 20, p. 730-736. Saari J., 1998. Thermal Analysis of High-speed Induction Machines, Acta Polytechnical Scandinavica, Electrical Enginnering Series No.90, Finland, 73p. Boglietti A., Cavagnino A., Parvis M. and Vallan A., 2006. Evaluation of radiation thermal resistances in industrial motors. IEEE Transactions on Industry Applications, vol. 42, p. 688-693. Lin Z., 2003. Gas-Liquid Two-Phase Flow and Boiling Heat transfer. Xi'an Jiaotong University Press, Xi an, China. Chen W., Xing Z., Tang H. and Wu H., 2011. Theoretical and experimental investigation on the performance of screw refrigeration compressor under part-load conditions. International Journal of Refrigeration, vol. 34, p. 1141-1150.