PLL Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

Similar documents
PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

TMC Temperature Monitoring Control Temperature Range -30 to 250 F (-35 to 120 C)

User's Manual H-VC5. Chore-Logic. H-VC5 User manual. Version HPS 11/11/2006 User manual 1.02 ST50737MA 3/07. Page 1

Chore-Tronics Load Cell Indicator

CT2 Retro Box Installation Instruction Manual

Conductivity Network Sensor

120 VAC SYSTEM CONTROL KIT Model: CK-63

Fan Speed. Auto Swing. Timer. Power. Mode. Fan. Only. Saver. Temp. Dry. Fan. Speed. Auto Swing. Timer. Power. Mode. Saver. Only. Temp.

SYSTEM CONTROL KIT Model: CK-41P

Expanded Backup Control Installation & Operator s Instruction Manual

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Safety & Installation Instructions

24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG

Spa Control System OWNER S MANUAL

OPERATION, SERVICE & PARTS MANUAL

OPERATION, SERVICE & PARTS MANUAL

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Installation, Operation & Service Manual

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.

ion Genesis Pump Controller

120 VAC SYSTEM CONTROL KIT

FreezeAlarm. General Description FA-D /FA-D-AAB. Applications. Features. Specifications. Dimensions

WIRING MODEL 20 Low Water Cut-Off and Pump Control MAXIMUM PRESSURE: 20 PSI INTERNAL WIRING BLUE WHITE UPPER PROBE (FEED OFF) FEED PROBE (FEED ON) ALL

MaxLite LED Vapor Tight Linear Fixture

MaxLite 4, 6, 8 & 9 LED Architectural & Commercial Downlights

Automatic Phone-Out Home Monitoring Systems

MaxLite LED High Bay Fixtures

Safety & Installation Instructions

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07

Installation Instructions

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

Freeze Alarm. General Description VD-6300-MCS / VD-6301-MCS. Applications. Features. Specifications. Dimensions

AIM TECHNICAL MANUAL PATENT PENDING STOP REMEMBER TO ACTIVATE UNIT BEFORE TESTING. See page 9 for Activation Instructions

CO2 Sensor User and Installation Guide

User s Manual and Warranty Information for Counterweighted Chain Drive ThyssenKrupp Access

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

INSTALLATION INSTRUCTIONS

Model 8710 Wireless Thermostat. Owner s Manual. Includes Operating Instructions and Warranty Information READ AND SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

ATMOX MAXX System THE Complete Moisture Control System for Crawlspaces. User s Guide

MaxLite LED Round Pendant Highbay Series

Remote Sensor Module: EB-RSM-01

INSTALLATION & OPERATION MANUAL

Sound Cover [ , , , ]

Remote Relay Module (RRM)

INSTRUCTIONS FOR OPERATION AND CARE OF

SYSTEM CONTROL KIT READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

36 & 48 E-Z Cone Fan. Installation & Operator s Instruction Manual (Direct Drive)

SC Installation, Operation & Application Guide

Installation and Maintenance Instructions

10810 W. LITTLE YORK RD., STE. 130 HOUSTON TX VOICE (713) FAX (713) web: IMPORTANT!!!

Door/Window Sensor Installation Instructions

READ AND SAVE THESE INSTRUCTIONS

WARNING Important Safety Information

VX SERIES Wireless Thermostat with Occupancy Sensor

AG Series Electric Heaters

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

WARNING Important Safety Information

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

48 Vanguard Belt Drive Fans Installation and Operators Instruction Manual

Multiple Boilers Electro TS Series Application EB-C-STG5

AV17 Series Switch-Tek Manual Direct and Remote Drum Mount Float Alarm 17 SEPT 08 Rev A

Non-Programmable Digital Thermostat

COMBUSTION AIR SYSTEM

Owner s Manual. Digital. Heat Pump. 5+2 Day Programmable. Model S1-THEH21P5S HVAC SERVICE PARTS TM

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS

Patent Pending invent for New Construction

Installation Manual. THM-0100 Setpoint Thermostat Version THM HBX Control Systems Inc.

MODEL EPC-D-F-ATS INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS!

Installation and Owner Man u al

Instruction Manual: IM E. Installation and Operation Manual for Powerware PVL 50, 80, 100, 120, 160, 200 KA

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Humidity Monitor model 01080

* These Remote Mics must be SPRM-GP

OPERATING INSTRUCTIONS

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

Electric Radiator. A cost effective approach to save fuel and reduce noise for generators from 2 to 10 kw

CSD-1 CRN Electra Steam, Inc. Instruction Manual for JR06 Steam Generator, JG- and JJ- Models

SERIES 500. Installation & Maintenance Instructions. Ceiling Mounted Fan Forced Heater WARNING SAVE THESE INSTRUCTIONS. Recessed Mount.

MaxLite LED MICRO-T PANEL

Operating Manual. Gasgard 100 Control System. Order No.: /00. MSAsafety.com

Installation Manual NPE-180A/240A WARNING. Add-on Controller Installation Kit

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

INSTALLER S & OWNER S MANUAL


FW-RA-LED Remote Multiplex Annunciator Panels

Thermostat Series. Installation Manual TSTBM-RRS--TW-A Revised 02-13

Advantium 16 System Monitor

TECHNICAL MANUAL TM... Fryer, Deep-Fat, Electric w/solid State Controls 440 Volt, 60 HZ, 3 Phase NSN:

be liable for any other loss or damage, whether direct, indirect, incidental or consequential.

5+2 DAY. Digital Thermostat. residential. & 1-cool. up to 2-heat PROGRAMMABLE THERMOSTAT. Venstar Inc. 05/08

Hg5 HV Amalgam Separator Installation and Operations Manual

WARNING Important Safety Information

Control Panel For Water Wash Hoods AM2

Transcription:

Installation and Operation Manual Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control PLL Pump-Lead-Lag Warning This Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety control. All equipment must have its own certified limit and safety controls required by local codes. The installer must verify proper operation and correct any safety problems prior to the installation of this Heat-Timer control. HT# 059003-00D

Contents PLL Layout 2 Overview of the Operating Modes 3 Rotation 3 Alarming on No-Flow 3 2-Call, 2-Flow (3-Pump) 3 Ending the Alarm 3 Mounting The Enclosure 4 Wiring Power s 4 Wiring 4 PLL Layout Output Wiring 5 Dip Switches...................... 6 Warranty 7 Wiring and Piping Diagrams 8 2-Pump 1-Call 1-Flow 8 2-Pump 1-Call 2-Flow 10 3-Pump 1-Call 1-Flow 12 3-Pump 2-Call 2-Flow 14 Specification 16 Power or Pump3 Alarm Indicates Power to control In 3-Pump 1 Call, It serves as a Pump Alarm Mounting Tab Manual Reset button to exit Alarm status Pump Alarms Indicates the failed pump Dip Switches Changes Operating Mode and Rotation HT # 059003-00D Power 120 VAC Output Output Pump3 or Aux Output Output Output Alarm Output Call 1 Flow 1 Call 1 Flow 2 Mounting Tabs 2 Pump Lead Lag Installation and Operation Manual

Overview of the Operating Modes The PLL control is a Lead-Lag Pump control. It is designed to operate in different modes that can satisfy many applications. It can provide lead-lag rotation to a dual or triple pump systems. In addition, it is capable of controlling two operating pumps and one auxiliary pump in boiler feed applications. Rotation 1-Call / 1-Flow 2-Pump Mode Dip1=ON, DIP2=OFF 3-Pump Mode Dip1=OFF, DIP3=ON The PLL rotates the lead pump in a 2-pump system (See 2-Pump 1-Call 1-Flow on page 8)or 3-pump system (See 3-Pump 1-Call 1-Flow on page 12) either based on alternating demand/per call or timed rotation. Rotation can be field configured via dip switches. Alternating demand activates a different pump each time a pump call is initiated. The call must be initiated through terminals. Timed rotation has two options; 24 hours and 7 days rotation. When rotation of the lead pump is to take place while it is in operation, the new lead pump relay will energize while the current lead pump is running. Thus, allowing both pumps to run at the same time for a few extra seconds to eliminate a no-flow period which may cause boiler short-cycling. 1-Call, 2-Flow (2-Pump) 2-Pump Mode Dip1=ON, DIP2=ON This mode is similar to the 1-Call/1-Flow Mode (See 2-Pump 1-Call 2-Flow on page 10) with the exception of each pump having its own flow input. This mode is useful in VFD Pump applications where each of the VFD provides its own the flow feedback signal. Alarming on No-Flow If the lead pump fails to provide a flow signal for over 30 seconds, by shorting the Flow1 input terminals, the PLL will de-energize that pump s relay, energize the alarm relay, turn on the respective pump alarm s LED, and energize the next pump s relay. If the new lead pump fails to provide flow for over 30 seconds while it is in alarm, the PLL will de-energize the 2nd pump s relay, turn on the respective pump alarm s LED. In a 3-Pump system, it will energize the third pump relay and so on. However, on a 2-Pump System, the PLL will not operate any pumps until the situation has been rectified and either the Manual Reset button is pushed. 2-Call, 2-Flow (3-Pump) 3-Pump Mode Dip1=OFF, DIP3=OFF This configuration is typically used in a two-boiler Feed application (See 3-Pump 2-Call 2-Flow on page 14). No rotation is available in this mode. The PLL control operates a single pump per boiler. A maximum of two boiler pumps can be connected to a single PLL. A third Auxiliary pump is used to replace any of the boiler pumps in no-flow situations. In that case, the PLL will de-energize the failing pump s relay and energize the alarm outputs, the respective solenoid valve output, the auxiliary pump relay. In addition, it will turn on the the respective Pump Alarm LED. If the second primary pump flow fails for over 30 seconds while the first primary pump is in alarm, the PLL will de-energize the 2nd pump relay and energize its the relevant solenoid valve relay and Alarm LED. This allows the auxiliary pump to replace both primary pumps until the situation is rectified and the Reset button is pushed. Ending the Alarm When any of the pumps is in alarm, its pump relay will remain de-energized until the Manual Reset button is pressed. This will cause the Alarm Output Relays to de-energize and the Pump Alarm LEDs to turn off. Pump Lead Lag Installation and Operation Manual 3 HT 059003-00D

Warning The PLL is an operating control only. It is the responsibility of the installer to verify that all the safety and limits required by code are working properly before and after the PLL is installed. Mounting The Enclosure Locate the PLL near the equipment to be controlled but away from excessively high or low temperatures. The surface should be flat and sufficiently strong to hold the PLL. Screw the enclosure box to the surface using the external mounting tabs. Use the bottom knockouts. Do not drill any knockouts in the enclosure. Place the metal plate on the knockout from inside the enclosure for proper grounding and to prevent possible injury. Do not use rear knockouts. After installation, lock the enclosure with the screw and nut provided to prevent unauthorized access and for safety. Wiring Power s Bring the power wires through the bottom knockouts of the enclosure. A metal plate is provided for grounding. Install the metal plate on the inside of the bottom knockouts. The conduit fitting shall hold this plate. Attach 120V 60 Hz to the Line and Neutral terminals. Heat-Timer recommends the installation of a Surge Suppressor and a Power Switch before the Power Line connection for safety and ease of service. Warning Class 1 voltage wiring must use a different knockout and conduit from any Class 2 voltage wiring. ing Plate P P OUTP Wiring Wiring the Pump Call s The PLL accepts dry contact inputs only. If voltage is placed across these terminals, the PLL may be damaged. Depending on the Dip Switch mode selected, the PLL may require the use of one or two Pump Call s. See Dip Switches on page 6. Wire each Pump input into the corresponding input terminals of the PLL. See Overview of the Operating Modes on page 3. HT # 059003-00D Wiring the Flow Switch s The Flow wiring must be dry contacts only. If voltage is placed across the PLL input terminals, the PLL may be damaged. Wire each Flow input into the corresponding input terminals of the PLL. A single PLL can accept up to two Flow inputs, depending on the configuration requirements. See Overview of the Operating Modes on page 3. If the lead pump fails to provide a flow signal for over 30 seconds, by shorting the Flow1 input terminals, the PLL will de-energize that pump s relay, energize the alarm relay, turn on the respective pump alarm s LED, and energize the next pump s relay. Alert If no flow switch is used, use a jumper on the flow input terminals. (Heat-Timer recommends using a flow switch for better system response and operation. Flow1 Call Call Flow1 Call Flow2 Call Flow2 4 Pump Lead Lag Installation and Operation Manual

Output Wiring Alert The PLL Pump Lead Lag control DOES NOT source any power for pumps, alarms, or solenoid valves. A separate power source must provide the power to the equipment used. The PLL relays switch the power to the equipment. Wiring the Pump Outputs Wire the Pump 1 and Pump 2 terminals to the pumps or pump s starters. When in any of the 3 Pump Modes, wire the terminals to the Auxiliary Pump or pump starter. See Dip Switches on page 6 Each set of contacts is capable of switching 1 Amp Inductive, 6A Resistive at 120VAC. Wiring the Output The output terminals do not source any power. A separate power source must be supplied. Connect the relay outputs to an alarm. The Heat-Timer Vis-U-Larm (HT #925011-00) is a visual audio alarm that is designed to work with the PLL. It has both a Red Alarm light in addition to a sound alarm. Each set of contacts is capable of switching 1A Inductive, 6A Resistive at 120VAC. UTPUTS Visual/Audio Al Visual Gold Ala Wiring the Web or EMS Alarm Output Connect the other Alarm output to any of the Aux Temp s on a Heat-Timer Platinum heating control with the Internet communication package. The Web Alarm output allows a Platinum heating control with Internet communication package to notify the user of an alarm status either through the web (Web Alarm), E-Mail, or a cellular phone text message. An EMS alarm output allows an EMS system to receive an alarm notification. To Heat-Timer Platinum Web Alarm Switch or EMS Alarm Pump Lead Lag Installation and Operation Manual 5 HT 059003-00D

Wiring the Solenoid Valve Outputs The Solenoid outputs are only available in 2-Call 2-Flow 3-Pump Mode. The solenoids are used to switch the flow of the system from the failed pump to the Auxiliary pump. See 3-Pump 2-Call 2-Flow on page 14 The Solenoid output terminals do not source any power. A separate power source must be supplied. Connect the Output to the solenoid valve to be activated when Flow1 terminals are open during Call1 for more than 30 seconds. Connect the Output to the solenoid valve to be activated when Flow2 terminals are open during Call2 for more than 30 seconds. Each set of contacts is capable of switching 1A Inductive, 6A Resistive at 120VAC. Dip Switches The control is designed to operate in one of the four available modes (See Overview of the Operating Modes on page 3). Note that the older model had only two operating Modes; 2-Pump/1-Call 1- flow and 3-Pump/2-Call 2-Flow. The Dip Switch functions differ from the new model. The following will only explain the newer Dip Switch operation. However, the Old Dip Switch Diagram is self explanatory. Solenoid Power Setting Operation Mode (Dip Switch 1, 2, and 3) Dip Switch 1 function remained the same on both new and old Dip Switch settings. It affects the number of pumps used. Dip Switch 1 On = 2 Pump Mode, Off = 3 Pump Mode OLD and New Dip Switch 2 function affects the 2-Pump Mode only. Dip Switch 2 On = 1-Call/2-Flow Mode, Off = 1-Call/1-Flow Mode Alert The PLL terminals are not aligned with the relays and LEDs. When wiring make sure to select the proper terminals as per the PLL Layout on page 2. Dip Switch 3 function affects the 3-Pump Mode only. Dip Switch 3 On = 1-Call/1-Flow Mode, Off = 2-Call/2-Flow Mode Setting Pumps Rotation Schedule (Not Available in 2Call-2Flow 3-Pump Mode) Dip Switch 4 On = Per Call Rotation, Off = No Per Call Rotation. Dip Switch 5 On = 1 Day Rotation, Off = No 1 Day Rotation. Dip Switch 6 On = 7 Day Rotation, Off = No 7 Day Rotation. The PLL can rotate the lead pump based on demand or time. When several rotation Dip Switches are set to ON, the higher Dip Switch number takes priority over lower number ones. OLD DIP SWITCHES No. PUMP ROTATION 3-Pump Per Call Off 4 Hour Off 12 Hour Off 1 Day Off 7 Day Off Exercise Off Not Used 8 7 6 5 4 3 2 1 O N 2-Pump Per Call On 4 Hour On 12 Hour On 1 Day On 7 Day On Exercise On HT # 059003-00D Setting Pump Exercise Dip Switch 7 On = Exercise Pump, Off = No Pump Exercise When Dip Switch 7 is set to On, the PLL will energize the pump relay for 10 seconds for every week of no-operation. This feature is helpful in reducing pump rotor lock due to sediment deposit and rust in the system pipes. In vacuum pump applications, it assist in periodic vacuum pump lubrication. D 1-FLOW INPUT No. PUMP 2-PUMP 3-PUMP ROTATION 3-Pump 1-Call / 1-Flow 2-Call / 2-Flow Per Call Off 1 Day Off 7 Day Off Exercise Off Not Used 2-Pump 1-Call / 2-Flow 6 Pump Lead Lag Installation and Operation Manual CALLS DIP SWITCHES Flow2 Call Flow1 Call 8 7 6 5 4 3 2 1 O N 1-Call / 1-Flow Per Call On 1 Day On 7 Day On Exercise On Flow Pump Call

LEDs Relay LEDs A LED is assigned to each of the relays to show its operation status. When the relay is energized, its relay is lit. Power LED The upper left LED is used to indicate the control power in all modes except 3-Pump/1-Call 1-Flow. See Overview of the Operating Modes on page 3 Alarm LEDs Each of and has their own Alarm LED. The LED will be lit whenever the respective pump fails to have flow for 30 seconds. The upper left LED is used to indicate Pump3 Alarm in 3-Pump/1-Call 1-Flow Mode. See Overview of the Operating Modes on page 3 Warranty WARRANTIES AND LIMITATIONS OF LIABILITY AND DAMAGE: Heat-Timer Corporation warrants that it will replace, or at its option, repair any Heat-Timer Corporation manufactured product or part thereof which is found to be defective in material workmanship within one year from the date of installation only if the warranty registration has been properly filled out and returned within 30 days of the date of installation. Damages to the product or part thereof due to misuse, abuse, improper installation by others or caused by power failure, power surges, fire, flood or lightning are not covered by this warranty. Any service, repairs, modifications or alterations to the product not expressly authorized by Heat-Timer Corporation will invalidate the warranty. Batteries are not included in this warranty. This warranty applies only to the original user and is not assignable or transferable. Heat-Timer Corporation shall not be responsible for any maladjustments of any control installed by Heat-Timer Corporation. It is the users responsibility to adjust the settings of the control to provide the proper amount of heat or cooling required in the premises and for proper operation of the heating or cooling system. Heat-Timer Corporation shall not be required to make any changes to any building systems, including but not limited to the heating system, boilers or electrical power system, that is required for proper operation of any controls or other equipment installed by Heat-Timer Corporation or any contractor. Third Party products and services are not covered by this Heat-Timer Corporation warranty and Heat-Timer Corporation makes no representations or warranties on behalf of such third parties. Any warranty on such products or services is from the supplier, manufacturer, or licensor of the product or service. See separate Terms and Conditions of Internet Control Management System ( ICMS ) services, including warranties and limitations of liability and damages, for ICMS services. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED AND HEAT-TIMER CORPORATION SPECIFICALLY DISCLAIMS ANY AND ALL WARRANTIES OF MERCHANTABILITY FOR A PARTICULAR PURPOSE. UNDER NO CIRCUMSTANCES SHALL HEAT-TIMER CORPORATION, ITS AUTHORIZED REPRESENTATIVES, AFFILIATED OR SUBSIDIARY COMPANIES BE LIABLE FOR SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES, EXCEPT AS SPECIFICALLY STATED IN THESE TERMS AND CONDITIONS OF SALE. THE SOLE REMEDY WITH RESPECT TO ANY PRODUCT OR PART SOLD OR INSTALLED BY HEAT-TIMER CORPORATION SHALL BE LIMITED TO THE RIGHT TO REPLACEMENT OR REPAIR F.O.B. FAIRFIELD, NJ. HEAT-TIMER CORPORATION SHALL NOT BE LIABLE OR RESPONSIBLE FOR LOSS OR DAMAGE OF ANY KIND RESULTING FROM DELAY OR INABILITY TO DELIVER FOR ANY REASON, INCLUDING BUT NOT LIMITED TO FIRE, FLOOD, LIGHTNING, POWER FAILURE OR SURGES, UNAVAILABILITY OF PARTS, STRIKES OR LABOR DISPUTES, ACCIDENTS AND ACTS OF CIVIL OR MILITARY AUTHORITIES. 03122010 Pump Lead Lag Installation and Operation Manual 7 HT 059003-00D

Wiring and Piping Diagrams 2-Pump 1-Call 1-Flow DIP Switch Settings: Dip1 = ON (2-Pump Mode) Dip2 = OFF (1-Call + 1-Flow Mode) Dip4-6 = Choose Rotation option Electric ing Plate ing Plate Flow1 Call HT # 059003-00D To Heat-Timer Platinum Web Alarm Switch or EMS Alarm 8 Pump Lead Lag Installation and Operation Manual

Mechanical 2 Rotating Pump System Output Output Pump Call1 Flow1 Boiler or Heating Source Flow Switch Alert Heat-Timer is aware that each installation is unique. Thus, Heat-Timer is not responsible for any installation related to any electrical or plumbing diagram generated by Heat-Timer. The provided illustrations are to demonstrate Heat-Timer s control operating concept only. Pump Lead Lag Installation and Operation Manual 9 HT 059003-00D

2-Pump 1-Call 2-Flow DIP Switch Settings: Dip1 = ON (2-Pump Mode) Dip2 = ON (1-Call + 2-Flow Mode) Dip4-6 = Choose Rotation option Electric ing Plate Flow2 ing Plate Flow1 Call HT # 059003-00D To Heat-Timer Platinum Web Alarm Switch or EMS Alarm 10 Pump Lead Lag Installation and Operation Manual

Mechanical 2 Rotating VFD Pump with Feedback System Boiler or Heating Source Output Output Pump Call1 Flow1 Flow2 VFD VFD Alert Heat-Timer is aware that each installation is unique. Thus, Heat-Timer is not responsible for any installation related to any electrical or plumbing diagram generated by Heat-Timer. The provided illustrations are to demonstrate Heat-Timer s control operating concept only. Pump Lead Lag Installation and Operation Manual 11 HT 059003-00D

3-Pump 1-Call 1-Flow DIP Switch Settings: Dip1 = OFF (3-Pump Mode) Dip3 = ON (1-Call + 1-Flow Mode) Dip4-6 = Choose Rotation option Electric ing Plate ing Plate Pump3 Flow1 Call HT # 059003-00D To Heat-Timer Platinum Web Alarm Switch or EMS Alarm 12 Pump Lead Lag Installation and Operation Manual

Mechanical 3 Rotating Pump System Output Output Pump3 Output Pump Call1 Flow1 Boiler or Heating Source Flow Switch Pump3 Alert Heat-Timer is aware that each installation is unique. Thus, Heat-Timer is not responsible for any installation related to any electrical or plumbing diagram generated by Heat-Timer. The provided illustrations are to demonstrate Heat-Timer s control operating concept only. Pump Lead Lag Installation and Operation Manual 13 HT 059003-00D

3-Pump 2-Call 2-Flow DIP Switch Settings: Dip1 = OFF (3-Pump Mode) Dip2 = OFF (2-Call + 2-Flow Mode) Electric ing Plate Pump3 Solenoid Power Call Flow1 Flow2 ing Plate Call HT # 059003-00D To Heat-Timer Platinum Web Alarm Switch or EMS Alarm 14 Pump Lead Lag Installation and Operation Manual Flow2

Mechanical PLL Multi-Boiler Feed Pump Application Output Output Output Solenoid 1 Output Solenoid 2 Output Pump Call1 Flow1 Pump Call2 Flow2 Boiler2 Flow Switch Boiler1 Flow Switch Alert Heat-Timer is aware that each installation is unique. Thus, Heat-Timer is not responsible for any installation related to any electrical or plumbing diagram generated by Heat-Timer. The provided illustrations are to demonstrate Heat-Timer s control operating concept only. Pump Lead Lag Installation and Operation Manual 15 HT 059003-00D

Specification Operating Temperature.......................................... 20 F/-6 C to 120 F/49 C Voltage :..................................................... 120 VAC 60 Hz Maximum Rating:................................................. 12 VA Max Pump Outputs...........................................3 Pumps Relays (Relays are SPST) Alarm Outputs........................................... 2 Alarm Relays (Relays are SPST) Solenoid Valve Outputs.....................................2 Solenoid Relays (Relays are SPST) Output Relay Rating:................ 1 Amp inductive, 6 Amp resistive at 120 VAC 60 Hz, 15A total for all circuits Operating Modes......... 4 (2-Pump 1-Call 1-Flow, 2-Pump 1-Call 2-Flow, 3-Pump 1-Call 1-Flow, 3-Pump 2-Call 2-Flow LED:.............................. 10 (7 (1 per Relay), 2 (1 per Pump Alarm), and 1 Power or Pump3 s:.............................................. 2 Pump Call inputs, 2 Flow inputs Rotation Options.............................................. Per Call, 1 day, and 7 Day Pump Exercise Options......................... On (10 seconds per 1 week of no operation per pump), Off Pump Alarm Delay.................................................. 30 seconds fixed Buttons:......................................................... Manual reset Dimensions:................................................7 ⅛ W x 9 ⅝ H x 3½ D Weight:........................................................... 2 pounds HT# 059003-00D 20 New Dutch Lane, Fairfield, NJ 07004 Ph: (973) 575-4004 Fax: (973) 575-4052 http://www.heat-timer.com