ELECTRONIC FIREPLACE DAMPER

SYSTEM CONTROL KIT Model: CK-41P

COMBUSTION AIR SYSTEM

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

SLANT/FIN AUTOMATIC VENT DAMPER For Galaxy, Sentinel and Sentry Series Boilers INSTALLATION INSTRUCTION MANUAL AND TROUBLESHOOTING GUIDE

24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

24 VAC SYSTEM CONTROL KIT

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

POWER VENTER. Model: PVE Series

120 VAC SYSTEM CONTROL KIT

(Information about THERMAL dampers for gas-fired appliances available on request.) WARNING

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

COMBUSTION AIR SYSTEM Model: CAS-3

120 VAC SYSTEM CONTROL KIT Model: CK-63

Crown Boiler Company

ADC150 Automatic Draft Control

120 VAC SYSTEM CONTROL KIT

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

ENERVEX ADC100 DRAFT CONTROL

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

RS Chimney Fan For Gas & Oil Applications. Installation & Operating Manual USA CAN

COMBUSTION AIR SYSTEM

SYSTEM CONTROL KIT READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS

EUTECTIC EC-10DV Series

ASX7-4-IOM-6 J

WARNING FLAIR INTERNATIONAL CORPORATION 600 OLD WILLETS PATH HAUPPAUGE, NEW YORK U.S.A. TEL.: (516) FAX: (516) AMERICAN

INSTALLATION AND SERVICE MANUAL

MFD Mechanical Fireplace Damper

INSTALLATION AND SERVICE MANUAL

BGH Series Hot Surface Ignition Control

For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G

ASX7-5-IOM-3 J

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE

40 SERIES GAS BURNER MODEL 400 NATURAL GAS/PROPANE INSTALLATION INSTRUCTIONS AND OWNER S HANDBOOK

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

ENERVEX MFD MECHANICAL FIREPLACE DAMPER

CAUTION FOR YOUR SAFETY

24 VAC SYSTEM CONTROL KIT

Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions

Fig. 1 - Unit PGD4, PGS4, WPG4

POWER VENTER SYSTEM MODEL: PVO-300, PVO-600

INSTALLATION INSTRUCTIONS

D896 Automatic Vent Damper

CSD-1 COMMERCIAL BOILER CONTROLS

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

SUBMITTAL SCHEDULE & DATA

FIREPLACE SIZES FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VACINITY OF THIS OR ANY OTHER APPLIANCE.

PVK-80 Power Vent - Installation Instructions -

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

Leisure Line Power Vent Operations & Maintenance Manual And Safety Instructions

DR-180 Through the Wall Exhaust Fan PRODUCT MANUAL & INSTALLATION GUIDE

LUMINOUS A PATIO HEATER LIKE NO OTHER

INSTALLER'S GUIDE MASONRY CHIMNEY VENT KIT WARNING: BAYVENT800B 18- CH23D2-05

BIG BOOT COMBUSTION AIR KIT Model: CAS-2BB, CAS-2CB, CAS-2B375

EW 40 Wireless Fan Control

Installation Instructions Remote Blowers

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

Bosch 80% AFUE Gas Furnace BGS80 Model

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

940ES Tankless Water Heater

Q7800H Integrated Burner Control Subpanel

Series RE Infrared Heater

SIDEWALL POWER VENTING KIT

Installation, Operation and Owner s Manual. Power Vent System

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

Owner s Information Manual

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Model Universal Oil Primary Control

Radiant Patio Heater. Performance that outshines. Manual for Installation, Operation & Maintenance

Owner s Manual DO NOT DISCARD WARNING CAUTION WARNING. Model: 6000PLUS

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

940ES Tankless Water Heater

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Owner s Guide Installation & Operation

External Roof-mounted Power Vent System

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

RS chimney fan for gas and oil applications

Installation, Operation & Service Manual

X341119P10 Gas Furnace Var. Speed Blower Var. Speed Inducer Two Stage Heat Direct Vent Models:

XIII Troubleshooting

INFRARED RADIANT HEATERS

USER S INFORMATION MANUAL

Use, Care, and Installation Guide

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ...

TJERNLUND PRODUCTS, INC.

GAS -FIRED VENTED ROOM HEATERS MODEL 61TV

RS Chimney Fan for Solid Fuel Applications

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

INSTALLATION AND OPERATION INSTRUCTIONS FOR ZERO CLEARANCE AND INSERT UNITS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

Transcription:

ELECTRONIC FIREPLACE DAMPER Model: FSE Series The Flue Sentinel Electronic Fireplace Damper is designed to increase the comfort and energy efficiency of residential homes with gas-fired fireplaces. Consisting of a stainless steel pipe/blade assembly and solid-state controller housed in a weather-proof enclosure, the damper is installed outdoors on the top of the chimney of a gas-fired fireplace. The damper automatically opens the flue outlet when the fireplace is turned on and automatically closes off the flue outlet when the fireplace is turned off. By closing off the flue outlet the fireplace is not in use, the damper prevents drafts and conserves energy by preventing heat in the home from escaping through an open flue. The Flue Sentinel is design certified by the Canadian Standards Association (CSA) to CSA Requirement No. 2.03- US for Automatic Vent Damper Devices for Use Outdoors on Fireplace Chimneys and is covered by U.S. Patent No. 6,915,799. WARNING: Do NOT install this damper on a chimney burning solid fuel such as wood. Do NOT install this damper on a chimney used for venting central heating or water heating appliances. READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION. This device MUST be installed by a qualified agency in accordance with the manufacturer's installation instructions. The definition of a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the precautions required, and has complied with all the requirements of the authority having jurisdiction. Please retain these instructions after installation. Installed By: Phone: Installation Date: MFG BY: www.fieldcontrols.com

SPECIFICATIONS Voltage (Range) Frequency Current (running) Maximum current rating for output circuit Operating Temperature Range Timing OPERATING SPECIFICATIONS 24VAC (Max 27.6, Min 20.4 VAC) 50/60 Hz 80 ma 5A Controller: (-40) - 140 F Pipe: (-40) - 650 F 7 seconds to open 30-40 seconds to close (incl. time delay) D C B A Flue Sentinel Dimensions and Weight- FSE-8 through FSE-16 MODEL DIM A DIM B DIM C DIM D WT. (LB) FSE-8 7.8 10.5 17.0 13.8 7.8 FSE-10 9.8 10.5 19.0 15.8 8.9 FSE-11 10.8 10.5 20.0 16.8 9.4 FSE-12 11.8 10.5 21.0 17.8 10.0 FSE-13 12.8 12.5 22.0 18.8 11.3 FSE-14 13.8 12.5 23.0 19.8 12.0 FSE-16 15.8 12.5 25.0 21.8 13.3 *All dims are in inches page 2

D C B A Flue Sentinel Dimensions and Weight- FSE-18 through FSE-24 MODEL DIM A DIM B DIM C DIM D WT. (LB) FSE-18 17.8 13.5 27 23.8 15.6 FSE-20 19.8 14.5 29.0 25.8 17.8 FSE-22 21.8 15.5 31.0 27.8 20.1 FSE-24 23.8 16.5 33.0 29.8 22.9 *All dims are in inches page 3

INSTALLATION The Flue Sentinel has been designed to fit a variety of chimney types including masonry and manufactured chimneys. It features a mounting collar that seals the chimney, adjustable legs for means of attachment and a crimped outlet for mounting the chimney top. Figure 1 is an example of a typical installation Installation of the Flue Sentinel must comply with the following requirements The Flue Sentinel must be installed only on a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney acceptable to the authority having jurisdiction. The Flue Sentinel must be located on a chimney so that it serves only the single fireplace appliance for which it is installed. The Flue Sentinel shall be installed in accordance with local codes, or in the absence of local codes, in accordance with the National Fuel Gas Code, ANSI Z223.1. If the Flue Sentinel is to be installed on an air-cooled chimney, it must be installed with the appropriate Flue Sentinel Mounting Kit per the kit instructions. Installation Steps: 1. Set the damper in the opening of the chimney flue to check the fit. The damper s mounting collar should rest evenly on the top edge of the flue. Also check the orientation of the damper control housing and mounting legs to ensure the proper attachment and routing of the wiring harness. 2. Remove the damper and apply a bead of high temperature sealant on the top edge of the flue. 3. Center the damper in the opening of the chimney flue. 4. Adjust the mounting legs to rest on top of the chimney and secure with screws. Tighten the mounting leg bolts at the collar brackets. 5. Install the chimney top and secure per the manufacturer s instructions. 6. Install the warning tag on the damper wiring harness near gas valve. To identify the requirement that the Flue Sentinel device be removed before converting to wood burning. Notes Ignition Module not shown. 120/24V Transformer *4-Wire Cable *Typically 18/4. Run in conduit if required or if installed on exterior of masonry chimney. **The Flue Sentinel is electrically interlocked with the main burner valve/controls of the gas log set. See Basic Wiring Diagram on pg. 5. On/Off Switch Chimney Top Flue Sentinel Mounting Leg Facade 2" x 4" Framing 1/2" Drywall or Sheetrock (See Local Code) Manufactured Chimney Chase Minimum Clearance to Combustibles Per Chimney Manufacturer Gas Log Set **Gas Valve Gas Line Figure 1 page 4

WIRING WARNING: This damper device MUST be interlocked with all automatic gas valves on the fireplace appliance. DO NOT negate the action of any existing safety of operational control. The following requirements must be met to ensure safe and proper operation: The Flue Sentinel Electronic Fireplace Damper must be electrically connected to the fireplace appliance using the chimney upon which the damper is installed. The damper must be installed in accordance with the NEC NFPA 70 (most recent edition) and/or local codes. The damper must be installed using the wiring harness supplied with it. This harness has a mated connector which plugs into the damper controller. The damper s wiring harness must terminate at the gas valve. The wiring connecting the damper controller to the gas valve must be a minimum of 18 AWG and must be run in conduit if installed on the exterior of the chimney or required by code. Figure 2 is a wiring connection diagram for a typical installation with an intermittent ignition system. The damper control wiring must always be connected as follows: Brown - 24 VAC Hot Orange - Signal In Yellow - Signal Out Black - 24 VAC Common Figure 2 IGNITION CONTROL MODULE 24V GND TH-W GAS VALVE SPARK ELECTRODE/ SENSOR TRANSFORMER L1 120 VAC 24 VAC L2 FIREPLACE SWITCH HARNESS COLOR CODE Standard Wire Connector 2 4 High Temp Wire Connector 2 4 1 3 1 3 FLUE SENTINEL ELECTRONIC FIREPLACE DAMPER BLACK BROWN ORANGE YELLOW page 5 VIEW SHOWING END OF RECEPTACLE WIRE CONNECT CODE COLOR 1 BROWN 2 ORANGE 3 YELLOW 4 BLACK VIEW SHOWING END OF RECEPTACLE WIRE CONNECT CODE COLOR 1 WHITE 2 RED 3 GREEN 4 BLACK

SEQUENCE OF OPERATION When the fireplace is turned on, a 24V signal is sent by the fireplace control to the damper controller. The damper controller motor then rotates the damper blade, which is indexed to a cam, to the open position to allow products of combustion to pass through the flue outlet. The cam proves the damper is in the open position and switches 24V from the motor to the main gas valve or ignition system, which fires the main burner. When the fireplace is turned off, the fireplace control removes the 24V signal to the damper controller, shutting off the main burner. After a 30-40 second delay, the damper controller motor then rotates the damper blade to the closed position and resets itself for the next time the fireplace is turned on. FINAL INSPECTION Turn on the gas and electrical supplies to the appliance. Check the operation of the Flue Sentinel by cycling the appliance at least three times as follows: 1. Switch the fireplace control to turn on the fireplace. 2. The damper will open and fire the main burner. The damper must be in the open position when appliance main burner is operating. 3. Switch the fireplace control to turn off the fireplace. The main burner will immediately shut off and, after approximately 30-40 seconds, the damper will rotate to the closed position. If the Flue Sentinel Electronic Fireplace Damper and/or fireplace appliance does not operate as described above, consult the Troubleshooting Chart below for the proper course of action to resolve the problem. TROUBLESHOOTING CHART PROBLEM POSSIBLE CAUSES ACTION Damper won t open No power or insufficient power at damper No signal into damper Obstruction preventing damper blade from rotating Defective damper controller Check for opens in the power supply circuit and correct Check for opens in fireplace control/circuit and correct Check for protruding screws or binding in pipe/blade assembly and correct Replace controller Damper opens but appliance main burner(s) does not fire Damper rotates continuously Damper won t close, main burner off Defective gas valve or ignition control on appliance Defective damper controller Defective damper controller No power or insufficient power at damper Obstruction preventing damper blade from rotating Check for power at gas valve and/or ignition control. If present, replace defective part If not present, check for power at controller, yellow wire should be energized. If not, replace controller Replace controller Check for power at controller, only black and brown wires should be energized. If not, check wiring diagram Check for protruding screws or binding in pipe/blade assembly and correct Damper won t close, main burner on Defective damper controller Fireplace control still sending signal to damper to open page 6 Replace controller Check for shorts in fireplace control/circuit and correct

MAINTENANCE CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. The Flue Sentinel has been designed to provide years of maintenance free service. However, for continued safe operation, the Flue Sentinel, chimney and fireplace appliance should be examined once a year by a qualified service agency. It is also recommended that the homeowner examine these components at least every (6) months, with particular attention given to deterioration from corrosion or other source page 7

WARRANTY For warranty about this or any Field Controls product, visit: www.fieldcontrols.com/warranty MFG BY: Phone: 252.522.3031 Fax: 252.522.0214 www.fieldcontrols.com Field Controls, LLC P/N 0100-00 Rev E 01/14