SECTION SPECIAL EXHAUST SYSTEMS. A. Laboratory Ventilation and Hazardous Exhaust Systems. 3. Chemical Fume Hoods and Storage Cabinets

Similar documents
CHEMICAL FUME HOOD PROGRAM

Adv. 8.4 Guidelines for Biosafety Cabinets Rev

SECTION LABORATORY EQUIPMENT CONSTRUCTION STANDARD PART 1: GENERAL Scope of Standard

LABORATORIES, CHEMICAL AND BIOLOGICAL

Section 1.0: LAB VENTILATION TABLE OF CONTENTS. C. General Ventilation Considerations 3. D. Pressurization 7. E. Supply Air Arrangements 8

Section 5.0: HAZARDOUS MATEIRAL STORAGE TABLE OF CONTENTS. A. Regulations, Standards and References 2. B. Scope 3. C. Approvals and Listings 3

LABORATORY EQUIPMENT. A. Section Accessibility for People with Disabilities. B. Section Plumbing Basic Materials and Methods

PHYSICAL FACILITIES Consultant s Handbook Division 01 General Special Requirements for Laboratories. Page 1 of 6

PDH & Professional Training

UC DAVIS Campus Design Guide DIVISION 11 - EQUIPMENT

Division 11 - Equipment

Fume Hood Safety TYPES OF FUME HOODS

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

Biosafety Cabinets and Fume Hoods Supplemental Material (OHS_BIO304)

Safe Operating Procedure (Revised 2/10)

Lab Design shall comply with the UC Lab Safety Design Manual located at: LABORATORY FUME HOODS

Appendix A.4.1. Safe Fume Hood User Guide

Biological Safety Cabinets or Fume Hoods Which one to use?

This document provides general instructions on the use of chemical fume hoods to protect lab personnel against exposure to hazardous materials.

UC DAVIS Campus Standards & Design Guide DIVISION 11 - EQUIPMENT

NFPA 45 NFPA 211 NFPA 1600

XPert Balance and Bulk Powder Enclosures

University of California, Davis Laboratory Self-Inspection Checklist

Laboratories and Hazardous Materials. Company Overview

Florida International University. Biosafety Cabinet Program

University of Houston Campus Design Guidelines and Standards Construction Systems and Assemblies: Section 12.0 A.01 Laboratory Design Guide

Biological Safety Cabinets. Presented by Mr. Rene Soetens President

A. Standards: Except where modified or exceeded by the requirements of this Specification, conform to the following standards:

IMC Significant Changes Summary Tier I

Table of Contents. Laboratory Fume Hoods. UniFlow Fume Hood Systems. Fume Hood System Components. Custom Hoods, Enclosures & Cabinets

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

First Revision No. 15-NFPA [ Chapter 2 ]

2008 NYC Fire Code. New Laboratory Standards. Operational & Maintenance Provisions effective July 2008

Environmental Health and Safety Biological Safety Program Guidance Document

5.0 Installation Instructions

VP, Facilities and Construction Management

Laboratory Information

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

Ventilation for New Low-Rise Residential Buildings July 20, 2015

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

F1010 Laboratory and Research Area Renovation and Construction

2015 MECHANICAL CODE REQUIREMENTS

Laboratory Fume Cupboards

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

Ventilation System Description. September 8, 2000 HETA

PART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s

SECTION DUCTWORK

Inspection Checklist Mechanical Rough in

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

Animal Tissue Culture SQG 3242 Equipment and Lab design. Dr. SITI PAULIENA MOHD BOHARI

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

SEMICONDUCTOR FABRICATION FACILITIES

NEW! Thermo Scientific 1300 Series B2 Class II, Type B2 Biological Safety Cabinet

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

REQUIREMENTS FOR HOOD PLANS

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

SEMICONDUCTOR FABRICATION FACILITIES

Section 9 - Tumble Dryers. Tumble Dryers LEPH

SEMICONDUCTOR FABRICATION FACILITIES

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

Biological Safety Cabinets. Biological Safety Cabinets

A. General Safety LAB/ROOM: INSPECTED BY: DATE:

SECTION AIR DUCT ACCESSORIES

LABORATORY SAFETY DESIGN GUIDE

Clean Air Device. Yale University. Office of Environmental Health & Safety. Primary Containment Device

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

GreenJet Transfer Fans

MD and Its Impact on Lab Facilities

Innovation in air purification unmatched air quality

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

READ AND SAVE THESE INSTRUCTIONS WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS OBSERVE THE FOLLOWING:

DIVISION 15 MECHANICAL

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

SEMICONDUCTOR FABRICATION FACILITIES

City of Duluth Festival Center 04/25

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

SECTION BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

TAB C-3 LABORATORY PLANNING AND DESIGN CRITERIA

Schust Engineering, Inc. 701 North Street P.O. Box 128 Auburn, IN (260) Fax: (260)

LABORATORY INSPECTION CHECKLIST

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SAFETY AND INSTALLATION MANUAL MODEL 8100

Laboratory Safety Audit

Glossary of Terms Laboratory & Fume Exhaust Fans

Laboratory Safety Audit

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope

CHAPTER 5: EXHAUST SYSTEMS

APPUZO RANGE HOOD INSTALLATION

Transcription:

SECTION 15852 SPECIAL EXHAUST SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Laboratory Ventilation and Hazardous Exhaust Systems 1. Pre-Design Considerations 2. General Design Criteria 3. Chemical Fume Hoods and Storage Cabinets 4. Ducts, Fans and Control Systems 5. Testing, Inspecting and Certification 6. Dust Collectors 7. Gas Cabinets B. Dust Collectors C. Gas Cabinets D. Laundry Dryer Exhaust E. Demolition F. Related Sections: 1. Section 11610 Laboratory Fume Hoods 2. Section 11611 Laboratory Biological Safety Cabinets 3. Section 12345 Metal Laboratory Casework 4. Section 12346 Wood Laboratory Casework 5. Section 15010 Basic Mechanical Requirements 6. Section 15050 Basic Mechanical Materials and Methods 7. Section 15240 Mechanical Sound and Vibration Control JULY 2012 UCB STANDARDS 15852-1

1.02 REFERENCES 8. Section 15850 Air Handling 9. Section 15880 Air Cleaning 10. Section 15990 Testing, Adjusting and Balancing A. "Industrial Ventilation, a manual of Recommended Practice" published by American Conference of Governmental Industrial Hygienists (ACGIH) B. National Fire Protection Association (NFPA) C. American Society for Testing and Materials (ASTM) D. American National Standards Institute (ANSI) E. American Industrial Hygiene Association (AIHA) F. Center for Disease Control (CDC) G. The National Institute of Health (NIH) H. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) I. International Building Code (IBC) 1.03 SYSTEM DESCRIPTION: A. Laboratory Ventilation and Hazardous Exhaust Systems 1. *Pre-Design Considerations* Other safety cabinets and enclosures for highly-reactive or toxic gases, and other specialized operations such as Dark Rooms Photographic, Spray Painting Rooms Booths, Animal Quarters-Vivariums, glove boxes, Food Preparation and Serving Areas, Chemical or Gas Storage Rooms, etc. will have different and/or additional requirements than those listed below. EH&S must be consulted before planning such installations. Any deviation from these design criteria must be reviewed and approved by EH&S. a. Laboratories shall be ventilated per ASHRAE Standard 62, NFPA 45, NFPA 91, ANSI/AIHA Z9.5, and UCB Sections 15850 and 15885. b. Early in the design process, the HVAC Design Engineer responsible for the fume hood exhaust system shall obtain a complete list of the chemicals, biological and radiological materials, and gases to be used and stored in the lab and submit to the University Environmental Health and Safety JULY 2012 UCB STANDARDS 15852-2

compliance group through the University Project Manager. This list shall be used to analyze fume hood exhaust for flammability, toxicity, corrosiveness, and explosion hazards. In selecting and analyzing fume hazard control techniques, the HVAC Design Engineer shall work closely with University EH&S personnel. c. If perchloric acid must be used, a specialized, dedicated hood (stainless steel, porcelain coated, or non-plasticized PVC lined) labeled for perchloric acid use only must be installed. A regular chemical fume hood may not be used for perchloric acid. The perchloric hood must have its own nonreactive duct and exhaust fan, built-in water wash-down system, and other features as described in the ACGIH Industrial Ventilation Manual. d. Radioisotope hood installations and the use of radioactive materials on campus, require prior review, approval and licensing by EH&S Health Physics. Conventional chemical fume hoods are suitable for many low level radioisotope applications, however, the use of some materials such as radioactive iodine, requires a specialized radioisotope hood equipped with integral filter components. In these cases, service contracts must be set up for maintenance, calibration and filter replacement or disposal. e. Biosafety cabinet installations and proposals for biological or biomedical research must be reviewed and approved by EH&S and the UCB Institutional biosafety Committee (IBC) to evaluate conformance with requirements of the Center for Disease Control (CDC) and the National Institute of Health (NIH). Such requirements can be found in CDC/NIH publication: Biosafety in Microbiological and Biomedical Laboratories. The CU-Boulder campus is not approved for biohazardous work above Biosafety Containment Level 2. Biosafety cabinet selection and room designs must comply with National Science Foundation Publication 49: International Standard for Class II (Laminar Flow) Biohazard Cabinetry in addition to CDC and NIH requirements. If NIH funding is used to facilitate project, then the NIH Building and Construction requirements must be followed. Biohazard cabinetry equipped with integral filter components will require a special service contract for maintenance, calibration and filter replacement or disposal. Cabinet will require certification by a qualified Vendor to meet Manufacturer s operating specifications and/or NSF 49 Standard prior to being placed into service for BL-2 required containment. 2. General Design Criteria a. Laboratory modules in which hazardous chemicals and gases are being used shall be maintained at an air pressure of at least 0.03" wg* that is negative to the corridors or adjacent non-laboratory areas. Laboratory modules in which hazardous biological materials are being used shall be maintained at an air pressure of at least 0.03" wg* that is negative to the corridors or adjacent non-laboratory areas for all new construction and whenever JULY 2012 UCB STANDARDS 15852-3

feasible for renovated existing spaces. An exception to this requirement is where operations, such as those requiring clean rooms, preclude a negative pressure relative to surrounding areas; in this case, special precautions shall be taken (e.g., The HEPA units are laminar flow and will be located as far from the hood as possible in order to avoid air currents near the hood. In an emergency situation, a ventilation "off" switch will be located in the room near the door that will, when activated, shut off the air coming into the room (via a control damper) and shut off the air handler and fan. The main exhaust fan will continue to run, and the room will be negative.). Also meets LEED EQc5: Indoor Chemical and Pollutant Source Control. b. Air containing hazardous chemicals and gases shall be discharged through hood/duct systems maintained at a negative pressure relative to the pressure of normally occupied areas of the building. Air exhausted from laboratory modules shall not pass unducted or be recirculated through other areas. c. If a hood is to be connected to an existing central or manifold exhaust system serving multiple fume hoods, then the air system will have to be evaluated to see if it has sufficient capacity for the addition of other exhausted equipment. Each individual exhaust drop on a central or manifold exhaust system shall be labeled for the specific room(s) it services. d. Hazardous exhaust systems are not typically equipped with filters to capture contaminants. In some cases, however, prefilters may be installed to protect heat exchange coils or other HVAC equipment from accumulating debris. Consult with EH&S regarding filters specifications for hazardous exhaust systems. Ductless (filtered) fume hoods may be used in place of ducted fume hoods only on a limited case by case basis and after review by EH&S and meets compliance with Building and Fire Codes. e. Hoods shall be located in close proximity to where chemicals are stored, and should be located a minimum of 10 feet from any door or doorway or where interfering air currents and cross drafts from windows, high traffic areas, HVAC systems, or other apparatus, could adversely affect the proper function of the hood enclosure. Any source which decreases a hood s containment ability or capture efficiency shall be mitigated. f. Make-up air shall be provided to compensate for the air being exhausted. The location and volume of make-up air is critical to assuring proper fume hood operation and worker protection. Air distribution around fume hoods shall be such that cross drafts, dead air pockets, and reverse air currents are to be avoided. Care shall be exercised in the selection and placement of air supply diffusion devices to avoid air currents that would adversely affect the performance of laboratory hoods, exhaust systems, and fire detection or extinguishing systems. Unless otherwise specified, supply air velocities shall be no more than 35 fpm at work stations and fume hoods. JULY 2012 UCB STANDARDS 15852-4

3. Chemical Fume Hoods and Storage Cabinets a. Constant-volume chemical fume hoods must be capable of maintaining 100 fpm minimum face velocity through the sash opening with the sash at 13 measured from the top of the airfoil or 14 above work surface if airfoil is not present. Variable-Air-Volume fume hoods shall be capable of maintaining 100 fpm at all sash heights below 13 measured from the top of the airfoil or 14 above work surface if airfoil is not present or is flush with work surface (Provide sash with stops located 18 above working surface and with override release. Special local exhaust systems, such as fume extractor arm, drop canopy and slot exhaust, shall have sufficient capture velocities to entrain the hazardous chemicals being released per manufacturer specifications and/or ACGIH Industrial Ventilation, a manual of Recommended Practice. NOTE: Some hoods require 120 fpm min. face velocity. HVAC Design Engineer shall consult EH&S for minimum face velocity. i. Floor Mounted (Walk-In) Fume Hoods HVAC Design Engineer shall consult EH&S for minimum face velocity at specified sash position(s). ii. Combination Vertical and Horizontal Sash Fume Hoods - HVAC Design Engineer shall consult EH&S for minimum face velocity at specified sash position(s). b. Fume hoods must be equipped with audible and visual low air flow alarm which shall be field calibrated to alarm at 75 fpm face velocity. Provide one 2-gang duplex, 20A, 125V receptacle for electrical service to alarm. Receptacle shall be located on top panel of hood to accommodate alarm. A removable strap or cover shall be located over the power adapter plug to assure its fixed placement in the receptacle. Alarm shall be located on fume hood and installed per manufacturer specifications. Special equipment/systems such as Fume Extractor Arms, Drop Canopy and Slot exhausts, used for capturing hazardous vapors shall have an audible and visual low air flow or duct static pressure indicator. c. Chemical fume ducts are generally not equipped with fire sprinklers or fire dampers, but whenever code requires, ducts shall be in fire-rated or fireprotected shafts. Where fume hood exhaust contains flammable vapor, UCB Standards compliance with the requirements of Building and Fire Codes for automatic fire suppression systems protecting the fume hood and/or the exhaust duct. However, this requirement shall be carefully addressed on a case-by-case basis, since it may result in a variety of other potential hazards associated with fume hood operation. d. Class I Division I interior lighting and other electrical utilities are required where internal utilities are desired. JULY 2012 UCB STANDARDS 15852-5

e. Sinks inside fume hoods must have a minimum 3/8 raised edge around cup sink cut out, i.e., provide a 3/8 lip above work surface. Do not install sinks inside hoods unless they are specifically requested and needed. f. Chemical fume hoods shall include base chemical storage cabinets which meet UCB Standard, Sections 12345 or 12356. Stand-alone chemical storage cabinets should be located in close proximity to where chemicals will be used, preferably adjacent to fume hoods. Chemical storage cabinets should be vented per UCB Standard, section 12345, 12346 or manufacturer s instructions and provide a minimum of 10 air changes per hour. g. Flammable storage cabinets must be equipped with flame arrestors, and vented using metal or PVC duct. Materials used for venting must meet an NFPA Flame Spread Rating of 25 or less and be of rigid construction. Metal duct should be PVC coated or resistant to corrosive or reactive materials. PVC piping may be used to vent corrosive and other non-flammable storage cabinets. Chemical storage cabinets, whether they are stand-alone or built-in under a fume hood, must be UL listed for the materials they contain and must comply with the applicable requirements of NFPA 30, 45 and 99. Separate cabinets must be used to segregate, by hazard class, the following: acids, bases, oxidizers, flammables and organics. Cabinets must also be provided with spill-containment features or devices. Consult EH&S for additional requirements and restrictions in areas where flammable liquid dispensing occurs. h. Chemical fume hoods shall be equipped with an exterior mounted single point or remote adjustment baffle system. i. Exhaust fan, ON/OFF switches are not permitted on fume hoods or other special hazardous exhaust equipment/systems without expressed approval from CU EH&S. ON/OFF switches may be considered for special operations and situations, EH&S shall be consulted for review. Hazardous exhaust systems should be provided with emergency backup power and not shut down upon activation of any alarm, however, dedicated switches may be provided in the building fire alarm panel to allow capability for manual fan shut-down by the fire department. 4. Ducts, Fans and Control Systems a. All chemical exhaust shall discharge through unobstructed, uncapped vertical stacks. The stacks shall terminate at least 10 feet above roof level, away from eddy currents, air intakes and openings. Discharge velocities shall not be less than 3,000 fpm. Fan selection, stack height and discharge velocity determinations shall give consideration to preventing the reentry of contaminants into buildings. A discharge-height exception might be made by the AHJ if it deems that adequate velocity and dilution will be achieved by the specified fan. JULY 2012 UCB STANDARDS 15852-6

b. Controls and dampers, where required for balancing or control of the exhaust system, shall be of a type that, in event of failure, will fail open to assure continuous draft. If energy conservation devices are used, they shall not recirculate laboratory exhaust air or otherwise compromise the safety of the building occupants. c. Methods of providing emergency ventilation shall be considered, such as variable-speed fan systems, stand-by local exhaust systems, etc., to protect occupants against major chemical spills or similar hazards. d. Duct work shall be installed with a minimum of elbows, using round ducts and sweep ells wherever possible. To further minimize friction loss and turbulence, the interior of ducts shall be smooth and free from obstructions, especially at joints. Rectangular elbows shall not be used unless there is no other choice. If used, turning vanes and inspection doors upstream of the vanes shall be required. e. Ducts for ventilating chemical fume hoods and special exhaust equipment/systems for hazardous vapors must be stainless steel or PVC coated galvanized steel and of rigid construction. f. Ducts for venting flammable storage cabinets must be metal or PVC duct. Materials used for venting must meet an NFPA Flame Spread Rating of 25 or less and be of rigid construction. Metal duct should be PVC coated or resistant to corrosive or reactive materials. PVC piping may be used to vent corrosive and other non-flammable storage cabinets. g. Installation of ductwork must be in compliance with NFPA 91 and ANSI Z9.5, including provisions for properly sealing penetrations, grounding and sealing duct construction materials. Penetration of fire barriers should be avoided. Fume hoods and special exhaust equipment/systems shall be equipped with a balancing damper. h. The fan housing and components shall be corrosion resistant and meet the AMCA standard for spark-resistant construction. The motor must be vapor tight (Class I, Division I) if it is located in the air stream. All fans, ducts, and power supplies shall be clearly labeled to indicate exactly which areas they serve. i. Ducts for ventilating flammable storage cabinets shall be tied into the hazardous exhaust as far down steam from the fume hood as practical to prevent fire-flashback. j. Ducts for ventilating corrosive or reactive chemical storage cabinets shall be tied into the hazardous exhaust so as not to immediately mix with flammable storage cabinet exhaust. JULY 2012 UCB STANDARDS 15852-7

k. Fans used for hazardous exhaust and are located in enclosed areas, such as attics, penthouses, and mechanical rooms, shall comply with ASHREA. l. Internal fans or blowers are not permitted on or within fume hoods. Fans or blowers must not be located inside any duct that is used to vent hazardous exhaust. 5. Testing, Inspecting and Certification B. Dust Collectors a. Testing, inspecting and certifying hazardous exhaust systems, fume hoods and chemical storage cabinets will be performed by Facilities Management Department and Environmental Health and Safety. b. Testing procedures shall conform to UCB Section 15890 and sections 4.7, 4.8, 5 (excluding 5.5.4 and 5.5.5) and 6 of the ANSI/ASHRAE 110-1995 Standard: Method of Testing Performance of Laboratory Fume Hoods. Calibrated air velocity measuring devices as specified in Chapter 9 of the ACGIH Industrial Ventilation, a Manual of Recommended Practice shall be used in testing procedures. EH&S will use a calibrated, directreading air velocity measuring device for certification and inspection purposes. If a meter has not been calibrated at, or adjusted for 5,000 feet above sea level, a density-correction factor must be used when measuring air velocities. EH&S shall certify that the fume hood is in safe operating condition and meets applicable UCB Standards. 1. Provide the following information on the drawings C. Gas Cabinets a. Manufacturer's name and model number b. CFM at total pressure c. Horsepower and TEFC motor: 3600 or 1725 d. Drive type: direct or belted e. Maximum sq. ft. of ground slab that the unit can occupy f. Overall maximum height of unit including leg extensions and plenum silencer g. Capacity in cu. ft. of storage hopper h. Length of legs to provide clearance under hopper without violating overall maximum height restriction of building space. 1. Continuously mechanically ventilated gas cabinets are required for the storage of cylinders of all gases that are greater than lecture bottle size and have an NFPA Health Hazard Rating of 3 or 4. Lecture bottles of these gases must be used and stored inside a chemical fume hood (NFPA 45 8.1.4.2 Special Ventilation Requirements of Gas Cylinders). (Examples of NFPA Health Hazard Rating 4: JULY 2012 UCB STANDARDS 15852-8

arsine, chlorine, hydrogen fluoride, phosgene; NFPA Health Hazard Rating 3: ammonia, carbon monoxide.) 2. Continuously mechanically ventilated, sprinklered gas cabinets are required for all cylinders larger than lecture bottle size that contain pyrophoric gases (NFPA 45 8.1.4.3 Special Ventilation Requirements of Gas Cylinders). 3. All gas cabinets must comply with 2000 current Uniform Fire Code 8003.1.3.2 4. Duct for venting gas cabinet must be stainless steel or PVC coated galvanized steel and of rigid construction. 5. Compatibility of the gases and other chemicals being vented must be taken into account when determining the proper ventilation materials, mixing distance, etc. 6. The maximum allowable amount of flammable gases in any one area is determined by the square footage of the area, the types and concentrations of gas being used and stored, and whether or not the gases are stored in gas cabinets. Using NFPA 45 and 2000 UFC 8001.15A as guidelines, the maximum allowable amount of flammable gases stored outside of flammable gas cabinets is 0.012 cu ft (internal volume)/ ft 2 area. This equates to about four full size cylinders per 500-ft2 area. The maximum allowable amount may be doubled if the gases are stored in ventilated flammable gas cabinets. 7. A gas detecting system is required when a cylinder larger than lecture bottle size containing a gas with a Health Hazard Rating of 4 is being used or stored in the laboratory (NFPA 55, Chapter 3 Toxic Gases). 8. A gas detecting system may also be required if a cylinder larger than lecture bottle size containing a gas with a Health Hazard Rating of 3 has been approved by EH&S to be stored outside of a gas cabinet. 9. EH&S will determine if a gas detecting system is required based on gas types, volumes, concentrations, toxicity, physiological warning properties and how the gases are to be used. 10. Gas cabinets shall be vented to meet Manufacturer s exhaust specifications. D. Laundry Dryer Exhaust 1. Dryer vents providing shared exhaust of multiple dryers shall have an exhaust fan designed for this purpose. The fans shall be easily accessible for service and easily cleanable. 2. The shared exhaust vent shall have a Lint Collection Box installed inline, upstream from the exhaust fan. It shall be easily accessible for maintenance, and made of corrosive resistant materials with an in-line filter material and a differential-pressure sensor with contacts for remote alarming. JULY 2012 UCB STANDARDS 15852-9

E. Demolition 1. If a project's scope includes or will affect either supply or exhaust ventilation, the design team shall verify if there are fume hoods or other special exhaust systems that could be affected. 2. For hood disposal or relocation, hood owners/users shall complete a Property Services, Facilities Management, Environmental Health & Safety Equipment Disposal/Resale Form, return the original to EH&S with a copy to the Party responsible for the project, and post a copy on the fume hood for the Contractor. 3. Interior room duct(s) that serviced disposed fume hood(s) should be removed and capped at the wall or ceiling so lab /room occupants cannot access the ducts for unauthorized use. All remaining hoods or special exhaust equipment must be balanced to conform to Section 15852 or Manufacturer s specifications immediately following the removal of hood from exhaust ventilation system. END OF SECTION 15852 JULY 2012 UCB STANDARDS 15852-10