Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Similar documents
The impact of thermal loads on indoor air flow

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Human response to thermal environment in rooms with chilled beams

Thermal Comfort with Convective and Radiant Cooling Systems

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

American Society of Heating, Refrigerating and Air-Conditioning Engineers

Comparison of radiant and convective cooling of office room: effect of workstation layout

Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

Typologies of Hybrid Ventilation in Schools

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

Experimental study of space cooling using ceiling panels equipped with capillary mats

PRESENTATION TITLE. Effect of Supply Air Temperature on Indoor Thermal Comfort in a Room with Radiant Heating and Mechanical Ventilation

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

Thermal Environment Evaluation in Commercial Kitchens of United States

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

A study of radiant cooling for a room with daytime application in tropical climate

State of the Art of HVAC Technology in Europe and America

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Sprinklers Modeling for Tunnel Road Fire Fighting

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Air and operative temperature measurements in a plus-energy house under different heating strategies

Halton Vario Design Guide

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

Comfort Zone Or Acceptable Comfort Zone? : Comparison of Resident Behavior of Operating Air Conditioner According to Charge for Energy

IEA EBC Annex 59 - Possibilities, limitations and capacities of indoor terminal units

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Displacement Ventilation

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Influence of temperature and drying air velocity on the kinetics of convective drying in the food industry

2013 ASHRAE. Standards & Guidelines CD. Contents

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

NATIONAL INSTITUTES of HEALTH FUME HOOD TESTING PROTOCOL. For CONSTANT VOLUME FUME HOODS

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

Adsorption refrigeration system using waste heat

Simulation of Full-scale Smoke Control in Atrium

,Chaojian He6, f. School of Guangxi University, Nanning , China.

How to ensure Thermal Comfort in buildings with CFD

Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems

Ventilation Strategies for Healthy IEQ and Energy Efficiency

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Considerations in the Design of Smoke Management Systems for Atriums

for commercial kitchen ventilation

Performance Rating of Active Chilled Beams

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

ASSEMBLY HALL AIR DISTRIBUTION

Don t Turn Active Beams Into Expensive Diffusers

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

MD and Its Impact on Lab Facilities

An experimental study of the impact of tunnel suppression on tunnel ventilation

Corn drying experiments by pilot dryer

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

A Study of Drying Uniformity in a New Design of Tray Dryer

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

Experimental study of fan coil assisting radiant floor heating system

Space Air Diffusion II

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

This document is a preview generated by EVS

State-Of-The-Art Developments to Save Energy in Coating Drying. Bob Bates, P.Eng Metso Paper

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Research on fire protection methods and a case study "Futurum"

Computer Models For Fire and Smoke

Heat Transfer in Evacuated Tubular Solar Collectors

How to improve air cooler vacuum steam condensers performance in the field

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Transcription:

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International Center for Indoor Environment and Energy, Department of mechanical Engineering, Technical University of Denmark Corresponding email: risto.kosonen@halton.com SUMMARY The impact of the heat load strength and distribution on the performance of lengthwise installed exposed chilled beam was studied in a test room. The cooling capacity varied between 56 /m 2-111 /m 2, which are typical cooling loads in office buildings. In addition, two experiments at 84 /m 2 were performed with all of the heat sources close to the window side of the room and with the heat sources split on both sides of the room. The results from the physical measurements and the performed smoke visualization showed that the flow from the chilled beams was not disturbed with the heat load of 56 /m 2. However higher loads depicted significant impact of the convective flow from the heat sources on the distribution of the air in the room. The maximum velocity increased from 0.20 m/s to 0.26 m/s when the cooling capacity increased from 56 /m 2 to 111 /m 2. INTRODUCTION The local air velocity, temperatures of the room air and air jets, and fluctuations in air velocity are the key factors that determine occupants thermal comfort in general and in particular the draught discomfort. In this respect the design of ventilation systems focuses on evaluation of the maximum velocity in the occupied zone which can be obtained under different sollutions. The aim is to achieve velocity lower than the maximum velocity recommended in the present standards and guidelines (ISO 7730 1994 [1], ASHRAE 55 2004 [2], EN CEN 1752 1998 [3]) The effect of the convection flows on the flow range in the room is usually ignored and the assessment focuses only on the flow supplied to the room from the air terminal device. However, the convection flows caused by heat sources may significantly affect the supplied flow as well as the airflow distribution in the whole room. This article addresses the effect of thermal loads on the operation of an exposed chilled beam system. The impact of the heat load strength and distribution on the performance of an exposed chilled beam was studied based on measurements of the room air distribution.

METHODS Experimental design Two sets of experiments were designed in order to study: 1) the impact of the heat load strength on the air distribution in the room and 2) the impact of heat load distribution on the airflow characteristics in the occupied zone. Experimental facilities The experiment was conducted at Halton Research Centre, Finland. A test room (L x x H = 6.5 m x 2.75 m x 3m (H)) was used to simulate a real office. Two active chilled beams, type CBQ-A-2500/2200 for exposed installation were installed in series as shown in Figure 1. The chilled beams were installed at the height of 2.5 m. The inlet water temperature was 14 ºC. The mass flow rate of the water for one beam was in range of 0.03 to 0.1 kg/s. The primary airflow rate was 2.0 l/s per m 2 and supply air temperature was 18 o C. Real computers (123 per computer) were used to simulate the heat load from office equipment. A window with size of 1.3 m x 1.9 m (H) was simulated by heated/cooled panels. In most of the experiments the heat load from the window was 350 (surface temperature of 41 o C) except one experiment when the window was cooled to produce -144 effect (surface temperature 20 o C). Heat gain from solar radiation was also simulated by heating 5.5 m² area of the floor close to the window by electric panels (300 ). Lightning was integrated into the chilled beams and gave heat gains of 140. The heat generated by occupants was simulated with dummies (120 each). The number of the used dummies was changed during the experiments when the impact of the heat load was studied. The experimental conditions for during these experiments are listed in Table 1 and Table 2. During these experiments, the cooling capacity was varied between 56 /m 2-111 /m 2 by balancing the number of dummies and the heat gain of the simulated solar load (Table 1.). The experiments with the impact of heat load distribution were performed only at one heat load level in the room, 84 /m 2 as specified in Tables 1 and 2. Table 1. Distribution of heat loads in the test room Heat loads /m² Heat gain from windows, Heat gain from PCs, Heat gain from dummies, Heat gains from floor panels, Heat gain from lightning, 56/m² -144 3x123 3x120 300 140 84/m² 350 3x123 3x120 300 140 98/m² 350 3x123 5x120 300 140 111/m² 350 3x123 7x120 300 140

window window Figure 1. Test arrangement used to study the effect of convection flow on an exposed beam. Table 2. Experimental conditions in the test room Heat loads /m² Airflow rate, l/s per m 2 Temperature in the room, ºC Surface temperature of window, ºC 56/m² 2 23.5 20 84/m² 2 24.1 41 98/m² 2 24.3 41 111/m² 2 24.9 41 Mean air velocity, air temperature and turbulence intensity were measured at 15 locations within the occupied zone at the heights of 0.1m, 0.2m, 0.5m, 1.1m, 1.5m and 1.8m above the floor, e.g. at 90 measurement points (Fig. 2). Smoke visualization of the airflow pattern was performed during the experiments. 98 /m2 111 /m2 3 basic dummies Figure 2. Measurement grid and the location of dummies. Air flow velocities were measured with 8 channel low velocity anemometer HT-400 with omnidirectional velocity sensor, type sensor HT 412. The used 6 omni-directional velocity probes have spherical velocity sensor with a diameter of 2 mm, ensuring a fast response. The temperature sensor is shielded against radiation. Instantaneous values of velocity and temperature are measured simultaneously. Measurements of velocity and temperatures were time averages over 180 s. The characteristics of the instrument complied with the requirements in the standards (ASHRAE 113 2005 [4],ISO 1993 [5], ISO 1998 [6]). The room air temperature, inlet water temperature, supply and exhaust air temperatures were measured with temperature sensors of type PT100 class A. The water flow rate was measured

with Krohne Electromagnetic Flowmeter IFC010 with accuracy less than ± 1% of the readings. The airflow rate was measured with differential pressure transmitter Furness Controls FCO33 with accuracy less than ± 0.5% of the readings. RESULTS Impact of the heat load strength The impact of the heat load strength was studied by changing the number of the used dummies. The position of the dummies was shown in Fig. 2. The results from the physical measurements and the performed smoke visualization shown in Figure 3 reveal that the flow from the chilled beams was not disturbed significantly by the convection flows in the experiment with the lowest heat load (56 /m²). For the experiments with heat loads 84, 98 and 111 /m² a significant impact of the convective flow from the heat sources on the distribution of the air supplied to the room was identified. The higher heat load from the simulated window at the right side of the test room created strong convective flow (Fig 3). a b c d Figure 3. Velocity profile in a vertical plane across the middle of the test room: a) heat load of 56/m², b) heat load of 84/m², c) heat load of 98/m², d) heat load of 111/m²

In Table 3, the results for the average, maximum and minimum values of the temperature, velocity and draught rating in the occupied zone are presented. The values are obtained from all of the measurement location over the occupied zone. Table 3. Minimum, maximum and average temperatures, velocities and DR-index. Heat loads (/m 2 ) v max (m/s) v min (m/s) v avg (m/s) T max (ºC) T min (ºC) T avg (ºC) DR max (%) DR min (%) DR avg (%) 56 /m² 0.20 0.04 0.096 24.0 22.9 23.5 15 2.5 7.7 84 /m² 0.24 0.05 0.098 24.5 22.9 23.7 18 2.3 7.8 98 /m² 0.22 0.04 0.098 24.9 22.8 24.0 18 0 7.8 111/m² 0.26 0.05 0.11 25.0 23.1 24.1 19 0 9.1 The results in the table show that there was significant increase of the maximum velocities in the occupied zone of the room when the heat load increased. Similar result was observed for the maximal temperatures. However, there was no or very small increase in the maximum and average draught rating. In all cases studied, the air velocities were not too high (maximum 0.26 m/s). There was only couple of location with the highest cooling capacity (111 /m 2 ) where the air velocity was higher than the value of 0.25 m/s recommended in the standards for summer conditions. In practice it should be possible to adjust the air flow rate supplied from chilled beam, which will decrease the velocity in the occupied zone and thus will reduce the risk of a draught. Impact of heat load distribution The effect of the heat load distribution on the airflow field in the occupied zone was studied at 84 /m 2 and outdoor air flow rate of 2 l/s per m 2 (see Table 1 and Table 2). Three different thermal load distributions were applied as shown in Figure 4: 1) normal office room with thermal load on the window and side walls,;2) 50% on the window wall and 50% on the corridor wall; and 3) all load on the window wall.

Solar load indow Computers 50 % 50 % Solar load indow Dummies 100 % Dummies Solar load indow Figure 4. Velocity profiles with different heat load distribution (84 /m 2 ).

In all cases studied, the air velocities were relatively low (less than 0.24 m/s). The highest air velocities occurred in cases where the load had been altered from that of a normal office. By locating the heat sources close to the window wall, the maximum velocity was found in the proximity of the corridor wall, while, when the heat sources were evenly distributed between the window and corridor walls, the maximum speed occurred in the middle of the room. The performed smoke visualization further depicted the measured results. Figure 5 presents visualization in the case when the heat sources are located close to the window wall. Figure 5. Smoke visualization when all heat sources are located closet to the window wall. Overall in the measured cases, the location of the thermal load did not significantly affect the maximum velocity. However, the location of the maximum velocity is strongly depending on how the loads are located in the room space. DISCUSSION AND CONCLUSIONS The local air velocity, temperatures of the room air and air jets, and fluctuations in air velocity are the key factors that determine the risk of a draught. Indoor climate standrads recommend maximum allowable velocity in the occupied zone needed for occupants comfort. Therefore in designing an indoor environment, it is important to evaluate different solutions in regard to the maximum velocity in the occupied zone of rooms. This is particularly important for office buildings and on other business premises with relatively high requirements for cooling capacity. It is still not acknowledged during the design of indoor environment that convection flows caused by heat sources may significantly affect the flow distribution in rooms. Most often the focus is only on the flow generated by the air supply terminal devices. However as the present results show the point of occurrence of the maximum velocity in the occupied zone depends

on the heat sourse streangth and its distribution in the room, as well as on the flow pattern of terminal device. Thus, the air flow interaction in rooms ventilated with chilled beams is of great importance for occupants comfort. The results from the physical measurements and the performed smoke visualization showed that the flow from the chilled beams was not disturbed with the heat load of 56 /m 2. However higher loads depicted significant impact of the convective flow from the heat sources on the distribution of the air in the room. The maximum velocity increased from 0.20 m/s to 0.26 m/s when the cooling capacity increased from 56 /m 2 to 111 /m 2. ith the conducted installation, the room air velocity was within the acceptable level (below 0.24 m/s) when the cooling capacity was below 100 /m 2. Higher cooling capacity increases the draught risk and local velocities in the occupied zone. Experience shows that at high cooling load it may possible to adjust the air flow rate supplied from chilled beam, which will diminish the maximum and average velocity in the occupied zone and thus will reduce the risk of a draught. Simple analytic modelling of the jets and thermal loads that affect the air flows of a room space has limitations due to the complex interaction of the flows in rooms. Therefore, fullscale tests and CFD predictions are recommended. The design tools currently available enable studying the flow ranges of room devices but without taking account of the effect of the convection flows from thermal loads. It should be noted that there are no standardised methods for presenting air velocities, and each supplier has its own way to present velocity field in the occupied zone. This makes it difficult to compare the performance of different air supplied devices and installations. ACKNOLEDGEMENT The writers should like to thank TEKES (Finnish Technology Agency) for funding this project. REFERENCES 1. ISO 7730, Moderate thermal environments- Determination of the PMV and PPD indices and specification of the conditions for thermal comfort, 1994 2. ASHRAE Standard 55-2004: Thermal Environmental Conditions for Human Occupancy, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA. 3. CEN CR 1752-1998 Design for Buildings Design Criteria for the Indoor Environment, European Committee for Standardization, December 1998. 4. ANSI/ASHRAE Standard 113-2005: Method of testing for room air diffusion. American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA. Vol.25, No.2, pp. 127-132. 5. ISO Guide to the Expression of Uncertainty in Measurement, First Ed. International Organization for Standardization, Geneva, Switzerland, 1993, ISBN 92-67-10188-9. 6. ISO/DIS/7726 International Standard: Ergonomics of the thermal environment - Instruments for measuring physical quantities. International Organization for Standardization, Geneva, Switzerland, 1998.