FloCon Commissioning Modules Fan coil and chilled beam headers Patent No. GB B

Similar documents
NEW. Hydronic HVAC Systems. FloCon Watchman TM. Patent Numbers: GB , GB , GB Rev: /2015

Mains Pressure Hot Water from an existing vented copper cylinder... Allows the cold water tank to be removed, freeing loft space.

Balancing & Control. Frese PV Compact. Differential Pressure Control Valve

System Design for efficiency using electronic, intelligent HIU s. Neil Parry CIBSE Accredited Heat Network Consultant

PANDORA HEAT BANKS OXFORD BROOKES, HARCOURT HILL. Operation and Maintenance. THERMAL INTEGRATION LTD. Tel: Internet:

TA-COMFORT-S. Prefabricated units Heating interface unit for surface heating and hot water services

Pressure Boosting Solutions

Euron. Compact Wall Mounted Gas Fired Condensing Boilers and Combis with Outputs 24kW - 30kW BOILERS

PAC, NQAC, HQAC, SQAC, EQAC AIR-COOLED CONDENSERS OPERATING AND INSTALLATION INSTRUCTIONS

Design & Product Guide. Danfoss FlatStations.

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

HEATING & COOLING COIL PRODUCTS

Pre-engineered GeoTHERMAL PUMP station

Balancing & Control. Frese SIGMA Compact. Dynamic Balancing Valve

Herz York Direct Heat Interface Unit

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

DISTRIBUTION SYSTEMS. Water Piping and Pumps

SATK 30 heat interface unit

Copper convection heaters:

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

High Capacity Instantaneous Steam Fired Water Heater

Homepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK

Air Cooled Scroll Chiller / Heat Pump

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

Chapter 2.3: Steam System

NKW. Heater series HEATERS

Function of the FENIX Hydrodynamic Trap working on Variable Load Applications

Scroll Water Cooled Chiller

Screw Water Cooled Chiller SCW210

THERMAL INTERFACE UNITS. Designed and manufactured in the UK. Designed for performance

heat interface units A BOILER WITHOUT A FLAME HIU Single PHE options

Polaris-I-60. active chilled beam. the future of space conditioning

BOILER HOUSE PRODUCTS GMS

COOLING and DE-HUMIDIFICATION WITHOUT USING REFRIGERANTS

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

E-Z Valve. Thermostatic valves with radiator connection systems For single and two-pipe heating systems

Solar heating systems

Stainless steel range of condensing boilers. Designed to meet carbon reduction targets. Lifetime service and support. Outputs from 50kW to 660kW

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

Stored Water District Heating Interface Units. Heat Interface Units

Automatic balancing valves ASV-PV (new generation) DN 32-50

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

heat interface units A BOILER WITHOUT A FLAME

EHH SERIES DRAW THROUGH FAN COILS CFM

The Ultimate Solution for Electric Central Heating. Fusion. Comet

ACCREDITED. Product range Code A2L Pre-assembled set point temperature regulating unit with manifolds and box, with UPM3 Auto L pump

Sirius FS. Working towards a cleaner future

CRAFTSMAN EXAMINATION, NOVEMBER 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

1.1 This section applies to air handling units for HVAC Systems.

SUPERIOR QUALITY HEAT INTERFACE UNITS PUTTING YOU IN CONTROL. Pegler Yorkshire

IntaKlean Installation & Servicing Instructions IKMF22 and IKMF28

... Green Building Details

CALEFFI. Anti-condensation circulation unit. 282 series 01225/14 GB. replaces dp 01225/11. Code completion Setting 45 C 55 C 60 C 70 C.

Planning guide. (2010/09) en

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C, 140 AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump

Saving Energy and the Environment with the latest developments in Heat Pipe Technology

ACBH/ACBV ACTIVE CHILLED BEAM INSTALLATION MANUAL. Date: 05/12 Reference # : L-50.

Systems for central heating

Pressure Independent Control Valves

SUBCRITICAL & TRANSCRITICAL SYSTEMS

For commercial & industrial systems. Large volume dirt collection capacity

Air Conditioning Inspections for Buildings Condensers

MTW Series Modular Oil Free Centrifugal Chillers

Mitsubishi Electric Guide to Chiller Technologies. Information Guide 58

Pressure Independent Control Valves

Halton Rex for Vario R6O - Variable air volume chilled beam

Method to test HVAC equipment at part load conditions

Modula Standard Performance

Electric Coils. Blower Coils. Product Information

Automatic Boiling & Chilled Water for commercial and domestic kitchens. Rapid Over Bench Boil Units. Express Under Bench Boil Units

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

Metropolitan high output natural and powered trench heaters

Threaded. Flanged. Model PSH. Primary Secondary Header A-451

Panther Fan Coil Unit

CALEFFI. Solar storage-to-boiler thermostatic connection kit series 01164/09 GB. Function

CONDAIR ME. In-duct evaporative humidifier and cooler Very low energy operation. Humidification and Evaporative Cooling

Steam Site Guide. Steam Site Guide. Heat Exchange Applications - SI Units

ingle phase three phase hoppers central systems single phase three phase hoppers central syste CONVEYING

Technote. Frese AquaHeat HW - DH. Application. Design. Features and Benefit. Operation. Optional.

Patent Pending CO 2 OLrac. Blade Server Cooling

Multibox. Floor Heating Controller Flush individual room control for floor heating systems

CASSETTE UNIT. Comfort Circle

Cooler Range. For use with AESSEAL Seal Support Systems.

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

NATURAL REFRIGERANT SYSTEMS

Technical Product Guide

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

Dehumidification Systems

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

University of Delaware

Design Guide Stored Hot Water Solutions in Heat Networks 2018

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Hybrid VRF Next Generation 2-Pipe Heat Recovery Systems

HYDRONICS BY JOHN SIEGENTHALER

Transcription:

www.savmodules.com FloCon Commissioning Modules Fan coil and chilled beam headers Patent No. GB2 376 066B

2 FloCon Commissioning Module Concept In traditional systems, using copper pipe, the valves must be close to the fan coils to allow full flushing of the pipe work. Once you employ flexible, multi-layer, plastic coated metal pipe where no flushing is needed, all valves can be centralized. This allows off-site assembly, swift commissioning and effortless maintenance. TRADITIONAL DESIGN - FLUSHING BYPASS LOCAL TO FAN COIL BSRIA FLUSHING & CLEANING GUIDE AG1/2001 FLUSHING PATH 4 Fan Coils = 8 branch tees (24 joints) - Copper pipe in 3 meter lengths FloCon MODULE DESIGN - MANIFOLD IS COMMON FLUSHING BYPASS 2-6 Fan Coils per module Flexible Multi-layer Pipe Recommend 15m to furthest terminal Flexible Multi-layer Pipe Max module inlet size - 32mm Valve Module Max pipe feed to terminal units - 20mm FLUSHING PATH 4 Fan Coils need only 2 branch tees (just 6 joints in all) Manifold & multilayer pipe more cost efficient to install (See BSRIA costing sheets) Simple multi-layer pipe installation Multi-layer pipe supplied in up to 200 metre coils Joint-less continuous pipe runs from FloCon module to fan coil

FloCon Commissioning Module Features 3 Return manifold Flow manifold Large bodied strainer Flushing bypass and air vent FULL OFF-SITE ASSEMBLY AND TESTING UNDER STRICT QUALITY CONTROL COMPACT BOX IS VAPOUR SEALED TO PREVENT CONDENSATION THE BIG 3 Large Bodied Strainer Centralized Flushing, Back Flushing, Venting & Balancing Insulated and Vapour Sealed Box FLUSHING THROUGH MAIN BRANCH TERMINAL BRANCH AIR PURGE BACK FLUSHING THROUGH TERMINAL BRANCH As BSRIA Guide AG1/2001: - Remove CM strainer baskets - flush/chemical clean steel pipes - final fill with treated water - replace CM strainer baskets - vent all CMs.

4 Commissioning Traditional Commissioning Extremely laborious - decentralized valves at remote terminal units mean much use of stepladders! Step 1 Step 2 Start Step 3 Step 4 Step 4 Finish Step 1: Flush Pipework up to Fan Coil Step 2: Vent Fan Coils Step 3: Back-Flush Fan Coils Step 4: Proportional Flow Balance As BSRIA Guide AG1/2001 FloCon Commissioning Modules Grouping makes life so much easier. Step 1 Step 2 Start Step 3 Finish Step 1: Flush Valve Module Step 2: Vent, Back-Flush & Flow Balancing can be performed at one visit. Step 3: Balance modules against each other As BSRIA Guide AG1/2001: Remove CM strainer baskets,flush/chemical clean steel pipes, final fill with treated water, replace CM strainer baskets, vent all CMs.

Change and Churn 5 ADDING A FAN COIL 1. Drain Branch 2. Cut into pipework 3. Run new pipework out to Fan Coil 4. Re-balance flow rates to all Fan Coils on branch 1. Position new Fan Coil unit 2. Run new flexible pipes from module 3. Re-balance module balancing valves With Traditional Layout With Valve Modules MOVING A FAN COIL 1. Drain Branch / Move terminal unit 2. Remove Valves and pipework back to mains 3. Refill branch pipework 1. Move terminal unit 2. Extend or re-route pipework 3. Re-balance valves in module 4. Re-balance flow rates to all Fan Coils With Traditional Layout With Valve Modules

6 Variable Speed Pumping Systems Energy saving is a critical issue in the design of modern buildings and variable-speed pumps offer significant potential for energy savings. However, designers face the challenge of utilising the undoubted energy saving potential of variable speed pumps, without losing the energy efficiency of modulating control. BSRIA and CIBSE recommend a minimum Valve Authority of 0.3 to ensure acceptable modulation control. The objective of good regulation control is to minimize the difference between the actual and set point temperature to improve energy efficiency and comfort control. Traditional Layout Control valves must be sized against main branch DPCV pressure FloCon Commissioning Modules Control valves can be sized against local valve module DPCV with typical ΔP 2 of 0.2-0.7 bar. DPCV MODULE WITH INDIVIDUAL TERMINAL UNIT CONTROL VALVES DIFFERENTIAL PRESSURE CONTROL VALVE MODULE WITH ZONE VALVE PRACTICAL DESIGN GUIDE FOR VARIABLE VOLUME PUMPING SYSTEMS is available upon request. Call us on 020 8941 4153 or visit www.savmodules.com

Technical Data 7 Flow Capacities - Max. Working Temperature: 95 o C Max. Working Pressure: 10bar Note: Manifold ports can be adapted to receive different pipe sizes. Hence a mixture of sub-circuit sizes from the same manifold is possible. Inlet Pipe Size mm (OD) Maximum Flow (l/s) 15 0.12 20 0.29 26 0.54 32 1.12 Terminal Pipe Sizes Maximum Flow mm (Outer Diameter) mm (Internal Diameter) (l/s) 14 10 0.04 16 12 0.08 20 16 0.16 26 20 0.28 Terminal Unit Flow Equation: Q=kW/(4.2* t) where Q = flow in l/s, kw = Term. Unit duty in kw, t = difference between Flow & Return temperatures in o C Commissioning Sets Nom. Size Flow Range (l/s) Maximum balancing kv kvs pressure (kpa) 15 LL 0.014 0.028 54200 Q 2 0.473 0.473 15 ML 0.028 0.055 54200 Q 2 0.825 0.976 15 SL 0.055 0.095 54200 Q 2 0.85 1.799 15 SS 0.095 0.12 2366 Q 2 1.911 1.799 20 0.12 0.29 1250 Q 2 4.427 4.057 25 0.21 0.54 1203 Q 2 7.648 7.452 32 0.46 1.12 284 Q 2 16.56 16.628 Equations: P(Pa) = 2 /2 or P(kPa) = (Qx36/kv) 2 Where Q = flow kg/s, = density kg/m 3, = velocity m/s Pipe Pressure Losses - Outer Diameter 1000 14mm di 16mm di 20mm di 26mm di 500 400 300 Pressure Drop (Pa/m) 200 100 50 NB: Pressure losses are for straight pipe 10 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.9 1 Flow Rate (kg/s) 2 pv Type - VZL2 DPCV - AVP-F 2 port valve mm kvs mm kvs 15 0.25 15 1.60 15 0.40 15 2.50 15 0.63 20 2.50 15 1.00 20 4.00 DPCV DN mm kvs DN mm kvs 15 1.60 20 6.30 15 2.50 25 8.00 15 4.00 32 10.00

FloCon Commissioning Module Installations - Fan Coils and Chilled Beams Albion Riverside Luxury Apartments BskyB Head Office 30 St Mary Axe Harvey Nichols London Stock Exchange The SAV solution offers better more accurate control of differential pressure and easier, faster commissioning - a sixth of every floor at 30 St Mary Axe, could be balanced and finely tuned from a single point. Dave Gatwood, Project Manager, Hills Mechanical SAV FloCon Modules fitted with DPCV's allow us to commission one module at a time if necessary. Variable speed systems are simple to commission in this way and phased occupancy of the building is made easier. Adjustment of pump speed according to measured readings satisfies our responsibility under the Part 'L' regulations. Measurement of pressure drop and flow become highly predictable, so we can now truly commission the system instead of simply measuring flow rates. Duncan Selby, Comdronic Ltd The benefits at the commissioning stage have been remarkable. There were zero problems in a 125,000 ft 2 building! Our commissioning engineers describe the Modules as a dream to work with and all their figures were within the design set margins. Stuart Bareham - Waterman Building Services The installation was highly successful, resulting in an overall time saving compared to a traditional system. We are now proposing the Commissioning Module solution on a number of new projects we are now involved with. JS Key, Contracts Manager, Balfour Kilpatrick Limited UK Customer Support Centre SAV, Scandia House, 131 Armfield Close, West Molesey, Surrey KT8 2JR Tel: +44 (0)20 8941 4153 Telefax: +44 (0)20 8783 1132 Email: info@savmodules.com Web: www.savmodules.com