SERVICE MANUAL MSC-A07YV - (WH) MSC-A09YV - (WH) MSC-A12YV - (WH) HFC. Wireless type Models

Similar documents
SERVICE MANUAL MSC-GA20VB - (WH) MSC-GA25VB - (WH) MSC-GA35VB - (WH) Wireless type Models

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SERVICE MANUAL. Wireless type Models MS-GA50VB - MS-GA60VB - MS-GA80VB - SPLIT-TYPE, AIR CONDITIONERS. No. OB369 CONTENTS

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL INDOOR UNIT

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

MSZ-GE06NA- 8, 9 MSZ-GE09NA- 8, 9 MSZ-GE12NA- 8, 9 MSZ-GE15NA- 8, 9 MSZ-GE18NA- 8, 9

MUH-24RV - MSH-30RV -

SERVICE MANUAL MSZ-HC25VA - E1 MSZ-HC35VA - E1 MSZ-HC35VA - E2 MSZ-HC35VAB - E1 MSZ-HC35VAB - E2 INDOOR UNIT. No. OBH466. Models

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE MSZ-FH25VE2 MSZ-FH35VE2 MSZ-FH50VE2 INDOOR UNIT. No. OBH623. Models

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE INDOOR UNIT. No. OBH623. Models SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA INDOOR UNIT. No. OBH501. Wireless type Models

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models

SERVICE MANUAL INDOOR UNIT. No. OBH788

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models

SERVICE MANUAL. Wireless type Models MSZ-A09RV - (WH) MUZ-A09RV - MSZ-A12RV - (WH) MUZ-A12RV - E1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No.

SERVICE MANUAL MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. OB368 R410A CONTENTS

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC

SERVICE MANUAL MUH-A18WV - MUH-A24WV - MUH-A30WV - E1. Wireless type Models HFC

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1 OUTDOOR UNIT. No. OB381. Models HFC

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUX-A22WV - E1 HFC. Multi system type Model SPLIT-TYPE, AIR CONDITIONER. No. OB318 R410A CONTENTS. Revision A: MUX-A22WV -

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F.

SERVICE MANUAL MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF INDOOR UNIT. No. OBH801. Models

SERVICE MANUAL MUH-GA50VB- MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1 OUTDOOR UNIT. No. OB368 REVISED EDITION-B. Wireless type Models HFC.

TECHNICAL & SERVICE MANUAL

OPERATING INSTRUCTIONS

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K

TAC-09CHSA/*** TAC-12CHSA/*** TAC-18CHSA/*** TAC-24CHSA/*** SERVICE MANUAL WALL MOUNTED SPLIT-TYPEAIR CONDITIONERS. No.TE1307.

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MSC-09RV - E1 MU-07RV - MSC-09RV - MU-09RV - MSC-12RV - MU-12RV - MSC-07RV - MUH-07RV - MSC-09RV - MUH-09RV - MSC-12RV - MUH-12RV -

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN

MUH-A07WV - MSC-A09WV - MUH-A09WV - MSC-A12WV - MUH-A12WV - Multi system type Models MUX-A10WV - MSC-A09WV - MUX-A19WV - MSC-A12WV -

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

SERVICE MANUAL MXZ-A18WV - MXZ-A26WV - MXZ-A32WV - E1 HFC. Inverter-controlled multi system Models SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC

Part 3 Troubleshooting

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G09LTCN AO*G12LTCN AO*G14LTCN

DESIGN & TECHNICAL MANUAL

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOU9RLS2H AOU12RLS2H AOU15RLS2H

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS

DESIGN & TECHNICAL MANUAL

SUZ-SA71VA3.TH SUZ-SA100VA2.TH

OPERATION MANUAL. Wireless Remote Controller Kit

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

OWNER S MANUAL. R 410A Ductless Split System Air Conditioner and Heat Pump

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH

TCL SERVICE MANUAL. Models WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS. No.TE CONTENTS

TECHNICAL & SERVICE MANUAL. Ceiling Cassettes

CONTENTS SAFETY PRECAUTIONS. En-1 DANGER! CAUTION!

XHS1271 XHS1872. This air conditioner uses the new refrigerant R410A. COOL/DRY/HEAT Model

OWNER S MANUAL VMH 09/12/18/24

Wireless Remote Controller Kit

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

53 KNL / 53 QNL OWNER S MANUAL

DESIGN & TECHNICAL MANUAL

OPERATING MANUAL AIR CONDITIONER DUCT TYPE. ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL

RAS-07EKH/RAS-07EAH RAS-09EKH/RAS-09EAH

AY-AP09DJ SPLIT TYPE ROOM AIR CONDITIONER OPERATION MANUAL AE-A09DJ AY-AP09DJ OUTDOOR UNIT INDOOR UNIT

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH

XS1271 XS1872 INSTRUCTION MANUAL MODE D EMPLOI This air conditioner uses the new refrigerant R410A.

Air Conditioner CONTENTS

OPERATING MANUAL AIR CONDITIONER CASSETTE TYPE. AUT Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

DESIGN & TECHNICAL MANUAL

Ductless Split Air Conditioner

Transcription:

SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MSC-A07YV - (WH) E MSC-A09YV - (WH) E MSC-AYV - (WH) HFC utilized R40A. OB39 CONTENTS Indication of model name MSC-A07YV - E MSC-A09YV - E MSC-AYV - E. TECHNICAL CHANGES 3. PART NAMES AND FUNCTIONS 3 3. SPECIFICATION 5 4. NOISE CRITERIA CURVES 6 5. OUTLINES AND DIMENSIONS 7 6. WIRING DIAGRAM 8 7. REFRIGERANT SYSTEM DIAGRAM 8 8. MICROPROCESSOR CONTROL 9 9. SERVICE FUNCTIONS 7 0. TROUBLESHOOTING 9. DISASSEMBLY INSTRUCTIONS 6. PARTS LIST 8 NOTE: This manual describes technical data of indoor units. As for outdoor units MU-A07/A09/AYV - E, refer to the service manual OB330. As for outdoor units MUH-A07/A09/AYV - E, refer to the service manual OB33. As for outdoor units MUX-A0/A9/A0/A5/A6WV - E, refer to the service manual OB307 REVISED EDITION-A. As for outdoor units MUX-AWV - E, refer to the service manual OB38. As for outdoor units MXZ-A8/A6/A3WV - E, refer to the service manual OB39.

TECHNICAL CHANGES MSC-A07WV- MSC-A09WV- MSC-AWV- E E E MSC-A07YV- MSC-A09YV- MSC-AYV-. Design of front panel has changed.. Air filter has changed to the catechin air filter. E E E PART NAMES AND FUNCTIONS MSC-A07YV - E MSC-A09YV - E MSC-AYV - E INDOOR UNIT Air cleaning filter (white bellows type) Front panel Air inlet Panel Catechin air filter (With deodorizer) Air outlet to Breaker Power supply cord Remote control receiving section Vertical vanes Fan Horizontal vane Remote controller Operation section (When the front panel is opened) Display section Emergency operation switch Operation indicator lamp Remote control receiving section 3

MSC-A07YV- E MSC-A09YV- E MSC-AYV- E ACCESSORIES <Indoor unit> Installation plate Installation plate fixing screw 4 o 5 mm 3 Remote controller holder 4 Fixing screw for 3 3.5 o 6 mm 5 Battery (AAA) for remote controller 6 Wireless remote controller 7 Felt tape (Used for left or left-rear piping) 8 Air cleaning filter 5 REMOTE CONTROLLER Signal transmitting section Operation display section PM OPERATE /STOP (ON /OFF)button ON/OFF TOO WARM AM TOO COOL TEMPERATURE buttons Open the front lid. Indication of remote controller model is on back. CLOCK PM AM ON/OFF TOO WARM TOO COOL FAN SPEED CONTROL button OPERATION SELECT button ECONO COOL button I FEEL HEAT /FAN COOL DRY / MODE ECONO COOL FAN STOP VANE START HR. MIN. RESET CLOCK OFF-TIMER button ON-TIMER button HR. button MIN. button (TIME SET button) RESET button CLOCK SET button VANE CONTROL button 4

3 SPECIFICATION Indoor model MSC-A07YV - E MSC-A09YV - E MSC-AYV - E Function Cooling Heating Cooling Heating Cooling Heating Indoor unit power supply Single phase Single phase Single phase 30V,50Hz 30V,50Hz 30V,50Hz Capacity Air flow(high/med. w/low w) Power outlet Running current Power input Power factor Fan motor current Model K /h A A W % A 474/37 w/76w 50/40 w/34 w 0 0.7 35 90 0.7 RC4V9-LA 474/384 w/306w 588/456 w/34w 0 0.7 35 90 0.7 RC4V9-LA 58/444 w/34w 606/498 w/396w 0 0.9 40 9 0.9 RC4V9-KA Winding " WHT-BLK 43 WHT-BLK 43 WHT-BLK 36 resistance(at 0:) BLK-RED 334 BLK-RED 334 BLK-RED 99 Dimensions WOHOD Weight Air direction mm kg 85O78O44 9 5 85O78O44 9 5 85O78O44 0 5 Sound level(high/med. w/low w) db 36/3 w/5 w 36/3 w /5 w 36/3 w/5 w 39/3 w /5 w 40/33 w/6 w 39/33 w/6w Fan speed(high/med. w/low w) rpm 900/750 w/600 w 950/80 w/700 w 900/770 w/650w,050/870 w/700w 930/760 w/600w 960/830 w/700w Fan speed regulator Thermistor RT(at 5:) Thermistor RT(at 5:) Remote controller model k" k" 3 0 0 KPA or KG3A 3 0 0 KPA or KG3A 3 0 0 KPA or KG3A Electrical data Fan motor Special remarks NOTE:. Test conditions are based on ISO 55. Cooling : Indoor DB7 C WB9 C Heating : Indoor DB0 C Outdoor DB35 C WB4 C OutdoorDB 7 C/WB 6 C Indoor-Outdoor piping length 5m.Remote controller model KPA and KG3A are the same in terms of specification. W Reference value 5

4 NOISE CRITERIA CURVES MSC-A07YV- E FAN SPEED FUNCTION COOL High HEAT SPL(dB(A)) 36 LINE MSC-A09YV- E FAN SPEED FUNCTION SPL(dB(A)) COOL 36 High HEAT 39 LINE 90 Test conditions, Cooling : DB7: WB9: Heating : DB0: WB -: 90 Test conditions. Cooling : DB7: WB9: Heating : DB0: WB -: OCTAVE BAND SOUND PRESSURE LEVEL, db re 0.000 MICRO BAR 80 70 60 50 40 30 0 0 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 5 50 500 000 000 4000 8000 NC-70 NC-60 NC-50 NC-40 NC-30 NC-0 OCTAVE BAND SOUND PRESSURE LEVEL, db re 0.000 MICRO BAR 80 70 60 50 40 30 0 0 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 5 50 500 000 000 4000 8000 NC-70 NC-60 NC-50 NC-40 NC-30 NC-0 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz MSC-AYV- E 90 FAN SPEED FUNCTION High COOL HEAT SPL(dB(A)) 40 39 Test conditions, Cooling : DB7: LINE WB9: OCTAVE BAND SOUND PRESSURE LEVEL, db re 0.000 MICRO BAR 80 70 60 50 40 30 0 0 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 5 50 500 000 000 4000 8000 NC-70 NC-60 NC-50 NC-40 NC-30 NC-0 INDOORUNIT m 0.8m MICROPHONE WALL BAND CENTER FREQUENCIES, Hz 6

5 OUTLINES AND DIMENSIONS MSC-A07YV - E MSC-A09YV - E INDOOR UNIT Installation plate 8.5 33.5 4.5 Unit: mm Indoor unit 3.5 7 783 4.5 4 8.5 36 36 8.5 Wall hole [65 85 4 5 Installation plate 78 Air in 7 or more Liquid line [6.35-0.5m Gas line [9.5-0.43m { Insulation [37 O.D [ I.D 60 6 58 606 9 49 30 Air out Power supply cord Lead to right.0m Lead to left 0.3m 44 90 0 Drain hose [6 (Connected part O,D) Insulation [8 Wireless remote controller MSC-AYV - E INDOOR UNIT Installation plate 6.5 6.5 7.5 783 Indoor unit 8.5 58 4.5 4 8.5 36 36 8.5 Wall hole [65 85 4 5 Installation plate 78 Air in 7 or more Liquid line [6.35-0.5m Gas line [9.5-0.43m { Insulation [37 O.D [ I.D 60 6 58 606 9 49 30 Air out Power supply cord Lead to right.0m Lead to left 0.3m 44 90 0 Drain hose [6 (Connected part O,D) Insulation [8 Wireless remote controller 7

6 WIRING DIAGRAM MSC-A07YV - E MSC-A09YV - E MSC-AYV - E INDOOR UNIT MODELS WIRING DIAGRAM TO OUTDOOR UNIT CONNECTING FOR MUH OR MXZ TYPE V FOR MU OR MUX TYPE V PE POWER SUPPLY CORD ~/N 30V 50Hz TB L 3 N BRN BLU CIRCUIT BREAKER GRN/YLW BRN RED BLU WHT BLK GRN LD03 CN 5 MV 5 TAB CN0 3 CN0 CN 0 5 F NR C SR4 ELECTRONIC CONTROL P.C. BOARD POWER MONITOR, RECEIVER P.C.BOARD T REMOTE CONTROLLER CN CN CN 3 5 CN 3 RT RT BLK GRY YLW BRN WHT RED 3 MF 4 5 6 SYMBOL C F MF MV NAME SYMBOL NAME SYMBOL NAME INDOOR FAN CAPACITOR FUSE(3.5A) INDOOR FAN MOTOR (INNER FUSE) VANE MOTOR NR RT RT SR4 VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR SOLID STATE RELAY TB T TERMINAL BLOCK TRANSFORMER NOTE:. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.. Use copper conductors only. (For field wiring) 3. Symbols below indicate. /: Terminal block, : Connector 7 REFRIGERANT SYSTEM DIAGRAM MSC-A07YV - E INDOOR UNIT MSC-A09YV - E Refrigerant pipe [9.5 (with heat insulator) MSC-AYV - E INDOOR UNIT Unit:mm Refrigerant pipe [.7 (with heat insulator) Indoor heat exchanger Indoor coil thermistor RT Flared connection Indoor heat exchanger Indoor coil thermistor RT Flared connection Room temperature thermistor RT Room temperature thermistor RT Flared connection Flared connection Refrigerant flow in cooling Refrigerant pipe [6.35 (with heat insulator) 8 Refrigerant flow in cooling Refrigerant pipe [6.35 (with heat insulator)

8 MICROPROCESSOR CONTROL MSC-A07YV - E MSC-A09YV - E MSC-AYV - E Once the operation mode are set, the same operation mode can be repeated by simply turning the OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes. WIRELESS REMOTE CONTROLLER Signal transmitting section Operation display section OPERATE /STOP (ON /OFF)button ON/OFF TOO WARM AM PM TOO COOL TEMPERATURE buttons INDOOR UNIT DISPLAY SECTION Operation Indicator lamp The operation indicator at the right side of the indoor unit indicates the operation state. The following indication does not depend on the shape of lamp. Operation Indicator lighted not lighted Open the front lid. Indication Operation state Difference between target temperature and room temperature FAN SPEED CONTROL button OPERATION SELECT button ECONO COOL button RESET button I FEEL ON/OFF COOL HEAT /FAN DRY / MODE ECONO COOL TOO WARM FAN VANE RESET CLOCK CLOCK AM PM TOO COOL STOP START HR. MIN. OFF-TIMER button ON-TIMER button HR. button MIN. button (TIME SET button) CLOCK SET button VANE CONTROL button This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained. This shows that the room temperature is approaching the target temperature. Approx. : or more Approx. : or less 8-. COOL ( ) OPERATION () Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. () Select COOL mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature. The setting range is 6 ~ 3 C Difference between room. Thermostat control temperature and set temperature during operation Thermostat is ON or OFF by difference between room temperature and set temperature Initial temperature difference Thermostat Set temperature Room temperature minus set temperature : 0.3 : or more ON Room temperature minus set temperature : less than -0.3 : OFF -0.3 : 0.3 :. Indoor fan speed control Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of thermostat s OFF-ON. In Auto the fan speed is as follows. Initial temperature difference Fan speed Room temperature minus set temperature :.7 degrees or more High Room temperature minus set temperature : Between and.7 degrees Med. Room temperature minus set temperature : less than degree Low Difference between room temperature and set temperature during operation deg..7 deg. 3 deg. 9

3. Coil frost prevention Temperature control When the indoor coil thermistor RT reads 4 C or below(msc-a07/a09yv) / 0 C or below(msc-ayv) for 5 minutes, the coil frost prevention mode starts. The indoor fan operates at the set speed and the compressor stops for 5 minutes. After that, if RT still reads below 4 C (MSC-A07/A09YV) / 0 C (MSC-AYV), this mode is prolonged until the RT reads over 4 C (MSC-A07/A09YV) / 0 C (MSC-AYV). Time control When the three conditions as follows have been satisfied for hour and 45 minutes, the compressor stops for 3 minutes. The indoor fan operates at the set speed. a. Compressor has been continuously operating. b. Indoor fan speed is Low or Med. c. Room temperature is below 6 C. When compressor stops, the accumulated time is cancelled. When compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 6 C. However, when two of the above conditions (b.and c.) are satisfied again, time accumulation is resumed. Operation chart Example ON ON Compressor Outdoor fan OFF OFF Indoor fan ON ( continuously at set speed) 8-. DRY ( ) OPERATION () Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. () Select DRY mode with the OPERATION SELECT button. (3) The microprocessor reads the room temperature and determines the set temperature. Set temperature is as shown on the right chart. DRY operation will not function when the room temperature is 3 C or below. (4) When DRY operation functions the fan speed is lower than COOL operation except at (fan speed) Low. Set temperature Set temperature and : initial room temperature in dry mode 35 30 5 0 The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room temperature. 5 0 0 5 0 5 30 35 : Initial room temperature Difference between room. Thermostat control temperature and set temperature Thermostat is ON or OFF by difference between room temperature and set temperature. during operation Initial temperature difference Thermostat Set temperature Room temperature minus set temperature : 0.3 : or more ON Room temperature minus set temperature : less than -0.3 : OFF -0.3 : 0.3 :. Indoor fan speed control Indoor fan operates at the set speed by FAN SPEED CONTROL button. In Auto fan speed becomes Low. 3. The operation of the compressor and indoor / outdoor fan <MU-A07/A09/AYV, MUH-A07/A09/AYV, MUX-A0/A9/A0/A/A5/A6WV> Compressor operates by room temperature control and time control. Indoor fan and outdoor fan operate in the same cycle as the compressor. When the room temperature is 3 C or over: When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and minute ON. When the room temperature is under 3 C. When the thermostat is ON, the compressor repeats minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and minute ON. 0

Operation time chart Example Thermostat OFF ON OFF ON ON ON ON Indoor fan OFF OFF OFF ON ON ON Outdoor fan Compressor OFF OFF OFF 8 min. 3 min. 4 min. min. 4. Coil frost prevention The operation is as same as coil frost prevention during COOL operation.(refer to 8-.3.) However when coil frost prevention works while the indoor fan is OFF, its speed becomes set speed. 8-3. FAN ( ) OPERATION <MU-A07/A09/AYV, MUX-A0/A9/A0/A/A5/A6WV> () Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. () Select FAN mode with the OPERATION SELECT button. (3) Select the desired fan speed. When AUTO, it becomes Low. Only indoor fan operates. does not operate. 8-4. HEAT ( ) OPERATION <MUH-A07/A09/AYV, MXZ-A8/A6/A3WV> () Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. () Select HEAT mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 6 ~ 3 C. Difference between room temperature and set temperature during operation. Thermostat control Thermostat is ON or OFF by difference between room temperature and set temperature. Set temperature Initial temperature difference Thermostat -0.3 deg. Room temperature minus set temperature : less than -0.3 : ON Room temperature minus set temperature : 0.3 : or more OFF 0.3 deg.. Indoor fan speed control () Indoor fan operates at the set speed by FAN SPEED CONTROL button. In Auto the fan speed is as follows. Initial temperature difference Fan speed Set temperature minus room temperature:.7 degrees or more High Set temperature minus room temperature: Between and.7 degrees Med. Set temperature minus room temperature: less than degree Low Difference between room temperature and set temperature during operation deg..7 deg. 3 deg. () Cold air prevention control When the compressor is not operating, () if the temperature of indoor coil thermistor RT is 0 C or less, the fan stops. () if the temperature of indoor coil thermistor RT is more than 0 C, the fan operates at Very Low. When the compressor is operating, () if the temperature of RT is C or more, the fan operates at set speed. () if the temperature of RT is less than C and () if the temperature of room temperature thermistor RT is 5 C or less, the fan stops. () if the temperature of room temperature thermistor RT is more than 5 C, the fan operates at Very Low. Released Cold Air Prevention 8: : NOTE : If the temperature of RT reads from 8 C to C at the air conditioner stating and also after defrosting, this control works. Fan speed Set speed Very Low or stop

(3) Warm air control. When the following any condition of (a. ~ c.) and the condition of are satisfied at the same time, warm air control works. a.) When outdoor unit starts operating in HEAT mode. b.) When cold air prevention has been released. c.) When defrosting has been finished When the temperature of indoor coil thermistor RT is less than 37 C. When warm air control works, the fan speed changes as follows to blow out warm air gradually. Gradation of fan speed in initial <Time condition> <Indoor fan speed> less than minutes Low minutes to 4 minutes Med. more than 4 minutes High The upper limit of the fan speed in MANUAL is the set speed. The upper limit of the fan speed in AUTO is the speed decided by indoor fan speed control.(refer to 8-4..().) When the temperature of RT has been 37 C or more, or when the set speed has been changed, this control is released and the fan speed is the set speed. NOTE: As for high pressure protection, defrosting and R.V. coil control, refer to service manual for outdoor unit. 8-5. I FEEL CONTROL ( ) OPERATION () Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. () Select I FEEL CONTROL ( ) mode with the OPERA- TION SELECT button. (3) The operation mode is determined by the initial room temperature at start-up of the operation, as shown on the right table. Initial room temperature MU & MUX type MUH &MXZ type 5: or more more than3:, less than 5: 5: or more 3:or more, less than 5: less than 3: Mode COOL mode of "I FEEL CONTROL" DRY mode of "I FEEL CONTROL" HEAT mode of "I FEEL CONTROL" Once the mode is fixed, the mode does not change by room temperature afterwards. Under the ON-TIMER ( ) operation, mode is determined according to the room temperature at set time the operation starts. When the system is stopped on the remote controller and restarted within hours in I FEEL CONTROL ( ) mode, the system operates in previous mode automatically regardless of the room temperature. Operation time chart Example Previous operation COOL mode of I FEEL CONTROL or COOL mode Restart COOL mode of I FEEL CONTROL When the system is restarted after hours and more, the operation mode is determined by the room temperature at start-up of the operation. Operation time chart Example Previous operation COOL mode of I FEEL CONTROL or COOL mode Restart COOL or DRY or HEAT mode of I FEEL CONTROL that determined by room temperature at start-up of the operation.

(4) The initial set temperature is decided by the initial room temperature. Mode MU & MUX type Initial room temperature MUH & MXZ type Initial set temperature COOL mode of "I FEEL CONTROL" 6: or more 5: or more, less than 6: 6: or more 5: or more, less than 6: 4: Initial room temperature minus : Initial room temperature minus : DRY mode of "I FEEL CONTROL" HEAT mode of "I FEEL CONTROL" more than 3:, less than 5: 3: or more, less than5: less than 3: 6: When the system is restarted with the remote controller, the system operates with the previous set temperature regardless of the room temperature at restart. (5) TEMPERATURES buttons In I FEEL CONTROL ( ) mode, set temperature is decided by the microprocessor based on the room temperature. In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone. Fuzzy control When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user s preference to heat or cool. So this is called Fuzzy control, and works only in I FEEL CONTROL mode. In DRY mode of I FEEL CONTROL, the set temperature doesn t change. TOO COOL To raise the set temperature ~ degrees( C) TOO WARM To lower the set temperature ~ degrees( C) 8-5-. COOL mode of I FEEL CONTROL. Thermostat control Thermostat control is as same as COOL OPERATION.(8-..). Indoor fan speed control Indoor fan speed control is as same as COOL OPERATION.(8-..) 3. Coil frost prevention Coil frost prevention is as same as COOL OPERATION.(8-.3.) 8-5-. DRY mode of I FEEL CONTROL. Thermostat control Thermostat control is as same as DRY OPERATION.(8-..). Indoor fan speed control Indoor fan speed control is as same as DRY OPERATION.(8-..) 3. The operation of the compressor and indoor/outdoor fan The operation of the compressor and indoor/outdoor fan is as same as DRY OPERATION.(8-.3.) 4. Coil frost prevention Coil frost prevention is as same as DRY OPERATION.(8-.4.) 8-5-3. HEAT mode of I FEEL CONTROL <MUH-A07/A09/AYV, MXZ-A8/A6/A3WV>. Thermostat control Thermostat control is as same as HEAT OPERATION.(8-4..). Indoor fan speed control Indoor fan speed control is as same as HEAT OPERATION.(8-4..) NOTE: As for high pressure protection, defrosting and R.V. coil control, refer to service manual for outdoor unit. 3

8-6. FAN MOTOR CONTROL () Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (High,Med.,Low), the microprocessor controls SR4 and adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly. High Med. Low High () Fan motor lock-up protection When the rotational frequency feedback signal is not output for seconds, (or when the microprocessor cannot detect the signal for seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICA- TOR lamp flashes on and off to show the fan motor abnormality. (Refer to page.) 8-7. AUTO VANE OPERATION () Vane motor drive These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. V) transmitted from indoor microprocessor. () The horizontal vane angle and mode changes as follows by pressing the VANE CONTROL button. (3) Positioning The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle. Confirming of standard position is performed in case of follows. (a) When the OPERATE/STOP(ON/OFF) button is pressed. (b) When the vane control is changed from AUTO to MANUAL. (c) When the SWING is finished. (d) When the test run starts. (e) When the power supply turns ON. (4) VANE AUTO ( ) mode In VANE AUTO mode, the microprocessor automatically determines the vane angle to make the optimum room-temperature distribution. In COOL and DRY operation Vane angle is fixed to Angle. In FAN operation <MU-A07/A09/AYV, MUX-A0/A9/A0/A/A5/A6WV> In HEAT operation <MUH-A07/A09/AYV, MXZ-A8/A6/A3WV> Vane angle is fixed to Angle 4. (5) Dew prevention During COOL or DRY operation at Vane Angle 4 or 5 when the cumulative operation time of compressor exceeds hour, the vane angle automatically changes to Angle for dew prevention. (6) SWING MODE ( ) By selecting SWING mode with the VANE CONTROL button, the horizontal vane swings vertically. The remote controller displays. 4

(7) Cold air prevention in HEAT operation <MUH-A07/A09/AYV, MXZ-A8/A6/A3WV> When any of the following conditions occurs in HEAT operation, the horizontal vane angle changes to Angle automatically to prevent cold air blowing on users. Compressor is not operating. ➁ Defrosting is performed. ➂ Indoor coil thermistor RT reads 4: or below. ➃ Indoor coil thermistor RT temperature is raising from 4 C or below, but it does not exceed 8:. Indoor coil thermistor RT temperature Released Cold air prevention 4: 8: Horizontal vane Set position Angle NOTE : If the temperature of RT reads from 4 C to 8 C at the air conditioner stating, this control works. (8) ECONO COOL ( ) operation (ECONOmical operation) When the ECONO COOL button is pressed in COOL mode, set temperature is automatically set C higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(rt). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. ECONO COOL operation is cancelled when the ECONO COOL button is pressed once again or VANE CONTROL button is pressed or operation mode is changed. NOTE : ECONO COOL operation does not work in COOL mode of I FEEL CONTROL. SWING operation In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to Horizontal. According to the temperature of indoor coil thermistor RT at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next upward blow time is decided. For initial 0 min. the swing operation is performed in table G~H for quick cooling. Also, after 0 min. when the difference of set temperature and room temperature is more than degrees, the swing operation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows. Temperature of indoor coil thermistor RT Downward blow time (sec.) Horizontal blow time (sec.) A B C D E F G H 5 C or less 5 C to 7 C 7 C to 8 C 8 C to 0 C 0 C to C C to C C to 4 C more than 4 C 5 8 4 7 0 3 3 0 7 4 8 5 8-8. TIMER OPERATION. How to set the timer () Press OPERATE/STOP(ON/OFF) button to start the air conditioner. () Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially AM0:00 blinks at the current time display of TIME MONITOR, so set the current time correctly with CLOCK SET button. (3) Press ON or OFF TIMER buttons to select the operation. button... AUTO START operation (ON timer) button... AUTO STOP operation (OFF timer) 5

(4) Press HR. and MIN. button to set the timer. Time setting is 0-minute units. HR. and MIN. button will work when or mark is flashing. These marks disappear in minute. After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights. NOTE : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during TIMER operation, or the set time may deviate within the range of about 0 minutes. NOTE : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur. A power failure occurs. The circuit breaker functions.. Cancel TIMER setting can be cancelled with the ON or OFF TIMER buttons. ( or ) To cancel the ON timer, press the button. To cancel the OFF timer, press the button. TIMER is cancelled and the display of set time disappears. PROGRAM TIMER The OFF timer and ON timer can be used in combination. and display shows the order of the OFF timer and ON timer operation. (Example ) The current time is 8:00 PM. The unit turns off at :00 PM, and on at 6:00 AM. (Example ) The current time is :00 AM. The unit turns on at 5:00 PM, and off at 9:00 PM. PM PM AM PM NOTE : TIMER setting will be cancelled by power failure or breaker functioning. 8-9. EMERGENCY-TEST OPERATION In case of test run operation or emergency operation, use the EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote controller run down. The unit will start and the OPERATION INDICATOR lamp will light. The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at High speed and the system is in continuous operation. (The thermostat is ON.) After 30 minutes of test run operation the system shifts to EMERGENCY COOL [/ HEAT<MUH-A07/A09/AYV, MXZ- A8/A6/A3WV>] MODE with a set temperature of 4 C. The fan speed shifts to Med. speed. The coil frost prevention works even in emergency operation [, and defrosting<muh-a07/a09/ayv, MXZ- A8/A6/A3WV> too]. In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode. Emergency operation continues until the EMERGENCY OPERATION switch is pressed once again (MU-A07/A09/AYV, MUX-A0/A9/A0/A/A5/A6WV)/once or twice (MUH-A07/A09/AYV, MXZ-A8/A6/A3WV) or the unit receives any signal from the remote controller. In case of latter normal operation will start. NOTE : Do not press the EMERGENCY OPERATION switch during normal operation. The following indication does not depend on the shape of lamp. OPERATION INDICATOR lamp Press once <Cool> Press again <Heat> EMERGENCY OPERATION switch 6 Press once again <Stop> w Heat is available only in MUH-A07/A09/AYV and MXZ-A8/A6/A3WV.

9 SERVICE FUNCTIONS MSC-A07YV - E MSC-A09YV - E MSC-AYV - E 9-. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to page 5.) Set time : minute -second Set time : 3 minutes 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit of JPG and JPS.) 9-. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit. How to modify the remote controller P.C. board Remove batteries before modification. The board has a print as shown below : Remote controller model : KPA J J Remote controller model : KG3A J J NOTE :. For remodelling, take out the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.. Remote controller model KPA and KG3A are the same in terms of specification. The P.C. board has the print J and J. Solder J and J according to the number of indoor unit as shown in Table. After modification, press the RESET button. Table. unit. unit. 3 unit. 4 unit unit operation modification units operation Same as at left Solder J 3 units operation Same as at left Same as at left Solder J 4 units operation Same as at left Same as at left Same as at left Solder both J and J How to set the remote controller exclusively for particular indoor unit After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored. 7

9-3. REMOTE CONTROLLER (How to set the type) This remote controller setting needs to be switched according to the type of air conditioner (COOL & HEAT or COOL ONLY). If the setting is incorrect, the air conditioner does not operate normally. Therefore, check if the setting corresponds to the type of air conditioner. If not, correct the setting as shown below. Slide switch Type COOL & HEAT COOL ONLY The position of the slide switch 9-4. MU & MUX TYPE / MUH & MXZ TYPE SWITCH OVER AND AUTO RESTART FUNCTION. MU & MUX TYPE / MUH & MXZ TYPE SWITCH OVER The indoor units for MU & MUX type and MUH & MXZ type are common specifications. Set switch according to the type of outdoor unit. The units are set for MUH & MXZ type when they are shipped from the factory. SW- sets the AUTO RESTART FUNCTION ON / OFF. SW- switches over the MU & MUX type / MUH & MXZ type. When the units are shipped from the factory, SW is as follows. SW-: AUTO RESTART FUNCTION ON SW-: MUH & MXZ type } How to switch over MU & MUX TYPE / MUH & MXZ TYPE! Turn off the main power for the unit. @ Pull out the electronic control P.C. board, and change switch(sw-) on the indoor electronic control P.C. board according to the type of outdoor unit as following figures. TAB F L0 C CN0 CN CN0 FRONT MU & MUX type Set switch upside. MUH & MXZ type Set switch downside. IC0 CN CN5 CN SW SW SW SW SW. AUTO RESTART FUNCTION If a ground is incorrect, it may cause an electric shock. When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The AUTO RESTART FUNCTION sets to work the moment power has restored after power failure.then, the unit will restart automatically. However if the unit is operated in I FEEL CONTROL mode before power failure, the operation is not memorized. In I FEEL CONTROL mode, the operation is decided by the initial room temperature. AUTO RESTART FUNCTION is ON when the units are shipped from the factory. How to release AUTO RESTART FUNCTION! Turn off the main power for the unit. @ Pull out the electronic control P.C. board, and change switch(sw-) on the indoor electronic control P.C. board as following figures. AUTO RESTART FUNCTION ON Set switch downside. NOTE: If the indoor-outdoor connecting wire is incorrectly connected on the terminal block, the unit does not operate normally. AUTO RESTART FUNCTION OFF Set switch upside. SW SW Operation! If the main power (30V AC) has been cut, the operation settings remain. @ After the power is restored, the unit restarts automatically according to the memory. (However, it takes at least 3 minutes for the compressor to start running.) NOTE The operation settings are memorized when 0 seconds have passed after the remote controller was operated. If main power is cut while AUTO START/STOP timer is active, the timer setting is cancelled. If the unit has been off with the remote controller before power failure, the auto restart function does not work as the power button of the remote controller is off. To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the same time. When some air conditioners are connected to the same supply system, if they are operated before power failure, the starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding system that allows the units to start one by one. 8

HEAT /FAN / HEAT /FAN / 0 TROUBLESHOOTING MSC-A07YV - E MSC-A09YV - E MSC-AYV - E 0-. Cautions on troubleshooting. Before troubleshooting, check the following: ) Check the power supply voltage. ) Check the indoor/outdoor connecting wire for mis-wiring.. Take care the following during servicing. ) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug. ) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board. 3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires. Lead wiring Housing point 3. Troubleshooting procedure ) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work. ) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration. 3) When troubleshooting, refer to the flow chart on page 0 and the check table on page. 4. How to replace batteries Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally. Remove the front lid and insert batteries. Then reattach the front lid. Press the RESET button. Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct. RESET button NOTE : If the RESET button is not pressed, the remote controller may not operate correctly. NOTE : INFORMATION FOR MULTI SYSTEM AIR CONDITIONER (OUTDOOR UNIT : MXZ-A8WV- E MXZ-A6WV- E MXZ-A3WV- E ) Multi system air conditioner ( MXZ-A8WV- E MXZ-A6WV- E MXZ-A3WV- E ) can connect two or more indoor units with one outdoor unit. According to the capacity, two or more units can operate simultaneously. When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units that will start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode. Operation Indicator lighted When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 0 minutes) to blow out the warm air. In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it. 9 flashing

0-. Instruction of troubleshooting MSC-A07YV - E MSC-A09YV - E MSC-AYV - E Start Indoor unit operates. doesn't operate. Indoor unit operates. doesn't operate normally. Indoor unit doesn't receive the signal from remote controller. OPERATION INDICATOR lamp on the indoor unit is flashing on and off. Indoor unit operates. But indoor unit doesn't blow out cool air. operates in only Test Run operation. doesn't operate even in Test Run operation. doesn't stop even if indoor unit stops. Unit doesn't operate normal operation in COOL or HEAT mode. Indoor unit operates, when the EMERGENCY OPERATION switch is pressed. Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed. Check room temperature thermistor. Refer to "Test point diagram and voltage" on page 5. MUH-A07/A09/AYV MUX-A9/A0/A/ A5/A6WV Refer to "Check of outdoor unit". MU-A07/A09/AYV Check of wiring diagram of outdoor unit". MUH-A07/A09/AYV Refer to "Check of outdoor unit". MUH-A07/A09/AYV MXZ-A8/A6/A3WV Refer to "Check of R.V. coil" and others. Refer to B "Check of remote controller and receiver P.C. board" on page 3.. Check indoor / outdoor connecting wire.. Refer to C "Check of indoor electronic control P.C. board" on page 3. MUX-A0/A9/A0/ A/A5/A6WV Refer to "Check of indoor/outdoor units' connection and outdoor unit". MUH-A07/A09/AYV MXZ-A8/A6/A3WV Flash on and off at 0.5- second intervals Cause: Indoor/ Mis-wiring MUH-A07/A09/AYV MXZ-A8/A6/A3WV -time flash Cause: Outdoor / Indoor unit Trouble of serial signal -time flash Cause: Indoor unit Trouble of room temperature/ indoor coil thermistor 3-time flash Cause: Indoor unit Trouble of indoor fan motor MXZ type 5-time flash Cause: Outdoor power system abnormality 6-time flash Cause: Trouble of thermistor in outdoor unit 7-time flash Cause: Trouble of outdoor control system 0-time flash Cause: MXZ type Outdoor refrigerant system abnormality Refer to D "How to check mis-wiring and serial signal error (When outdoor unit doesn't work)" on page 4. W Check room temperature thermistor and indoor coil thermistor. Refer to "Test point diagram and voltage" on page 5. Refer to A "Check of indoor fan motor" on page. Refer to "Check of inverter/ compressor" and "Check of power supply". 0 MUH-A07/A09/AYV MXZ-A8/A6/A3WV Refer to "Check of outdoor thermistor" and others. MUH-A07/A09/AYV MXZ-A8/A6/A3WV Replace the deicer P.C. board and others. W.<The case of the trouble of the serial signal> When the power is turned off and then turned on again, the indication shows the trouble of mis-wiring. As for outdoor unit MU type, refer to service manual OB330. As for outdoor unit MUH type, refer to service manual OB33. As for outdoor unit MUX type, refer to service manual OB307 REVISED EDITION-A or OB38. As for outdoor unit MXZ type, refer to service manual OB39. MXZ type Refer to outdoor refrigerant system related items.

0-3. Troubleshooting check table The following indication does not depend on the shape of lamp. flashing Operation Indicator Flashing of the OPERATION INDICATOR lamp (on the left-hand side) indicates possible abnormalities. The OPERATION INDICATOR lamp (on the left-hand side) is lighting during normal operation. Before taking measures, make sure that the symptom reappears, for accurate troubleshooting. Self check table. Abnormal point MUH or MXZ type Mis-wiring MUH or MXZ type Serial signal 0.5-second ON 0.5-second OFF -time flash Operation indicator lamp Symptom Detection method Checkpoint.5-second OFF does not run. When serial signal stops for 4 to 5 seconds after st on of 5C relay by POWER turning on. When serial signal from outdoor unit stops for 4 to 5 seconds. Check switch SW-.(MU & MUX type or MUH & MXZ type) Check wiring (visual check and conductivity check). Check indoor electronic control P.C.board. Check outdoor DEICER P.C. board and others. Check electrical parts. Indoor coil thermistor Room temperature thermistor -time flash.5-second OFF does not run. Detect Indoor coil/room temperature thermistor short or open circuit every 8 seconds during operation. Check resistance of thermistor. Reconnect connector. Check indoor electronic control P.C.board. 3 4 5 6 Indoor fan motor MXZ type Outdoor power system MUH or MXZ type Defrost thermistor MUH or MXZ type Outdoor control system error 3-time flash.5-second OFF 5-time flash.5-second OFF 6-time flash.5-second OFF 7-time flash.5-second OFF Indoor fan motor repeats seconds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping. does not run. does not run. does not run. When rotational frequency feedback pulse signal is not emit during -second indoor fan operation. When the compressor operation is continuously three times interrupted by over current protection within minute after startup, it stops operation. When the defrost thermistor shorts or opens after the compressor start-up. When it cannot properly read data in the nonvolatile memory of outdoor electronic control P.C. board. Disconnect connector CN and then check connector CN -3 to make sure rotational frequency feedback signal of.5v or over exists. Check indoor electronic control P.C. board. Check indoor fan motor. Reconnect connector. Check the inverter output. Check the compressor. Check outdoor DEICER P.C. board and others. Check resistance of thermistor. Reconnect connector. Refer to service manual OB33 or OB39. Check outdoor DEICER P.C. board and others. Refer to service manual OB33 or OB39. 7 MXZ type Outdoor refrigerant system error 0-time flash.5-second OFF does not run. When the compressor operation has been interrupted by LEV protection continuously 5 minutes, the compressor stops operation. Refer to "Check of LEV". Check refrigerant circuit and refrigerant amount. Check outdoor electronic control P.C. board. Refer to service manual OB39. 8 MXZ type Operation mode setting Operation Indicator Lighted Flashing.5-second OFF operates but indoor unit does not run. When the operation mode of each indoor unit is differently set to COOL(includes DRY) and HEAT at same time, the operation mode of indoor unit that has operated at first has the priority. Unify the operation mode.

0-4. Trouble criterion of main parts MSC-A07YV - E MSC-A09YV - E MSC-AYV - E Part name Room temperature thermistor (RT) Indoor coil thermistor (RT) Check method and criterion Measure the resistance with a tester. (Part temperature 0 C ~ 30 C) rmal MSC-A07/A09/AYV 8kΩ ~ 0kΩ Abnormal Open or short-circuit Figure Measure the resistance between the terminals with a tester. (Coil wiring temperature0 C ~ 30 C) Indoor fan motor (MF) INNER FUSE 36i3 C CUT OFF Motor part Sensor part Color of lead wire WHT-BLK BLK-RED rmal MSC-A07/A09YV MSC-AYV 396 ~ 430Ω 303 ~ 39Ω 30 ~ 348Ω 87 ~ 3Ω Measure the voltage Power ON. Color of rmal lead wire MSC-A07/A09/AYV BRN-YLW YLW-GRY 4.5 ~ 5.5V (When fan revolved one time) 0V 5V 0V (Approx.) Abnormal Abnormal Open or short-circuit Remain 0V or 5V FUSE WHT RED BLK YLW GRY BRN Vane motor (MV) Measure the resistance between the terminals with a tester. (Part temperature0 C ~ 30 C) rmal MSC-A07/A09/AYV 40 ~ 60Ω Abnormal Open or short-circuit RED YLW BRN ORN ROTOR GRN When OPERATION INDICATOR lamp flashes 3-time. Indoor fan motor doesn t operate. A Check of indoor fan motor Turn OFF the power supply. Check connector CN visually. Reconnect the lead wires. Are lead wires connected? Is soldered point of the connector correctly soldered? Resolder it. Disconnect lead wires from connector CN on indoor electronic control P.C. board. Measure resistance between lead wires. and.5 and then.3 and.5. Is resistance 0 (short circuit) or (open circuit)? ( 0 or ) (others) Turn ON the power supply. Stop it if the unit operates. Insert screwdriver into air outlet to rotate indoor fan motor slowly for revolution or over, and measure voltage.(+) and.3(-) on CN. Repair or replace the indoor fan motor. Does voltage repeat 0V DC and 5V DC? Replace the indoor electronic control P.C. board.

Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn t operate with the remote controller. B Check of remote controller and receiver P.C. board wcheck the remote controller is exclusive for this air conditioner. Switch on the remote controller. Is LCD display on the remote controller displayed? (not clear) Replace the batteries. (Refer to page 9.) Remove batteries, then set them back and press the RESET button. Check if the unit operates with the remote controller. Does the unit operate with the remote controller? Turn on a radio to AM and press switch on the remote controller. OK Is noise heard from radio? Replace the remote controller. Are there any fluorescent lights of inverter or rapid-start type within the range of m? Reinstall the unit away from lights. Attach a filter on receiving part. Measure the voltage between receiver P.C. board connector CN30.3 ( ) and.5 (+) when the remote controller button is pressed. Is the voltage approx. 4V DC? (5V or 0V DC) Replace the power monitor, receiver P.C. board. Replace the indoor electronic control P.C. board. The unit doesn t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn t light up by pressing the EMERGENCY OPERATION switch. C Check of indoor electronic control P.C. board Check the both parts side and pattern side of indoor electronic control P.C. board visually. Turn OFF the power supply. Remove indoor fan motor connector CN and vane motor connector CN5 from the indoor electronic control P.C. board and turn ON the power supply. Does the unit operate with the remote controller? Does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch? Turn OFF the power supply. Replace the vane motor. Turn OFF the power supply. Replace the fuse. Is winding resistance of vane motor 0 "? Is winding resistance of fan motor 0 "? Replace the fan motor. Be sure to check both resistances. Is fuse (F) blown? Be sure to check both fuse and varistor in any case. Is varistor (NR) burnt? Replace the varistor. Replace the indoor electronic control P.C. board. 3

When OPERATION INDICATOR lamp flashes 0.5-second intervals or -time. does not operate. D How to check mis-wiring and serial signal error <MUH-A07/A09/AYV, MXZ-A8/A6/A3WV> Start Turn OFF the power supply(indoor/outdoor unit). w Set the switch(sw-) on indoor electronic control P.C. board to MU or MUX type, when the outdoor unit is MU or MUX type. If the setting is MUH or MXZ type, the unit does not work. w Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self-check to be displayed in 3 seconds. Make them sure. Is the outdoor unit "MUH" type? Turn ON the power supply(indoor/outdoor unit). Press once EMERGENCY OPERATION switch. 3 min. later, what self-check result is displayed on OPERATION INDICATOR lamp on indoor unit? w Is this mis-wiring, poor contact, or disconnection of wire? Mis-wiring is indicated. (0.5-sec. ON, 0.5-sec. OFF) Serial signal error is indicated. (0.5-sec. ON,.5-sec. OFF) Set the switch(sw-) on the indoor electronic control P.C. board to MU or MUX type. w Does the unit operate? Refer to the "Instruction of troubleshooting." OK. Turn OFF the power supply(indoor / outdoor unit) and disconnect indoor and outdoor connecting wire on indoor side.. Short-circuit between indoor terminal block N and 3. 3. Turn ON the power supply(indoor unit) and press once EMERGENCY OPERATION switch. Is there 0V DC between both ends of R3 on indoor electronic control P.C. board? ( By tester, the stylus is between 0 ~ 0V. ) Turn OFF the power supply(indoor unit). Connect ON indoor and outdoor connecting wire. Replace the indoor electronic control P.C. board. Turn ON the power supply(outdoor unit). Is there 30V AC between outdoor terminal block L-N (TB)? Check the outdoor power supply, power supply cord and connection. Is there 5V DC between J05 + J0 - on the deicer P.C. board? Turn ON the power supply(indoor unit). Replace the deicer P.C. board. During EMERGENCY OPERATION, is there 0V DC between both ends of R60? (By tester, the stylus is between 5 ~0V) Make the wiring between CN730 on the deicer P.C. board and outdoor terminal block correct. Replace the deicer P.C. board. As for outdoor unit MUH type, refer to service manual OB33. As for outdoor unit MXZ type, refer to service manual OB39. 4

TEST POINT DIAGRAM AND VOLTAGE MSC-A07YV - E MSC-A09YV - E MSC-AYV - E Indoor electronic control P.C. board Fuse 50V AC 3.5A } Indoor fan motor 30 V AC Varistor (NR) V DC { + -- } Power supply input 30 V AC R3 Indoor coil thermistor (RT) Room temperature thermistor (RT) Timer short mode } point JPG, JPS (Refer to page 7.) Emergency operation switch Power monitor, receiver P.C. board + -- } 5V DC SW (Refer to page 8.) sets the Auto restart function ON/ OFF. switches over MU&MUX type/ MUH & MXZ type. CN30 Indoor coil thermistor (RT) Room temperature thermistor (RT) 40 Resistance (k') 30 0 0 0 0 0 0 30 40 50 60 Temperature (;) 5

DISASSEMBLY INSTRUCTIONS <"Terminal with lock mechanism" Detaching points> In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to () and ()) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work. () Slide the sleeve and check if there is a locking lever or not. () The terminal with this connector is a terminal with lock mechanism Sleeve Locking lever Slide the sleeve. Pull the terminal while pushing the locking lever. Connector Hold the sleeve, and pull out the terminal slowly. MSC-A07YV - E MSC-A09YV - E MSC-AYV - INDOOR UNIT OPERATING PROCEDURE. Removing the front panel () Remove the screw caps of the front panel. Remove the screws. () Pull the panel down to your side slightly and unhook the catches at the top. E Photo PHOTOS Screws of the front panel. Removing the electronic control P.C. board and the power monitor, receiver P.C. board NOTE : In case of removing only indoor electronic control P.C. board, work (3) is not necessary. () Remove the front panel. (Refer to.) () Remove the power monitor, receiver P.C. board holder from the bottom of electrical box. (3) Open the power monitor, receiver P.C. board holder and remove the power monitor, receiver P.C. board. (4) Remove the screw of the electrical cover and the electrical cover. (5) Remove the screw of the V.A. clamp and the V.A. clamp. (6) Remove the screw of the cord clamp and the cord clamp. (7) Remove the screw of the terminal block. (8) Remove the screw of the ground wire. (9) Pull out indoor electronic control P.C. board slightly. (0) Disconnect all (except CN0) the connectors on the electronic control P.C. board. () Remove the electronic control P.C. board. () Disconnect the connector of power monitor, receiver P.C. board (CN0) on the electronic control P.C. board. Photo Screw of the ground wire Terminal block fixing screw Power monitor, receiver P.C. board holder Indoor electronic control P.C. board Cord clamp fixing screw Screw of the V.A. clamp Screw of the electrical cover 6

OPERATING PROCEDURE PHOTOS 3. Removing the electrical box () Remove the front panel. (Refer to.) () Remove the electrical cover. (Refer to.) (3) Remove the V.A. clamp. (Refer to.) (4) Remove the cord clamp. (Refer to.) (5) Remove the terminal block. (Refer to.) (6) Remove the screw of ground wire. (Refer to.) (7) Disconnect the connector of the indoor coil thermistor (CN), the fan motor connector (CN and CN) and the vane motor connector (CN5) on the electronic control P.C. board. (8) Remove the fan motor lead wire and indoor coil thermistor from the electrical box. (9) Remove the lead wire of vane motor from the bottom of electrical box. (0) Remove the screw fixing the electrical box, remove the electrical box. Photo 3 Indoor coil thermistor connector Fan motor connector Vane motor connector Screw of the electrical box 4. Removing the nozzle assembly and the vane motor () Remove the front panel. (Refer to.) () Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, remove the nozzle assembly. (4) Remove the screws of the vane motor, disconnect the vane motor connector. (5) Remove the vane motor. Photo 4 Screws of the vane motor 5. Removing the indoor fan motor and the line flow fan () Remove the front panel. (Refer to.) () Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, remove the nozzle assembly. (Refer to 4.) (4) Remove the screw of the lead cover and lead cover. (5) Release the hooks to open the motor band slightly. (6) Loosen the hexagon socket set screw from the line flow fan. (7) Remove the screws fixing the motor bed, remove the fan motor with motor band and the motor bed. (8) Remove the screws fixing the left side of the heat exchanger. (9) Lift the left side of the heat exchanger. (0) Remove the line flow fan. Photo 6 Hexagon socket set screw Photo 5 Photo 7 Drain hose Screws of the left side of the heat exchanger Screw of the lead cover Hooks of the motor band 7 Screws of the motor bed

PARTS LIST MSC-A07YV - MSC-A09YV - MSC-AYV - E E E (WH) (WH) (WH) -. INDOOR UNIT STRUCTURAL PARTS (W) 9 (W) -. ACCESSORY AND REMOTE CONTROLLER 0 8 3 4 7 (See page 30.) 5 6 (W) (W) These figures show about MSC-AYV. -. INDOOR UNIT STRUCTURAL PARTS 3 4 5 6 7 8 9 E0 749 34 E0 75 34 E0 89 000 E0 749 067 E0 89 00 E0 408 4 E0 763 00 E0 764 00 E0 749 975 E0 408 970 E0 75 970 BOX(WH) BOX(WH) PANEL ASSEMBLY(WH) SCREW CAP(WH) FRONT PANEL(WH) CATCH CATECHIN AIR FILTER CATECHIN AIR FILTER AIR CLEANING FILTER CORNER BOX (RIGHT) INSTALLATION PLATE INSTALLATION PLATE Q'ty/unit Symbol. Part. Part Name in Wiring MSC-A07YV- Diagram E (WH) MSC-A09YV- E (WH) MSC-AYV- E (WH) Remarks Including.3,4,5 PCS/SET PCS/SET MAC-300FT -. ACCESSORY AND REMOTE CONTROLLER 0 E0 749 46 E0 57 083 REMOTE CONTROLLER REMOTE CONTROLLER HOLDER 8

MSC-A07YV - E (WH) MSC-A09YV - E (WH) MSC-AYV - E (WH) -3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS SLEEVE BEARING 3 4 5 9 8 7 6 3 4 5 ROOM TEMPERATURE THERMISTOR -4. INDOOR UNIT HEAT EXCHANGER (W) 3 FUSE 6 VARISTOR 7 8 9 0 (W) This figure shows about MSC-AYV. -3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS Part number that is circled is not shown in the illustration.. 3 4 5 6 7 8 9 0 3 4 5 6 7 8 9 0 Part. E0 00 504 E0 66 70 E0 749 35 E0 749 040 E0 749 04 E0 7 38 E0 89 385 E0 763 034 E0 749 468 E0 89 45 E0 830 45 E0 83 45 E0 749 303 E0 5 308 E0 749 300 E0 75 300 E0 749 333 E0 69 375 E0 665 505 E0 5 505 E0 749 307 E0 749 30 E0 408 509 E0 75 509 E0 749 385 Part Name SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBLY(WH) VANE UPPER (WH) VANE LOWER (WH) FUSE VARISTOR VANE CRANK SET POWER MONITOR, RECEIVER P.C. BOARD ELECTRONIC CONTROL P.C.BOARD ELECTRONIC CONTROL P.C.BOARD ELECTRONIC CONTROL P.C.BOARD VANE MOTOR ROOM TEMPERATURE THERMISTOR INDOOR FAN MOTOR INDOOR FAN MOTOR MOTOR BAND TERMINAL BLOCK FAN MOTOR RUBBER MOUNT FAN MOTOR RUBBER MOUNT INDOOR COIL THERMISTOR LINE FLOW FAN BEARING MOUNT BEARING MOUNT VARISTOR Symbol in Wiring Diagram F NR MV RT MF MF TB RT NR RC4V9- RC4V9- MSC-A07YV- E (WH) Q'ty/unit MSC-A09YV- E (WH) MSC-AYV- E (WH) Remarks 3.5A AUTO RESTART AUTO RESTART AUTO RESTART PCS/SET PCS/SET -4. INDOOR UNIT HEAT EXCHANGER 3 E0 749 60 E0 75 60 E0 5 666 E0 55 666 E0 5 667 INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION(GAS) UNION(GAS) UNION(LIQUID) {9.5 {.7 {6.35 9