SUBJECT: ASSESSMENT FOR INTERNAL SURFACE FINISHES OF LIGHTBETON PANEL FOR COMPLIANCE WITH THE NEW ZEALAND BUILDING CODE(NZBC)

Similar documents
Classification report

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Dear Customer. Please find attached the January 2017 amendments to C/AS4 Acceptable Solution for Buildings with. Innovation and Employment.

Test Report: ICL/CR15/11/087

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

MEDIUM-DENSITY HOUSING # 7. Fire safety

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION REPORT

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

Additional Reaction to Fire Classification Report

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Dear Customer. Please find attached the January 2017 amendments to C/AS2 Acceptable Solution for Buildings. and Employment.

BCTC CARPET TECHNICAL CENTRE

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Dear Customer. Please find attached the January 2017 amendments to C/AS3 Acceptable Solution for Buildings. Innovation and Employment.

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

REVIEW ON TWO PERFORMANCE-BASED TESTS FOR ASSESSING FLAME SPREAD IN HONG KONG

SBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Centrum stavebního inženýrství a.s.

Abrasion Resistance of Fluoropolymer and polyester Coatings

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

DVS HOME VENTILATION SYSTEMS. Product. Scope. Building Regulations. Technical Specification. Appraisal No. 375 [2014]

Reaction to fire classification report No C

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

Centrum stavebního inženýrství a.s.

Additional reaction to fire classification report No H

Reaction to fire classification report No C-rev.1

CERTIFICATE OF APPROVAL No ME 5085

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation

BUILDING FIRE SAFETY AND HAZARD ASSESSMENT METHODS FOR COMBUSTIBLE SURFACE FINISHES C.A. WADE

Analysis Report

ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

2.2 Factors in design

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Fire Safety Fire Resistant Building Components

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

Contact person Date Reference Page Richard Johansson P (2) Fire Research

Classification of Fire Performance of Wall and Ceiling Lining Materials

Commentary. for Building Code Clauses C1 C6 and Verification Method C/VM2

CLASSIFICATION IN REGARD OF REACTION TO FIRE according to EN :2007

Facts about insulation and fires 29 October 2014

REACTION TO FIRE TESTS FOR BUILDING PRODUCTS DETERMINATION OF THE HEAT OF COMBUSTION ACCORDING TO STN EN ISO 1716: 2003

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

Practice Advisory 18: Fire safety design for tall buildings

New European Fire Testing Classification for Construction Products

Reaction to fire testing of Vescom vinyl wall covering with a Fibre Structure, a total weight of 550 g/m 2 according to EN 13823:2002

BS EN ISO : 2010

PUBLIC SUMMARY REPORT OF THE EGOLF EN 13823

TFI Report Classification

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

Form: KSD-100:10 Page 1 of 3

Loss Prevention Standard

Construction Products Regulation (CPR) and cables. British Cables Association Guidance to Specifiers

C/VM1 Verification Method for Solid Fuel Appliances

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F

CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE

ISO INTERNATIONAL STANDARD

New European Cable Testing and Classification

Analysis Report

Guidance Note. 3. Fire Propagation and flame Flame Spread in in Powder Coatings. Abrasion Resistance of Fluoropolymer and polyester Coatings

BS EN ISO : 2010

CERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC

Appendix A: US Fire Statistics Tables

Large-scale fire test for interior materials of the Korean high speed train

Are Your Kitchen Hood Filters Compliant?

BS EN : 2001 & IEC :2000

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Belcom Cable excellence engineered through quality. CPR Construction Products Regulation

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

+ = FIRE LABORATORY INTRODUCTION. APPLUS+ LGAI - Our company history. High Technology Knowledge. Customer Confidence. Branding

DELTA Classification Report

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

Draft for Comment Please comments to Part A(i)

CERTIFICATE OF APPROVAL No CF 5635 P3 SRL

IMO Resolution MSC 61(67): Annex 1: Part 2

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

STS Directory Accreditation number: STS 0030

Transcription:

07 th May 2018 Ref: /jobs/18039 Light Beton Panel compliance.doc Plytech International Ltd 23 Business Parade North Highbrook Auckland 2013 Email: craig.f@plytech.co.nz Attention: Craig Floyd SUBJECT: ASSESSMENT FOR INTERNAL SURFACE FINISHES OF LIGHTBETON PANEL FOR COMPLIANCE WITH THE NEW ZEALAND BUILDING CODE(NZBC) Dear Craig Thank you for your request to provide advice on the compliance with the New Zealand Building Code for internal surface finishes requirements of the following LightBeton Panels. 19mm thick LightBeton MDF panel consisting of a 16mm thick FR MDF core and covering surface of 2mm to 2.7mm thick concrete overlay in Classic Grey and Classic White colors. 18mm thick LightBeton mineral sandwich panel consisting of 2mm thick concrete layer, backed with 3mm thick mineral board, 10mm particle board and 3mm thick mineral board in Cassic Grey, Urban Grey, Classic White and Anthracite colours. Product Description A LightBeton panel consists of a 2mm thick concrete surface layer which can be applied to various panel substrates. According to the LightBeton brochure, LightBeton panels are backed with either fibre glass, polypropylene honeycomb or MDF panels. However our assessment has only been carried out for following products which have test data supplied. 19mm thick LightBeton FR MDF panel consisting of a 16mm thick FR MDF core and covering surface of 2mm to 2.7mm thick concrete overlay with Classic Grey and Classic White colours.

LightBeton FR MDF Panel 18mm thick LightBeton mineral sandwich panel consisting of 2mm thick LightBeton surface covering, backed with 3mm thick mineral board, 10mm particle board and 3mm thick mineral board. The 3mm thick mineral board(density 960kg/m3) has magnesium oxide base which is cement bound and fibre reinforced before it is bonded to a 10mm thick particle board.

New Zealand Building Code Compliance The building code C3.4a states The internal surface finishes for walls and ceilings are tested to assess the risk of the spread of flame across the surface using one of two methods which enables a material Group Number between 1 and 4 to be assigned to the material and demonstrate compliance with the Table above. A postscript S can also be provided which denotes that the smoke production also needs to be considered. The first method is the ISO9705 (full scale room corner-test) and assigned a Group Number between 1 to 4 (least to most combustible). The second method is using the ISO5660 (bench scale fire test on a small sample of material) with the input parameters and method of calculating the Material Group Number given in Appendix A of C/VM2.

There is also an overview provided by MBIE (Ministry of Business Innovation and Employment NZ) website for comparing Group numbers in New Zealand to Australian and European test standards. https://www.building.govt.nz/building-code-compliance/c-protection-from-fire/c-clauses-c1- c6/surface-finishes/overview/ In Europe, the risk of the spread of flame across the surface finish of the materials are assessed using the methods specified in the EN13501-1:2007+A1:2009 standard. The classification levels are A1, A2, B, C, D, E and F, from least to most combustible. The Single Burning Item (SBI) as described in EN 13501-1:2007+A1:2009 is a test method for determining the reaction to fire behaviour of building products when exposed to the thermal attack by a propane burner. The results of this test, using a Fire Growth Rate (FIGRA ratio) have been correlated by MBIE to the ISO 9705 Group Numbers and the requirements of NZBC Clause 3.4(a) in the same manner as the ISO 5660 cone calorimeter test. Compliance can also be demonstrated using Table C1 of Acceptable Solution (C/ASx) for materials with Australian and European classification without the need for the further testing. LightBeton Panel Testing Results and Discussion The classification report defines the classification assigned to the products in accordance with the procedures given in the standard EN13501-1:2007+A1:2009: Fire Classification of Construction Products and Building Elements Part 1: classification using data from reaction to fire tests. Based on Classification Report No. 2015-1724-K1 issued 16.07.2015, the classification of 19mm overall thickness LightBeton Classic Grey and Classic White panels with 16mm FR MDF backing and 2mm thick LightBeton finishing is ranked as Class B related to its behavior in case of fire and Class s1 for smoke development. This corresponds to the most onerous requirement which is Group Number 1S (C/ASx Table C1) therefore this product complies with the Group Number 1S requirements. LightBeton finishing can also be fixed on timber, plywood or particleboard with a minimum thickness of 12mm or more as it has already been tested on 16mm FR MDF board in accordance with NZBC C/VM2 Table A2.

Based on Classification Report No. P172579, Issue No. DE/4 dated 02/10/2017, the classification of 18mm thick LightBeton mineral sandwich panel consisting of 2mm thick LightBeton finishing, 3mm mineral board, 10mm particle board and 3mm mineral board is ranked into Class B related to its behavior in case of fire and Class s1 for smoke development. This corresponds to the most onerous requirement which is Group Number 1S (C/ASx Table C1) therefore this product complies with the Group Number 1S requirements. Conclusion The spread of fire over internal surface finishes for walls and ceilings consisting of 19mm overall thickness LightBeton FR MDF panel and 18mm overall thickness LightBeton mineral sandwich panel is Class B and Class S1 for behavior in case of fire and smoke respectively based on the classification reports which corresponds to Group Number 1S (C/ASx Table C1) therefore these products will comply with the building code C3.4a if the installation is carried out in accordance with the manufacturer s instructions. DISCLAIMER 1. This report is based on the following documentation supplied by Plytech International Ltd. Classification Report No. 2015-1724-K1 issued 16.07.2015 Classification Report No. P172579, Issue No. DE/4 dated 02/10/2017 2. This opinion represents the views of Origin Fire Consultants. 3. If a more authoritative opinion is required, then this would have to be obtained from a recognised testing laboratory. 4. This report does not relieve other designers and consenting authorities to assess the relevance of this report to the particular building project. Prepared by: Sajeesh Nair PG Cert. (Fire), MSc. (Electronics)

Checked by: Michael James CPEng, MIPENZ(Mech, Fire), ME (Fire), BE (MECH), NZCE (HVAC) Auckland Council Producer statement author number 2046