Title 24, Part 6 Certification of Economizer Fault Detection and Diagnostics (FDD)

Similar documents
DUCT LEAKAGE (Page 1 of 3)

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE

Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards 2013 Residential Compliance June 2014

City of Reedley Community Development Department 1733 Ninth Street Reedley, CA (559) FAX

Residential Water Heater Alteration or Replacement Requirement Per the 2016 California Energy Code (CEC)

SBEC Residential Energy Efficiency Rebate Programs for New Homes

Rain garden and native planting area registration forms

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS

RULEBOOK ON ELECTROMAGNETIC COMPATIBILITY

SBEC Residential Energy Efficiency 2019 Rebate Programs for New Homes

SBEC Residential Energy Efficiency 2019 Rebate Programs for Existing Homes

Claim Form. Watts Water Heater and FloodSafe Connectors ATTENTION WATTS WATER HEATER AND FLOODSAFE CONNECTOR OWNERS:

Record of Amendments. Version Date Amendment Section/page affected

Official Journal of the European Union. (Non-legislative acts) REGULATIONS

HERS Verified Single Dwelling Unit Hot Water System Distribution (Page 1 of 6)

PQS Independent type-testing protocol

Single Dwelling Unit Hot Water System Distribution Project Name: Enforcement Agency: Permit Number:

C-NRPP Quality Assurance Guidance for Radon Test Devices

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

DEPARTMENT OF THE ARMY TECHNICAL MANUAL (FSN ) This copy is a reprint which includes current pages from Changes 1 through 3.

IE Code IE Competency Title Credit OAC Ref.

Fire Permit Application

DEPARTMENT OF THE ARMY TECHNICAL MANUAL

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Bold items are particular to the City of Euless

Article 3: Police Regulated Occupations and Businesses. Division 37: Burglary, Robbery and Emergency Alarm Systems

TITLE: Ice-lined Refrigerator or Combined Refrigerator-Icepack Freezer, Compression Specification reference:

Part 2-55: Medical electrical equipment. Particular requirements for the basic safety and essential performance of respiratory gas monitors

CONFORMITY ASSESSMENT GUIDELINES. Version 1.0

The New EMC Directive 2004/108/EC

Operating Letter. Operating Letter #730 January 1, 2014 WARRANTY AND TECHNICAL SERVICE

MGN 453 (M) Maritime and Coastguard Agency Logo MARINE GUIDANCE NOTE

ECONOMIZER CONTROLLER ET-858

Under Section 608 of the CAA, EPA has established regulations (40 CFR Part 82, Subpart F) that:

PQS Quality Assurance protocol. TITLE: Cold Room/Freezer Room:

The New EMC Directive 2004/108/EC

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS

This document is a preview generated by EVS

Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU

Co-ordination of the Group of Notified Bodies for the Construction Products /Regulation 305/2011/EU

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator

City of Duluth Festival Center 04/25

Tennessee Code/TITLE 62 PROFESSIONS, BUSINESSES AND TRADES/CHAPTER 32 FIRE PROTECTION/PART 1 FIRE PROTECTION SPRINKLER SYSTEMS

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

Ohio Department of Health, Bureau of Environmental Health and Radiation Protection, Radon Licensing Program. School Radon Testing Checklist

FULL AND LEGAL NAME OF CORPORATE ENTITY

Guidance Note No 21/1. CE Marking Windows and doorsets to BS EN 16034

DATE: CHECK AMOUNT: CHECK NUMBER: RENEWAL APPLICATION. COMPANY CERTIFICATE OF REGISTRATION And INDIVIDUAL LICENSE RENEWAL

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

SECTION AUTOMATIC TRANSFER SWITCHES

BID PROPOSAL-REVISED

REBATE. Ductless Mini-Split Heat Pump

American National Standard for Electrical Lamp Bases Specifications for Bases (Caps) for Electric Lamps

OPERATING INSTRUCTIONS 2-1 OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) 2-5 OPERATOR TROUBLESHOOTING 3-1

GNB-CPR Position Paper: Issuance of certificates under CPR

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Templates for Maintenance Documents

NEMA Standards Publication SB Fire Service Annunciator and Interface

MONTGOMERY COUNTY RULES GOVERNING ALARMS SECTION 1. PURPOSE SECTION 2. DEFINITIONS

Union County Vocational - Technical Schools Scotch Plains, New Jersey

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

Oracle Retail Merchandising System Release Notes Release 12.0 May 2006

(Inspector) Scott Ullrich Mailing Address (if Different from Business Location): Address. (FIRE) David Topping City State Zip

Issue Update: Revised Recommended Language for Verification Contracts and Statements for Recycling Appliances and Vehicles

FOR THE PERIOD JANUARY 1, TO DECEMBER 31, GENERAL INFORMATION

Massachusetts COOL SMART

2013 Building Energy Efficiency Standards Workshop

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

Application Information

TECHNICAL COMMITTEE ON FIRE PUMPS

Water Heater Innovations Marathon Water Heater Limited Warranty Policies & Procedures

HVAC Controls Upgrades: Requirement Details ( )

BOARD OF EXAMINERS OF LANDSCAPE ARCHITECTS

HazLoc Essential Guides:

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

Reacti-Therm I and III Heating Modules

SUPPLEMENTARY REGULATIONS SPECIFIC TO CERTIFICATION OF PERSONAL PROTECTIVE EQUIPMENT (PPE)

DIRECTIVE NO: D-B

The Danish Energy Agency will carry out inspections in June 2013

STAFF REPORT TO THE CITY COUNCIL. Conduct Public Hearing to vacate certain public right of way adjacent to Sycamore Avenue and San Pablo Avenue

CERTIFICATION MANUAL FOR NF PROGRAMMES MANAGED BY EUROVENT CERTITA CERTIFICATION: GENERAL PROVISIONS

ANN ARBOR CITY NOTICE ORDINANCE NO. ORD ALARM SYSTEMS

CE marking & your legal obligations

Global Water Instrumentation, Inc.

SECTION AUTOMATIC TRANSFER SWITCHES

PIKES PEAK REGIONAL BUILDING DEPARTMENT Fire Alarm Contractor License Application

CONTENTS AUTOMATIC TRANSFER SWITCHES

48TF GAS HEATING/ ELECTRIC COOLING UNITS

NEMA Standards Publication ICS (R 2007) Adjustable Speed Electrical Power Drive Systems

PROCEDURES FOR APPROVAL OF LIFE-SAVING APPLIANCES AND FIRE SAFETY SYSTEMS, EQUIPMENT AND PRODUCTS

Loss Prevention Standard

Compatibility between Smoke Alarms and Arc-Fault Circuit Interrupters

ALABAMA Propane Gas Association

STATEMENT OF THE HEALTH AND SAFETY STRATEGY FOR THE SYDNEY RUSSELL SCHOOL

Council Directive 93/68/EEC of 22 July 1993 amending Directives

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

Transcription:

Title 24, Part 6 Certification of Economizer Fault Detection and Diagnostics (FDD) Title 24, Part 6 Section 120.2(i) requires that economizer FDD functions be installed on air cooled unitary air conditioning systems over 4.5 tons cooling capacity, with the ability to detect the faults specified in Section 120.2(i). Each air conditioning system manufacturer, controls supplier, or FDD supplier wishing to certify that their FDD analytics conform to the FDD requirements of Title 24, Part 6 may do so in a written declaration. This requires that a letter be sent to the California Energy Commission declaring that the FDD conforms to Title 24, Part 6 Section 120.2(i). The declaration at the end of this document could be used to submit to the California Energy Commission. Guidance on information that may be included with the Declaration The air conditioning system manufacturer, controls supplier, or FDD supplier provides evidence as shown below: a. The following temperature sensors are permanently installed to monitor system operation: i. Outside air ii. Supply air iii. Return air, when required for differential economizer operation. Evidence: Photograph or schematic of all required sensors indicating their recommended mounting instructions. b. Temperature sensors have an accuracy of ±2 F over the range of 40 F to 80 F Evidence: Photocopy of sensor specification c. When refrigerant pressure sensors are used, they have an accuracy of ±3 percent of full scale Evidence: Photocopy of sensor specification d. The controller is capable of providing system status by indicating the following: i. Free cooling available ii. Economizer enabled iii. Compressor enabled iv. Heating enabled v. Mixed air low limit cycle active vi. The current value of each sensor Evidence: Laboratory test: describe how the mode is simulated and the wording used to indicate the status. e. The unit controller is capable of manually initiating each operating mode so that the operation of compressors, economizers, fans, and heating system can be independently tested and verified. Evidence: Photocopy of controller manual showing instructions for manually initiating each operating mode. 1

f. The unit control is capable of reporting faults to a fault management application accessible by day to day operating or service personnel, or annunciated locally on zone thermostats Evidence: Supplier s description of how they comply, and supporting documentation such as a photocopy of controller manual or photograph of fault management application or zone thermostat, showing indication of a fault. g. The unit control is capable of detecting the following faults: i. Air temperature sensor failure/fault ii. Not economizing when it should iii. Economizing when it should not iv. Damper not modulating v. Excess outdoor air Guidance on Fault Detection Test Specifications To provide evidence that the required faults are detected by the FDD functionality, the FDD Provider could perform a No Fault and Fault test for each of the tests in Table 1. A pre defined Test Procedure such as the one provided in the example shown in Table 2 could be used to fill out Table 1. Table 1 Sample of a completed fault test Faults Tests Air temperature sensor failure/fault Not Economizing when it should Economizing when it Should not Damper not modulating 1. Damper is Stuck Open X X X 2. Damper Stuck at Minimum X X 3. Bad or Unplugged Actuator X X X 4. Sensor Hard Failure X X X X 5. Actuator Mechanically X X X X Disconnected Excess outdoor air Guidance for Reporting of Test Results The results of each test could be provided in a report with a cover letter using a standard test results reporting format that provides the following information for each test: a. Organization and individual conducting the test b. Time, Date, and Location of test c. Make and model of unit/control tested d. Range of models represented by test e. Test procedure used, including description of the method for imposing fault with repeatability 2

f. Test driving Conditions (outdoor air temperature, return air temperature or enthalpy as required by the type of high limit control being used) g. Results of the test: Which alarms were generated? h. Provide a bill of materials for the configuration that is being certified. i. The FDD supplier shall describe any special field or data verifications that are required for the particular FDD analytics (beyond those included in Acceptance Test requirements). j. Sample of documentation that would accompany each qualifying set of FDD analytics. k. Name and contact information of company personnel in charge of certification l. A mapping from the manufacturer s alarm description to what is required by Title 24 similar to Table 1. Table 2 Sample Test Procedure Step Description Purpose 1 Close the economizer damper fresh air blades, then secure the blades in a manner that prevents opening. when Damper Stuck at Minimum 2 Simulate conditions such that the damper actuator attempts to open the fresh air blades. Verify the damper blades remains secured and that the fault(s) specified in Table 1 are detected. Record the annunciated fault(s) and fault text. 3 Release the blades and allow the economizer damper to modulate open. Verify the annunciated fault(s) have cleared. 4 Open fully the economizer damper fresh air blades, then secure the blades in a manner that prevents closing. 5 Simulate conditions such that the damper actuator attempts to modulate the fresh air blade closed. Verify the damper remains secured and that the fault(s) specified in Table 2 are detected. Record the annunciated fault(s) and fault text. 6 Release the blades and allow the economizer damper to modulate. Verify the annunciated fault(s) have cleared. 7 Disconnect 1 sensor and verify the fault(s) specified in Table 1 are detected. Record the annunciated fault(s) and fault text. 8 Reconnect the sensor and verify that the annunciated fault(s) have cleared. 9 Repeat steps 7 8 for each available sensor. 10 Electrically disconnect the damper actuator and verify the fault(s) specified in Table 1 are detected. Record annunciated fault(s) and fault text. 11 Reconnect the damper actuator. Verify the fault(s) have cleared and normal economizer operation has resumed. 12 Mechanically disconnect the damper actuator from the damper blade assembly. when Damper is Stuck Open when Sensor Hard Failure when Bad or Unplugged Actuator when Actuator Disconnected 3

13 Simulate conditions such that the damper actuator would be moving the damper blades. Verify the fault(s) specified in Table 2 are detected. Record annunciated fault(s) and fault text. 14 Reconnect the damper actuator to the damper blade assembly. Verify the fault(s) have cleared and normal economizer operation has resumed. 15 Simulate conditions necessary to generate system status of Free cooling available. Record text of annunciated status. 16 Simulate system conditions necessary to generate system status of Economizer enabled. Record text of annunciated status. 17 Simulate system conditions necessary to generate system status of Compressor enabled. Record text of annunciated status. 18 Simulate system conditions necessary to generate system status of Heating enabled. Record text of annunciated status. 19 Simulate system conditions necessary to generate system status of Mixed air low limit cycle active. Record text of annunciated status. Test for System Status Capability Certification a. Send declarations, and on a voluntary basis evidence of functionality or test reports to: Attn: FDD Certification Building Standards Development Office California Energy Commission 1516 Ninth St., MS 37 Sacramento, CA 95814 4

Consistent with the requirements of Title 24 Sections 100.0(h) and 120.2(i), companies wishing to certify to the California Energy Commission shall execute a requirement under penalty of perjury attesting that all information provided is true, complete, accurate, and in compliance with the applicable provisions of Title 6. Companies may fulfill this requirement by providing the information and signing the declaration below. When providing the information below, be sure to enter complete mailing addresses, including postal/zip codes. Certifying Company Contact Person Name * Phone 1 Certifying Company Name ** Phone 2 Address Fax E mail Company Website (URL) * If the contact person named above is NOT the person whose signature is on the Declaration, then the full contact information for the person whose signature is on the Declaration must also be provided on a separate page. ** If the company named above is: A) a parent entity filing on behalf of a subsidiary entity; B) a subsidiary entity filing on behalf of a parent entity; or C) an affiliate entity filing on behalf of an affiliate entity, the above contact information must be provided for any additional entities on a separate page. Manufacturer (if different from Certifying Company) Contact Person Name Phone 1 Manufacturing Company Name Phone 2 Address Fax E mail Company Website (URL) Declaration I declare under penalty of perjury under the laws of the State of California that: (1) all the information in this statement is true, complete, accurate, and in compliance with all applicable provisions of Section 120.2(i) of Title 24, Part 6 of the California Code of Regulations; (2) each Fault Detection and Diagnostic (FDD) system has been tested in accordance with all applicable requirements of Section 120.2(i)1 120.2(i)8 of Title 24, Part 6 of the California Code of Regulations; (3) [if the party submitting this statement is a corporation, partnership, or other business entity] I am authorized to make this declaration, and to file this statement, on behalf of the company named below. Certifying Company Name Date Name/Title (please print) Signature 5