CSAGV 27 / 80. GROUPE FRIGORIFIQUE A CONDENSATION PAR AIR HELICOÏDE Fluide réfrigérant R 407 C

Similar documents
M2Z M NOTICE D INSTALLATION INSTALLATION INSTRUCTION MANUALE D INSTALLAZIONE MANUAL DE INSTALACIÓN AUFSTELLUNGS- HANDBUCH INSTRUÇÕES DE INSTALAÇÃO

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

K 60 D 070 Z KIT RÉGULATION SYSTÈME POUR POMPE À CHALEUR INVERTER AVEC CHAUFFAGE D APPOINT ÉLECTRIQUE

AOF CLIMATISEUR MONOBLOC A CONDENSATION A EAU SINGLE PACKAGED ROOM AIR CONDITIONER WITH WATER COOLED CONDENSER

PHRT 9 / 18 PHRT 12 PHRT 16 PHRT 18. Pompe à chaleur avec équipement hydraulique - Fluide réfrigérant R 410 A

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHT 13 / 16. Pompe à chaleur haute température avec équipement hydraulique (chauffage seulement) - Fluide réfrigérant R 407 C

Instructions for installation

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

K 60 D 066 Z KIT RÉGULATION POUR POMPE À CHALEUR EN RELÈVE DE CHAUDIÈRE APPLICATION 1 ZONE RADIATEURS / ACTION TOUT OU RIEN

This air conditioner uses the new refrigerant R410A.

K 60 D 067 Z KIT RÉGULATION POUR POMPE À CHALEUR EN RELÈVE DE CHAUDIÈRE APPLICATION 1 ZONE RADIATEURS OU PLANCHER - ACTION PROPORTIONNELLE

CENTRIFUGAL AIR CONDENSERS

Condensing Unit Installation and Operating Instructions

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

STARBOX - CONDENSER UNITS

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

HT V2 HT Split

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

This chapter is devided into two sections:

High temperature air-to-water heat pumps

CONDENCIAT CD. Condensing units. Quiet operation Low speed fans All year round operation USE. Cooling capacity : 25 to 165 kw.

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

Installation Instructions

Aquaciat Free cooling

Installation and maintenance condensing unit manual

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT HVAC MAINTENANCE TECHNOLOGY. Test Code: 5937 Version: 01

Service Step by Step Trouble-Shooting Check-List

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

PDF Created with deskpdf PDF Writer - Trial ::

power Describe the purpose of lockout/tag-out devices Demonstrate use of lockout/tagout

ECOCIAT. Domestic hot water heat recovery unit. Use. Range

04/ EDPAC025FAA - EDPAC035FAA - EDPAC045FAA - EDPAC037FAA - EDPAC057FAA -EDPAC067FAA

ACTIVA SERIES ROOF TOP Air Conditioners 017/040

Ductless Split Air Conditioner

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

Air Conditioning Operation and Troubleshooting Matt Dunham

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI

Caresaver Universal Refrigerant Recovery Unit

POWER PACKS FOR SUB-CRITICAL CASCADE R744 APPLICATIONS RECIPROCATING ACCESSIBLE-HERMETIC OCTAGON COMPRESSORS

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

Installation Instructions

Ventilation and air conditioning QUALITY FOR LIFE. Refrigerating systems and heat pumps. Operating manual

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

General safety precautions English

Condensing Unit Installation and Operating Instructions

General safety precautions English

Installation Manual. Instrucciones de instalación y manual de usuario 1

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA

Installation Instructions

R100 Oil-Less Refrigerant Recovery Unit

Refrigerant Recovery Machine. Model No Operating Manual

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

Installation Operation Maintenance

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

INSTRUCTIONS P01-A Danfoss Commercial Compressors March 2006

Installation Instructions

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Installation Instructions

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

SECTION AIR COILS

INSTALLATION INSTRUCTIONS

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS

Installation instructions Danfoss heat pump DHP-R

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

CPF PRODUCT DESCRIPTION

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

APPLICATION DATA SHEET

1. Information before installation General terms of delivery, storage and transport

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

HVACR Refrigeration

Installation Operation Maintenance

Installation Instructions

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

CONTENTS. 1.1 General terms of delivery Voltage Water treatment... 2

CONDENSING UNITS AIR COOLED CONDENSER. COOLING ONLY

Series 6, Vertical Floor-Mount Units

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Installation Instructions

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Horizontal/Side Discharge Condensing Units

Technology for Vacuum Systems. Instructions for use

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

Be sustainable while protecting your business

Transcription:

(Etiquette signalétique) NOTICE D INSTALLATION INSTALLATION INSTRUCTION MANUALE D INSTALLAZIONE MANUAL DE INSTALACIÓN AUFSTELLUNGS- HANDBUCH F I E D CSAGV 27 / 80 GROUPE FRIGORIFIQUE A CONDENSATION PAR AIR HELICOÏDE Fluide réfrigérant R 407 C AIR COOLED CONDENSING UNIT WITH AXIAL FAN R 407 C refrigerant GRUPPO MOTOCONDENSANTE A CONDENSAZIONE AD ARIA Fluido refrigerante R 407 C GRUPO FRIGORÍFICO CONDENSACIÓN POR AIRE VENTILACIÓN AXIAL Fluido refrigerante R 407 C KÜHLAGGREGAT MIT AXIALLUFTKONDENSATION Kältemittel R 407 C Octobre 2007 10 11 368 - F..I.E.D - 03

MARKING This product marked conforms to the essential requirements of the Directives: - Low voltage No. 2006/95/EC. - Electromagnetic Compatibility no. 89/336 EEC, modified 92/31 and 93/68 EEC. - Pressure Equipment Directive No. 97/23/EC. SUMMARY 1 - General............................................. 2 2 - Dimensions and weight................................. 3 3 - Installation........................................... 4 4 - Connections......................................... 4 5 - Operating features.................................... 6 6 - Accessories.......................................... 7 7 - Starting............................................. 7 8 - Maintenance......................................... 8 9 - Start-up data sheet.................................... 9 R 407 C Fluid R 407 C, as opposed to R22, is not a pure fluid but a blend composed of: - 23% R 32 + 25% R 125 + 52% R 134 A. The compressors approved for operation with this fluid are filled beforehand with polyalcohol oil. Contrary to mineral oil, it is very hygroscopic: it absorbs the humidity of the ambient air very quickly. This can modify its lubricant properties and lead in time to the destruction of the compressor. MAINTENANCE INSTRUCTIONS 1 - Never add oil to the appliance; the compressor is filled with polyalcohol oil, a special oil which cannot tolerate the presence of other oils. 2 - The instruments used for: - filling, - pressure measurements, - emptying under vacuum, - recovering the fluid, must be compatible and only used for the R 407 C fluid. 3 - The weight of the refrigerant contained in the storage bottle must be checked constantly. Do not use it from the moment the remaining weight is less than 10% of the total weight. APPLIANCES FILLED WITH R 407 C 4 - In the case of a new charge: - do not use the charging cylinder, - use a balance and a dip pipe type R 407 C cylinder, - charge the weight of R 407 C as per the value indicated on the unit s identification plate, - IMPORTANT: see instruction 3 above. 5 - The charge must be undertaken in liquid phase. 6 - In case of leakage, do not complete the charge: recover the remaining refrigerant for recycling and perform a total charge. Recovery, recycling or the destruction of the fluid must be done in compliance with the laws in force in the country concerned. 7 - If the refrigerant circuit is opened, you must: - avoid the entry of air into the circuit as much as possible, - replace the filter drier, - perform the "vacuum operation" at a minimum level of 0.3 mbar (static). 8 - Do not release R 407 C fluid into the atmosphere. This fluid is a fluorinated greenhouse gases, covered by the Kyoto Protocol with a Global Warming Potential (GWP) = 1653 - (CE Directive 842 / 2006). 1 - GENERALITIES The equipment must be installed, started-up and maintained by authorised and qualified personnel, in accordance with local rules and professional standards. The recommendations and instructions presented in the manual and on labels must be followed. 1.1 - GENERAL SUPPLY CONDITIONS The units must be securely anchored to the truck s trailer during transport. Generally speaking, the material is transported at the consignee s risk. In the event of damages during transport, the consignee must notify the carrier by registered letter within three days following delivery. 1.2 - VOLTAGE Before carrying out any operation, check that the voltage indicated on the unit corresponds to the mains voltage. Before servicing the unit, ensure that the electrical power supply has been shut off and warning signs installed. 1.3 - TECHNICAL AND PHYSICAL CHARACTERISTICS See technical data. 2

2 - DIMENSIONS AND WEIGHT Dimensions (in mm) are given for standard units without options. General tolerance ±10 mm. a b c Condenser air discharge Condenser air suction Suction line Liquid line HP and LP hose entry G Power supply Location of the 4 anti-vibration pads (accessory) (100 x 100 x 25 mm) under girders Centre of gravity (in the centre of the unit) 1,175 c a b 180 125 262 262 1,050 975 40 CSAGV 27 CSAGV 35 CSAGV 40 Net weight 263 kg 270 kg 280 kg 4 Ø 22.5 mm holes for sling attachment G G Access to switch box 1,175 a b c b a 125 262 1,050 262 90 140 90 1,955 1085 CSAGV 48 CSAGV 54 CSAGV 70 CSAGV 80 Net weight 525 kg 530 kg 563 kg 587 kg 4 Ø 22.5 mm holes for sling attachment x G Access to switch box 3

3 - INSTALLATION Prior to all servicing or other actions on the equipment, installation, commissioning, operation, or maintenance, the personnel in charge of these operations shall become familiar with the instructions and recommendations provided in the installation manual of the unit as well as the elements of the project's technical file. The personnel responsible for receiving the unit must conduct a visual inspection in order to identify all damage to which the unit may have been subjected during transport: refrigerating circuit, electrical cabinet, cassis and cabinet. The unit must not be installed near the following: - sources of heat, - combustible materials, - return / air intake of an adjacent building. The unit must be installed, started, maintained and repaired by qualified servicing personnel in compliance with the requirements of all directives, laws and regulations and in accordance with standard trade practices. During installation, troubleshooting and maintenance operations, the use of pipes as a step: under the stress, the pipe may rupture and the refrigerant may cause serious burns. The unit is delivered on a wooden pallet and shrink-wrapped. The units are secured to the pallet by 4 screws for transport. A lift truck may be used to remove the unit from its pallet. Handle the unit with care. Crane installation: once the plastic film has been removed, the machine may be lifted by placing the hoisting hooks into the four Ø 22.5 holes. Spacers or protective pads should be placed between the slings and body to avoid damage. The unit's centre of gravity and weight are indicated on the space requirement diagrams and in the table of the technical documentation. Before installation, verify the following points: - the unit must be installed outside in an appropriate location and in compliance with environmental requirements (sound level, integration, etc...), - the unit s installation location must be perfectly level and strong enough to support the weight of the unit and must have adequate inundation protection, - sufficient space around the unit should be provided in order to facilitate servicing and maintenance operations (see drawing above), - air suction to the coil and fan discharge must not be obstructed, - install the unit above the region s average snowfall level, - vibrations and noise must not be transmitted to adjacent buildings, - install the machine on anti-vibration pads and fit hoses on piping elements, as required, - if necessary, consult an acoustics specialist concerning the unit s optimum location. AVOID: - excessive exposure to sea-air or corrosive gases, - the proximity of the extractor fan, - projections of mud (next to a roadway or path, for example), - areas where there is strong wind blowing against the unit's air exhaust. Protection index of the unit: - IP 24 : for the electrical equipment, (IPXXB : for the mechanical hazards). 3000 300 A 1000 Clearances to be respected A Clearance may be zero for models CSAGV 27 to 40. 300 mm for models CSAGV 48 to 80. 300 4 - CONNECTIONS 4.1 - REFRIGERANT CONNECTION Connect the refrigerant lines to the corresponding connectors (Ø in inches). - CSAGV 27 : 5/8-1"1/8 48-54 : 2 x 5/8-1"1/8 35-40 : 5/8-1"1/8 70-80 : 2 x 5/8-1"1/8. Important: The unit is delivered charged with nitrogen. Carefully determine refrigerant connections: - diameter (the diameters indicated are valid for a maximum length of 8 m), - routing, to facilitate oil return to the compressor. The refrigerant lines should be as short as possible with a maximum length of 15 m and maximum difference in level variation of 6 m. Provide a trap for differences in elevation greater than 3 m on the suction line. 4

The suction connection must always be insulated to avoid condensation and overheating of the gas. If the evaporator is located above the CSAGV, make sure that the suction connection does not allow fluid to return back toward the CSAGV during shutdown. If there is a risk of fluid migration back toward the CSAGV compressor, perform a "pump down" cycle by installing a solenoid valve on the fluid line as close as possible to the evaporator; minimum LP pressure switch adjustment: 1 bar. Use only clean and dry copper refrigeration-quality tubing for refrigerant connection. Tubing must be routed sufficiently far away from removable panels to enable maintenance access. Avoid "Flare" type connections. Tubes must be carefully brazed to avoid contaminating the inside of the tube by either solder overflow or penetration of etching agent. The use of silver solder is preferable. All brazing operations must be performed in a neutral atmosphere (nitrogen, for example) to preclude oxidation of the tube. Leak detection must be performed with a nitrogen and R 407 C mixture. During this test, the CSAGV shutoff valves must remain closed. Do not employ HCFC fluid (R 22, for example). Vacuum operations shall be performed in accordance with Good Trade Practices in order to eliminate all air, nitrogen or humidity detrimental to the correct operation and service life of the installation. Preferable vacuum level: 250 micros, 0.33 mbar. Do not forget to open the CSAGV's shutoff valves and purge the nitrogen remaining in the CSAGV prior to performing vacuum operations. Maximum load of R407C (standard CSAGV): - CSAGV 48 (per circuit) : 9.2 kg 27-54 (per circuit) : 9.2 kg 35-70 (per circuit) : 12.5 kg 40-80 (per circuit) : 13.5 kg R 407 C Fluid R 407 C, as opposed to R22, is not a pure fluid but a blend composed of: 23% R 32 + 25% R 125 + 52% R 134 A, which requires that it always be used in the liquid phase. The compressors approved for operation with this fluid are filled beforehand with polyolester oil. Contrary to mineral oil, it is very hygroscopic: it absorbs the humidity of the ambient air very quickly. This can modify its lubricant properties and lead in time to the destruction of the compressor. R 407 C CHARGE 1 - Never add oil to the appliance; the compressor is filled with polyolester oil, a special oil which cannot tolerate the presence of other oils. 2 - The appliances used for: - filling, - pressure measurements, - emptying under vacuum, - recovering the fluid, must be compatible and only used with the R 407 C fluid. 3 - The weight of the refrigerant contained in the storage bottle must be checked constantly. Do not use it from the moment the remaining weight is less than 10% of the total weight. 4 - Make sure that the charge is conducted exclusively in liquid phase. 5 - When the refrigerant is filled in the storage cylinder, make sure that it is always in liquid phase. 6 - In case of leakage, it is recommended that the remaining liquid be recovered for recycling and to perform a predetermined total charge. Recovery, recycling or the destruction of the fluid must be done in compliance with the laws in force in the country concerned. 7 - If the refrigerant circuit is opened, you must: - avoid the entry of air into the circuit as much as possible, - replace the filter drier. 8 - Do not release R 407 C fluid into the atmosphere. This fluid is a fluorinated greenhouse gases, covered by the Kyoto Protocol with a Global Warming Potential (GWP) = 1653 - (CE Directive 842 / 2006). 4.2 - ELECTRICAL CONNECTIONS 4.2.1 - GENERALITIES: In all cases, refer to the wiring diagrams supplied with the unit or supplied upon request. The acceptable voltage variation is: ±10% during operation. The electrical connection conduits must be fixed. Short circuit current: 10 ka as per CEI 947-2. Class 1 unit. Use the holes fitted with grommets for passing cables into the unit. Use the stuffing boxes for passing cables into in the electrical box. The electrical installation must comply with the standards and regulations applicable where the unit is being installed (in particular NFC 15-100 CEI 364). The unit is designed to be connected to a main supply with a TT, IT or TN.S neutral point connection (as per NF C 15-100). Electrical diagram: 1-system units: 1005682. 2-system units: 1005684. 5

4.2.2 - MAINS SUPPLY The power supply must be three-phase 400V / 50 Hz, in the electrical box, connected either directly to power switch S1 for units with 1 circuit, or on the power terminal strip for 2-circuit units (see electrical diagrams). CAUTION: Before starting the unit, ensure that the phase rotation order is correct. The phase-sequence controller restricts the unit from operating if the 3 supply phases are not in order or if a phase is absent. The power supply must come from an isolation and electric protection device (not supplied) in accordance with existing regulations. The sizing of the power supply cables is to be ensured by the installer in accordance with the installation conditions and as per current standards. Cable sizes, indicated below, are given for information purposes. They are calculated in accordance with NFC 15-100 ( CEI 364) with the following hypotheses: - Maximum current, see table below. - Multi-pole copper cable with PR insulation. - Installation in non-ventilated cable duct (installation method No. 41). No other power cable. - Ambient temperature 40 C. The lengths indicated below correspond to a voltage drop less than 5% in the cable. CSAGV 27 35 40 48 54 70 80 Starting current A 140 150 190 160 165 180 220 Max. total current A 20.5 28.9 30.6 39.6 41 57.8 61.2 Power supply cable section mm 2 6 6 10 16 16 16 25 Max. connection length m 100 100 100 100 100 100 150 The complete electrical specifications are given in the table of the technical documentation. 4.2.3 - PROPORTIONAL "HEAD PRESSURE" CONTROL KIT Based on the information gathered by the specific pressure sensor(s), the control varies the supply voltage of the electric fans in accordance with the diagram opposite. Factory-set for optimal operation. For all other settings, consult us. U Max. voltage Min. voltage P 4.2.4 - CONTROL The refrigeration circuits are controlled by an external potential-free, normally-open contact (not supplied) adapted to the 230 VAC of the control circuits. See details in the electrical diagrams. The connection shall be made using 500V, 1.5 mm 2 type cable. 4.2.5 - ALARM REPORT A potential-free, normally open contact (2A resistive - 250 VAC max.) per refrigerant circuit is placed on the CSAGV terminal strip for remote signaling purposes. - Circuit A: terminals 15 and 16 - Circuit B: terminals 19 and 20 (for CSAGV 48 to 80) See electrical diagrams Connection Circuit A Control Circuit B Control (for CSAGV 48 to 80) Condensation pressure (Bar) The closing of the contact signals one of the following faults: - HP, - LP, - Compressor overheating, - Ventilation overheating, - Phase order, - No power. 13 14 17 18 5 - OPERATING FEATURES The control circuit is powered by a 230 V transformer. Note: This transformer features a 24 VAC (50 VA) output. The refrigerant circuit(s) is(are) controlled by an external contact (not included) with one contact per circuit (see paragraph 4.2.4). Each control circuit is equipped with an anti- short-cycle delay device. Phase order relay on all models restricting operation in case of phase inversion on the 3-phase 400 V power supply. Alarm report per refrigerant circuit in the form of a terminal-mounted potential-free contact (see paragraph 4.2.5). The dual speed fan motor(s) is(are) factory-wired to operate at high speed and supplied by the proportional condensation pressure setting. 6

6 - ACCESSORIES 6.1 - VIBRATION KIT The kit includes a set of four vibration pads, 25 mm thick, code 70600035. 6.2 - HP AND LP PRESSURE GAUGES Code 70970007. The accessory includes 1 set of 2 pressure gauges (HP and LP). - Remove the caps on the riser of the front panel. - Install the pressure gauges. - Connect the capillary tubes to the pressure taps while observing the following precautions: IMPORTANT: Make sure that the capillary does not touch any metal parts that may damage it. Capillary tube Plastic collar Pressure gauge mounted on the device's upright Plastic fasteners Protective foam Pressure tap on refrigerant tube Reserve loops Protective foam 7 - STARTING 7.1 - CHECK: The tightness of connections. That valves are open. HP and LP pressures in relation with the initial calculation. That there are no leaks. That the machine is stable. That the power cables are well fixed to their connection terminals (loose terminals can cause heat build-up on the terminal board). That the electric cables are well insulated from any sections of sheet metal or metal parts which could damage them. That electrical wiring is a safe distance from refrigeration lines. That the machine is earthed. That there are neither tools nor other foreign objects in the unit. 7.2 - STARTING-UP THE UNIT Power up the unit. Start the unit Check that the evaporation unit also operates. 7.3 - CHECKS TO BE MADE Check that the rotation direction of the fan(s) is correct. If not, reverse 2 phases on the electrical power supply. HP and LP by passing the pressure lines through the hole provided (see page 3) and intensities as per the commissioning instructions and pre-established calculations. 7

8 - MAINTENANCE INSTRUCTIONS IMPORTANT Before doing any work on the installation, make sure that it is switched off and that access to it is prevented. Any work must be carried out by personnel qualified and authorised to work on this type of machine. 8.1 - PERIODIC CHECKS Carry out the following operations at least once a year (the frequency depends on the installation and operating conditions): - Cleaning the air exchanger. - Checking the wear parts. - Checking the operating set points and temperatures. - Check the refrigerant circuit in accordance with the regulations in force. - Checking the safety devices. - De-dusting the electrical equipment cabinet. - Checking that the electrical connections are secure. - Checking the earth connection. - Check for leaks. 8.2 - REFRIGERANT CIRCUIT RECOMMENDATIONS A new filter dryer must be installed after all servicing operations performed on the refrigerant circuit. 8.2.1 - INSTALLATION AND MAINTENANCE Prior to all servicing or other actions on the equipment, installation, commissioning, operation, or maintenance, the personnel in charge of these operations shall become familiar with the instructions and recommendations provided in the installation manual of the unit as well as the elements of the project's technical file. The unit must be installed, started, maintained and repaired by qualified servicing personnel in compliance with the requirements of all directives, laws and regulations and in accordance with standard trade practices. During installation, troubleshooting and maintenance operations, the use of pipes as a step: under the stress, the pipe may rupture and the refrigerant may cause serious burns. During unit maintenance operations, the composition and the condition of the coolant will be checked, as well as the absence of all trace of refrigerant. During the unit's annual seal test, in accordance with the law, check that the high and low-pressure pressure controllers are correctly connected on the refrigerating circuit and that they disconnect the electrical circuit in case of tripping. During maintenance operations, make sure that there is no trace of corrosion or oil stains around the refrigerating components. Prior to all maintenance and servicing on the refrigerating circuit, one must first shut down the unit then wait a few minutes before installing temperature or pressure sensors. Certain equipment, such as the compressor and piping, may reach temperatures above 100 C and high pressures may lead to serious burns. 8.2.2 - TROUBLESHOOTING All maintenance and servicing operations on the refrigerating circuit must be conducted in accordance with standard trade practices and safety rules: recovery of the refrigerant, inert shielded (nitrogen) brazing, etc. All brazing operations must be conducted by qualified welders. For equipment charged with R407C, refer to the specific instructions in the installation manual. This unit is equipped with pressurized equipment, for example piping. Use only genuine parts listed in the spare parts list for replacing defective refrigeration components. Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735-1. Leak detection, in the case of pressure testing: - Never use oxygen or dry air, as the risk of fire or explosion is present. - Use dehydrated nitrogen or a nitrogen and refrigerant mix indicated on the manufacturer's plate. - For units equipped with pressure gauges, the test pressure must not exceed the gauges' maximum allowable pressure rating. All part replacement with other than genuine parts, all modifications of the refrigerating circuit, all replacement of refrigerant by a fluid other than that indicated on the manufacturer's plate, all use of the unit outside the application limits defined in the documentation, shall result in the cancellation of PED CE marking compliance which shall fall under the liability of the individual who carried out these modifications. 8

9 - START-UP DATA SHEET CSAGV Range CSAGV 27 to 80 Code: Serial Number: Started by: Company: Site: Date: Voltage measured on unit V L1-L2 L2-L3 L3-L1 FANS Measured amperage, circuit A A/phase L1 L2 L3 Circuit breaker thermal setting A Measured amperage, circuit B A/phase L1 L2 L3 Circuit breaker thermal setting A COMPRESSORS Measured amperage, circuit A A/phase L1 L2 L3 Circuit breaker thermal setting A Measured amperage, circuit B A/phase L1 L2 L3 Circuit breaker thermal setting A HEAD PRESSURE CONTROL Setting TEMPERATURES ( C) / PRESSURES (BAR) Outside temperature Circuit A Circuit B Suction, compressor Discharge, compressor Inlet, thermostatic expansion valve Outlet, thermostatic expansion valve Condensing pressure Evaporating pressure Superheating = (Compressor suction temperature - Evaporating temperature) Sub-cooling = (Condensating temperature - Expansion valve inlet temperature) 9

F I E D

F I E D

F I E D Par souci d'amélioration constante, nos produits peuvent être modifiés sans préavis. Due to our policy of continuous development, our products are liable to modification without notice. Per garantire un costante miglioramento dei nostri prodotti, ci riserviamo di modificarli senza preaviso. En el interés de mejoras constantes, nuestros productos pueden modificarse sin aviso prévio. Unsere Produkte werden laufend verbessert und können ohne Vorankündigung abgeändert werden. R.D. 28 Reyrieux BP 131 01601 Trévoux CEDEX France Tél. 04 74 00 92 92 - Fax 04 74 00 42 00 Tel. 33 4 74 00 92 92 - Fax 33 4 74 00 42 00 R.C.S. Bourg-en-Bresse B 759 200 728