Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires

Similar documents
Keywords: Fire detection, smoke alarm, nuisance, UL 217, polyurethane foam

Smoke Alarm Research at NIST

BEYOND COOKING: SMOKE ALARM NUISANCE SOURCES EVALUATED. Joshua B. Dinaburg, P.E. Dr. Daniel T. Gottuk, P.E. SUPDET 2016 March 4, 2016

A Comparison of Aspirated Smoke Detectors

Polarized Light Scattering of Smoke Sources and Cooking Aerosols

Dr. Daniel T. Gottuk Joshua B. Dinabug SUPDET 2014

Impact on Smoke Alarm Performance Considering New Nuisance and Fire Tests

Keywords: VEWFD; Smoke detection; Smoke production; In-situ testing.

Smoke Alarm Research at NIST

Aspirating Gas Detection CFD Modelling Predicts Application Performance

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

UL268 7 th challenge with single infrared smoke detector

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Results from a Full-Scale Smoke Alarm Sensitivity Study

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Smoke Transport and FDS Validation

Smoke Alarm Presence and Performance in U.S. Home Fires By Marty Ahrens, NFPA, Quincy, MA. 1. Abstract

TrueAlarm Smoke Detectors

Potential Impact of New UL Fire Test Criteria

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Fire Resistance Proficiency Testing of Gypsum/Steel-Stud Wall Assemblies. William L. Grosshandler 1

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

Validation of a Smoke Detection Performance Prediction Methodology. Volume 4. Evaluation of FDS Smoke Detection Prediction Methodology

Frequently Asked Smoke Alarm Questions

Validation of a Smoke Detection Performance Prediction Methodology. Volume 2. Large-scale room fire tests

Carbon Monoxide Safety Information

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Brine Generation Study

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

A NATIONAL SET OF HYDROGEN CODES AND STANDARDS FOR THE US

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Smoke Alarms in U.S. Home Fires

High Rise Buildings with Combustible Exterior Wall Assemblies: Fire Risk Assessment Tool

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

First Revision No. 6-NFPA [ Section No. 2.2 ]

A Method for Fire Detecting by Volume and Surface Area Concentration Based on Dual Wavelengths

CLEAN AGENTS & CLASS C FIRE HAZARDS

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Validation of a Smoke Detection Performance Prediction Methodology. Volume 3. Evaluation of Smoke Detector Performance

Demand-Controlled Ventilation For Commercial Kitchens

1. Revise and A to read as follows:

Home Fires Involving Heating Equipment

Towards Predicting High Sensitivity Smoke Detector Operational Performance in Building Environments

SECTION : FIRE ALARM & DETECTION SYSTEMS

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

Smoke Layer Height and Heat Flow through a Door

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

Summary of International Road Tunnel Fire Detection Research Project Phase II

Workshop Proceedings: Technology Needs for Fire Prevention

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Home Cooking Fires. November 2018 Marty Ahrens. November 2018 National Fire Protection Association

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

CALIFORNIA STATE FIRE MARSHAL SMOKE ALARM TASK FORCE FINAL REPORT ANALYSIS AND RECOMMENDATIONS

TrueAlarm Analog Sensing

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

A Building Manager s Guide to Maintaining Fire Code Compliance

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Operation & Maintenance Manual

NFPA 72 Code Changes vs 2013

TrueAlarm Analog Sensing

Multi-Point Peripherals

CCTV, HOW DOES IT WORK?

Melrose Fire Department

ARC MAPPING IN THE ADVENT OF AFCI, GFCI, AND GFEP CIRCUIT PROTECTION DEVICES

Ionization Smoke Alarms A Substantial Product Hazard

Chapter 2 Background. 2.1 VID Technology

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

UPHOLSTERED FURNITURE AND MATTRESSES IN NEW AND EXISTING BUILDINGS

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

NFPA 101 Life Safety Code Culture change 2012

LaserFOCUS VLF-250 Engineering Specification

Smoke Alarms: Comparing the Differences in Response Times and. Nuisance Alarms. Chris Kasperczyk. University of Cincinnati.

EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM

DONALD H. BERG, ARCHITECT

Residential Fire Protection

Certification Report of the ST3000 Pressure Transmitter

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Research and Its Impact on the Code

TrueAlarm ES Analog Sensing

ASHRAE JOURNAL ON REHEAT

Food Service Technology Center

research highlight Canadian Housing Fire Statistics Findings

Smoke & Carbon Monoxide

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration

Effective Alarm Management for Dynamic and Vessel Control Systems

FALSE ALARM ACTIVITY IN THE U.S. 2012

LEARNING SPECIAL HAZARD DETECTION TYPES

Smoke detection in hazardous areas:

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods

Transcription:

Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires Erik Johnsson, Mariusz Zarzecki National Institute of Standards and Technology, Gaithersburg, MD, USA Abstract A series of 21 experiments was conducted to examine the potential to use kitchen-installed photoelectric smoke detection devices to warn of approaching ignition of food during unattended cooking. An electric range, range hood, and cabinets were installed in a mock-up kitchen. Research smoke meters and standard off-the-shelf photoelectric smoke detectors were installed above the food, on the ceiling, and on the upper wall. In addition to smoke meter and smoke detector outputs, pan and food temperatures along with digital videos of the experiments were recorded. Cooking oils and bacon were heated to ignition in frying pans on the range top. The standard-threshold smoke alarms activated minutes before ignition. Typically, smoke production reached alarm levels at least 2 min before ignition. Frying hamburger tests were also conducted to compare smoke levels from attended, but smoky, cooking to the unattended cooking smoke levels. Analysis indicates that there is an extensive time window of elevated smoke obscuration during the unattended cooking above smoky attended cooking and prior to ignition sufficient to allow warning that would either alert the cook to return and de-energize the range or to interface with an automatic de-energizing device connected to the range. Keywords: kitchen fires, photoelectric smoke detection, unattended cooking, cooking fire prevention, pre-ignition warning Introduction In the United States from 2009 to 2013, cooking caused 45 % of home structure fires, 17 % of the associated deaths, 42 % of the injuries, and 16 % of the property damage. [1]. Ranges and cooktops were involved in most each of these losses and account for over 300 deaths and 4000 injuries per year. About half of cooking fires result from the equipment being unattended. Unattended cooking fires remain a leading cause of fire incidents, injuries, property loss, and deaths even though efforts to research the issue and develop technology to impact

the problem have been ongoing for over 20 years. As one of the leading causes of residential fires, unattended cooking fires remain a high priority fire problem requiring solutions. The National Institute of Standards and Technology (NIST), the Consumer Product Safety Commission (CPSC), Underwriters Laboratories (UL), the National Fire Protection Association s (NFPA) Fire Protection Research Foundation (FPRF), and contractors to these organizations have researched engineering solutions to address unattended cooking fires for nearly 20 years. Most devices conceived for this purpose are thermal and expected to warn of approaching ignition temperatures. Recent work by Dinaburg and Gottuk at Jensen Hughes and sponsored by the FPRF and NIST developed recommendation for a test standard for cooking pre-ignition detection devices [2]. In 2015, the Association of Home Appliance Manufacturers (AHAM), in cooperation with Underwriters Laboratories (UL), proposed a modification to the 16th edition of UL 858 standard Cooking Oil Ignition Test for electric ranges [3] which has been adopted and will be effective April 4, 2019. The revised standard considers and tests any built-in device designed to prevent ignition of food on the range. For most studies of this problem, the focus on detecting approaching ignition has been range-centric; i.e., the solution needed to be connected to the range to interrupt the heating process during unattended cooking to prevent ignition [4, 5, 6]. However, NIST s recommendation in 1996 was to explore smoke as the most reliable and early warning of approaching ignition [7]. Due to nuisance alarms, smoke alarms have not typically been deployed in kitchens and are not listed for such use. Detection and alarming of smoke levels would necessarily need to be external from the range, probably on the ceiling, and would need to interface with a range to shut it down in the event of approaching ignition. NIST recently decided to revisit the potential for using smoke to enable warning of approaching ignition. To be effective, a time window needed to be found between normal cooking smoke levels and approaching-ignition smoke levels generated by unattended cooking. A smoke level threshold could then be set which allowed for sufficient time for the homeowner to hear an alarm and respond or for automatic range shutdown to be initiated prior to ignition. Experimental Description Experiments were designed to explore the smoke produced by unattended cooking of various foods. The foods and pan sizes and materials were selected based partly on the experiments performed by Dinaburg and Gottuk [2] and the results generated by particular combinations. The presence and operation of a range hood was also added to this effort. The goal of the experiments was to generate data that could be analyzed to establish the relationship between smoke and time before ignition for fire prevention. Relatively smoky normal cooking

was also needed to determine if it could be differentiated from the unattended cooking smoke levels. The experiments were conducted at NIST in a room 3.0 m wide x 2.45 m tall x 3.2 m deep with a 9.1 m wide and 2.0 m tall opening and a 0.44 m soffit which allows the smoke to be exhausted out of the test area and thought the exhaust duct. A room diagram is shown in Fehler! Verweisquelle konnte nicht gefunden werden.. A kitchen mockup was built using cement board cabinets and a built-in range and a range hood. A residential electric (coil burner) range was purchased and installed. A large front burner on the range with a 1.95 kw rating was used. The range hood exhausted above the false ceiling to the room exhaust and operated at 104 L/min (220 ft 3 /min). NIST used the same 25 cm (10 in) diameter stainless steel pans Jensen Hughes determined led to fastest ignition [2]. Fig. 1. Top view of the instrument layout in the test room. Measurements included power and current used by the range, smoke obscuration, and temperatures. Smoke was measured above the range, on the ceiling, and on one wall primarily with laser-based smoke meters and photoelectric smoke detectors. Temperatures were measured at the pan and also at each smoke measurement device location. Two high definition video cameras and a digital still camera were used as well. Table 1 provides the matrix of tests and their conditions. Canola oil and peanut oil were chosen for the NIST study because the Jensen Hughes

results showed that they presented a challenge to the use of photoelectric smoke detection technology with late, high-temperature smoke production and similar or slightly earlier ignition times as other oils [2]. To allow comparison, the same amount of oil was chosen as well: 300 ml ±3 ml for a 6.4 mm (¼ in) depth in the pan. Bacon (224 g ± 2 g) was also selected as a meat for unattended cooking because it tends to produce smoke and ignite relatively early compared to cooking oils. Hamburgers (112 g ± 1 g per patty) were selected as a surrogate for food undergoing an attended cooking process because smoke is often produced even while attended that can activate smoke alarms in adjacent rooms. Fifteen unattended and six attended cooking experiments were conducted. Oils and bacon were cooked on high heat while the hamburgers were cooked with typical procedures which involved flipping them at specified times and decreasing the heat from high to medium. Table 1. Test matrix with experimental conditions are listed for each. Unattended Cooking Attended Cooking Test Range Test Range Food Food No. Hood No. Hood 1 Canola Oil Off 16 1 Hamburger Off 2 Canola Oil Off 17 2 Hamburgers Off 3 Peanut Oil Off 18 2 Hamburgers Off 4 Bacon Off 19 3 Hamburgers Off 5 Canola Oil On 20 1 Hamburger Off 6 Peanut Oil On 21 1 Hamburger Off 7 Canola Oil On 8 Peanut Oil On 9 Peanut Oil Off 10 Peanut Oil On 11 Peanut Oil Off 12 Canola Oil Off 13 Canola Oil On 14 Bacon Off 15 Bacon Off Results and Discussion Fig. 2 is a plot of the food temperatures and duration of heating time at ignition for all of the experiments. Solid symbols represent the data for experiments with the range hood off. Symbols with the same color and shape are for experiments using the same foodstuff. There is no clear pattern of difference in ignition time or temperature related to the hood status. The plot does show similarly wide ranges of time and temperature for all of the foods tested. Peanut oil generally (but not

always) had higher ignition temperatures than canola oil. This is consistent with what was found in the Jensen Hughes study [2]. Food Temperature, o C 420 410 400 390 380 370 Canola Oil (Hood Off) Canola Oil (Hood On) Peanut Oil (Hood Off) Peanut Oil (Hood On) Bacon (Hood Off) 360 580 600 620 640 660 680 Time to Ignition, s Fig. 2. Food temperature versus ignition time for all experiments. The reason for conducting experiments that represent attended, yet smoky, cooking as well as those that represent unattended cooking and lead to ignition is to determine if there is a sufficient difference between the smoke levels long enough before ignition to provide an alarm or warning threshold. It is important that the threshold is above maximum normal cooking obscuration levels so nuisance warnings are not experienced. The threshold should also be at minimum obscuration levels achieved during unattended cooking to allow the most time available for warning and manual shutdown or automated shutdown before ignition occurs. Fig. 3 is a plot of the minimum obscuration levels for the smoke meter located on the ceiling for all of the experiments versus time before ignition. The time before ignition axis starts with 2 min before ignition on the left and ignition at 0 s on the right. The line drawn across the bottom of the plot is the maximum obscuration at the ceiling at any time during any of the hamburger experiments, 15.2 %/m. The plot shows that for the ceiling smoke meter position, which captures smoke as it starts to build a layer, all of the minimum obscurations for the different foods at 1 min before ignition and later are higher than the maximum obscuration produced by any of the hamburger experiments. This reveals that a time window on the order of 1 min is available at the ceiling location, during which a warning threshold could indicate approaching ignition without also being triggered by nuisance smoke levels.

Minimum Obscuration, %/m 70 60 50 40 30 20 10 0 120 100 80 Ceiling/Canola Ceiling/Peanut Ceiling/Bacon 60 Maximum Hamburger Obscuration at Ceiling - 15.2 %/m 40 20 0 Time before Ignition, s Fig. 3. Minimum obscuration for the ceiling smoke meter location plotted versus time before ignition. The maximum obscuration at the ceiling location is shown for all of the hamburger experiments. Some bacon data points are higher than the range displayed. Minimum Obscuration, %/m 30 25 20 15 10 5 0 120 Wall/Canola Wall/Peanut Wall/Bacon 100 Maximum Hamburger Obscuration at Wall - 12.5 %/m 80 Fig. 4. Minimum obscuration for the wall smoke meter location plotted versus time before ignition. The maximum obscuration at the wall location is shown for all of the hamburger experiments. The bacon data points are higher than the range displayed. Fehler! Verweisquelle konnte nicht gefunden werden. is similar to the previous figure but is for the wall location. The line drawn across the bottom of the plot is the maximum obscuration at the wall location at any time during any of the hamburger experiments, 12.5 %/m. The plot 60 40 Time before Ignition, s 20 0

shows that for the wall smoke meter position, which sees smoke after it has been further diluted (compared to at the ceiling) and descended as a thickening smoke layer, the minimum obscurations for the different foods are only greater than the maximum hamburger obscurations about 30 s to 35 s before ignition. This shows that a time window only on the order of 30 s is available at the wall location when a warning threshold could indicate approaching ignition without also being triggered by nuisance smoke levels. This is still sufficient time for a burner to be de-energized even accounting for the continued heating and increasing temperature (overshoot) of the pan and food after power is cut. This overshoot period was found to be about 5 s [2]. Conclusions and Future Work The following findings were observed: Similar qualitative results were found to the earlier NIST effort [7]. Ignition temperature results were comparable to Jensen Hughes results [2]. Smoke production above the range usually reached unacceptably high obscuration levels greater than 52 %/m (20 %/ft) at least 2 min before ignition. A 2 min window was found between normal cooking smoke levels (for hamburgers) and approaching-ignition smoke levels from unattended cooking for smoke measured above and near the range burner. A 1 min window was found between normal cooking smoke levels (for hamburgers) and approaching-ignition smoke levels from unattended cooking for smoke measured at the ceiling. A 30 s window was found between normal cooking smoke levels (for hamburgers) and approaching-ignition smoke levels from unattended cooking for smoke measured on the wall. The standard threshold smoke detectors not designed for kitchen use alarmed minutes before ignition. Standard smoke detectors used for this study do not have the dynamic range to provide smoke measurement data beyond their programmed alarm threshold. There are useful time windows (which vary by measurement location) for differentiation of smoke obscuration levels generated by normal and unattended cooking situations that could be utilized to either (1) alert an occupant to return and de-energize the range or (2) interface with an automatic de-energizing device connected to the range. This limited set of data was conducted in a single kitchen configuration. Results in kitchens of different dimensions than the configuration used in this test series could be impacted by the larger or smaller kitchen volumes. Larger kitchen volumes could decrease/delay the obscuration concentrations resulting in less time between alarm and ignition.

Follow-on work is needed by industry and organizations working on increasing cooking fire safety to establish standards for kitchendeployed unattended cooking alarms that are not necessarily built into a range. Photoelectric (or ionization) devices might need to be detuned to alarm or activate de-energizing devices at much higher smoke levels to allow the detectors to be positioned in areas of higher smoke concentrations. Additional more severe or smoky normal cooking activities (e.g., stir frying) would need to be performed to ensure that the higher alarm thresholds are sufficiently high to not cause nuisance alarms. It will be important to clearly differentiate unattended cooking alarm devices designed for kitchen use from standard smoke detectors to prevent inappropriate installations. While range-centric devices are gradually being developed along with standards, using smoke detection technology could more quickly and easily bring about significant decreases in residential cooking fires. Acknowledgements Appreciation goes to: Tom Cleary, Mike Selepak, and Artur Chernovsky of NIST, Josh Dinaburg and Dan Gottuk of Jensen Hughes, Larry Ratzlaff of Kidde Safety, and Bob Backstrom and Tom Fabian of UL. References [1] M. Ahrens, Home Fires Involving Cooking Equipment, National Fire Protection Association, Quincy, MA, November 2015. [2] Dinaburg, J. and Gottuk, D., Development of Standardized Cooking Fires for Evaluation of Prevention Technologies: Data Analysis, The Fire Protection Research Foundation, Quincy, MA, July 2014. [3] Underwriters Laboratories Inc., Standard for Household Electric Ranges, UL858 edition 16, UL, Northbrook, IL, November 2014. [4] ADL, Technical, Practical and Manufacturing Feasibility of Technologies to Address Surface Cooking Fires, Arthur D. Little, Inc., Boston, MA, May 2001. [5] Underwriters Laboratories Inc., Report of Research on Cooking Fires and Pan Contact Temperature Sensor Technology, UL, Northbrook, IL, August 2003. [6] U.S. CPSC, Identification and Evaluation of Temperature Sensors for Preventing Fires for Electric Smooth-Top Ranges, Final Report, Advanced Mechanical Technology, Inc., CPSC, Bethesda, MD, July 2003. [7] Johnsson, E., Study of Technology for Detecting Pre-Ignition Conditions of Cooking-Related Fires Associated with Electric and Gas Ranges and Cooktops. Final Report, NISTIR 5950; 130 p., NIST, Gaithersburg, MD, January 1998.