Description of EQ3XXXabcd (Controller): The Controller, Model EQ3XXX, performs all communication, command and control functions for the Eagle Quantum Premier System. The Controller supports both static and programmable logic. Among the features included in the Controller are 8 programmable unsupervised inputs, 8 unsupervised relay outputs, an RS-485 Modbus slave communication interface and an optional ControlNet communication board. The module is housed in a cast aluminium enclosure with optional DIN-rail mount or panel mount configurations. The Controller EQ3XXX can be connected to the following Field Devices: PIRECL IR Gas Detector, OPECL Open Path Gas Detector, X3301/X3302 Multi-spectrum Flame Detector, X2200 UV Flame Detector, X5200 UV/IR Flame Detector, X9800 IR Flame Detector, C7050 UV Flame Detector, EQ22XXDCU, EQ22XXDCUEX, EQ22XXIDC, EQ22XXIDCGF, EQ22XXIDCSC, EQ24XXNE, EQ24XXPLR, EQ25XXARM, EQ25XXSAM, EQ3700DCIO, EQ3710AIM, EQ3720RM, EQ3730EDIO, EQ3740IPM & EQ3750ASH. Description of EQ3700ab (DCIO): The (8 channel) Discrete Input/Output Module, Model EQ3700 DCIO, consists of 8 individually configured (wired as Input or Output) channels. Wiring supervision includes none, open circuits, and open and short circuits. In addition to defining the type of supervision, an input channel is also configured to generate the appropriate static logic alarm message to the controller. Heat, smoke, or unitised flame detectors can be wired into channels defined as inputs. Horns, strobes, beacons and solenoids can be wired into channels defined as outputs. The module is housed in a cast aluminium enclosure with optional DIN-rail mount or panel mount configurations. Description of EQ3710ab (AIM): The Analog Input Module, Model EQ3710 AIM, is an 8-channel microprocessor based module providing 4-20mA analog input. Each channel on the module has LED status indicators for both active and fault conditions. The module is housed in a cast aluminium enclosure with optional DIN-rail mount or panel mount configurations. Description of EQ3720ab (RM): The Relay Module, Model EQ3720 RM is an 8-channel microprocessor based module providing unsupervised relay contact operation. Each output point is intended for dry contact output operation. The relays can be wired for normally open or normally closed contacts and can be configured for a normally energized or de-energized relay coil. In addition, the module can be configured for hold last state, active or inactive after LON communications have been lost for more than one minute. The module is housed in a cast aluminium enclosure with optional DIN-rail mount or panel mount configurations. Description of EQ3730ab (EDIO): The Enhanced Discrete Input/Output Module, Model EQ3730 EDIO, provides 8 channels of configurable input or output points for the Eagle Quantum Premier System. These input and output points can be programmed for supervised or unsupervised operation. Each input point can accept fire detection devices. Each output point can be configured for signalling or releasing output operation. Each channel on the module is provided with individual indicators for active and fault conditions. The module is housed in a cast aluminium enclosure with optional DIN-rail mount or panel mount configurations. Description of EQ3740ab (IPM): The Intelligent Protection Module, Model EQ3740 IPM, is an 8-channel microprocessor based module that can be configured for supervised or unsupervised input/output operation. Each channel on the module has LED status indicators for both active and fault conditions. The module is housed in a cast aluminium enclosure with optional DIN-rail mount or panel mount configurations. Description of EQ3750ab (ASH): The Addressable Smoke and Heat Module, Model EQ3750 ASH expand the Eagle Quantum Premier System and provide power and communications to 64 addressable devices such as flame, gas, smoke and heat detectors. Description of EQ3800/EQ3810ab (PDM): The Power Distribution Module, Model EQ3800/EQ3810, integrates isolation, conditioning, monitoring and distribution to outputs that power thecontroller, cabinet devices and field devices. It is used to provide continuous power to the outputs by relying on two independent input power sources (one line power source and one backed up power source). Description of EQ2220 (GFM): The Ground Fault Monitor (GFM), model EQ2220 provides ground fault monitoring in a system. The GFM consists of an electronic circuit where the output is a contact closure in the presence of a ground fault. The GFM has three LED s used to provide a visual indication of device status. The GFM is intended for mounting in the same protective enclosure as the gas detection system controller. Description of Lon Termination Module (LTM): The LON Termination Module (LTM), Model Number 008982-001, consists of an RC circuit that is to act as interface between LON and EQP Controller. The LTM is intended for mounting in the same protective enclosure as the gas detection system controller. Page 1 of 5
Description of Hart Interface Module (HIM): The HART Interface Module (HIM), Model Nr. 008056-001, consists of an RC circuit that is to be connected only to the EQ3710 Analog Input Module. This interface module provides additional impedance to meet HART Interface specifications. The HIM is intended for mounting in the same protective enclosure as the gas detection system controller. Nomenclature for EQ3XXXabcd (Controller), where: X) description 001 Controller 246 NODES 005 Controller 246 NODES, (Customer specific configuration) 016 Controller 16 NODES 150 Controller 150 NODES a) mounting b) COM board 1 C ControlNet c) COM board 2 S Serial Port Expansion d) approval agency* A FM/CSA C CSA E ATEX/CE F FM R Russian S SIL T SIL/FM/CSA/ATEX/CE T-C T Plus US Coast Guard W-C W Plus US Coast Guard 2. Refer to drawing No. 007532-001 for details. Nomenclature for type EQ3700ab (DCIO), : A FM/CSA 2. Refer to drawing No. 007534-001 for details. Nomenclature for type EQ3730ab (EDIO): T SIL/FM/CSA/ATEX/CE 2. Refer to drawing No. 009153-001for details. Page 2 of 5
Nomenclature for type EQ3750ab (ASH): b) Approval agency W FM*/CSA*/ATEX*/CE*/IECEx 2. Refer to drawing No. 010641-001 for details. Nomenclature for type EQ3800/EQ3810ab (PDM): 2. Refer to drawing No. 007504-001for details. Nomenclature for type EQ3710ab (AIM), EQ3720ab (RM), EQ3740ab (IPM) and, where: 2. Refer to drawing No. 007944-001, 007804-001 and 007946-001 for details. For the EQ2220, Ground Fault Monitor (GFM), the LON Termination Module (LTM) Nr. 008982-001 and the HART Interface Module (HIM) Nr. 008056-001, no nomenclature is defined. Temperature range: The relation between EQP Module, ambient temperature range and maximum component temperature is as follows: Module Ambient temperature range Maximum component temperature EQ3XXX Controller -40 C to +85 C 130 C EQ3700 DCIO -40 C to +85 C 130 C EQ3710 AIM -40 C to +85 C 130 C EQ3720 RM -40 C to +60 C 130 C EQ3730 EDIO -40 C to +85 C 130 C EQ3740 IPM -40 C to +85 C 130 C EQ3750 ASH -40 C to +85 C 130 C EQ3800 PDM -40 C to +80 C 195 C EQ3810 PDM -40 C to +80 C 195 C EQ2220 GFM -40 C to +85 C 130 C Nr. 008982-001 LTM -40 C to +85 C 130 C Nr. 008056-001 HIM -40 C to +85 C 130 C Page 3 of 5
Electrical data EQ3XXX, Controller Rated power......12 W max. EQ3700, Discrete Input/Output Module (DCIO) Rated voltage......18-30 Vdc Rated current......max. 2A per channel, max. 10.4A per unit EQ3710, Analog Input Module (AIM) Rated voltage......18-30 Vdc Rated current... max. 0.9A per channel, max. 7.4A per unit EQ3720, Relay Module (RM) Rated power......max. 2A per channel, max. 10.4A per unit EQ3730, Enhanced Discrete Input/Output Module (EDIO) Rated voltage......18-30 Vdc Rated current......max. 2A per channel, max. 10.4A per unit EQ3740, Intelligent Protection Module (IPM) Rated power......max. 2A per channel, max. 6.2A per unit EQ3750, Addressable Smoke and Heat Module (ASH) Input current......690 ma max Loop current......225 ma max EQ3800/EQ3810, Power Distribution Module (PDM) Rated voltage......18-30 Vdc Rated current... 10A max. per input EQ2220, Ground Fault Monitor (GFM) Output relay contact rating...30 Vdc, 1 A max. LON Termination Module (LTM), Nr. 008982-001 HART Interface Module (HIM), Nr. 008056-001 Installation instructions: For ambient temperatures below 10 C and above +60 C use field wiring suitable for both minimum and maximum ambient temperature. Mounting instructions All wiring connected to the above mentioned EQP modules shall be fixed installed. Routine tests: All above mentioned EQP modules (except the EQ2220 GFM, LON Termination Module (LTM), Nr. 008982-001 and HART Interface Module (HIM), Nr. 008056-001) shall be tested with a dielectric strength test at 500 Vrms, during 1 minute, in accordance with IEC 60079-15, clause 34.2. Page 4 of 5
Ex coding: EQ3XXX: Ex nc IIC, Tamb. -40 C to +85 C EQ3700 (DCIO): Ex na nl nc IIC, Tamb. -40 C to +85 C EQ3710 (AIM): Ex na nl nc IIC, Tamb. -40 C to +85 C EQ3720 (RM): Ex na nl nc IIC, Tamb. -40 C to +60 C EQ3730 (EDIO): Ex na nl nc IIC, Tamb. -40 C to +85 C EQ3740 (IPM): Ex na nl nc IIC, Tamb. -40 C to +85 C EQ3750 (ASH): Ex na nl nc IIC, Tamb. -40 C to +85 C EQ3800 (PDM): Ex na II, Tamb. -40 C to +80 C EQ3810 (PDM): Ex na II, Tamb. -40 C to +80 C EQ2220 (GFM): Ex nc IIC, Tamb. -40 C to +85 C LON Termination Module (LTM): Ex na II, Tamb. -40 C to +85 C HART Interface Module (HIM): Ex na II, Tamb. -40 C to +85 C Schedule of limitations: The controller and modules shall be used in an area of no more than pollution degree 2 conform IEC 60664-1, and in an enclosure that complies with all relevant requirements of IEC 60079-15, rated at least IP54, and be connected to supply circuits where the rated voltage cannot be exceeded by 40% caused by transient disturbances. The controller and modules may only be installed, connected or removed when the area is known to be non-hazardous. The maximum surface temperature inside the controller and modules does not exceed 130 C (except for EQ3800/EQ3810, PDM, which does not exceed 195 C). For ambient temperatures above 60 C conductors suitable for at least 20 C above the ambient temperature must be used. Documents: Project record 10CA19739 (Hazardous Locations testing) Description: Drawing No.: Rev. Level: Date: Dwg. design reference EQ3XXX Controller DEMKO 007532-001 K 2010-12-07 (18 pages) Drw. design reference EQ3700 DCIO DEMKO 007534-001 F 2010-10-14 Drw. design reference EQ3710 AIM DEMKO 007944-001 D 2010-10-14 (4 pages) Drw. design reference EQ3720 Relay Module DEMKO 007804-001 C 2010-10-14 Dwg design reference EQ3730 EDIO DEMKO 009153-001 E 2010-05-18 Dwg design reference EQ3740 IPM DEMKO 007946-001 C 2010-10-14 (4 pages) Dwg design reference EQ3750 ASH DEMKO 010641-001 B 2011-03-08 (5 pages) Dwg design reference EQ3800/EQ3810 PDM DEMKO 007504-001 D 2010-09-08 (3 pages) Dwg design reference EQ2220 GFM DEMKO 007948-001 B 2010-05-18 Dwg design reference LTM, Redundant, EQP DEMKO 008991-001 B 2010-05-18 Dwg design reference HIM DEMKO 007950-001 B 2010-05-18 Instruction Manual for EQ3800/EQ3810 PDM 95-8558 - 2010-09 Instruction Manual for EQP System 95-8533 - 2010-12 Installation Manual for EQ3750ASH 95-8654 - 2010-10 Page 5 of 5