EC TYPE EXAMINATION (MODULE B) CERTIFICATE This is to certify that: LLOYD'S REGISTER VERIFICATION LIMITED (LRV), specified as a notified body under the terms of The Merchant Shipping (Marine Equipment) Regulations S.I. 1999 No. 1957, did undertake the relevant type approval procedures for the equipment identified below which was found to be in compliance with the essential Fire protection requirements of Marine Equipment Directive (MED) 96/98/EC as modified by Commission Directives 98/85/EC, 21/53/EC, 22/75/EC, 22/84/EC, 28/67/EC, 29/26/EC, 21/68/EU, 211/75/EU, 212/32/EU, 213/52/EU and 214/93/EU subject to any conditions in the Design Appraisal Document attached hereto. Manufacturer Address Annex A1 Item Product Type Olympia Electronics -N.D.LAKASAS P.N.ARVANITIDIS S.A 72 nd km Thessaloniki Katerini National Road 661 Kolindros- Greece A.1/3.51 FIXED FIRE DETECTION & FIRE ALARM SYSTEMS COMPONENTS FOR CONTROL STATIONS, SERVICES SPACES, ACCOMM SPACES, MACHINERY SPACES & UNATTENDED MACHINERY SPACES Addressable fire detection and alarm system: Model Description Operation Voltage Class/Type IP rating BSR-2114/MAR Fire detection panel 22-24V AC - IP3 5-6Hz BSR-214/MAR Fire detection panel 22-24V AC - IP3 5-6Hz BSR-655/A/MAR Optical smoke 21-28 V DC - IP44 BSR-66/A/MAR Rate of rise heat 18-3 V DC A2R IP22 BSR-536/A/MAR Manual call point 21-28 VDC A IP44 BSR-657/A/MAR Optical smoke and 21-28 V DC A2S IP44 thermal BSR-817/MAR Input-output unit 21-28 V DC - IP2 BSR-771/A/MAR Base isolator 14-3 V DC - IP2 BSR-2/MAR Repeater Panel for BSR-214/MAR, BSR-2114/MAR panels 22-24V AC 5-6Hz/ 16-3 V DC - IP3 Conventional fire detection and alarm system: Model Description Operation Voltage Class/Type IP rating BS-655/MAR Optical smoke 18-3 V DC - IP44 BS-536/MAR Manual call point 1-3 V DC A IP44 BS-657/MAR Optical smoke and thermal 18-3 V DC A2R IP44 Software version BSR-2114/MAR & BSR-214/MAR fire BSR-21 V4.12 detection panels BSR-2/MAR repeater panel BSR-2 V.6 Product Description Addressable fire detection and alarm system, Conventional fire detection and alarm system Specified Standard EN 54-2 (1997) including AC (1999) and A1 (26) EN 54-4 (1997) including AC (1999), A1 (22) and A2 (26)
EN 54-5 (2) including A1 (22) EN 54-7 (2) including A1 (22) and A2 (26) EN 54-11 (21) including A1 (25) EN 54-17 (27) including AC (27) EN 54-18 (25) including AC (27) IEC 692-54 (21) including IEC 692-54 Corrigendum 1 (211) IEC 6533 (1999) The attached Design Appraisal Document (schedule) forms part of this certificate. This certificate remains valid unless cancelled or revoked, provided the conditions in the attached schedule are complied with and the equipment remains satisfactory in service. of issue 4 November 215 Expiry date 3 November 22 Certificate No. Signed Lloyd's Register Verification Ltd Sheet No 2 of 5 Name LR427.213.12P.A. Huntley-Hawkins For and on behalf of Lloyd s Register Verification LRV EC Distinguishing No. 38 Note: This certificate is not valid for equipment; the design or manufacture of which has been varied or modified from the specimen tested. The manufacturer should notify the notified body named on this certificate of any modification or changes to the equipment in order to obtain a valid Certificate. Subject to compliance with the conditions in the attached Design Appraisal Document (schedule), which forms part of this certificate, and those of Articles 1.1(i) and 11 of the Directive, the Manufacturer is allowed to affix the Mark of Conformity to the Product described herein. yy Last two digits of year mark affixed. This certificate is issued under the authority of the MCA. 38/yy Lloyd s Register Verification Limited (Reg. no. 4929226) is a limited company registered in England and Wales. Registered office: 71 Fenchurch Street, London, EC3M 4BS, UK. A subsidiary of Lloyd s Register Group Limited. Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as the 'Lloyd's Register'. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.
3 of 5 4 November 215 ATTACHMENT TO EC TYPE EXAMINATION (MODULE B) CERTIFICATE No. The undernoted documents have been appraised for compliance with the relevant requirements of International Conventions and European Union legislation for the EC Type Examination of Marine Equipment for use on Merchant Ships Registered in the European Economic Area. This Design Appraisal Document (schedule) forms part of the Certificate. APPROVAL DOCUMENTATION Form 2571 4.6.215 Manuals for the components of Addressable fire detection and alarm system: BSR-2114/MAR, BSR-214/MAR, BSR-655/A/MAR, BSR-66/A/MAR, BSR-536/A/MAR, BSR-657/A/MAR, BSR-817/MAR, BSR- 771/A/MAR, BSR-2/MAR Undated Manuals for the components of Conventional fire detection and alarm system: BS-655/MAR, BS-536/MAR, BS- 657/MAR Undated Construction information No.92121141_2_1_EN 3.9.215 Internal audit No.92121141_8_1_EN 3.9.215 Component drawings No.921536_64_2 Component drawings No.921655_64_1 Panel drawing No.BSR-21XX_Ver71 Dimensions datasheet for the components of fire detection and alarm system TEST REPORTS Inspection and Surveillance of Production Facilities No.4171333 24.9.215 H.E.E.Q.A.C Report No. 53994-1 E -Type Testing of BSR-66/A/MAR in accordance with EN 54-5:2 +A1:22 1.9.214 H.E.E.Q.A.C Report No. 545-1 E - Type Testing of BSR-817/MAR in accordance with EN 54-18:25/ AC: 27 3.9.214 H.E.E.Q.A.C Report No. 541-1 E -Type Testing of BSR-657/A/MAR in accordance with EN 54-5:2 +A1:22, EN 54-7:2 +A1:22 +A2:26 28.11.214 H.E.E.Q.A.C Report No. 5432-1 E -Type Testing of BS-657/MAR in accordance with EN 54-5:2 +A1:22, EN 54-7:2 +A1:22 +A2:26 28.11.214 H.E.E.Q.A.C Report No. 5415-1 E -Type Testing of BSR-771/A/MAR in accordance with EN 54-17:25/ AC: 27 3.4.215 H.E.E.Q.A.C Report No. 54111-1 E -Type Testing of BSR-214/MAR, BSR-655/A/ MAR, BSR-66/A/MAR, BSR-536/A/MAR, BSR-657/A/MAR, BSR-817/MAR, BSR-771/A/ MAR, BSR-2/MAR, BS-655/MAR, BS- 536/MAR, BS-657/MAR, BSR-2114/MAR in accordance with IEC 692-54 3rd Ed. :21 +Cor1:211, IEC 6533 2nd Ed.:1999, IACS E1 REV.6, Rev.6 Oct 214 1.6.215 H.E.E.Q.A.C Report No. 54112-1 E -Type Testing of BSR-214/MAR, BSR-655/A/ MAR, BSR-66/A/MAR, BSR-536/A/MAR, BSR-657/A/MAR, BSR-817/MAR, BSR-771/A/ MAR, BSR-2/MAR, BS-655/MAR, BS- 536/MAR, BS-657/MAR, BSR-2114/MAR in accordance with IEC 692-54 3rd Ed. :21 +Cor1:211, IACS E1 REV.6, Rev.6 Oct 214 1.6.215 H.E.E.Q.A.C Report No. 54126-1 E -Type Identity Verification of BSR-2114/MAR, BSR-214/MAR to Type Tested in accordance with EN 54-2:1997+A1:26, EN 54-4:1997 +A1:22 +A2:26 1.5.215 BRE GLOBAL Report No.TE248823 - Technical evaluation of the Olympia Electronics S.A, BSR-21 range of analogue addressable control and indicating equipment to EN54-2:1997 + A1:26, EN54-4:1997+A1:22+A2:26 and EN 513-4 :1995+A1:1998+A2:23 17.12.21
4 of 5 4 November 215 BRE GLOBAL Report No.TE248823-SW - Software evaluation of the Olympia Electronics S.A, BSR-21 range of control & indicating equipment to the requirements of Clause 13 in EN 54-2 2.12.21 H.E.E.Q.A.C Report No. 54126-2 E -Type Identity Verification of BSR-655/A/MAR, BS-655/MAR to Type Tested in accordance with EN 54-7:2 +A1:22 + A2:26 1.5.215 BRE GLOBAL Report No.TE255158 - Technical evaluation of the Olympia Electronics BSR-655/A Analogue Addressable Optical Smoke Detector and the BS-655 Conventional Optical Smoke Detector to EN 54-7: 2 + A1: 22 + A2: 26 4.11.213 H.E.E.Q.A.C Report No. 54126-3 E -Type Identity Verification of BSR-536/A/MAR, BS-536/MAR to Type Tested in accordance with EN 54-11:21 +A1:25 1.5.215 ΕVΡU A.S. Report No. 928S/212 - Type Testing of BSR-536/A/MAR in accordance with EN 54-11:21 +A1:25 17.6.212 ΕVΡU A.S. Report No. 928/212 - Type Testing of BSR-536/A/MAR in accordance with EN 54-11:21 +A1:25 15.6.212 ΕVΡU A.S. Report No. 236E/212 - Type Testing of BSR-536/A/MAR in accordance with EN 5522: 21, EN 513-4: 211, EN 54-11:21 +A1:25 15.6.212 ΕVΡU A.S. Report No. 943/211 - Type Testing of BS-536/MAR in accordance with EN 54-11:21 +A1:25 1.12.211 H.E.E.Q.A.C Report No. 5418-1 E - Type Testing of BSR-2 / MAR in accordance with EN 54-2:1997+A1:26, EN 54-4:1997 +A1:22 +A2:26 3.4.215 H.E.E.Q.A.C Report No. 54153- E - IP44 INGRESS PROTECTION DEGREE TESTING OF BSR-655/A/MAR, BSR- 536/A/MAR, BSR-657/A/MAR, BS-655/MAR, BS-657/MAR, BS-536/MAR AND IP22 INGRESS PROTECTION DEGREE TESTING OF BSR- 66/A/MAR in accordance with EN 6529:1991 +Α1:2 +Α2:213 25.9.215 CONDITIONS OF CERTIFICATION 1. Production items of the subject equipment are to be manufactured in accordance with either an approved Production Quality Assurance system (Module D), a Product-Quality assurance system (Module E) or Product Verification Process (Module F). The wheelmark cannot be affixed to the product until a conformity assessment module is in place. 2. Each item, batch or lot of the equipment is to be issued with a Declaration of Conformity and have the Mark of Conformity affixed after a conformity assessment module is in place. 3. If the specified standards are amended during the validity of this Certificate, this product type is to be reapproved prior to it being supplied to vessels to which the amended standards apply. 4. Should a change of Place of Production from that stated below be required, i.e. where the final stages of manufacture/assembly/testing of this product take place, the new Place of Production is to be advised to us prior to the change taking place. This Certificate will require to be updated for Approval to be maintained. 5. Installation on board: The arrangements and installation of the system on board the vessel are not part of this design appraisal and certificate. All such arrangements are to be to the satisfaction of the Surveyors attending on board. 6. The following standards are not applicable to this equipment: - EN 6332-1-2 (24) and - IEC 692-376 (23).
5 of 5 4 November 215 PLACE OF PRODUCTION Olympia Electronics -N.D.LAKASAS P.N.ARVANITIDIS S.A 72nd km Thessaloniki Katerini National Road 661 Kolindros- Greece Lloyd's Register Verification Ltd LR427.213.12 P.A. Huntley-Hawkins Marine Technology and Engineering Services Lloyd s Register EMEA Direct phone: +44 () 33 41 432 E-mail: electrotechnical@lr.org For and on behalf of Lloyd s Register Verification LRV EC Distinguishing No. 38