John Basbagill, Sarah Russell-Smith, Cris Wise CEE 243

Similar documents
AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

IT S HOT UP HERE! A STUDY OF THERMAL COMFORT IN THE LILLIS BUSINESS COMPLEX 4TH FLOOR OFFICES

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO

Harrington Tower Building

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TC-9102 Applications

DEHITMIDlFICATION WITHOUT REHEAT USING FACE AND BYPASS DAMPERS

BUILDING VENTILATION GUIDE

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Owner s Manual. Part Number 33CSSP2-FC BACK LIT LIQUID CRYSTAL DISPLAY MODE BUTTON

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

Welsh Commissioning Group, Inc.

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION

Temperature Relative Humidity

Appendix 13. Categories of Cooling and Heating systems

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

HUMIDITY CONTROL IN A BASEMENT ART VAULT

Demonstration of 2nd Generation Ducted GE "Brillion" Hybrid Water Heater in the PNNL Lab Homes

WELCOME Webinar: South Central Region December 15, 2010

Installer Guide. WARNING Important Safety Information. 1 Specifications

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

b.) Technical Information:

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

Winter Energy Saving Tips

INSTALLATION & OPERATIONS MANUAL

ASHRAE Guideline 36 Advanced HVAC Control Sequences

Relative Humidity in Schools Jim Cummings and Chuck Withers

Computing Services Center

Installer Guide. WARNING Important Safety Information. 1 Specifications

LAZY A/C with KEN GEHRING President Emeritus at Therma-Stor LAZY AC

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Air Conditioning Options Winnetka Public School District 36 Winnetka, Illinois November 4, 2016

To: Steve Ardolf, MSU Mankato From: Chris Plum, CEE. CC: Tim Ellingson, CEE. Angela Vreeland, CEE Dan Briese, MSU Mankato Date: April 21, 2014.

Priorclave Tactrol Controller Warning Lights and Fault Codes

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

Redesign of Bennett Hall HVAC System

Continuous Commissioning of Commercial Kitchen and Dining Facilities Case Study

Civil Engineering Building

TESTS OF ADSIL COATING

OTFAMU Fresh Air Make Up System For Chilled Water OPERATOR S MANUAL. Technicold Marine Systems

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

TEC210x-2 Series Networked Thermostats

Unico Training. Class for R E Michel Salesmen

Displacement Ventilation in Classrooms

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

User reference guide. Daikin Altherma Low temperature split EHBH04CB EHBH08CB EHBH11CB EHBH16CB EHBX04CB EHBX08CB EHBX11CB EHBX16CB

Calculated Energy Savings for Disabling Anti- Sweat Door Heat on Glass Display Case Doors

HVAC Controls Upgrades: Requirement Details ( )

JH Series Installation

Zone. In the. Contractors and technicians may often find themselves. In today s wired world, zoning has evolved from wired to wireless.

HVAC Controls Upgrades: Requirement Details ( )

Homer High Tunnel Data Comparisons,

Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International

Continuous Commissioning: A Valuable Partner to Retrofit Projects

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

ENGINEERING. Edition No. 13 October 2002

Assigning profiles to an e-stack or Passive Stack (S1500, S1200 & R-Series)

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

Humidity Control in Tropical Climate with Heat Pipes - The GREEN Way

COMcheck Software Version Review Mechanical Compliance Certificate

Air Conditioning Control. Air Cond. to program : AC001. MODEL 3000 / ACCESS 4000 Programmer s Manual - Aircon. Rev 4.50 [MENU 7-5-6] p 1.

Benefits Offered by Passive Dehumidification Wheel Speed Control

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

ASHRAE JOURNAL ON REHEAT

Model 1750A/ 1770A Dehumidifier Installation Instructions

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

How Ground Source Heat Pumps Work

The following report is prepared and published by:

1.0 Digital Controller

I/O ZONE 560/583 USERS GUIDE

Study Final Report. Priority Cool Refrigerant Study

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

Table 1. Serie of Digital Room Thermostats.

GARCIA GALUSKA DESOUSA Consulting Engineers

A-Series Parameters and Symptoms Over Time ( ) Note: All high-resolution photos; zoom in for clear details.

THERMAL ICE STORAGE: Application & Design Guide

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

RSMSD Technical Guide

Mechanical Technical Report 3. Mechanical Systems Existing Conditions Evaluation

ENGLISH REMOTE CONTROL MANUAL

Victoria & Albert Museum, London Medieval & Renaissance Galleries: A Passive Approach to Humidity Control

MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

MicroTech Unit Ventilator

Reference Guide for Microprocessor Controller

CEE 243. Week 2 HVAC systems at Y2E2

MicroTech II Vertical Self-Contained Unit Controller

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

McQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC)

Fundamentals of Hydronic Design

Installation and Advanced Programming Instructions. HP8211-1RJ and HP8321-1RJ Heat Pump Thermostats

Service Step by Step Trouble-Shooting Check-List

Transcription:

SCC systems analysis John Basbagill, Sarah Russell-Smith, Cris Wise CEE 243 June 2, 2010

Big Ideas Functional intents are based on set points given in SCC Facility Data Manual. When data does not match functional intent, consultation with building manager is needed to determine whether functional intent values are correct. Air handlers maintain space air temperatures with minimal fluctuations. ti For AH42, 52, 62, 72, 82 & 92, space air temperatures are consistently lower than functional intent: -verify 74±2 F set point for AH42-82 -verify 75±2 F set point for AH92 -determine whether cooling coil is functioning as intended Unexpected positive correlations exist between space air temperatures and OAT. 2

Legends Used on Graphs Functional Status Legend Needs immediate attention; little consistency with functional intent; major issue(s) System working but a few issues to be addressed; some consistency with functional intent; moderate issue(s) System is performing as intended; much consistency with functional intent; no/very minor issue(s) Annotations Used in Graphs Functional Intent Inconsistent Consistent Green line(s) indicate functional intent. Red highlights anomalies or patterns inconsistent with functional intent. Black highlights patterns consistent with functional intent. 3

Systems Summary System AH01 AH02 Functional Status Area Served Basement Basement Major Problem(s) Space air temperatures 2-4 F below Manual set point Space air temperatures 2-4 F below Manual set point AH42 4 th floor day room & multi-purpose room Space air temperatures 4 F below Manual set point AH52 AH62 AH72 AH82 5 th floor day room & multi-purpose room Space air temperatures 2-4 F below Manual set point 6 th floor day room & multi-purpose room Space air temperatures 3-5 F below Manual set point. 7 th floor day room & multi-purpose room High fluctuation in space air temperature. Damper 8 th floor day room & multi-purpose room valve closes. Space air temperatures 2 F below Manual set point. Heating/cooling coil valve position always 50%. AH92 Small Chilled Water Loop 9 th floor day room & multi-purpose room Ground floor server room Space air temperatures 2-3 F below Manual set point. Mixed air and supply air positively correlate with OAT for colder temperatures. Supply water temperature 3-5 F below Manual set point. 4

AH42 Air Temperature (44) POD A/B/C Day Room POD A/B/C Multi Purpose Supply Air Temperature (245) Valve Position (47) On/Off Status(272) Air Temperature (46) Mixed Air Temperature (45) Cooling Coil Economizer Supply Fan Return Fan Heating Coil Cooling Coil Supply Air Temperature (243) Combined Valve Position (43) Outside Air Damper Position (244) Return FanOn/Off Status (246) 5

Summary of the AH42 System Functional Status Functional Intent Patterns Consistent w/ Functional Intent Patterns Inconsistent w/ Functional Intent Day room and multi-purpose rooms are maintained at 74±2 F. Day room and multi-purpose room temperatures stay fairly constant. 1. Day room ranges from 69-73 F and averages 72 F. Multi-purpose room ranges from 65-78 and averages 71 F F. 2. Supply air temperature is too cold and range is too large. Testable Hypothesis 1. Multi-purpose p room space temperature is set 4 degrees below manual set point. 2. Cooling coil valve position causes supply air temperature to be too cold. Conclusions/Recommendations Space temperature does not align with Manual set point. Supply temperature and cooling coil position work together as expected. Cooling coil is open too much in cold weather. Determine whether cooling coil is malfunctioning. Determine whether actual set point is correct or if manual gives correct set point. Rewrite manual set point if incorrect. 6

AH42 Day Room Space Air Temp. vs. OAT Multi-Purpose Room Space Air Temp. vs. OAT AH42-Day Room SpaceAirTemperature (44) [Deg F] AH42-Multi-Purpose Room SpaceAirTemperature (46) [Deg F] Space temperature stays fairly constant Day room temperature slightly below deadbanddb d Multi purpose room temperature below deadband. Multi-purpose room temperature positively correlates with OAT 7

AH42 Day Room & Multi-Purpose Room Space Air Temp. vs. Time AH42 Day Room SpaceAirTemperature (44) [Deg F] AH42 Multi-Purpose Room SpaceAirTemperature (46) [Deg F] Both space air temperatures suddenly decrease by 2 in late September; change in set point? (from 2/1/2009 12:00:00 AM to 12/31/2009 11:59:00 PM) Multi-purpose room air temperature t consistently tl lower than functional intent and day room air temperature Yes! T 8

AH42 Multi-Purpose Room Supply Air Temp., Cooling Coil Valve Position vs. OAT Constant value agrees with Building EQ pattern but no data in warm weather Multi-Purpose Room Supply Air Temp., Cooling Coil Valve Position vs. Time Cooling coil and supply air temperature work together as expected (11/212009 from 7:15 PM to 8:15 PM) Cooling coil valve position open during cold weather Cooling coil valve position positively correlates with OAT 9

AH52 Air Temperature (64) POD A/B/C Day Room POD A/B/C Multi Purpose Valve Position (67) On/Off Status(260) Air Temperature (66) Mixed Air Temperature (65) Cooling Coil Supply Fan Economizer Return Fan Heating Coil Cooling Coil Combined Valve Position (63) Outside Air Damper Position (261) Return FanOn/Off Status (262) 10

Summary of the AH52 System Functional Status Functional Intent Patterns Consistent w/ Functional Intent Day room and multi-purpose rooms are at 74±2 F. Both space temperature dead bands are within ±2 F. Patterns Inconsistent w/ Functional Intent Day room 3 F below functional intent. Multi-purpose room 5 F below functional intent. Testable Hypothesis 1. Space temperatures are set 3 and 5 F below manual set point. 2. Cooling coil providing too much cooling. Conclusions/Recommendations Cooling coil and damper not open, so inconclusive why spaces are below functional intent. Determine whether cooling coil is ever fully open. Determine actual set points for both spaces and rewrite manual if different than manual set point. 11

AH52 Day Room Space Air Temp. vs. OAT Multi-Purpose Room Space Air Temp. vs. OAT Day room air temperature consistently lower than functional intent. Slight positive correlation with OAT. Multi-purpose room temperature does not cross functional intent deadband 12

AH52 Day Room Heating/Cooling Coil Combined Valve Position vs. OAT Multi-Purpose Room Cooling Coil Valve Position vs. OAT Day room is being heated and cooled Valve position never fully open, so no cooling to multi-purpose room? Cooling coil either closed (heating only) or open only 50% (no heating or cooling) in warmer weather 13

AH52 Outside Air Damper Position vs. OAT Damper never closed/open? 14

AH62 Air Temperature (84) POD A/B/C Day Room POD A/B/C Multi Purpose Valve Position (87) On/Off Status(272) Air Temperature (86) Mixed Air Temperature (85) Cooling Coil Supply Fan Economizer Return Fan Heating Coil Cooling Coil Outside Air Combined Valve Damper Position (273) Position (83) Return FanOn/Off Status (262) 15

Summary of the AH62 System Functional Status Functional Intent Day room and multi-purpose rooms are set at 74±2 F. Rooms should receive 100% air replacement. Patterns Consistent w/ Functional Intent 1. Day room and multi-purpose room temperatures stay fairly constant. 2. Mixed air temperature positively correlates with OAT. Patterns Inconsistent w/ Functional Intent 1. Day room and multi-purpose rooms average 73 F ±5 F. 2. Damper valve periodically closes. Testable Hypothesis Spaces have a high range of temperatures because occupancy levels change dramatically. Conclusions/Recommendations Investigate occupancy levels of the day room and multi-purpose room. 16

AH62 Outside Air Damper Position vs. OAT 100% is fully closed and 0% is fully open. Damper is closed periodically. Fans run continuously so damper should always be open for 100% air replacement. 17

AH62 Outside Air Damper Position vs. Time Outside Air Damper Position vs. Time Periodic closing of damper valve; air should be 100% replaced Damper valve periodically closes for about 1½ hours 18

AH72 Air Temperature (104) POD A/B/C Day Room POD A/B/C Multi Purpose Vl Valve Position (107) On/Off Status(284) Air Temperature (106) Mixed Air Temperature (105) Cooling Coil Economizer Supply Fan Return Fan Heating Coil Cooling Coil Combined Valve Position (103) Outside Air Damper Position (285) Return FanOn/Off Status (286) 19

Summary of the AH72 System Functional Status Functional Intent Day room and multi-purpose rooms maintained at 74±2 F. Damper position should be 100% open for 100% air replacement. Patterns Consistent w/ Functional Intent Day room and multi-purpose room temperatures stay fairly constant. Mixed air temperature positively correlates with OAT. Patterns Inconsistent w/ Functional Intent Day room and multi-purpose room temperatures are low with the average for each at ~72 F. Testable Hypothesis Set point listed in manual is not the same as set point for which system was actually configured. Conclusions/Recommendations Check set points for consistency across manual and physical system. 20

AH72 Multi-Purpose Room Space Air Temp. vs. OAT Set point temperature appears to be 72 F. Space temperature has slight positive correlation with OAT. Slight dip could indicate over cooling 21

AH72 Day Room & Multi-Purpose Room Space Air Temp. vs. Time AH72 Day Room Space Air Temperature (104) [Deg F] AH72 Multi-Purpose Room Space Air Temperature (106) [Deg F] Drop in average temperature; was there a change in set point? (from 12/18/2009 12:00:00 AM to 4/7/2010 11:59:00 PM) 22

AH82 Air Temperature (124) POD A/B/C Day Room POD A/B/C Multi Purpose Valve Position (127) On/Off Status(296) Air Temperature (126) Mixed Air Temperature (125) Cooling Coil Economizer Supply Fan Return Fan Heating Coil Cooling Coil Combined Valve Position (123) Outside Air Damper Position (297) Return FanOn/Off Status (298) 23

Functional Status Summary of the AH82 System Functional Intent Patterns Consistent w/ Functional Intent Patterns Inconsistent w/ Functional Intent Testable Hypothesis Conclusions/Recommendations Day room and multi-purpose room maintained at 74±2 F. Day room and multi-purpose room temperatures stay fairly constant. Mixed air temperature positively correlates with OAT. 1. Temperature for each room is maintained at a temperature lower than expected. Day room averages 71 F and multi-purpose room averages 72 F. 2. Heating/cooling coil valve position data shows that no heating/cooling is occurring. 1. Temperature set point listed in manual is not the same as set point for which system was actually configured. 2. Heating/cooling coil sensor is not measuring actual position. Check set points for consistency across manual and physical system. Physically y verify if heating/cooling coils are functioning. 24

AH82 Day Room & Multi-Purpose Room Space Air Temp. and Mixed Air Temp. vs. OAT Day Room Multi-Purpose Room Mixed air temperature positively correlates with OAT Both space air temperatures lower than assumed functional intent over a wide temperature range 25

AH82 Day Room & Multi-Purpose Room Space Air Temp. and OAT vs. Time Day Room Multi-Purpose Room Day room space air temperature negatively correlates with OAT Multi-purpose room space air temperature remains relatively constant (from 3/10/2010 12:00:00 AM to 3/15/2010 00:00:00 PM) 26

AH82 Day Room Space Air Temp. & Heat/Cool Coil Combined Valve Position vs. Time AH82 is neither heating nor cooling all year regardless of winter/summer seasons 27

AH92 28

Summary of the AH92 System Functional Status Functional Intent 1. Penthouse mechanical room supply temperature is maintained at 75±2 F F. 2. Mixed air temperature is maintained at 65±2 F. Patterns Consistent w/ Functional Intent Mechanical room is 75 F when OAT is 65 F and above. Patterns Inconsistent w/ Functional Intent 1. For OAT 35-65 F, mechanical room space temperature positively correlates with OAT, increasing until the room reaches 70 F. 2. Mixed air temperature positively correlates with OAT. 3. Outside air damper position remains fully open when OAT is below 56 F. Testable Hypothesis Conclusions/Recommendations 1. Mixed air temperature set point listed in manual is incorrect. 2. Outside air damper position does not close when OAT is very cold (i.e., below 56 F) Mixed air temperature positively correlates with OAT. Verify set point for mixed air temperature. Space air temperature is below functional intent when OAT is below 60 F. Check if valve is physically closing at colder OAT temperatures. 29

AH92 Penthouse Mechanical Room Space Air Temp. vs. OAT Unexplained djump in supply temperature. There is a small positive correlation with space temperature and OAT. Is this during cold months? Space air temperature almost consistently matches functional intent when OAT exceeds 70ºF. 30

AH92 Penthouse Mechanical Room Space Air Temp. vs. Time Was this a really hot day? Space air temperature oscillates daily with OAT, until OAT is very hot. Yes! This spike During winter months, corresponds to space temperature t is very high OAT frequently lower than functional intent. (from 2/15/2009 12:00:00 AM to 2/28/2010 11:59:00 PM) 31

AH92 Outside Air Damper Position vs. OAT There is a positive correlation, as OAT increases the damper position closes The damper is fully open when it is really cold. This will cause the air to be too cold and the AH only has a cooling coil.. The damper is fully open when it is hot. This will make AH92 have to cool more. 32

Actions to Take Consult building manager to determine if Manual set points are correct. Check whether coil valve position is operating according to functional intent. Verify whether damper valves are closed when Manual says they should be open. Determine whether high range of space air temperatures is due to high occupancy levels. If so, see whether occupants are uncomfortable; if so, find ways to reduce range for these occupancy loads. 33

Questions? 34