Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Similar documents
Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Purdue e-pubs. Purdue University

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Development and Application of Micro Channel Heat Exchanger for Heat Pump

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

R32 Compressor for Air conditioning and Refrigeration applications in China

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

Low GWP Refrigerants for Air Conditioning Applications

Purdue e-pubs. Purdue University. Ian H. Bell Purdue University. Eckhard A. Groll Purdue University

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

A Literature Review On Heat Exchanger Air Side Fouling In Heating, Ventilation And Airconditioning

Control Method Of Circulating Refrigerant Amount For Heat Pump System

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Study of R161 Refrigerant for Residential Airconditioning

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Air-Cooled Heat Exchanger Performance for R410A

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

System Using Exhaust Heat from Residential GHPs

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Experimental Investigation of Purification Function of Air Conditioner

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Sub-Critical Operation of the CO2 Expander/ Compressor

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Performance Measurement of R32 Vapor Injection Heat Pump System

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Performance of CO2 Cycles with a Two-Stage Compressor

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Efficiency of Non-Azeotropic Refrigerant Cycle

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Experimental and Numerical Study on a Dryexpansion Shell-and-Tube Evaporator Used in Wastewater Source Heat Pump (WWSHP)

Experimental Study on the Performance of Twisted Capillary Tube

Compressor Capacity Control

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

Low Global Warming Refrigerants For Commercial Refrigeration Systems

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Diagnosing Troubles in Refrigeration Units with Screw Compressors

High Efficiency R-134a Compressor for Domestic Refrigerator

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Geothermal ORC Systems Using Large Screw Expanders

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

Development of HFC-134a Compressor for Domestic Refrigerator

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Advanced round-tube, plate-fin (RTPF) heat-exchanger coils contribute to the high efficiency of heat pumps

Key words: heat exchanger, fouling, pressure drop

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Global Journal of Engineering Science and Research Management

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Development of Large Refrigerant Compressors

Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger Bo Xu Shanghai Jiao Tong University, China, People's Republic of, xubo88888888@aliyun.com Junye Shi Shanghai Jiao Tong University, China, People's Republic of, jpchen70@aliyun.com Ying Wang Shanghai Jiao Tong University, China, People's Republic of Jiangping Chen Shanghai Jiao Tong University, China, People's Republic of Feng Li SICHUAN CHANGHONG ELECTRIC CO.,LTD, China, People's Republic of See next page for additional authors Follow this and additional works at: http://docs.lib.purdue.edu/iracc Xu, Bo; Shi, Junye; Wang, Ying; Chen, Jiangping; Li, Feng; and Li, Dong, "Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger" (2014). International Refrigeration and Air Conditioning Conference. Paper 1370. http://docs.lib.purdue.edu/iracc/1370 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

Authors Bo Xu, Junye Shi, Ying Wang, Jiangping Chen, Feng Li, and Dong Li This article is available at Purdue e-pubs: http://docs.lib.purdue.edu/iracc/1370

2140, Page 1 Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger Bo Xu 1 *, Junye Shi 1, Ying Wang 1, Jiangping Chen 1, Feng Li 2, Nianjie Wang 2, Wei Dong 2 1 Shanghai Jiaotong University, Shanghai, China +8602134206087, xubo88888888@aliyun.com 2 SICHUAN CHANGHONG ELECTRIC CO.,LTD Mianyang, China * Corresponding Author ABSTRACT Microchannel heat exchanger (MCHX) has many advantages compared with traditional heat exchanger. The research and application of it also develop fast in recent years. However, in the stationary and commercial air conditioning field, it has not been widely used yet. One of the obstacles is the dust fouling. The affect of dust fouling problem on air conditioning systems with louver fin and wavy fin was researched in this article. The results show the fouling problem of the MCHX can cause drastically performance degradation of the system, the cooling capacity decreased by 23% and 17.2%, the energy consumption increased by 52.5% and 28.4%, and COP decreased by 49.5% and 35.6% for air condition systems with louver fin and wavy fin MCHX respectively after they run for 3 months in the factory environment. Based on this situation, a fan blowback control strategy was introduced into the air conditioning system. After added the control strategy, the cooling capacity decreased by 5.5% and 2%, the energy consumption increased by 7.8% and 2.3%, and COP decreased by 12.3% and 4.3% for the systems with louver fin and wavy fin MCHX respectively. 1. INTRODUCTION Microchannel heat exchanger (MCHX) has been widely used in mobile air conditioning system because of its advantages of lower weight, more compact, higher efficiency, and smaller inner volume for refrigerant charge reduction. It also has a good prospect in the stationary and commercial air conditioning field. However, because the air face velocity in the stationary air conditioning is relative lower than mobile system, MCHX is easier to have dust choked, which results the drastically decreasing of the performance of the system. This problem is the main obstacle that MCHX is widely used in household air conditioners. Many researchers have studied about the foul problem of the MCHX. Ali and Ismail (2008) experimentally investigated evaporator air-side fouling of room air-conditioners showing that COP decreased by more than 57% due to 300g of real fouling collected from various evaporator coils. Ian and Echhard (2011) studied about the air-side pressure drop of MCHX because of particulate fouling and found that the air-side pressure drop of the MCHX can increased over 200% for a dust injection of 267g. It s difficult to solve the problem because the compact design of the MCHX and fin -flat tube network structure, like grill, makes the fibers dust easy to block between the fins. In this paper, we put forward a novel control strategy: after a period of running time, the condenser fan reversely blows for a few minutes to blow away the fibers dust on the surface. And its performance was compared with the original system. 2. TEST SAMPLES AND EQUIPMENTS

2140, Page 2 2.1 Test sample As shown in figure 1, two types of MCHX were tested in this experiment. One is louver fin MCHX(#1), the other is wavy fin MCHX(#2). As their different shapes and structures of fins, the fouling condition on the surface of MCHX will be different after a period of time, so will be their performance. The parameters and specifications of the two samples can be observed in table 1 Figure 1: Simple structure diagram of louver fin (a) and wavy fin (b) Table 1: Comparison of different parameters of samples Heat exchanger #1(louver fin MCHX) #2(wavy fin MCHX) Dimentions(mm) 575 500 16 550 500 20 Fin thichness(mm) 0.1 0.1 Fin pitch(mm) 1.4 1.4 Fin height(mm) 8 8 Size of tube(mm) 16 2 20 2 Number of tube row 1 1 Wavy length/height(mm) - 6/2.6 Louver angel( ) 27-2.2 Test equipment In the test, we replace the condenser of the traditional air conditioning system into the MCHX. To test whether the fan blowback control strategy works or not, we prepare two groups of experimental systems. Each group contains two air conditioning systems with louver fin and wavy fin respectively. The group running just as traditional air condition called group one. The other group called group two, their condenser fan will blowback 5 minutes every day according to the control strategy. The performance of the systems was tested on the enthalpy difference method test bench. The initial performance was tested and recorded as baseline without fouling on the condenser. Then they were installed in the real room for long-term running to observe the fouling problem and its impact on the system performance. After a period of time, the systems were sent back to test again. The test condition was set according to the requirement of Chinese national standard GB/T7225 (QSIQ, 2004). As shown in figure 2, the test bench includes evaporator and condenser chamber, and each chamber owns a set of air condition unit which is responsible for controlling the room air condition. The wind tunnel in the evaporator chmber can measure air volume flow rate and outlet enthalpy, which are used to calculate the refrigeration capacity of tested air conditioning system. The test accuracy of each parameter can be observed in table 2

2140, Page 3 1 outdoor unit with condenser; 2 expansion valve; 3 environmental control; 4 wind tunnel; 5 evaporator Figure 2: Schematic of enthalpy difference method test bench Table 2: Test accuracy of different parameters Measures Parameters Testing range Accuracy Temperature (a) -10~50 ±0.1 (b) -10~120 ±0.5 Power 0~5000 W ±5 W Air-pressure drop (a)-50~500 Pa ±2.5 Pa (b) 0~1000 Pa ±2.5 Pa Analyzed parameters Uncertainty Heat transfer rate ±3% COP ±3% 3. EXPERIMENTAL RESULTS AND ANALYSIS 3.1 The performance comparison of group 1 systems As shown in figure 3 to 5, the long-term performance of two air conditioning systems with louver fin and wavy fin MCHX were experimentally studied in the factory environment, where fibers accounted for a large proportion of dust. We can find that one month later, the cooling capacity decreased by 3.2% and 0.7%, the energy consumption increased by 7.4% and 2.9%, and COP decreased by 10.1% and 3.4% for #1(louver fin MCHX) and #2(wavy fin MCHX) respectively. After 3 months later, the performance of the systems decrease drastically, the cooling capacity decreased by 23% and 17.2%, the energy consumption increased by 52.5% and 28.4%, and COP decreased by 49.5% and 35.6% for #1 and #2 respectively. We can see both sytems have a decrease in performance because of fouling, and the decrease of system with #1 is quicker and more serious than #2, because the louver gap can capture the small fibers dust easier than the wavy gap. At the early stage of the experiment, the decrease of the performance of wavy fin MCHX is not apparent yet, however, after 3 months, its decreasing is still very serious because the compact design of the MCHX makes the fibers dust blocked. As shown in figure 6, we took photographs of two MCHX after they run for three months.).

2140, Page 4 Figure 3: The comparison of the cooling capacity of group 1 on different time Figure 4: The comparison of the energy consumption of group 1 on different time Figure 5: The comparison of COP of group 1 on different time

2140, Page 5 Figure 6: The dust on #1(a) and #2(b) of the group 1 air condition systems after 3 months As shown in figure 7 and 8, the condensing temperature and discharge temperature of compressor were measured in the experiment. We can see as the dust choked the fin gap, the condensing temperature and the discharge temperature of the compressor both become higher. This is mainly because the fibers dust choked the space between the fins, which results the drastically decreasing of the heat transfer efficiency of the condensor, so the heat transfer temperature difference and condensing temperature increases. Meanwhile, as the discharge temperature and pressure of condenser increases, the compression ratio becomes higher, which causes the increases of energy consumption and decreases of COP. Figure 7: The discharge temperature of compressor of group 1 systems on different time

2140, Page 6 Figure 8: The condensing temperature of group 1 systems on different time 3.2 The performance comparison of group 1 and group 2 As described above, we added group 2 which run according to the control strategy to verify its effectiveness. We tested the perfoamance of group 2 and compared with group 1, which is shown in figure 9 to 11. We can see the performance of group 2 improved a lot compared with group 1. After they run for 3 months, the cooling capacity decreased by 5.5% and 2%, the energy consumption increased by 7.8% and 2.3%, and COP decreased by 12.3% and 4.3% for louver fin and wavy fin MCHX respectively. This is main because the regularly blowback of the fan can prevent the fibers dust depositing on the surface of the MCHX and the particulate dust blocking the flow channel of the air. Though there still have a layer of dust on the surface of the fin, it just affects the heat transfer coefficient and doesn t decrease the air volume of the condensor, so the decrease of heat transfer of the condensor is limited, which results the better performance of group 2. We can also find that the perfoamance of the system with wavy fin MCHX is better than the system with louver fin, this is main because the dust on the surface of the wavy fin can be blowed out more easily than the louver fin. This also proved by figure 12, which shows the detail condition of the fin. Figure 9: The comparison of the cooling capacity of two groups on different time

2140, Page 7 Figure 10: The comparison of the energy consumption of two groups on different time Figure 11: The comparison of COP of two groups on different time Figure 12: The dust on #1(a) and #2(b) of the group 2 air condition systems after 3 months

2140, Page 8 4. CONCLUSION From the test result and analysis above, we can conclude: Fouling problem of the MCHX can cause drastically performance degradation of the system, for the traditional air condition systems with MCHX which running in the factory environment, the performance of the systems decrease drastically, the cooling capacity decreased by 23% and 17.2%, the energy consumption increased by 52.5% and 28.4%, and COP decreased by 49.5% and 35.6% for louver fin MCHX and wavy fin MCHX respectively 3 months later. As the dust choked the fin gap, which results the decreasing of the heat transfer efficiency of the condenser, the condensing temperature and the discharge temperature of the compressor both become higher. The fan back control strategy can help to solve the dust fouling problem effectively, for the air condition systems added the control strategy, the cooling capacity decreased by 5.5% and 2%, the energy consumption increased by 7.8% and 2.3%, and COP decreased by 12.3% and 4.3% for louver fin and wavy fin MCHX respectively 3 months later. The performance of the air condition system with wavy fin is better than the louver fin in both conditons. Especially after added the control strategy, the perfoamance of the air condition system the wavy fan MCHX is much better than before. This can provide a soulution to solve the dust fouling problem and provide advices for the further researches. REFERENCES Ali, A. H. H, Ismail, I. M. 2008. Evaporator air-side fouling: effect on performance of room air conditioners and impact on indoor air quality. HVAC & R Research vol. 14, no. 2: p. 209-219 Ian H. Bell, Eckhard A. Groll. 2011. Air-side particulate fouling of microchannel heat exchangers: Experimental comparison of air-side pressure drop and heat transfer with plant-fin heat exchanger. Applied Thermal Engineering, vol. 31: p. 724-749 Ian H. Bell, Eckhard A. Groll, H. Konig. 2011. Experimental analysis of the effects of particulate fouling on geat exchanger heat transfer and air side pressure drop for a hybrid dry cooler, Heat Transfer Engineering, vol. 32: p. 264-271 QSIQ (China Administration of Quality Supervision, Inspection and Quarantine). Room air conditioners. Beijing, China; 2004, GB/T7725-2004. ACKNOWLEDGEMENT The paper is supported by Key Technologies R&D Program of China during the 12th Five-Year Plan Period (2012BAF01B06 ).