AFTER SALES SERVICE DIV. SM 21

Similar documents
INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

KFTC Series 18,000 to 48,000 Btu/h Cooling Only & Heat Pump INSTALLATION MANUAL

GHP OUTDOOR UNIT INSTALLATION INSTRUCTIONS E1 Combination Multi Type

The breaker trips at once when it is set to ON. The breaker trips in few minutes when it is set to ON.

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

DAIKIN AIR CONDITIONER

INSTALLATION MANUAL Duct Type Series MH FECA

Split-type Air-Conditioner

MXZ-4B80VA MXZ-5B100VA INSTALLATION MANUAL

INSTALLATION MANUAL. AIR CONDITIONER Indoor Unit (Duct type) PART No Contents. En-1 1. SAFETY PRECAUTIONS WARNING

INSTALLATION MANUAL For authorized service personnel only.

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3B54VA MXZ-4B71VA. English

Split-type Air-Conditioner

INSTALLATION INSTRUCTION

1. BEFORE INSTALLATION

Split-type Air-Conditioner

1. BEFORE INSTALLATION

A/C-HEATER SYSTEM - MANUAL

1. BEFORE INSTALLATION

Operation & Installation Manual

1. BEFORE INSTALLATION

Air Conditioner. user installation & manual manual. imagine the possibilities

60Hz R410A ON/OFF CONDENSING UNIT MODEL: MTVCN. Service Manual Contents

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

Safety Precautions (1)

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

FLOOR TYPE AIR CONDITIONERS

BR342 Ducted Installation Instructions Australian Version Electronic Wall Control

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION MANUAL. R410A Split Series. Model RXS24LVJU. Installation manual R410A Split series. Manual de instalación Serie Split R410A.

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Instructions for Operation and Maintenance of Containers

Installation Instructions

Installation Instructions

AIR CONDITIONER. Please read this owner, s manual carefully before using the air conditioner, and keep this manual for the future reference.

INSTALLATION INSTRUCTIONS

Installation Instructions

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E

TCB-DP22CUL. Drain Pump Kit. Model name : AIR CONDITIONER (SPLIT TYPE) Installation Manual. Installation Manual 2 Air Conditioner (Split type) English

INSTALLATION MANUAL. BP (Branch Provider) Unit. Models BPMKS967A2B BPMKS967A3B BPMKS967B2B BPMKS967B3B. Installation manual BP (Branch Provider) Unit

Horizontal/Side Discharge Condensing Units

InverterFlex Series Multi-Zone Ducted Indoor Unit B-VFH09DA-1 B-VFH12DA-1 B-VFH18DA-1 B-VFH24DA-1

MULTI HEAT PUMP PANEL CONSOLE TYPE DUCTLESS INVERTER INDOOR UNIT INSTALLATION MANUAL. Models: CH09MCU230VI CH12MCU230VI CH18MCU230VI

INSTALLATION MANUAL SPLIT TYPE ROOM AIR CONDITIONER (PART NO )

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English

Indoor Unit Operation & Installation Manual

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

Nortek Global HVAC, LLC

AIR CONDITIONER CASSETTE

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Installation Instructions

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM1403DT-A RAV-SM1603DT-A. Model name: Concealed Duct High Static Pressure Type

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

FAN COIL USER MANUAL TC18C2DWB1 TC24C2DWB1 TC37C2DWB1 TC48C2DWB1 TC60C2DWB Innovair Corporation. All Rights Reserved.

INSTALLATION INSTRUCTIONS

AIR CONDITIONER (MULTI TYPE) Installation Manual. Indoor Unit. Model name:

Part 3 Troubleshooting

CENTRAL AIR CONDITIONER SPLIT SYSTEM

1. BEFORE INSTALLATION

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

[FLARE CONNECTION TYPE] ATTENTION

INSTALLATION MANUAL. R410A Split Series. Models RXS15LVJU RXS18LVJU. Installation manual R410A Split series. Manuel dinstallation Série split R410A

Installation & Maintenance Manual

AIR CONDITIONER CASSETTE

Service Manual & Installation Manual

Using Portable Spot Air Conditioners in Industrial Applications

Installation Instructions

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2

Installation Manual MMU-AP0154SH-E MMU-AP0184SH-E MMU-AP0244SH-E AIR CONDITIONER (MULTI TYPE) Indoor Unit. Model name: 1-Way Cassette Type.

1.9 APPLICATION DATA Installation of indoor unit

SLIM CONCEALED DUCT AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL. Models:

Mini-Split Air Conditioner

Installation Instructions

AIR CONDITIONER BRANCH BOX INSTALLATION MANUAL. For authorized service personnel only. [UTP-PY03A] [UTP-PY02A] PART NO.

SPLIT SYSTEM Air Conditioners

FDT11 FDT15 FDT18. DUCTED TYPE SPLIT SYSTEMS (3 Phase, Fixed Speed)

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

FOR SLIM DUCT/CEILING TYPE

1. BEFORE INSTALLATION

Installation Instructions

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

WineZone Ceiling Mount Ductless Split 15

1. BEFORE INSTALLATION

AIR CONDITIONER (SPLIT TYPE) Installation Manual. Indoor Unit. Installation Manual 1 English. Kurulum kılavuzu 26 Türkçe.

OPERATION MANUAL. Split series room air conditioners Multi system room air conditioners FDBQ25B7V1

Installation Instructions

T.Sawano H.Segawa N.Tsuji H.Tomimoto

SLIDER CASEMENT AIR CONDITIONER

AIR CONDITIONER CASSETTE

13-1. Temperature Regulator

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

APPLICATION DATA SHEET

INSTALLATION MANUAL AIR CONDITIONER

INSTALLATION MANUAL. System Air Conditioner (Cooling and Heating) Cassette Type Series CH070CAV1 CH105CAV CH140CAV DB A(1) ENGLISH ESPAÑOL

INVERTER SPLIT - TYPE

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

GMZ2-14H-S GMZ2-18H-S

PJG012D008C F '17 PAC-T-268 CAUTION WARNING. (5) Duct connected-low / Middle static pressure type (FDUM) (a) Indoor unit SAFETY PRECAUTIONS

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

Transcription:

AFTER SALES SERVICE DIV. SM 21

CONTENTS 1. Trouble about refrigerant piping work (Page) 1-1) Trouble on cutting copper tubes!! 1(above) 1-2) Problem of storage of copper tubes!! 1(below) 1-3) Trouble caused by using thin wall tubes!! 2(above) 1-4) Trouble that the tubes are left without proper care!! 2(below) 1-5) Trouble caused by mixing foreign substances into tubes!! 3 1-6) Problem due to using REFNET JOINTS not recommended by DAIKIN!! 4(above) 1-7) Trouble due to REFNET JOINT connection fault!! 4(below) 2. Trouble about drain piping work 2-1) Problem caused by faulty selection of drain pipe size!! 5(above) 2-2) Table of specified drain pipes (for your reference) 5(below) 2-3) Problem of choke inside a drain pipe!! 6(above) 2-4) Problem of reverse gradient of drain piping!! 6(below) 2-5) Trouble by faulty selection of piping size for collective drain piping!! 7(above) 2-6) Suitable collective piping sizes for central drain system. 7(below) 3. Trouble about electric wiring work 3-1) Problem of seizure on power supply wiring!!(1) 8(above) 3-2) Problem of seizure on power supply wiring!!(2) 8(below)

1-1) Trouble on cutting copper tubes!! An actual example of cutting copper tubes with a hack saw instead of a regular tube cutter. Copper tubes were sawed off. The chips will go into tubes and create damage to the equipment while it runs. When a tube is sawed, a) the end is cut zigzag. b) the end is unevenly deformed. It will result in making poor flare to cause gas leakage. Be sure to cut tubes with a regular tube cutter to suit the pipe sizes. Always choose the proper size cutter among a large, a middle, and a small-sized cutter. Copper tube cutter large-sized type middle-sized type small-sized type 1-2) Problem of storage of copper tubes!! Piping materials are casually kept on the floor at a construction site. No seal plugs are placed on the ends of the tubes. No seal plugs are found on the ends of tubes. The tubes are directly laid on the floor. Since moisture, dust, sand, and rubbish could go into the tubes, these circulate in a refrigerant circuit during operation of the unit and are blocked at an expansion valve or a capillary tube, and also at a filter in the worst case, resulting in insufficient capacity and finally a malfunction will occur. Using the tube deformed on which a worker stepped may cause an insufficient capacity of the unit or an offensive noise due to the refrigerant passes through the narrow section of the tube. The best way is to store the tubes on a stand to prevent them from rolling. Put caps on both tube ends or wrap the ends with vinyl tape securely so that moisture, dust, rubbish and sand will not enter the tubes.

1-3) Trouble caused by using thin wall tubes!! An actual example of too thin wall tubes Even little stress can damage and deform the tube walls due to weakness. These tubes have less thickness in the wall than Daikin s recommended tubes. Accordingly high pressure during operation can cause the tubes to deform and crack resulting in gas leakage. As you see in the photo, since the tubes can easily hollow, the unit will operate with insufficient capacity. Also, sometimes, as the refrigerant passes through the narrow area, an offensive noise can be heard. Be sure to use copper tubes mentioned below. Tube OD [mm] Wall thickness of copper tubes specified by DAIKIN[mm] 6.35 0.8 9.52 0.8 12.7 0.8 15.9 1.0 19.1 1.0 22.2 1.2 1-4) Trouble that the tubes are left without proper care!! An actual example of tubes which are stored without proper care after the connected component was removed, during repaire of the unit. The tubes are left without proper care after the component was removed. Moisture caused by rainwater or condensation, dust, rubbish and sand enter the tubes resulting in a block in the expansion valve, capillary tube or filter. This may cause a compressor failure or insufficient operation. < Key point > When tubes are removed and stored even for a short time, be sure to provide care on the end of the tubes with blind cap. If blind caps are not available, it is recommended to wrap the tube ends including flare nut with vinyl tapes. (see the left picture) Pay attention so that dust, rubbish, or moisture on the tubes or flare will not enter the tubes when making care them.

1-5) Trouble caused by mixing foreign substances into tubes!! In the outdoor unit, icing is sometimes found on the filter. This shows a typical filer choking phenomenon in which the upstream side is hot while the downstream side is frozen. Actual example of frosting caused by filter choke During the piping work, moisture, dust, rubbish or sand entered the circuit. The refrigerant in the downstream side is shorted and pressure decreases to reduce the capacity due to the filter choke. Extreme super heated operation could take place if such an abnormal operation continues. Censequently, the safety switch will actuate to stop the operation. This will finally result in compressor failure. Frozen choke has occured in the distributor on the outdoor unit heat exchanger. Be careful that moisture will not remain in tubes. a. Perfect care for tubing b. Remove moisture in tubes by the flashing work c. Pay attention to the potential of moisture mixing into tubes when piping work is done on rainy day (especially in outdoor work). d. Be sure to perform vacuum drying process before the test run.

1-6) Problem due to using REFNET JOINTS not recommended by DAIKIN!! REFNET JOINTS NOT recommended by DAIKIN The Refnet joints other than DAIKIN s recommendation were used. Inadequate operation due to inaccurate distribution of refrigerant. Air conditioner will maifunction because oxidized film in a tube chokes the expansion valve, etc. Inadequate quality of REFNET JOINT not recommended by DAIKIN may cause gas leakage at brazed part. Due to lack of insulation pad for REFNET JOINT, water condensation may occur causing water drops. Be sure to use genuine parts. (If non-genuine parts are used, the warranty shall not be applied). 1-7) Trouble due to REFNET JOINT connection fault!! An actual example in which the Refnet Joint is not positioned correctly as shown in the picture below. Fault positioning of Refnet Joint in terms of direction. (Gravity influences to create drifting). Excessive noise by refrigerant passing will arise. Capacity shortage will occur which is caused by refrigerant drift. When the Refnet Joint is installed, be sure to install it in correct direction within the specified range as illustrated below.

2-1) Problem caused by faulty selection of drain pipe size!! A smaller sized pipe is used than the pipe size specified by DAIKIN. How did the problem occur? VP25 (inside diameter) is used in Japan while PVC25 (outside diameter) is normally used in China. This is likely to cause incorrect selection of pipe size. As the size is too small to drain sufficiently: The unit will display a malfunction and then stop, and it will become impossible to operate. Water leak will occur. Refer to the table below and use the pipe size specified. Since the pipe size suitable for every type of model is listed in the DAIKIN Engineering Data books, make sure the correct pipe size is choosen prior to installation. Pay particular attention for reading the outside diameter and the inside diameter correctly. Be sure to use the size specified. 2-2) Table of specified drain pipes (for your reference) PVC32;Outside diameter=32m m,inside diameter =27m m VP25;Outside diameter=32mm,inside diameter =25m m PV C 25;O utside diameter=2 5m m,insidediameter=19 m m VP 20;O utside diameter=2 6 mm,inside diameter=20 m m Type Drain piping Ceiling Mounted Cassette Type FXYC PVC32(VP25) (Double Flow) Ceiling Mounted Cassette Type FXYF PVC32(VP25) (Multi Flow) Ceiling Mounted Cassette Corner FXYK PVC32(VP25) Type Ceiling Mounted Built-in Type FXYS PVC32(VP25) Ceiling Mounted Duct Type FXYM PVC32(VP25) (FXYM200/250KJ should be referred to the separate Engineering Data book). Ceiling Suspended Type FXYH PVC25(VP20) Wall Mounted Type FXYA PVC25(VP20)

2-3) Problem of choke inside a drain pipe!! A drain trap is provided(a bend as shown left). Due to water remaining in the bend and dust or rubbish accumulating inside the drain piping, the pipe is blocked and water will not flow out, and--- The unit will display malfunction and stop, and then will become impossible to operate. Water leak will occur. Correct layout of drain piping with a trap under beam. It is a basic policy not to provide a trap. If a trap is to be installed, it should be made so as to be able to clean up inside the drain pipe. Take notice that H1 should have at least 50mm or more in order to cope with reverse flow caused by negative pressure generated in the indoor unit. 2-4) Problem of reverse gradient of drain piping!! An actual example of the bend with an excessive long pitch of the suspension. Excessive long pitch of the suspension for drain piping It becomes impossible for the drain to flow out due to the reverse gradient with the bent at the center as shown in the picture left. The unit will display malfunction and stop, and then will become impossible to operate. Water leakage will occur. The pitch of suspension must be set at an interval of 0.8~1.0m and pay attention so that piping will not bend (take 1/100 or more for the gradient!!)

2-5) Trouble by faulty selection of piping size for collective drain piping!! Faulty example Smaller sized piping is used at the collective part. As the water flow decreases at the collective part, a protection device actuates to stop the operation. Correct example At least 30mm (ID) or more should be used for collective piping. Check the table below and make sure the correct size pipe is selected and used. 2-6) Suitable collective piping sizes for central drain system. Selection of drain piping Calculation for drain exhaust Figure it out as 2[l/hr]drain per 1HP will be expected. (Calculation example of collective drain water) In case of 3 units 3HP and 2 units 3HP [(3 units 2HP) + (2 units 3HP)] 2[l/hr] = 24[l/hr] Selection of drain piping Select proper size to suit the drainage through the table below. (Selection example) When referring to the table below through the calculation result above, the collective piping must be selected PVC 40 or more in accordance with 24[l/hr]. Suitable size table of collective drain piping (relations between a diameter of horizontal line and permissible drainage capacity). PVC piping Inside diameter (reference values :mm) JIS piping Inside diameter (reference values :mm) PVC25 19 VP20 20 PVC32 27 VP25 25 Permissible flow rate[l/hr] Gradient 1:50 Gradient 1:100 PVC40 34 VP30 31 125 88 PVC50 44 VP40 40 247 175 Note Impossible for collective piping (Reference data) Used for collective piping Note:Large sized piping with PVC40 or more should be used for downstream line from the collective point and for the subsequent line.

3-1) Problem of seizure on power supply wiring!! (1) An actual example that the T-phase wire of a power supply line which has been loosened. The crimp terminal is not used. The screw is not securely tightened. A safety device will actuate to stop the unit. Impossible to operate because of no power supply. In the worst case, the over-current keeps flowing and results in a seizure. <Key points> Fix a wire securely using a crimp terminal (round type). If it is not possible to use a crimp terminal, make the tip of wiring to a round shape and put it behind a washer of the terminal, securely tightening the screw. 3-2) Problem of seizure on power supply wiring!! (2) The power supply wiring has been burnt out due to poor tightening of the wire and subsequent continuous over-current. Because it was tightened over the insulation part, the screw was loosened. The safety device will actuate to stop the unit due to the poor contact of the wiring. In the worst case, the over-current keeps flowing and results in a seizure. <Key points> Fix the wire securely using a crimp terminal (round type). If it is not possible to use a crimp terminal, make the tip of wiring to a round shape and put it behind a washer of the terminal, securely tightening.

AFTER SALES SERVICE DIV.