MODEL FL3102. Digital Frequency Infra-Red (DFIR) Flame Detector MANFL3102. Instruction Manual 07-08

Similar documents
High Temperature Remote Gas Calibrator

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

Model TL104 MANTL104. Test Lamp for Flame Detection

MODEL FL4000H. Multi-Spectral Infrared Flame Detector

FlameGard 5 MSIR. Multi-Spectral Infrared Flame Detector

Models FL3110/FL3111. UV/IR and UV only Flame Detectors. Instruction Manual 09/09

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

FlameGard 5 UV/IR HART

FlameGard 5 MSIR HART

Design Manual Installation Operation Maintenance

Model 2280A. Four Channel Control Module Hydrogen Sulfide Gas Applications

Model FMD. Field Mounted Display Module

SEC 2000 Millenium Infrared Gas Detector

Model 580A. Two Channel Control Module Combustible Gas Applications

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

FUNCTIONAL SAFETY MANUAL

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

FM Approved Fire & Gas Detection System

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

SEC Millenium Carbon Dioxide Gas Detector

Model 3300 Technical Support and Installation Manual

SEC Signature Process Gas Analyzer

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

FIREYE C9707A ALL FUEL SCANNER

Hydrocarbon Gas Detector

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

Carbon Monoxide Transmitter

GAS MONITOR Model Model

Model 2602A. Zero Two Series Control for Hydrogen Sulfide Gas Applications

RK-05 Carbon Monoxide Detector Operator s Manual

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

Model 4001 Series Single Channel Controller

FUNCTIONAL SAFETY MANUAL

Applying Neural Network Technology to the Next Generation Flame Detector

Model IR4000S CO 2. Single-Point Carbon Dioxide Monitor. Instruction Manual 12-11

RED1. Technical Support And Installation Manual. Models ST, E1, E2, E3, E4, and 420. Approved

Buzzer Unit. TAN-5000 Series. Operating Manual

Remote Relay Module (RRM)

SEC 5000 IREvolution Gas Detector

Model D12-IR. Digital Gas Transmitter...

21-light Remote Annunciator. Owner s Manual

Beacon 800 Gas Monitor Operator s Manual

Bench Top Ionizer Installation, Operation and Maintenance

Instruction Manual WARNING

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

Controllers. Instruction Manual WARNING

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

ACCURATE ELECTRONICS INC

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

FIRERAY 5000 range USER GUIDE

RK / RK Methane Detector Operator s Manual

F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0)

SEC Millenium Hydrocarbon Gas Detector

RS485 MODBUS Module 8AI

Two-Channel Gas Controller

Carbon Dioxide Sample-Draw Detector Operator s Manual

Combustible Gas Sample-Draw Detector Operator s Manual

RK-02 Multi Point Detector Operator s Manual

Model 4802A. Zero Two Series Control Module

Global Water Instrumentation, Inc.

Mark 25 Ultrapure Water Conductivity Analyzer

RK-HC-04 M2A Transmitter Operator s Manual

Dräger Flame 2100 Flame Detection

1022 R/T Remote Monitor

Series Temperature Controller Instruction Sheet

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

Design Manual Installation Operation Maintenance

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

Certificate of Compliance

MBCE-110/230UV Flame Sensor Module

Safe T Net 210. Instruction Manual Part Number Mar2010

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

! "! # Please read these installation and operating instructions completely and carefully before starting.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

Model S4000C. Intelligent Sensor for Combustible Gas Detection

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

RK Multi Point Detector Operator s Manual

SEC SIGNATURE ETO MONITOR TRAINING SENSOR ELECTRONICS CORPORATION

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

RK-04 M2 Transmitter Operator s Manual

LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

Danfoss gas detection units

Model IR4000M. Multi-Point Monitor. Instruction Manual 12-10

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Transcription:

MODEL FL3102 Digital Frequency Infra-Red (DFIR) Flame Detector The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual 07-08 General Monitors reserves the right to change published specifications and designs without prior notice. MANFL3102 Part No. Revision MANFL3102 D/07-08

Warranty Model FL3102 General Monitors warrants the Model FL3102 to be free from defects in workmanship or material under normal use and service within two (2) years from the date of shipment. General Monitors will repair or replace without charge any such equipment found to be defective during the warranty period. Full determination of the nature of, and responsibility for defective or damaged equipment will be made by General Monitors personnel. Defective or damaged equipment must be shipped to General Monitors plant or representative from which the original shipment was made. In all cases this warranty is limited to the cost of the equipment supplied by General Monitors. The customer will assume all liability for the misuse of this equipment by its employees or other personnel. All warranties are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired with out General Monitors approval or which have been subjected to neglect, accident, improper installation or application, or on which the original identification marks have been re moved or altered. Except for the express warranty stated above, General Monitors disclaims all warranties with regard to the products sold, including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of General Monitors for damages including, but not limited to, consequential damages arising out of/or in connection with the performance of the product. Warnings WARNING - Through engineering design, testing, manufacturing techniques, and rigid quality control, General Monitors supplies the finest flame detection systems available. The user must recognize his responsibility for maintaining the flame detection system in operational condition. WARNING - The Model FL3102 DFIR Flame detector contains components, which can be damaged by static electricity. Special care must be taken when wiring the system, to ensure that only the connection points are touched. SAFETY WARNING - Installation and Maintenance must be carried out by suitably skilled and competent personnel only. TOXIC, COMBUSTIBLE AND FLAMMABLE GASES & VAPORS ARE VERY DANGEROUS. EXTREME CAUTION SHOULD BE USED WHEN THESE HAZARDS ARE PRESENT. i

System Integrity Verification Model FL3102 General Monitors mission is to benefit society by providing solutions through industry leading safety products, services and systems that save lives and protect capital resources from the dangers of hazardous flames, gases and vapors. The safety products you have purchased should be handled carefully and installed, calibrated and maintained in accordance with the respective product instruction manual. Remember these products are for your safety. To ensure operation at optimum performance, General Monitors recommends that certain maintenance items be performed. Commissioning Safety Systems Before power up, verify wiring, terminal connections and stability of mounting for all integral safety equipment including, but not limited to: Power supplies Control modules Field detection devices Signaling / output devices Accessories connected to field and signaling devices After the initial application of power (and any factory specified warm-up period) to the safety system, verify that all signal outputs, to and from devices and modules, are within the manufacturers specifications. Initial testing should be performed per the manufacturers recommendations and instructions. Proper system operation should be verified by performing a full, functional test of all component devices of the safety system, ensuring that the proper levels of alarming occur. Fault/Malfunction circuit operation should be verified. Periodic Testing of Field Devices Periodic testing/calibrating should be performed per the manufacturers recommendations and instructions. Testing/Calibrating procedures should include, but not be limited to: Verify integrity of all optical surfaces and devices For flame detectors, use the appropriate test lamp When testing produces results outside of the manufacturers specifications, replacement of the suspect device(s) should be performed as necessary. Maintenance intervals should be independently established through a documented procedure, including a Maintenance log maintained by plant personnel or third party testing services. ii

Periodic System Verification The following system verifications should be performed at least annually: Verify wiring, terminal connections and stability of mounting for all integral safety equipment including, but not limited to: Power supplies Control modules Field detection devices Signaling / output devices Accessories connected to field and signaling devices Proper system operation should be verified by performing a full, functional test of all component devices of the detection system, ensuring that the proper levels of alarming occur. Fault/Malfunction circuit operation should be verified. Maintenance intervals should be independently established through a documented procedure, including a maintenance log maintained by plant personnel or third party testing services. iii

Quick Start Guide 1.0 Quick Start Guide 1.1 Upon Receipt of Equipment All items shipped by General Monitors are packed in shock absorbing containers, which provide a considerable degree of protection against physical damage. When received, the contents should be carefully removed and checked against the enclosed packing slip. All subsequent correspondence with General Monitors must specify the equipment part number and serial number. 1.2 Choosing Detector Locations Several variables are involved in selecting the locations to install detectors to ensure proper flame detection. There are no hard and fast rules defining the optimum location. There are some general suggestions that should be considered in regard to particular conditions at the site where the unit(s) are being installed: 1.2.1 Detector Field of View Each Model FL3102 Flame Detector has a 120 maximum Cone of Vision. This Cone has its vertex at the center of the detector (see Figure 1). 1.2.2 Optical Sensitivity Range The distance at which the detector will respond to a flame is a function of the intensity of that flame. The maximum distance is 50 feet (15.2m) for a gasoline fire with a surface area of 1 square foot (0.92m 2 ). 1.2.3 Environmental Factors Mounting should be as free from shock and vibration as possible and convenient for visual inspection and cleaning. Detectors mounted in dirty atmospheric conditions will require more frequent inspection, cleaning, and sensitivity checking. Observe the ambient temperature range for the specific model (see Section 8.1.4 Environmental Specifications). For outdoor installations or other areas exposed to intense, direct solar radiation, the detector may reach temperatures well above specifications. For this condition, a cover for shade may be required to bring the detector temperature within specifications. As with any cover or object near-by, make sure the field-of-view of the detector is not obstructed. Avoid conditions of ice build up on the optical detector windows. Complete icing-over of the IR detector window can result in fault conditions. i

Quick Start Guide 1.3 Detector Installation The Model FL3102 Detector is an explosion proof assembly rated for use in Class I, Divisions 1 & 2, Group B, C & D, Class II, Group E, F & G, and Class III areas. The detector(s) should be mounted pointing downward so that dust/moisture will not accumulate on the IR windows. The detector(s) should be mounted in locations, which will inhibit people or objects from obscuring the detector s Cone of Vision. NOTE Before installing these units, please read the warning statement on page 13 of this manual. These units must have a conduit seal installed. Mounting hardware should be used as shown in Figures 2 and 3. NOTE The swivel (961-003) is rated for Class I, Div 1 & 2, Groups C & D. Use mounting bracket for Group B areas. The overall dimensions of the detectors and mounting hardware are shown in Figure 4. ii

Quick Start Guide Figure 1 FL3102 Field of View iii

Quick Start Guide Figure 2 Swivel Elbow Drawing (Class I, Div 1&2, Groups C&D) REF HOLE : 4X Ø.26[6.6] 3.75[95.3] 5.00[127.0] 30 30 60 2.80[71.12] 4.66[118.4] 2.80[71.12] REAR VIEW WALL MOUNTING 4X M6 X 14 4X M6 WASHER BRACKET ASSEMBLY Figure 3 Mounting Bracket Drawing (Class I, Div 1&2, Groups B,C&D) iv

FIELD TERMINATIONS Model FL3102 Quick Start Guide TB2 TB1 CHAS GND 1 10 COM ALM C 2 9 COM ALM 1 3 8 +24VDC ALM 2 4 WARN C 5 7 6 +24VDC DATA- DATA2- WARN 1 WARN 2 6 7 5 4 0-20mA DATA2+ ALMTEST FLT C 8 3 RESET FLT 1 9 2 FLT 2 10 1 DATA+ Figure 4 FL3102 Outline Drawing WARNING General Monitors requires that the conduit entry be sealed per the Canadian Electrical Code Handbook (Part 1, Section 18-154). Conduit seals prevent water from entering the units housing through the conduit entry. Water entering the housing through the conduit entry will damage the electronics and nullify the warranty. v

Quick Start Guide 1.4 Terminal Connections All wire connections are made through the ¾ NPT openings in the Base Assembly to the terminal block (See Figure 7). The Terminal Block is located on the Base Assembly (See Figure 8) and accepts 12 AWG to 22 AWG stranded or solid-core wire. Each wire should be stripped as shown in Figure 5. Figure 5 Wire-Strip Length To connect the wire to the Terminal Block, insert the conductor into the connection space as shown in Figure 7 and tighten the corresponding screw terminal. Figure 6 Detector Housing and Base vi

Quick Start Guide Figure 7 Terminal Block Operation There are twenty possible terminal connections. On this and the following pages is a description and specification for each connection. 1.4.1 Alarm Relay TB2, Term 2 = ALARM C TB2, Term 3 = ALARM 1 TB2, Term 4 = ALARM 2 Description: The connections are to the SPDT ALARM relay. ALARM output is time delayed for 2, 4, 8, or 10 seconds. This time delay can be set by RS-485 or DIP-switch (see Section 3.5). The ALARM output can be normally energized or normally de- energized, latching or non- latching, and these options are also set via RS-485 or by DIP-switch. (See Section 3.5 Switch Selectable Options) Alarm Relay: TB2, Term 2 = ALM C = Alarm Common Normally de-energized TB2, Term 3 = ALM 1 = Normally Closed TB2, Term 4 = ALM 2 = Normally Open vii

Quick Start Guide Normally energized TB2, Term 3 = ALM 1 = Normally Open TB2, Term 4 = ALM 2 = Normally Closed The ALARM relay contact ratings are 8A @ 250VAC and 8A @ 30VDC. CAUTION For all relay connections see Figure 9. Figure 8 Terminal Connections 1.4.2 Warning Relay TB2, Term 5 = WARN C TB2, Term 6 = WARN 1 TB2, Term 7 = WARN 2 Description: These connections are to the SPDT WARN relay. The WARN output is immediate on the Model FL3102. The WARN output can be normally energized or normally de-energized, latching or non-latching. These options are also set via RS-485 or by a DIP-switch. (See Section 3.5, Switch Selectable Options) Warning Relay: TB2, Term 5 = WARN C = Warning Common viii

Quick Start Guide Normally de-energized TB2, Term 6 = WARN 1 = Normally Closed TB2, Term 7 = WARN 2 = Normally Open Normally energized TB2, Term 6 = WARN 1 = Normally Open TB2, Term 7 = WARN 2 = Normally Closed The WARN relay contact ratings are 8A @ 250VAC and 8A @ 30VDC. CAUTION For all relay connections see Figure 9. Figure 9 Relay Contacts 1.4.3 Fault Relay TB2, Term 8 = FLT C TB2, Term 9 = FLT 1 TB2, Term 10 = FLT 2 Description: These connections are to the SPDT FAULT relay. The FAULT output configuration is normally energized and non-latching. This is the standard output configuration and it cannot be changed. The FAULT circuit will be activated during the time-out function, a low power or loss of power condition, and during a failed COPM check. During these conditions, the FAULT relays will de-energize and the analog output signal will drop to 0 ma (2mA for COPM Faults) for the duration of the FAULT. Fault Relay: TB2, Term 8 = FLT C = Fault Common Normally energized TB2, Term 9 = FLT 1 = Normally Open TB2, Term 10 = FLT 2 = Normally Closed The FAULT relay contact ratings are 8A @ 250VAC and 8A @ 30VDC. CAUTION For all relay connections see Figure 9. ix

Quick Start Guide 1.4.4 Alarm Reset Terminal TB1, Term 3 = RESET The RESET, when activated, returns a latched ALARM and/or WARN output, that is no longer valid, to its original state. For this RESET function, place one contact of a SPST normally open momentary switch to TB1 Terminal 3 and the other contact to DC COM (the detector s common). To activate, just press and release the switch. 1.4.5 Alarm Test Terminal TB1, Term 4 = ALARM TEST By connecting one contact of a SPST normally open momentary switch to TB1 terminal 4 and the other contact to DC COM (the detector s common) the user can test the alarm outputs of the Flame Detector by activating this switch for one to eight seconds depending on the alarm time delay setting. The Alarm Test will activate the WARN and ALARM relay outputs as well as the appropriate analog output. The Flame Detector will remain in this state until the switch is released. The latching WARN and/or ALARM will have to be RESET manually. The Autotest feature cannot be daisy chained between two or more FL3102 Flame Detectors. 1.4.6 Analog Output TB1, Term 5 = 0-20mA (Analog Output) The 0 to 20mA output is a current signal that corresponds to following: FAULT signal: COPM Fault signal: Ready signal: WARN signal: ALARM signal:.0 to 0.2mA 2.0 + 0.2mA 4.0 + 0.2mA 16.0 + 0.2mA 20.0 + 0.2mA The maximum analog output load is 600 ohms. Cable Requirements: For interfacing with 250 ohm input impedance devices, the following maximum cable lengths apply (maximum 50 ohm loop): AWG FEET METERS 14 9000 2750 16 5800 1770 18 3800 1160 20 2400 730 22 1700 520 Figure 10 Maximum Cable Lengths for 250 Ohm Input x

Quick Start Guide 1.4.7 Power TB1, Term 7, 8 = +24VDC TB1, Term 9, 10 = COM These are the power connections. The supply voltage range is 20 to 36VDC at the detector (low voltage is detected at 18.5 VDC). The following maximum cable lengths apply for a +24VDC supply (maximum 20 ohm loop): AWG FEET METERS 14 4500 1370 16 2340 715 18 1540 470 20 970 300 22 670 205 Figure 11 Maximum Cable Lengths for +24VDC 1.4.8 RS-485 OUTPUT TB1, Term 1 = DATA+ TB1, Term 2 = DATA These are the connections for the RS-485 output. The RS-485 connection is used to either query the unit s status or to configure the unit. See Section 7 for detailed information on Modbus RTU protocol. NOTE If redundant RS-485 output is ordered, then the 0-20mA output is not available and the wiring terminals are: TB1, Term 5 = DATA2+ TB1, Term 6 = DATA2-1.4.9 Chassis Ground TB2, Term 1 = CHAS GND This connection is available for use in wiring that requires a connection to chassis ground. In general, all cable lengths specified are maximum values. Good design practices dictate cable lengths conservatively shorter than the maximum values given. xi

Quick Start Guide 1.5 Switch Selectable Options All settings on the Model FL3102 are done via a DIP-switch on the Power/Relay board or via RS-485 (overrides switch settings). To set these options, remove the detector head from the Base Assembly and locate the DIP-switch (see Figure 12). On the DIP-switch, ON/CLOSED means the switch is pushed in on the side labeled ON or CLOSED (opposite the OPEN side). OFF/OPEN means the switch is pushed in on the side with the number corresponding to the switch position or the side labeled OPEN. (Refer to the tables in Figure 13 for the switch assignments.) The settings for the WARN and ALARM outputs have been covered in section 3.4. The time delay specifies the amount of time a WARN condition persists before an ALARM condition will occur. ON 8 1 2 3 4 5 6 7 7 8 1 2 3 4 5 6 OPEN PIN 1 PIN 1 Figure 12 Dip Switch Location OPTION OFF / OPEN ON / CLOSED 100% Sens 1 sqft @ 50 ft 1&2 75% Sens 1 sqft @ 35 ft 2 1 50% Sens 1 sqft @ 25 ft 1 2 2 Second ALARM Time Delay 3 4 4 Second ALARM Time Delay 3&4 8 Second ALARM Time Delay 4 3 10 Second ALARM Time Delay 3&4 ALARM non-latching 5 ALARM latching 5 WARN non-latching 6 WARN latching 6 ALARM normally energized 7 ALARM normally de-energized 7 WARN normally energized 8 WARN normally de-energized 8 Figure 13 Dip Switch Options xii

Quick Start Guide NOTE - The instrument is now ready to operate! Please consult the manual for more information on the instrument s many features. NOTE - If you have any problems in the setup or testing of the detector, please refer to the Troubleshooting Section, or call the factory direct. Worldwide Service is available by calling: Lake Forest, California Phone: +1-949-581-4464 (24 hr. service) Fax: +1-949- 581-1151 Houston, Texas Phone: +1-281-855-6000 Fax: +1-281-855-3290 Ireland Phone: +353-91-751175 Fax: +353-91-751317 Singapore Phone: +65-6-748-3488 Fax: +65-6-748-1911 United Arab Emirates Phone: +971-4-8815751 Fax: +971-4-8817927 United Kingdom Phone: +44-1625-619583 Fax: +44-1625-619098 xiii

Table of Contents Model FL3102 WARRANTY WARNINGS... I... I SYSTEM INTEGRITY VERIFICATION... II 1.0 QUICK START GUIDE... I 1.1 Upon Receipt of Equipment...i 1.2 Choosing Detector Locations...i 1.2.1 Detector Field of View...i 1.2.2 Optical Sensitivity Range...i 1.2.3 Environmental Factors...i 1.3 Detector Installation...ii 1.4 Terminal Connections...vi 1.4.1 Alarm Relay... vii 1.4.2 Warning Relay... viii 1.4.3 Fault Relay...ix 1.4.4 Alarm Reset Terminal...x 1.4.5 Alarm Test Terminal...x 1.4.6 Analog Output...x 1.4.7 Power...xi 1.4.8 RS-485 OUTPUT...xi 1.4.9 Chassis Ground...xi 1.5 Switch Selectable Options... xii TABLE OF CONTENTS... 1 TABLE OF FIGURES... 5 2.0 INTRODUCTION... 7 2.1 General Description... 7 2.2 Principle of Operation... 8 2.2.1 IR Flame Detector... 8 2.2.2 COPM Circuitry... 9 2.2.3 Alarm Test... 9 2.2.4 Visual Indicators... 9 1

3.0 INSTALLATION... 10 3.1 Upon Receipt of Equipment... 10 3.2 Choosing Detector Locations... 10 3.2.1 Detector Field of View... 10 3.2.2 Optical Sensitivity Range... 10 3.2.3 Environmental Factors... 10 3.3 Detector Installation... 11 3.4 Terminal Connections... 15 3.4.1 Alarm Relay... 16 3.4.2 Warning Relay... 17 3.4.3 Fault Relay... 18 3.4.5 Alarm Test Terminal... 19 3.4.6 Analog Output... 19 3.4.7 Power... 20 3.4.8 RS-485 OUTPUT... 20 3.4.9 Chassis Ground... 20 3.5 Switch Selectable Options... 21 4.0 MAINTENANCE... 22 4.1 General Maintenance... 22 4.2 Cleaning the Lenses... 22 4.3 Sensitivity Check... 23 4.4 Storage... 23 5.0 TROUBLESHOOTING... 24 5.1 Trouble Shooting Chart... 24 5.2 Final Assemblies... 25 6.0 CUSTOMER SUPPORT... 26 7.0 MODBUS COMMUNICATIONS... 27 7.1 Baud Rate... 27 7.2 Data Format... 27 7.3 MODBUS Read Status Protocol (Query/Response)... 28 7.3.1 MODBUS Read Query Message... 28 7.3.2 MODBUS Read Response Message... 28 7.4 MODBUS Write Command Protocol (Query/Response)... 29 7.4.1 MODBUS Write Query Message... 29 7.4.2 MODBUS Write Response Message... 29 7.4.3 Function Codes Supported... 29 7.5 Exception Responses and Exception Codes... 30 7.5.1 Exception Responses... 31 7.5.1.1 Function Code Field... 31 7.5.1.2 Exception Code Field... 31 7.6 Command Register Locations... 32 7.6.1 Operational Mode Commands... 32 7.7 FL3102 Operational Mode Command Register Details... 35 7.7.1 Analog... 35 7.7.2 Mode... 35 7.7.3 Status/Error... 35 7.7.4 Fire Type... 36 7.7.5 Model Type... 36 2

3 Model FL3102 7.7.6 Software Revision... 36 7.7.7 COPM Fault... 36 7.7.8 EEPROM Override... 36 7.7.9 Options... 37 7.7.10 Comm 1 Address... 38 7.7.11 Comm 1 Baud Rate... 38 7.7.12 Comm 1 Data Format... 39 7.7.13 Fire Window COPM Fault Total (Photodiode)... 39 7.7.14 Fire Sensor COPM Fault Total... 40 7.7.15 Sun COPM Fault Total... 40 7.7.16 Remote Reset... 40 7.7.17 Remote Alarm Test... 40 7.7.18 Clear COPM Faults... 40 7.7.19 Comm 1 or 2 Total Receive Errors... 41 7.7.20 Comm 1 or 2 Bus Activity Rate %... 41 7.7.21 Comm 1 & 2 Function Code Errors... 41 7.7.22 Comm 1 & 2 Starting Address Errors... 41 7.7.23 Comm 1 Only Total Receive Errors... 41 7.7.24 Comm 1 & 2 RXD CRC Lo Errors... 41 7.7.25 Comm 1 & 2 RXD CRC Hi Errors... 41 7.7.26 Comm 1 Only Overrun Errors... 41 7.7.27 Comm 1 Only Noise Flag Errors... 42 7.7.28 Comm 1 & 2 Framing Errors... 42 7.7.29 Comm 1 or 2 Message Interval... 42 7.7.30 Comm 2 Only Total Receive Errors... 42 7.7.31 Comm 1 Only SCI Errors... 42 7.7.32 Clear Comm 1 & 2 Errors... 42 7.7.33 Comm 2 Address... 43 7.7.34 Comm 2 Baud Rate... 43 7.7.35 Comm 2 Data Format... 44 8.0 APPENDIX... 45 8.1 Specifications... 45 8.1.1 System Specifications... 45 8.1.1.1 Detector Location... 45 8.1.1.2 IR Detector center wavelength (Figure 15)... 45 8.1.1.3 Typical Response Time*... 45 8.1.1.4 Minimum Response Time... 45 8.1.1.5 Field of Vision* (Figure 16)... 45 8.1.1.6 Sensitivity... 45 8.1.1.7 Maximum Cable Parameters... 45 8.1.1.8 Warranty... 46 8.1.2 Mechanical Specifications... 46 8.1.3 Electrical Specifications... 46 8.1.3.1 Supply voltage range (see NOTE)... 46 8.1.3.2 Relay Contact Ratings... 46 8.1.3.3 RS-485 Output... 46 8.1.3.4 Baud Rate... 46 8.1.3.5 RFI/EMI Protection... 46 8.1.3.6 Status Indicator... 46 8.1.4 Environmental Specifications... 47 8.1.4.1 Operating temperature range... 47 8.1.4.2 Storage temperature range... 47

8.1.4.3 Humidity range... 47 8.1.5 Modbus RTU Protocol... 47 8.2 Approvals... 47 8.3 Spare Parts and Accessories... 47 8.3.1 Spare Parts... 47 8.3.2 TL103 Test Lamp... 48 8.3.3 Mounting Swivel / Union... 48 8.3.4 Mounting Bracket... 49 8.3.5 Optical Air Guard... 49 4

Table of Figures Model FL3102 Figure 1 FL3102 Field of View... iii Figure 2 Swivel Elbow Drawing (Class I, Div 1&2, Groups C&D)...iv Figure 3 Mounting Bracket Drawing (Class I, Div 1&2, Groups B,C&D)...iv Figure 4 FL3102 Outline Drawing...v Figure 5 Wire-Strip Length...vi Figure 6 Detector Housing and Base...vi Figure 7 Terminal Block Operation... vii Figure 8 Terminal Connections... viii Figure 9 Relay Contacts...ix Figure 10 Maximum Cable Lengths for 250 Ohm Input...x Figure 11 Maximum Cable Lengths for +24VDC...xi Figure 12 Dip Switch Location... xii Figure 13 Dip Switch Options... xii Figure 14 Model FL3102... 7 Figure 15 Spectral Response of IR Detectors... 8 Figure 16 FL3102 Field of View... 12 Figure 17 Swivel Elbow Drawing (Class I, Div 1&2, Groups C&D)... 13 Figure 18 Mounting Bracket Drawing (Class I, Div 1&2, Groups B,C&D)... 13 Figure 19 FL3102 Outline Drawing... 14 Figure 20 Wire-Strip Length... 15 Figure 21 Detector Housing and Base... 15 Figure 22 Terminal Block Operation... 16 Figure 23 Terminal Connections... 17 Figure 24 Relay Contacts... 18 Figure 25 Maximum Cable Lengths for 250 Ohm Input... 19 Figure 26 Maximum Cable Lengths for +24VDC... 20 Figure 27 Dip Switch Location... 21 Figure 28 Dip Switch Options... 21 Figure 29 IR Windows... 22 Figure 30 Troubleshooting Chart... 24 Figure 31 FL3102 (DFIR) Final Assembly... 25 Figure 32 Data Format... 27 Figure 33 MODBUS Query Messages... 28 Figure 34 MODBUS Read Response Messages... 28 Figure 35 MODBUS Write Query Message... 29 Figure 36 MODBUS Write Response Message... 29 Figure 37 Typical Response Times for FL3102... 30 Figure 38 Exception Responses... 31 Figure 39 Exception Code Field... 31 5

Figure 40 Operational Mode Commands... 33 Figure 40 Operational Mode Commands Continued... 34 Figure 41 Mode... 35 Figure 42 Status/Error... 35 Figure 43 Model Type... 36 Figure 44 EEPROM Override... 37 Figure 45 Options... 38 Figure 46 Comm 1 Baud Rate... 38 Figure 47 Comm 1 Data Format... 39 Figure 48 Remote Reset... 40 Figure 49 Remote Alarm Test... 40 Figure 50 Clear COPM Faults... 40 Figure 51 Comm 1 & 2 Errors... 42 Figure 52 Comm 2 Baud Rate... 43 Figure 53 Comm 2 Data Format... 44 6

2.0 Introduction 2.1 General Description Model FL3102 Fire is a phenomenon of combustion. Combustion is the continuous chemical reaction of a reducing agent (fuel) and an oxidizing agent (oxygen, etc.) with the evolution of thermal energy (heat). Fire is usually manifested in heat (IR), smoke, light (visible), and flame (UV). Flame is the gaseous region of a fire where vigorous combustion chain reactions take place. These reactions emit radiation covering the Infrared, Ultraviolet and the Visible Spectral Regions. The General Monitors Model FL3102 is a Dual Frequency Infrared (DFIR) Flame Detector (Figure 14). The Model FL3102 detects the Infrared spectral regions of flame to produce a system, which is highly immune to false alarms caused by lightning, arc-welding, hot objects, and other sources of radiation. In addition, the FL3102 can see through most smoky type fires such as diesel, rubber, etc. The Model FL3102 has features that include: Compact unitized design. Continuous optical path monitoring. 0-20mA, alarm relays and MODBUS RTU-485 standard. Wide field of view. High false alarm immunity. Figure 14 Model FL3102 7

2.2 Principle of Operation 2.2.1 IR Flame Detector The Model FL3102 is a discriminating Dual Frequency Infra-Red Detector, which makes use of Infrared detectors for different IR wavelengths and characteristics. This combination provides a flame detection system, which is highly immune to false alarms. Incorporated in the IR circuitry is a flicker discrimination circuit. This permits the detector to ignore steady static IR sources such as hot objects. The inherent flickering of a flame provides the necessary modulation to activate the IR circuit. The Model FL3102 Flame Detector processes these IR signals with a microcomputer and produces the following outputs: 0 to 20 Milliampere signal. Immediate WARN relay contacts. Time delayed ALARM relay contacts. FAULT relay contacts. RS- 485 MODBUS RTU output. Optional: Redundant RS- 485 Modbus RTU output. (See Sections 3 & 4 for more information on detector outputs.) Visible Region Infrared Region IR Detector's Spectral Sensitivity Sun's Radiation Reaching the Earth Wavelength 4.35um Figure 15 Spectral Response of IR Detectors 8

2.2.2 COPM Circuitry A self- testing feature called Continuous Optical Path Monitoring (COPM) checks the optical path, the detector(s), and the related electronic circuitry once every minute. If foreign material impairs the optical path of the infrared detector for two consecutive checks, the unit will indicate FAULT. The optical FAULT outputs are a 2.0 ma signal, de-energizing of the FAULT relay, and RS-485 output signal (see Section 3.4 Terminal Connections). After a COPM FAULT, a COPM check is performed every ten seconds until the obstruction is removed. Then the COPM check will resume a once per minute check. WARNING Dirty or partially blocked windows can significantly reduce the detectors field of view and detection distance. NOTE Since the optical path is checked once per minute and it requires two check failures to produce a FAULT, it may take up to two minutes for the unit to detect an obstruction. 2.2.3 Alarm Test The Model FL3102 Flame Detector has a built-in Alarm Test feature. By connecting one contact of a SPST momentary switch to TB1 position 4 and the other contact to DC COM (see Section 3.4 Terminal Connections), the user can test the alarm outputs of the Flame Detector by activating this switch for one to eight seconds depending on the Alarm Delay Setting. The Flame Detector will immediately go into WARN and then into the time delayed ALARM. After one to eight seconds the Flame Detector will activate the ALARM. A latching WARN and/or ALARM will remain latched until manually reset. 2.2.4 Visual Indicators Two light emitting diodes (LED s) are visible through a window. LED s are provided for a visual indication that corresponds with the detectors outputs. The following blinking sequence indicates the operation condition: Time out (10 seconds when the unit is first powered) - Green and red LED s blinking alternately. Ready - Green LED that flashes off 1 second, every 10 seconds. WARNing - Slow blinking red LED with green LED on steady. ALARM - Fast blinking red LED with green LED on steady. COPM FAULT - Slow blinking green LED. Low Volt age FAULT - Fast blinking green LED. 9

3.0 Installation 3.1 Upon Receipt of Equipment All items shipped by General Monitors are packed in shock absorbing containers, which provide a considerable degree of protection against physical damage. When received, the contents should be carefully removed and checked against the enclosed packing slip. All subsequent correspondence with General Monitors must specify the equipment part number and serial number. 3.2 Choosing Detector Locations Several variables are involved in selecting the locations to install detectors to ensure proper flame detection. There are no hard and fast rules defining the optimum location. There are some general suggestions that should be considered in regard to particular conditions at the site where the unit(s) are being installed: 3.2.1 Detector Field of View Each Model FL3102 Flame Detector has a 120 maximum Cone of Vision. This Cone has its vertex at the center of the detector (see Figure 16). 3.2.2 Optical Sensitivity Range The distance at which the detector will respond to a flame is a function of the intensity of that flame. The maximum distance is 50 feet (15.2m) for a gasoline fire with a surface area of 1 square foot (0.92m 2 ). 3.2.3 Environmental Factors Mounting should be as free from shock and vibration as possible and convenient for visual inspection and cleaning. Detectors mounted in dirty atmospheric conditions will require more frequent inspection, cleaning, and sensitivity checking. Observe the ambient temperature range for the specific model (see Section 8.1.4 Environmental Specifications). For outdoor installations or other areas exposed to intense, direct solar radiation, the detector may reach temperatures well above specifications. For this condition, a cover for shade may be required to bring the detector temperature within specifications. As with any cover or object near-by, make sure the field-of-view of the detector is not obstructed. Avoid conditions of ice build up on the optical detector windows. Complete icing-over of the IR detector window can result in fault conditions. 10

3.3 Detector Installation The Model FL3102 Detector is an explosion proof assembly rated for use in Class I, Divisions 1 & 2, Group B, C & D, Class II, Group E, F & G, and Class III areas. The detector(s) should be mounted pointing downward so that dust/moisture will not accumulate on the IR windows. The detector(s) should be mounted in locations, which will inhibit people or objects from obscuring the detector s Cone of Vision. NOTE Before installing these units, please read the warning statement on page 13 of this manual. These units must have a conduit seal installed. Mounting hardware should be used as shown in Figures 17 and 18. NOTE The swivel (961-003) is rated for Class I, Div 1 & 2, Groups C & D. Use mounting bracket for Group B areas. The overall dimensions of the detectors and mounting hardware are shown in Figure 19. 11

Figure 16 FL3102 Field of View 12

Figure 17 Swivel Elbow Drawing (Class I, Div 1&2, Groups C&D) REF HOLE : 4X Ø.26[6.6] 3.75[95.3] 5.00[127.0] 30 30 60 2.80[71.12] 4.66[118.4] 2.80[71.12] REAR VIEW WALL MOUNTING 4X M6 X 14 4X M6 WASHER BRACKET ASSEMBLY Figure 18 Mounting Bracket Drawing (Class I, Div 1&2, Groups B,C&D) 13

FIELD TERMINATIONS TB2 TB1 CHAS GND 1 10 COM ALM C 2 9 COM ALM 1 3 8 +24VDC ALM 2 4 WARN C 5 7 6 +24VDC DATA- DATA2- WARN 1 WARN 2 6 7 5 4 0-20mA DATA2+ ALMTEST FLT C 8 3 RESET FLT 1 9 2 FLT 2 10 1 DATA+ Figure 19 FL3102 Outline Drawing WARNING General Monitors requires that the conduit entry be sealed per the Canadian Electrical Code Handbook (Part 1, Section 18-154). Conduit seals prevent water from entering the units housing through the conduit entry. Water entering the housing through the conduit entry will damage the electronics and nullify the warranty. 14

3.4 Terminal Connections All wire connections are made through the ¾ NPT openings in the Base Assembly to the terminal block (See Figure 22). The Terminal Block is located on the Base Assembly (See Figure 23) and accepts 12 AWG to 22 AWG stranded or solid-core wire. Each wire should be stripped as shown in Figure 20. Figure 20 Wire-Strip Length To connect the wire to the Terminal Block, insert the conductor into the connection space as shown in Figure 23 and tighten the corresponding screw terminal. Figure 21 Detector Housing and Base 15

Figure 22 Terminal Block Operation There are twenty possible terminal connections. On this and the following pages is a description and specification for each connection. 3.4.1 Alarm Relay TB2, Term 2 = ALARM C TB2, Term 3 = ALARM 1 TB2, Term 4 = ALARM 2 Description: The connections are to the SPDT ALARM relay. ALARM output is time delayed for 2, 4, 8, or 10 seconds. This time delay can be set by RS-485 or DIP-switch, (see Section 3.5). The ALARM output can be normally energized or normally de- energized, latching or non- latching, and these options are also set via RS-485 or by DIP-switch. (See Section 3.5, Switch Selectable Options) Alarm Relay: TB2, Term 2 = ALM C = Alarm Common Normally de-energized TB2, Term 3 = ALM 1 = Normally Closed TB2, Term 4 = ALM 2 = Normally Open Normally energized TB2, Term 3 = ALM 1 = Normally Open TB2, Term 4 = ALM 2 = Normally Closed The ALARM relay contact ratings are 8A @ 250VAC and 8A @ 30VDC. 16

CAUTION For all relay connections see Figure 24. Figure 23 Terminal Connections 3.4.2 Warning Relay TB2, Term 5 = WARN C TB2, Term 6 = WARN 1 TB2, Term 7 = WARN 2 Description: These connections are to the SPDT WARN relay. The WARN output is immediate on the Model FL3102. The WARN output can be normally energized or normally de-energized, latching or non-latching. These options are also set via RS-485 or by a DIP-switch. (See Section 3.5 Switch Selectable Options) Warning Relay: TB2, Term 5 = WARN C = Warning Common Normally de- energized TB2, Term 6 = WARN 1 = Normally Closed TB2, Term 7 = WARN 2 = Normally Open Normally energized TB2, Term 6 = WARN 1 = Normally Open TB2, Term 7 = WARN 2 = Normally Closed 17

The WARN relay contact ratings are 8A @ 250VAC and 8A @ 30VDC. CAUTION For all relay connections see Figure 24. Figure 24 Relay Contacts 3.4.3 Fault Relay TB2, Term 8 = FLT C TB2, Term 9 = FLT 1 TB2, Term 10 = FLT 2 Description: These connections are to the SPDT FAULT relay. The FAULT output configuration is normally energized and non-latching. This is the standard output configuration and it cannot be changed. The FAULT circuit will be activated during the time-out function, a low power or loss of power condition, and during a failed COPM check. During these conditions, the FAULT relays will de-energize and the analog output signal will drop to 0 ma (2mA for COPM Faults) for the duration of the FAULT. Fault Relay TB2, Term 8 = FLT C = Fault Common Normally energized TB2, Term 9 = FLT 1 = Normally Open TB2, Term 10 = FLT 2 = Normally Closed The FAULT relay contact ratings are 8A @ 250VAC and 8A @ 30VDC. CAUTION For all relay connections see Figure 24. 18

3.4.4 Alarm Reset Terminal TB1, Term 3 = RESET The RESET, when activated, returns a latched ALARM and/or WARN output, that is no longer valid, to its original state. For this RESET function, place one contact of a SPST normally open momentary switch to TB1 Terminal 3 and the other contact to DC COM (the detector s common). To activate, just press and release the switch. 3.4.5 Alarm Test Terminal TB1, Term 4 = ALARM TEST By connecting one contact of a SPST normally open momentary switch to TB1 terminal 4 and the other contact to DC COM (the detector s common) the user can test the alarm outputs of the Flame Detector by activating this switch for one to eight seconds depending on the alarm time delay setting. The Alarm Test will activate the WARN and ALARM relay outputs as well as the appropriate analog output. The Flame Detector will remain in this state until the switch is released. The latching WARN and/or ALARM will have to be RESET manually. The Autotest feature cannot be daisy chained between two or more FL3102 Flame Detectors. 3.4.6 Analog Output TB1, Term 5 = 0-20mA (Analog Output) The 0 to 20mA output is a current signal that corresponds to following: FAULT signal: COPM Fault signal: Ready signal: WARN signal: ALARM signal:.0 to 0.2mA 2.0 + 0.2mA 4.0 + 0.2mA 16.0 + 0.2mA 20.0 + 0.2mA The maximum analog output load is 600 ohms. Cable Requirements: For interfacing with 250 ohm input impedance devices, the following maximum cable lengths apply (maximum 50 ohm loop): AWG FEET METERS 14 9000 2750 16 5800 1770 18 3800 1160 20 2400 730 22 1700 520 Figure 25 Maximum Cable Lengths for 250 Ohm Input 19

3.4.7 Power TB1, Term 7, 8 = +24VDC TB1, Term 9, 10 = COM These are the power connections. The supply voltage range is 20 to 36VDC at the detector (low voltage is detected at 18.5 VDC). The following maximum cable lengths apply for a +24VDC supply (maximum 20 ohm loop): AWG FEET METERS 14 4500 1370 16 2340 715 18 1540 470 20 970 300 22 670 205 Figure 26 Maximum Cable Lengths for +24VDC 3.4.8 RS-485 OUTPUT TB1, Term 1 = DATA+ TB1, Term 2 = DATA These are the connections for the RS-485 output. The RS-485 connection is used to either query the unit s status or to configure the unit. See Section 7.0 for detailed information on Modbus RTU protocol. NOTE If redundant RS-485 output is ordered, then the 0-20mA output is not available and the wiring terminals are: TB1, Term 5 = DATA2+ TB1, Term 6 = DATA2-3.4.9 Chassis Ground TB2, Term 1 = CHAS GND This connection is available for use in wiring that requires a connection to chassis ground. In general, all cable lengths specified are maximum values. Good design practices dictate cable lengths conservatively shorter than the maximum values given. 20

3.5 Switch Selectable Options All settings on the Model FL3102 are done via a DIP-switch on the Power/Relay board or via RS-485 (overrides switch settings). To set these options, remove the detector head from the Base Assembly and locate the DIP-switch (see Figure 27). On the DIP-switch, ON/CLOSED means the switch is pushed in on the side labeled ON or CLOSED (opposite the OPEN side). OFF/OPEN means the switch is pushed in on the side with the number corresponding to the switch position or the side labeled OPEN. (Refer to the tables in Figure 28 for the switch assignments.) The settings for the WARN and ALARM outputs have been covered in section 3.4. The time delay specifies the amount of time a WARN condition persists before an ALARM condition will occur. ON 8 1 2 3 4 5 6 7 7 8 1 2 3 4 5 6 OPEN PIN 1 PIN 1 Figure 27 Dip Switch Location OPTION OFF / OPEN ON / CLOSED 100% Sens 1 sqft @ 50 ft 1&2 75% Sens 1 sqft @ 35 ft 2 1 50% Sens 1 sqft @ 25 ft 1 2 2-Second ALARM Time Delay 3 4 4-Second ALARM Time Delay 3&4 8-Second ALARM Time Delay 4 3 10-Second ALARM Time Delay 3&4 ALARM non-latching 5 ALARM latching 5 WARN non-latching 6 WARN latching 6 ALARM normally energized 7 ALARM normally de-energized 7 WARN normally energized 8 WARN normally de-energized 8 Figure 28 Dip Switch Options 21

4.0 Maintenance 4.1 General Maintenance Once correctly installed, the unit requires very little maintenance other than regular sensitivity checks and cleaning of the lenses. General Monitors recommends that a schedule be established and adhered to. Model FL3102 NOTE The removal of particulate matter and any film buildup on the lenses and light rods is necessary to ensure proper sensitivity of the system. It is recommended that the window and light rods be cleaned at least every 30 days or more often if the detector is located in a particularly dirty environment. 4.2 Cleaning the Lenses A clean, soft, lint-free cloth, tissue or cotton swab should be used to apply the cleaning solution. Do not touch the lenses or light rods with fingers. 1. Wet the window with the solution. 2. Rub with a dry, unsoiled cloth until the window is clean. 3. Completely dry the window. 4. Repeat steps a, b and c for the light rods. (See figure 29). Take care only to clean the uncoated (non - aluminum) areas of the light rods. WARNING Dirty or partially blocked windows can significantly reduce the detectors field of view and detection distance. DO NOT USE A COMMERCIAL GLASS CLEANER OTHER THAN INDUSTRIAL STRENGTH WINDEX with Ammonia D The lenses are not glass. One IR lens material is quartz and the other IR lens material is sapphire. The cleaning solution should be General Monitors P/N 10272-1 (Industrial Strength Windex with Ammonia D). Figure 29 IR Windows 22

4.3 Sensitivity Check To verify that each detector is functioning correctly, a General Monitors Test Lamp and/or the ALARM TEST function (see section 2.2 Principle of Operation - Alarm Test) should be used. See Section 8.3, Spares & Accessories, for details on test lamps. 4.4 Storage These Flame Detectors should be stored in a clean, dry area and within the temperature and humidity ranges quoted in Section 8.1.4 Environmental Specifications. 23

5.0 Troubleshooting 5.1 Trouble Shooting Chart Model FL3102 This section is intended to be a guide in correcting problems, which may arise in the field. This section is no all-inclusive, and General Monitors should be contacted for assistance if the corrective action listed does not eliminate the problem. If equipment or qualified personnel required for various tests are not available, it is recommended that the defective unit be returned to General Monitors for repair. A complete written description of the problem should be included. Be sure to inhibit or disconnect external alarm wiring before making any check, which might send the unit into alarm, if an alarm condition will create problems. NOTE If the equipment is under warranty, any repairs performed by persons other than General Monitors authorized personnel may void the warranty. Please read the warranty statement carefully. PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION Be sure that the +24VDC No DC power to the Unit is applied with the correct polarity No output signal and green LED in window is off No output signal and green LED in window is rapidly blinking Constant 2mA signal and green LED in window is slowly blinking Low voltage FAULT (voltage at unit is approximately +18.5VDC) COPM FAULT, dirty or obscured optical path (light rods or windows) Figure 30 Troubleshooting Chart Be sure that unit is powered with at least +24VDC under load Clean IR windows and associated source light rods 24

5.2 Final Assemblies Figure 31 FL3102 (DFIR) Final Assembly 25

6.0 Customer Support GENERAL MONITORS OFFICES Model FL3102 Area Phone/Fax/Email UNITED STATES Corporate Office: 26776 Simpatica Circle Lake Forest, CA 92630 9776 Whithorn Drive Houston, TX 77095 Phone: +1-949-581-4464 Fax: +1-949-581-1151 Email: sales@generalmonitors.com Phone: +1-281-855-6000 Fax: +1-281-855-3290 Email: gmhou@generalmonitors.com UNITED KINGDOM Heather Close Lyme Green Business Park Macclesfield, Cheshire, United Kingdom, SK11 0LR Phone: +44-1625-619583 Fax: +44-1625-619098 Email: info@generalmonitors.co.uk IRELAND Ballybrit Business Park Galway, Republic of Ireland Phone: +353-91-751175 Fax: +353-91-751317 Email: service@gmil.ie SINGAPORE No. 2 Kallang Pudding Rd. #09-16 Mactech Building Singapore 349307 Phone: +65-6-748-3488 Fax: +65-6-748-1911 Email: genmon@singnet.com.sg MIDDLE EAST LOB12, #G20 P.O. Box 61209 Jebel Ali, Dubai United Arab Emirates Phone: +971-4-8815751 Fax: +971-4-8817927 Email: gmme@emirates.net.ae 26

7.0 Modbus Communications Model FL3102 Standard Model FL3102 Flame Detectors include a Single MODBUS Communications Board that is referenced as Comm 1. A Dual MODBUS feature is optional, which includes two independent communications channels referenced as Comm 1 and Comm 2. NOTE - Comm 2 is utilized as a backup communications channel, therefore it is not recommended to have both Comm 1 and Comm 2 channels active simultaneously. If the dual Comm option is ordered, the Analog output will not be available. 7.1 Baud Rate The Baud Rate is a selectable setting via the MODBUS Communications Interface. The selectable baud rates are 19.2K, 9600, 4800, or 2400 bits per second. 7.2 Data Format The Data Format is a selectable setting via the MODBUS Communications Interface. The selectable data formats are as follows: Data Bits Parity Stop Bit Format 8 None 1 8-N-1 8 Even 1 8-E-1 8 Odd 1 8-O-1 8 None 2 8-N-2 Figure 32 Data Format 27

7.3 MODBUS Read Status Protocol (Query/Response) 7.3.1 MODBUS Read Query Message Byte MODBUS Range Referenced to FL3102 1 st Slave 1-247 * FL3102 ID (Address) Address 2 nd Function 03 Read Holding Registers Code 3 rd Starting 00 Not Used by FL3102 Address Hi** 4 th Starting 00-FF (Hex) FL3102 Command Registers Address Lo** 5 th No. of 00 Not Used by FL3102 Registers Hi 6 th No. of 01 No. of 16 Bit Registers Registers Lo 7 th CRC Lo 00-FF (Hex) CRC Lo Byte 8 th CRC Hi 00-FF (Hex) CRC Hi Byte Figure 33 MODBUS Query Messages NOTE*- Address 0 is reserved for broadcast mode and will not be supported at this time. NOTE**- Start Address can be a maximum of 9999 Address Locations (0000-270E) 7.3.2 MODBUS Read Response Message Byte MODBUS Range Referenced to FL3100, FL31001 1 st Slave 1-247* (Decimal) FL3102 ID (Address) Address 2 nd Function 03 Read Holding Registers Code 3 rd Byte Count 02 No. of Data Bytes 4 th Data Hi 00-FF (Hex) FL3102 Hi Byte Status Data 5 th Data Lo 00-FF (Hex) FL3102 Lo Byte Status Data 6 th CRC Lo 00-FF (Hex) CRC Lo Byte 7 th CRC Hi 00-FF (Hex) CRC Hi Byte Figure 34 MODBUS Read Response Messages NOTE - Address 0 is reserved for broadcast mode and will not be supported at this time. 28

7.4 MODBUS Write Command Protocol (Query/Response) 7.4.1 MODBUS Write Query Message Byte MODBUS Range Referenced to FL3102 1 st Slave Address 1-247* (Decimal) FL3102 ID (Address) 2 nd Function Code 06 Preset Single Register 3 rd Register Address Hi** 00 Not used by FL3102 4 th Register Address Lo** 00-FF (Hex) FL3102 Command Registers 5 th Preset Data Hi 00-FF (Hex) FL3102 Hi Byte Command Data 6 th Preset Data Lo 00-FF (Hex) FL3102 Lo Byte Command Data 7 th CRC Lo 00-FF (Hex) CRC Lo Byte 8 th CRC Hi 00-FF (Hex) CRC Hi Byte Figure 35 MODBUS Write Query Message NOTE* Address 0 is reserved for broadcast mode and will not be supported at this time. NOTE** Register Address can be maximum of 9999 Address Locations (0000-270E) 7.4.2 MODBUS Write Response Message Byte MODBUS Range Referenced to FL3102 1 st Slave Address 1-247*(Decimal) FL3102 ID (Address) 2 nd Function Code 06 Preset Single Register 3 rd Register Address Hi** 00 Not used by FL3102 4 th Register Address Lo** 00-FF (Hex) FL3102 Command Registers 5 th Preset Data Hi 00-FF (Hex) FL3102 Hi Byte Command Data 6 th Preset Data Lo 00-FF (Hex) FL3102 Lo Byte Command Data 7 th CRC Lo 00-FF (Hex) CRC Lo Byte 8 th CRC Hi 00-FF (Hex) CRC Hi Byte Figure 36 MODBUS Write Response Message NOTE* - Address 0 is reserved for broadcast mode and is not be supported at this time. NOTE ** - Register Address can be a maximum of 9999 Address Locations (0000-270E) 7.4.3 Function Codes Supported Function Code 03 (Read Holding Registers) is used to read status from the slave unit. Function Code 06 (Preset Single Register) is used to write a command to the slave unit. 29

7.5 Exception Responses and Exception Codes Model FL3102 Baud Rate (bps) In a normal exchange, the master device sends a query to the FL3102. The FL3102 receives the query and returns a normal response to the master. If a normal communications error occurs, there are 4 possible responses from the FL3102: 1. If the FL3102 does not recognize the query due to a communications error, then no response is returned from the FL3102 and the master device will eventually process a timeout condition for the query. 2. If the FL3102 receives the query, but detects a communication error (CRC, etc.), then no response is returned from the FL3102 and the master device will eventually process a timeout condition for the query. 3. If the FL3102 receives the query without a communications error, but cannot process the response to the master within the master's timeout setting, then no response is returned from the FL3102 and the master device will eventually process a timeout condition for the query. In order to prevent this condition from occurring, the typical response times for the FL3102 are listed below: Query From Master (msec) Unit Response Delay Time to Query (msec) Response From Unit (msec) Master Response Delay Time Between End of Unit Response and Next Master Query (msec) Total Response Time (msec) 19.2K 4 4 4 100-120* 112 132 9600 8 5 8 100-120* 121 141 4800 16 6 16 100-120* 138 158 2400 32 8 32 100-120* 172 192 Figure 37 Typical Response Times for FL3102 NOTE* - Master Response Delay Time is dependent on the speed of response for the Master (DCS, PLC, etc.) Cycle Time can be significantly reduced with a faster Master. The 100ms Delay Time was taken from a typical Master, using a PC with Intellution Industrial Control Software, which was set at the minimum poll time. 4. If the FL3102 receives the query without a communications error, but cannot process it due to reading or writing to a non-existent or illegal FL3102 Function Code, Illegal Command Starting Address or Register Address, or Illegal Data Value, then the FL3102 will return an exception response message informing the master of the error. The exception response message has two fields that differentiate it from a normal response, which is explained in Section 7.5.1. 30

7.5.1 Exception Responses Byte MODBUS Range Referenced to FL3102 1 st Slave Address 1-247* (Decimal) FL3102 ID (Address) 2 nd Function Code 83 or 86 (Hex) MSB is set with Function Code 3 rd Exception Code 01-06 (Hex) Appropriate Exception Code (See below) 4 th CRC Lo 00-FF (Hex) CRC Lo Byte 5 th CRC Hi 00-FF (Hex) CRC Hi Byte Figure 38 Exception Responses 7.5.1.1 Function Code Field In a normal response, the FL3102 echoes the function code of the original query in the function code field of the response. All the Function Codes have a most-significant bit (MSB). In an exception response, the FL3102 sets the MSB of the function code to a one (1). With the function code s MSB set, the master can recognize the exception response and can process the data field for the exception code from the FL3102 response message. 7.5.1.2 Exception Code Field In a normal response, the FL3102 returns data and status in the data field, which was requested in the query from the master. In an exception response, the FL3102 returns an exception code in the data field, which describes the FL3102 condition that caused the exception. Below is a list of exception codes that are supported by the FL3102: Code Name Description 01 Illegal Function The function code received in the query is not an allowable action for the FL3102. 02 Illegal Data Address The data address received in the query is not an allowable address for the FL3102. 03 Illegal Data Value A value contained in the query data field is not an allowable value for the FL3102. 04 Slave Device Failure An unrecoverable error occurred while the FL3102 was attempting to perform the requested action. 05 Acknowledge The FL3102 has accepted the request and is processing it, but a long duration of time will be required to do so. This response is returned to prevent a timeout error from occurring in the master. 06 Device Busy The FL3102 is engaged in processing a longduration program command. The master should retransmit the message later when the slave is free. Figure 39 Exception Code Field 31

7.6 Command Register Locations 7.6.1 Operational Mode Commands See section number listed below and reference Section 7.7 for details of each register. 32

R - indicates Read Only Access R/W - indicates Read/Write Access Parameter Function Type Scale 33 Acc ess REG Addr Master I/O Addr Refer to Section Analog 0-20mA Current Output Value 16-Bit R 0000 40001 7.7.1 Mode Indicates Fire Status Mode Value (0-11) R 0001 40002 7.7.2 Status/Error Indicates Error Bit 8-Bit R 0002 40003 7.7.3 Fire Type LFF, HFF or both Bit (1,2,3) R 0003 40004 7.7.4 Model Type Identifies the Model FL3102 Decimal 3102 R 0004 40005 7.7.5 Software Rev Indicates the Software Revision ASCII 2-Char R 0005 40006 7.7.6 COPM Fault UV/IR COPM Fault Bit 2-Bit R 0006 40007 7.7.7 EEPROM Set Bit for EEPROM to Override Bit 1-Bit R/W 0007 40008 7.7.8 Override DIPswitch Settings Options Indicates Unit Options Bit 8-Bit R/W 0008 40009 7.7.9 Comm 1 Address Unit Address (Comm 1) Decimal (1-247) R/W 0009 40010 7.7.10 Hex (01- F7) Not Used 000A 40011 Comm 1 Baud Rate Comm 1 Data Format Indicates present Baud Rate (Comm 1) (2400, 4800, 9600,19.2K) Indicates present Data Format (Comm 1) (8N-1, 8E-1, 8O-1, 8N-2) Value (0-3) R/W 000B 40012 7.7.11 Value (0 3) R/W 000C 4013 7.7.12 Not Used 000D 4014 Fire Window Indicates No. of Fire Channel Value 8-Bit R 000E 4015 7.7.13 COPM Fault Total Window (Photodiode) Faults Fire Sensor Indicates Total No. of Fire Value 8-Bit R 000F 40416 7.7.14 COPM Fault Total Channel Detector COPM Faults Sun COPM Fault Indicates Total No. of Sun Value 8-Bit R 1010 4017 7.7.15 Total Channel Window/Detector COPM Faults Remote Reset Remotely Resets the Alarm Bit 1-Bit R/W 0011 4018 7.7.16 & Warn Relays Remote Alarm Remotely Activates Alarm Test Bit 1-Bit R/W 0012 40419 7.7.17 Test Clear COPM Faults Clears IR COPM Fault Counters Bit 1-Bit R/W 0013 40020 7.7.18 Comm 1 & 2 Total Receive Errors Comm 1 & 2 Bus Activity Rate % Comm 1 & 2 Function Code Errors Comm 1 & 2 Starting Address Errors Total # of Receive Errors (Comm 1 & 2) Bus Activity Rate in % of this Addressed Node vs. other Addressed Nodes (Comm 1 or 2) Total # of Function Code Errors (Comm 1 & 2) Total # of Starting Addresses Errors (Comm 1 & 2) Value 8-Bit R 0020 40033 7.7.19 Decimal Hex (0-100%) (0-64) R 0021 40034 7.7.20 Value 8-Bit R 0022 40035 7.7.21 Value 8-Bit R 0023 40036 7.7.22 Figure 40 Operational Mode Commands

R - indicates Read Only Access R/W - indicates Read/Write Access Parameter Function Type Scale Access Comm 1 Only Total Receive Errors Comm 1 & 2 RXD CRC Lo Errors Comm 1 & 2 RXD CRC Hi Errors Comm 1 Only Overrun Errors Comm 1 Only Noise Flag Errors Comm 1 & 2 Framing Errors Comm 1 & 2 Message Interval Comm 2 Only Total Receive Errors Comm 1 Only SCI Interrupt Errors Total # of Comm 1 Only Receive Errors Total # of RXD CRC Lo Errors (Comm 1 & 2) Total # of RXD CRC Hi Errors (Comm 1 & 2) Total # of Overrun Errors (Comm 1 Only) Total # of Noise Flags Errors (Comm 1 Only) Total # of Framing Errors (Comm 1 & 2) Indicates Comm 1 or 2 Message Interval in Milliseconds Total # of Comm 2 Only Receive Errors Total # of Serial Comm Interface Errors (Comm 1 Only) REG Addr Master I/O Addr Refer to Section Value 8-Bit R 0024 40037 7.7.23 Value 8-Bit R 0025 40038 7.7.24 Value 8-Bit R 0026 40039 7.7.25 Value 8-Bit R 1027 40040 7.7.26 Value 8-Bit R 0028 40041 7.7.27 Value 8-Bit R 0029 40042 7.7.28 Value 8-Bit R 002A 40043 7.7.29 Value 8-Bit R 002B 40044 7.7.30 Value 8-Bit R 002C 40045 7.7.31 Clear Comm Clear All Comm 1 & 2 Bit 1-Bit R/W 002D 40046 7.7.32 1 & 2 Errors Errors Not Used 002E 40047 Comm 2 Address Unit Address (Comm 2) Decimal Hex (1-247) (01-F7) R/W 002F 40048 7.7.33 Comm 2 Baud Rate Comm 2 Data Format Indicates present Baud Rate (Comm 2) (2400, 4800, 9600, 19.2K) Indicates present Data Format (Comm 2) (8N-1, 8E-1, 8O-1, 8N-2) Value (0-3) R/W 0030 40049 7.7.34 Value (0-3) R/W 0031 40050 7.7.35 Figure 40 Operational Mode Commands Continued 34

7.7 FL3102 Operational Mode Command Register Details 7.7.1 Analog A read returns a value, which is proportional to the 0-20mA output current. The current is based on a 16-bit value. The master scaling is 0-65535 decimal, which corresponds to the FL3102 scaling, which is 0-20mA. 7.7.2 Mode A read returns the fire status mode of the FL3102. Mode Decimal Value Power-up Delay 1 Warn Non-latching Only 2 Warn & Alarm Non-Latching 3 Warn Latching Only 4 Alarm Latching Only 5 Warn & Alarm Latching 6 Ready State (No Fire) 7 Alarm Test 10 COPM Fault Detected 11 Figure 41 Mode 7.7.3 Status/Error A read returns the errors that are occurring now, which are indicated by bit position. Byte Function Bit Position EPROM Checksum 8 EEPROM Checksum 7 RAM Test 6 Low Low (24V) Voltage Check 5 Fire Window COPM 4 Fire Sensor COPM 3 Sun COPM 2 Low (12V) Voltage Check 1 High Reset Line Shorted 8 Not Used 7-1 Figure 42 Status/Error 35

7.7.4 Fire Type A read indicates the detection of LFF, HFF or a combination of both when using the Model FL3102. LFF Only Detected = 01 (Lo Data Byte) HFF Only Detected = 02 (Lo Data Byte) Combination of Both = 03 (Lo Data Byte) High Data Byte Not Used. 7.7.5 Model Type A read returns the Decimal Value 3102, which identifies each particular type of unit by model number. Model Version Decimal Value FL3102 DFIR (Digital Frequency Infra-Red) 3102 Figure 43 Model Type 7.7.6 Software Revision A read returns the software revision of the FL3102 in 2 ASCII characters. (Usually a blank and then a letter revision ex. A, B, C, etc). 7.7.7 COPM Fault A read returns the type of Continuous Optical Path Monitoring (COPM) Fault, which is a Fire Window COPM Fault, Fire Sensor COPM Fault or a Sun COPM Fault. The Fire Window COPM indicates that the Fire window is dirty and needs to be cleaned, or that there is a hardware problem with the Sun Channel detection circuitry. Fire Window COPM Fault = 01 (Lo Data Byte) Sun COPM Fault = 02 (Lo Data Byte) Fire Sensor COPM Fault = 04 (Lo Data Byte) High Data Byte Not Used. 7.7.8 EEPROM Override A read indicates the status of the EEPROM Override bit. A write command changes the state of the EEPROM Override bit. When the EEPROM Override bit is enabled, the options for the Detector Sensitivity, Relay Delay, Relay Latching/Non-Latching and Relay Energized/Non-Energized features are now controlled by the data stored in the EEPROM and are no longer controlled by the 8-position DIP-switch located on the bottom of the Power/Relay Board. When the EEPROM Override bit is disabled the options are under the control of the 8- position DIP-switch. The EEPROM Override bit is located in the LSB of the Low Data Byte and the High Data Byte is not used. 36

Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write Figure 44 EEPROM Override EXCEPTION - If an EEPROM error occurs, then the Exception Code 04 (Slave Device Failure) is returned. NOTE - By grounding the ALARM TEST input during the first 10 seconds of the 2 minute power-up cycle, the FL3102 will Disable the EEPROM Override and set the Bit = 0, enabling the 8-position Dip-switch. The red and green LED s will flash simultaneously while the ALARM TEST input is grounded. The EEPROM Override bit will be set to zero and the Dip Switch enabled when the red and green LED s flash alternately after approximately10 seconds, at which time the ALARM TEST input can be released from ground. 7.7.9 Options A read returns the status of the settings for the Detector Sensitivity, Relay Delay, Relay Latching/Non-Latching and Relay Energized/Non-Energized features either from the Options DIP-switch or the EEPROM depending on the setting of the EEPROM Override bit listed above. A write command changes the settings for the EEPROM only when the EEPROM Override bit is set. EXCEPTION - If an attempt to change the EEPROM Options is made while the EEPROM Override bit is not set, then the unit shall return an Exception Code 03 (Illegal Data Value). EXCEPTION If an EEPROM write error occurs, then the Exception Code 04 (Slave Device Failure) is returned. These Functions are indicated on the Low Data Byte and the High Data Byte is not used. 37

Function Bit Conditions Access Position Alarm Latched 5 1 = Latched 0 = Non-Latched Read/Write 10 8 4 2 Time Delay in Seconds Alarm Time Delay 2 4 0 0 1 1 Read/Write Alarm Time Delay 1 3 0 1 0 1 Read/Write 100 75 50 % Sensitivity Sensitivity 2 2 0 0 1 Read/Write Sensitivity 1 1 (LSB) 0 1 0 Read/Write Figure 45 Options 7.7.10 Comm 1 Address A read returns the address of the FL3102. A write changes the address to the requested address. The range of the address is 1 to 247 (01 to F7 Hex). After the address has been changed to the slave unit, the MODBUS communications will cease because the address has changed; therefore the master will have to change its query address to the slave s new address in order to restart the communications. EXCEPTION - If the EEPROM write error occurs, then the Exception Code 04 (Slave Device Failure) is returned. NOTE - By grounding the RESET input during the first 10 seconds of the 2- minute power-up cycle, the FL3102 Address will default to 1. The red and green LED s will flash simultaneously while the RESET input is grounded. The address will be set to a default of 1 when the red and green LED s flash alternately after approximately 10 seconds, at which time the RESET input can be released from ground. 7.7.11 Comm 1 Baud Rate A read returns the baud rate of the FL3102. A write changes the baud rate to the requested baud rate. After the baud rate has been changed to the addressed unit, the MODBUS communications will cease because the baud rate has changed; therefore the master will have to change its baud rate to the slave s new baud rate in order to restart the communications. Baud Rate Low Data Byte Access 19.2K 03 Read/Write 9600 02 Read/Write 4800 01 Read/Write 2400 00 Read/Write Figure 46 Comm 1 Baud Rate This function is indicated on the Low Data Byte and the High Data Byte is not used. 38

EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception Code 03 (Illegal Data Value) is returned. EXCEPTION - If an EEPROM write occurs, then the Exception Code 04 (Slave Device Failure) is returned. Model FL3102 NOTE - By grounding the RESET input during the first 10 seconds of the 2 - minute power-up cycle, the FL3102 Baud Rate will default to 19.2K. The red and green LED s will flash simultaneously while the RESET input is grounded. The Data Format will be set to a default of 8-N-1 when the red and green LED s flash alternately after approximately 10 seconds, at which time the RESET input can be released from ground. 7.7.12 Comm 1 Data Format A read returns the Comm 1 data format of the FL3102. A write changes the data format to the requested data format. After the data format has been changed to the addressed unit, the MODBUS communications may cease or start producing Comm errors because the data format has changed; therefore the master will have to change its data format to the slave s new data format in order to restart or provide proper communications. Data Parity Stop Format Low Data Byte Access 8 None 1 8-N-1 00 Read/Write 8 Even 1 8-E-1 01 Read/Write 8 Odd 1 8-O-1 02 Read/Write 8 None 2 8-N-2 03 Read/Write Figure 47 Comm 1 Data Format This function is indicated on the Low Data Byte and the High Data Byte is not used. NOTE - By grounding the RESET input during the first 10 seconds of the 2- minute power-up cycle, the FL3102 Data Format will default to 8-N-1. The red and green LED s will flash simultaneously while the RESET input is grounded. The Data Format will be set to a default of 8-N-1 when the red and green LED s flash alternately after approximately 10 seconds, at which time the RESET input can be released from ground. 7.7.13 Fire Window COPM Fault Total (Photodiode) A read indicates the number of Fire Channel Window COPM Faults that have occurred in the slave device. This fault is usually caused by a dirty Fire Detector Window. The maximum count is 255 and then the counter will roll over to zero and begin counting again. 39

7.7.14 Fire Sensor COPM Fault Total A read indicates the total number of Fire Channel Sensor COPM Faults that have occurred in the slave device. This fault is usually caused by a faulty Fire Channel Sensor or Circuitry. The maximum count is 255 and then the counter will roll over to zero and begin counting again. 7.7.15 Sun COPM Fault Total A read indicates total number of Sun Channel Window or Sensor COPM Faults that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.16 Remote Reset Writing a 1 to the bit activates the Remote Reset function that resets the Alarm and Warn Relays. The function is active momentarily and will reset automatically after being used. Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write Figure 48 Remote Reset 7.7.17 Remote Alarm Test Writing a 1 to the bit activates the Remote Alarm Test function that activates the Warn and Alarm relay turn-on along with the Analog current status. Once the Alarm Test is complete the function should be disabled by writing a zero to Remote Alarm Test and then resetting the Alarm and Warn relays by writing a one to the Remote Reset (referenced above). Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write Figure 49 Remote Alarm Test 7.7.18 Clear COPM Faults Writing a 1 to the bit activates the Clear COPM Faults function that resets all of the Fire Window COPM faults, the Fire Sensor COPM Faults, and the Sun COPM Faults. The bit and enable function is active momentarily and will reset to disable and zero after being used Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write Figure 50 Clear COPM Faults 40

7.7.19 Comm 1 or 2 Total Receive Errors A read indicates the total MODBUS Comm 1 or 2 Receive Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. The total errors are an accumulation of the individual Comm errors listed below: 7.7.20 Comm 1 or 2 Bus Activity Rate % A read indicates the Comm 1 or 2 Bus Activity Rate in percent of this Slave's addressed node versus other addressed nodes. Range of this value is in hex (0-64), which translates to decimal (0-100%). 7.7.21 Comm 1 & 2 Function Code Errors A read indicates the number of Comm 1 & 2 Function Code Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.22 Comm 1 & 2 Starting Address Errors A read indicates the number of Comm 1 & 2 Starting Address Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.23 Comm 1 Only Total Receive Errors A read indicates the total MODBUS Comm 1 Only Receive Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.24 Comm 1 & 2 RXD CRC Lo Errors A read indicates the number of Comm 1 & 2 RXD CRC Lo Byte Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.25 Comm 1 & 2 RXD CRC Hi Errors A read indicates the number of Comm 1 & 2 RXD CRC Hi Byte Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.26 Comm 1 Only Overrun Errors A read indicates the number of Comm 1 Only Overrun Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. NOTE - An overrun error occurs, when the next received byte of data tries to overwrite an existing received data byte, which has not been processed. Therefore, the next received byte of data is lost. This can be controlled by implementing the proper DCS or PLC Error Handling Timing Setting (ex. Reply Timeout Setting, Delay Time, and Number of Retries) and proper Baud Rate Setting. 41

7.7.27 Comm 1 Only Noise Flag Errors A read indicates the number of Comm 1 Only Noise Flag Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.28 Comm 1 & 2 Framing Errors A read indicates the number of Comm 1 & 2 Framing Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.29 Comm 1 or 2 Message Interval A read indicates the time interval in milliseconds between Comm 1 or 2 Message Intervals. The maximum time interval indicated is 255. 7.7.30 Comm 2 Only Total Receive Errors A read indicates the total MODBUS Comm 1 Only Receive Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.31 Comm 1 Only SCI Errors A read indicates the number of Comm 1 Only SCI (Serial Communications Interface) Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 7.7.32 Clear Comm 1 & 2 Errors Writing a 1 to the bit activates the Clear Comm 1 & 2 Errors function which resets all of the MODBUS Comm Error counters to zero. The function is active momentarily and will reset automatically after being used. Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write Figure 51 Comm 1 & 2 Errors 42

7.7.33 Comm 2 Address A read returns the Comm 2 address of the FL3102. A write changes the address to the requested address. The range of the address is 1 to 247 (01 to F7 Hex). After the address has been changed to the slave unit, the MODBUS communications will cease because the address has changed. Therefore, the master will have to change its query address to the slave s new address in order to restart the communications. EXCEPTION - If the EEPROM write error occurs, then the Exception Code 04 (Slave Device Failure) is returned. NOTE - By grounding the RESET input during power-up cycle (approximately 10 seconds), the FL3102 Address will default to 1. 7.7.34 Comm 2 Baud Rate A read returns the Comm 2 baud rate of the FL3102. A write changes the baud rate to the requested baud rate. After the baud rate has been changed to the addressed unit, the MODBUS communications will cease because the baud rate has changed. Therefore, the master will have to change its baud rate to the slave s new baud rate in order to restart the communications. Baud Low Data Rate Byte Access 19.2K 03 Read/Write 9600 02 Read/Write 4800 01 Read/Write 2400 00 Read/Write Figure 52 Comm 2 Baud Rate This function is indicated on the Low Data Byte and the High Data Byte is not used. EXCEPTION - If an illegal data value is entered which is not listed above, then the Exception Code 03 (Illegal Data Value) is returned. EXCEPTION - If an EEPROM write occurs, then the Exception Code 04 (Slave Device Failure) is returned. NOTE - By grounding the RESET input during power-up cycle (approximately 10 seconds), the FL3102 Baud Rate will default to 19.2K. 43

7.7.35 Comm 2 Data Format A read returns the Comm 2 data format of the FL3102. A write changes the data format to the requested data format. After the data format has been changed to the addressed unit, the MODBUS communications may cease or start producing Comm errors because the data format has changed. Therefore, the master will have to change its data format to the slave s new data format in order to restart or provide proper communications. Data Parity Stop Format Low Data Access Byte 8 None 1 8-N-1 00 Read/Write 8 Even 1 8-E-1 01 Read/Write 8 Odd 1 8-O-1 02 Read/Write 8 None 2 8-N-2 03 Read/Write Figure 53 Comm 2 Data Format This function is indicated on the Low Data Byte and the High Data Byte is not used. NOTE - By grounding the RESET input during power-up cycle (approximately 10 seconds), the FL3102 Data Format will default to 8-N-1. 44

8.0 Appendix 8.1 Specifications Model FL3102 8.1.1 System Specifications 8.1.1.1 Detector Location Class I, Division 1 & 2, Groups B, C & D; Class II, Groups E, F & G; Class III Eexd - IIB + H2 - T6 TYPE 4x, IP66/7 8.1.1.2 IR Detector center wavelength (Figure 15) 4.35 microns 8.1.1.3 Typical Response Time* < 2 sec. @ 50 ft. 8.1.1.4 Minimum Response Time < 500 ms. 8.1.1.5 Field of Vision* (Figure 16) 120 maximum *NOTE Response Times and Field of View data have been derived by testing the Model FL3102 Flame Detector with a 1 square-foot gasoline fire. One cup of unleaded gasoline on top of a one-inch layer of water was ignited for each test. These are typical values and different results may occur depending on the variation of each fire. 8.1.1.6 Sensitivity 50 feet (15.2m); Maximum distance for a 1 square foot (.092m 2 ) gasoline fire to be reliably detected. (For settings see Section 3.5 Switch Selectable Options) 8.1.1.7 Maximum Cable Parameters 4-20mA Output Signal 9000 feet (2750 m), maximum 50 Ohms loop, with maximum 250 Ohms input impedance of readout unit. Remote power supply (see NOTE, page 6) 3000 feet (930 m), maximum 20 Ohms loop and 24VDC minimum. (See Section 3-4 Term. Connections) 45

8.1.1.8 Warranty Two Years 8.1.2 Mechanical Specifications Enclosure material Material (Aluminum): A-356, Optional (Stainless Steel) Color Finish Dimensions Height Width Depth Weight Red Chemical Film per MIL-C-5541, Epoxy Powder Coated 6.000 in (15.2cm) 6.000 in (15.2cm) 5.500 in (14.0cm) 5 lbs (2.3 kg) AL; 16 lbs (7.3 kg) SS 8.1.3 Electrical Specifications 8.1.3.1 Supply voltage range (see NOTE) Nominal supply voltage 24Vdc Range 20 to 36Vdc Maximum supply current 150mA Maximum output signal load 600 Ohms @ 24 VDC Output signal range FAULT signal COPM fault signal Ready signal WARN signal ALARM signal 8.1.3.2 Relay Contact Ratings 8A @ 250VAC, 8A @ 30VDC, Resistive MAX. 8.1.3.3 RS-485 Output Modbus RTU 128 units in series MAX. (247 units with repeaters) 0 to 20mA 0 to 0.2mA 2.0 ma + 0.2mA 4.0 + 0.2mA 16.0 + 0.2mA 20.0 + 0.2mA 8.1.3.4 Baud Rate 2400, 4800, 9600 or 19200 BPS (See Terminal Connections 3-4 for Alarm Output Connections) 8.1.3.5 RFI/EMI Protection Complies with EN50081-1, EN50082-1 8.1.3.6 Status Indicator Two LED s indicate status, fault conditions. 46

8.1.4 Environmental Specifications 8.1.4.1 Operating temperature range -40 F to 176 F -40 C to 75 C 8.1.4.2 Storage temperature range -40 F to 176 F -40 C to 75 C 8.1.4.3 Humidity range 0 to 100% RH, non-condensing 8.1.5 Modbus RTU Protocol For detailed information on data format, read commands, write commands, register details, register locations, refer to the Appendix beginning on page 26. 8.2 Approvals CSA approved, Cenelec & CE Marking pending 8.3 Spare Parts and Accessories 8.3.1 Spare Parts When ordering Spare Parts and/or Accessories, please contact your nearest General Monitors Representative or General Monitors directly and give the following information: 1. Part Number 2. Description 3. Quantity Item Description Part # 1 Lamp, IR Source 70596-2 2 IR Detector, CO 2 71064-1 3 IR Detector, Sun 71064-2 4 Window Cleaning Solution 10272-1 5 Swivel Elbow 961-003 6 Union 961-004 7 Bracket Assembly 71172-1 8 Instruction Manual MANFL3102 9 TL103 UV/IR Test Lamp TL103-1-2 10 Optical Air Guard 71250-1 47

8.3.2 TL103 Test Lamp Due to the advanced discrimination in the Model FL3102, the Model TL103 Test Lamp was developed. The General Monitors TL103 Test Lamp is a battery operated, rechargeable, test source specifically designed to test General Monitors IR Flame Detection Systems. It consists of a high-energy broad band radiation source which emits sufficient energy in the Infra-Red spectra to activate the IR detector. To simulate a fire, the test lamp automatically flashes at one of three DIP-switch selectable rates. The Model TL103, rated explosion proof, is CSA certified for use in Class I, Division 1, Groups C and D areas. The test lamp operates on internal lead-acid batteries which, when fully charged, will operate continuously for 25 to 30 minutes. An internal circuit will prevent operation when the batteries are low. Operating Instructions It is always important to begin a series of flame detector checks with a fully charged TL103. Stand within 10 feet (FL3102) from the unit to be tested and aim the TL103 directly into the detector windows. Press the ON button and be sure the high intensity pulsing beam strikes the detector face squarely. Shaking the lamp from side to side or up and down will increase the simulation of flame flicker, and improve the response of the flame detector to the lamp. If the system is operating normally, the control module will go into a WARNing condition after a few flashes of the Test lamp. If the lamp remains ON for the period set by the Time Delay Adjustment, the controller will go into ALARM. To conserve charge, do not operate the Test Lamp longer than is necessary to test each channel. When the battery level drops below the level required to maintain the proper intensity of the lamp, an internal low voltage circuit will shut the lamp off until the battery has been recharged. Recharging Instructions NOTE Charging must be carried out in a non-hazardous area. The charging receptacle is located inside the housing adjacent to the ON button. To gain access, it is necessary to unscrew the knurled plug from the body of the unit. The plug is secured to the ON button by a safety strap to keep it from being lost. Insert the charging plug into the receptacle. Complete recharging takes fourteen hours, minimum. IMPORTANT: Replace the knurled plug after charging is complete. It is recommended that the TL103 be kept on charge when not in use to prevent excessive battery discharge. The batteries may be charged an average of 500 times and the battery pack is replaceable. 8.3.3 Mounting Swivel / Union A mounting swivel and union are available to connect ¾ conduit into the base of the Model FL3102. The swivel design allows for optical alignment adjustments for the Model FL3102 when using rigid conduit. 48

NOTE Swivel is only rated for Class I, Div 1 & 2, Groups C & D areas. For Group B areas, use mounting bracket. 8.3.4 Mounting Bracket A mounting bracket is available to mount the FL3102 to a wall, pole, etc. The mounting bracket design allows for optical alignment adjustments for the Model FL3102 when installed to a fixed installation. 8.3.5 Optical Air Guard An optical air guard is available for applications such as paint spray booths, which require a method to keep detector optics clean. This air guard mounts at the front of the FL3102 and has a connection for shop air. The air when turned on creates an air wall to keep optics clean. 49

ADDENDUM Product Disposal Considerations This product may contain hazardous and/or toxic substances. EU Member states shall dispose according to WEEE regulations. For further General Monitors product WEEE disposal information please visit: www.generalmonitors.com/customer_support/faq_general.html All other countries or states: please dispose of in accordance with existing federal, state and local environmental control regulations. 50