Fire PROtec. Manual for automatic Fire Curtains. copyright by SIMON RWA Systeme GmbH Passau

Similar documents
Control box FSTronic DES-FS

DICTATOR Hold-Open Systems for Hazardous Areas

SMART FIRE CURTAINS INTISI7. for invisible fire protection closures

Installation and Operating Instructions

CONTROL DEVICE SLIDETRONIC HD

Control box FSTronic DES-FI

Smoke and Fire Curtains. Performance Door sets for security and Fire resistant applications. Northern Doors (UK) Ltd

CI/SfB (68.5) February Intelligent security and fire protection. SecureFire S e c

The new WAREMA external venetian blind 80 S PROVEN THINGS IN PERFECTION

1 P a g e w w w. s m o k e c o n t r o l. c o m. a u

WARNING FIRE DOOR CLOSING

1 P a g e w w w. s m o k e c o n t r o l. c o m. a u

Technical Manual (European Standards)

AUTOMATIC FIRE CURTAIN FIRE CURTAIN FM 1

Branching and Connection Box AAB. Operating manual AAB EN11. GTE Industrieelektronik GmbH

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

UV Flame Supervision System

WSC 204 (WSC / WSC 204MH 0102 / WSC 204KP 0102 / WSC 204BZ 0102)

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

BL 200 Strobes. Page F.01U A1.en/ 6/2/2004 ST / PMF1 / zab

PRODUCT INFORMATION. Sounder SG 200. BDL F.01U A3.en / ST FIR/ PRM1 / zab. Page 1 of 10

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

Installation and Operation Instructions

Reflective Optical Beam Smoke Detector User Guide

A REVOLUTIONARY APPROACH TO FIRE SAFETY

Smoke and Fire Curtains

Smoke Vent Control Panel RZN 4202 V1

Constant voltage 3-phase rectifier.

FirePro control MANUAL

HRX Technical Manual. Version 1.2

AirUnit. Installation instructions. mfh systems modern floor heating. Decentralised domestic ventilation

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

SCHMIDT LED Measured Value Display MD Instructions for Use

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS

Operation & Maintenance Manual

FSLIMPRO

Interface and EOL Modules 8

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

Automatic Smoke & Fire Curtain Surveying Manual. Table of Contents. Before the Survey 2. Carrying out the Survey 2-3

Installation, Operating and Maintenance Manual

Retroreflective sensor with polarization filter

5, SE GÅNGHESTER,

FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION

QA16 Addressable System

1 P a g e w w w. s m o k e c o n t r o l. c o. nz

FIREMASTER PLUS 2 TENABLE ZONE / HEAT PROTECTION ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION

NEW RUSIC DYNAMIC - RSV RUHSTRAT STROMVERSORGUNGEN fills the gap. The all purpose safety lighting systems! Emergency lighting.

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS

Public Safety DAS Annunciator Panel

Kædemotorer. Accessories

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

Instructions for the fan motor control system with integrated wiring terminals SILVER C

FIRERAY 5000 range USER GUIDE

OPTISENS TUR 2000 Technical Datasheet

RE-PR3-E-27 3-Phase Panel Mount 27kW

CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard

Speed Gate ST-01. Double-Sided Section STD-01 ASSEMBLY AND OPERATION MANUAL

Operating Manual MS220DA

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

DS7400Xi Addressable Control/ Communicator

PRODUCT SPECIFICATION FireMaster Plus Concertina

D-TEK O P E R A T I N G I N S T R U C T I O N S V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128

Table of Contents. 1. Mounting Tips... 2

SERIES 4000 AUTO GATE MANUAL

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

Operating Manual MS220KA and MSR220KA

Operating Instructions

COMPACT FLAME CONTROLLER CFC 2000

ELECTRONIC PARTS - CATALOGUE

FIRE DOOR. AlarmGard & FireGard. Preferred door solutions.

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FT-EPB Series. Single Motor

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Instruction manual. Digital Radar Motion Detector with Infrared Remote Control MWD BF. FEIG ELECTRONIC GmbH Lange Straße Weilburg/Lahn

FC724 Fire control panel

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number

MBZ300. Emergency power control unit. GB Installation instructions MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 PME PME. Reset.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

BS-100 DYFI. Installation handbook. Protecting environment, life and property... P-BS100/DCE

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

Operating instructions DVC-P / Bedienungsanleitung Druckregler DVC-P

/ / 2018

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

PRODUCT SPECIFICATION FireMaster Plus

s l it l on for Infrared Heaters

Retroreflective sensor with polarization filter

SP-4004 OPTICAL-ACOUSTIC OUTDOOR SIREN sp4004_en 03/13

QD6310. Fixed Gas Detector Operation Manual

Installation and Operating Manual

Motorised Infrared Optical Beam Smoke Detector. User Guide

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Halton SAFE / 7.14 user guide and installation instructions

DATASHEET VARIOSPEED 6 EMERGENCY RETRACT UNIT CONTROLS AT MOTOR (VS6-ERU-CAM)

Model 17A00 Expansion Enclosure

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

Transcription:

Fire PROtec Manual for automatic Fire Curtains Edition B /2007 All information are subject to technical changes, errors excepted

Contents 1. System Description Page 3-4 1.1 General 3 1.2 Fire curtain sizes 4 2. Technical Data Page 5 2.1 Roller 5 2.2 Electrical control panel 5 3. System Structure Page 6-7 3.1 Head box 6 3.2 Side guides / bottom bar 6-7 3.3 Motor/ Roller tube 7 4. Installation and Assembling Page 8-16 4.1 General 8 4.2 Head box 8-9 4.3 Fixing the roller 10 4.4 Side guides 11 4.5 Control panel 12-16 5. Service and Maintenance Page 17-18 5.1 Service and maintenance 17 5.2 Maintenance check list 18

1. System description Page 3/18 1.1 General The fire curtain system Fire PROtec consists of a high grade stainless steel reinforced woven fibre glass fabric which is rolled up in a compact metal sheet head box in normal state. Simon fire curtains generally work on the principle of gravity. In case of fire alarm the control panel will remove the supply voltage and the curtain shall descend under the power of gravity in a controlled manner. Even in case of complete power failure the fire curtain will safely descend under the power of gravity to the operational position within 60 seconds. The system fulfills highest demands on safety. An integrated round steel in the bottom bar supplies the requested energy for descending by gravity. The fire curtain retracts by an integrated 24 V DC tube motor. The external control panel RSV-500 controls the speed in both directions descending and retracting. FirePROtec as E90. fire curtains are classified according the European Standard EN 13501-2 Certifications and test reports Fire test according DIN 4102-18, fire resistance > 90 minutes 10,000 cycle test according EN 1192 Non toxic test Different experts reports The weight of the fibre glass fabric is 800 g/m². Fabric FirePROtec fire curtains are manufatured with high quality stainless steel reinforced woven fibre glass. The fabric is coated on both sides with special silicone, weight 800 g/m2. The fabric is not toxic (EPA 25/2006) and weather proofed (ÖP 360 1159). The side and bottom hem are sewed with high grade stainless steel thread

1. System description Page 4/18 1.2 Fire curtain sizes Please find below the maximum fire curtains sizes and areas in the table: Table of sizes Width of fire curtain (m) Drop (m) 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 1,5 2,25 3,0 3,75 4,5 5,25 6,0 6,75 7,5 8,25 9,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0 11,0 12,0 2,5 3,75 5,0 6,25 7,5 8,75 10,0 11,25 12,5 13,75 15,0 3,0 4,5 6,0 7,5 9,0 10,5 12,0 13,5 15,0 16,5 18,0 3,5 5,25 7,0 8,75 10,5 12,25 14,0 15,75 17,5 19,25 21,0 4,0 6,0 8,0 10,0 12,0 14,0 16,0 18,0 20,0 22,0 24,0 4,5 6,75 9,0 11,25 13,5 15,75 18,0 20,25 22,5 24,75 27,0 5,0 7,5 10,0 12,5 15,0 17,5 20,0 22,5 25,0 27,5 30,0 5,5 8,25 11,0 13,75 16,5 19,25 22,0 24,75 27,5 30,25 33,0 6,0 9,0 12,0 15,0 18,0 21,0 24,0 27,0 30,0 33,0 X Boxes highlighted indicate 2 motors per roller The below head box dimensions are shown accoring to the drop length of the fire curtain: Table of head box dimensions Drop (in mm) Single roller (W x H) Up to 3.000 Up to 6.000 150 x 180 180 x 210 The maximum witdh is 6 m Maximum drop 6 m.

2. Technical data Page 5/18 2.1 Roller TECHNICAL DATA FIRE CURTAIN Type FirePROtec Fabric Descending Rewinding Mounting Max. Sizes (1) Onesided PU-coated fibre class fabric 570 g/m², grey, not flammable according DIN 4102-1, A2 By gravity (fail safe) Via tube motor 24 V DC, 2,50 A with integrated hall sensor for synchronizing max. torque 4 Nm, integrated in the roller tube Ceiling/ Wall Width=30m,Drop=6m Head box Sheet steel 1.2 mm, powder coated in RAL 7035 (W x H) Single roller (up to max. 6 m width) 150 x 180 mm and 180 x 210 mm with drop >3m Multiple roller (from 6 m width) 150 x 300 mm and 180 x 350 mm with drop >3m Bottom bar Classification Fire resistance Sheet steel triangle powder coated in RAL 7035 with integrated round steel in fabric hem EN 12101-1, ASB 1, D120 (fail safe) 600 C for 2 hours according pren12101-1 Side guides Steel 1.5 mm, powder coated RAL 7035, dimensions (W x D) 50 x 100 mm. For applications with side guides the curtain fabric will always be delivered with a retaining mechanism. This avoids that the fabric can be pulled out from the side guides for example by wind pressure. (1) Special sizes available on request 2.2 Electrical Control Unit TECHNICAL DATA Electrical control unit type RSV-500 Input voltage Max. prefuse Output voltage Max. current load Backup battery (optional) Protection class Housing (WxHxD) Fuses LED-indications (at emergency switch type HE-075 ) Main + slave emergency switch Operation temperature range Weight 230VAC/50Hz * 16 A / characteristic C 24VDC 2.5 A NiMH (durability approx. 4 years) IP 54 Plastic housing, grey 220x145x55mm Mains input fuse (1 A delayed) Mains, OK, Fire alarm RESET-button retract curtain -5 Cupto40 C approx. 1.0 kg Attention! The wiring of the control panel must be done zero potential! For connecting external devices and additional modules see the enclosed connection plan!

3. System structure Page 6/18 3.1 Head box The following drawing is valid for a drop length up to 3 m. Removable plate Picture 3.1 a 3.2 Side gudes / bottom bar Head box A A Picture 3.2 a Detail B Detail A Side guides Bottom bar B B

3. System structure Page 7/18 3.2 Side gudes / bottom bar Detail A (section A-A) Bottom bar Picture 3.2 b Detail B (section B-B) Picture 3.2 c 3.3 Tube motor / Roller tube Wind up Picture 3.3 a Picture 3.3 b

4. Installation and assembling Page 8/18 4.1 General information how to install a complete system Fire PROtec The installer must have the necessary technical knowledge about moving parts and electronic components. According to the site construction and the fire curtain design different installation steps can be required. If you have any doubts how to install we highly recommend to contact us. We are able to send you our installer with all required experience. Only fixings (anchor, bolts etc.) are permitted with a fire resistance of 1000 C. Please proof the construction concerning load capacity. 4.2 Head box installation The head box shall be installed without roller. According to the project details the head box can be supplied in sections. If the head box is supplied in sections please control the signs on the different head box parts and assemble according to the signs. Adapter plates, support plates and matching screws are included. Please assemble the adapter plate and the single parts first and fix them on the wall or ceiling. Fix now the next head box parts as described below. There are different possibilities how to fix the head box. It depends on the site construction. Below there are the most popular installation methods: To fix the head box at the ceiling use the holes at the top of the head box (see picture 4.2 a). To fix the head box at the wall (see picture 4.2 b) the drillings must be made by others. You can fix the head box also this angle at the wall (see picture 4.2 c) or above a suspended ceiling (see picture 4.2 d). The special fixing material is not included in standard deliveries. The maximum distance between the fixings is 1,200 mm. Please take care that no screwing and fixing does protrude more than 15 mm into the head box. Otherwise the fabric could be damaged during descending or rewinding. We recommend e. g. for concrete constructions to use a fire rated anchor M10x25. Please consider that the head box is not symmetric (e. g. W x H 150 x180 mm). The fabric descents on one side of the head box, the opposite side will be covered by the removable plate (see picture 3.1). There is a drilling at the side cap to pass the motor cable out of the head box(see picture 4.3 b).

4. Installation and assembling Page 9/18 Installation samples Concrete ceiling Anchor M10 x 25 Roller fixing bolt Head box Roller fixing part Fabric Roller Side guide Removeable plate Picture 4.2 a Picture 4.2 b Picture 4.2 c Picture 4.2 d Installation dimensions head box (topview) Head box length (customer specific) Dimension X is variable accoding to the head box length Picture 4.2 e Notice: After installation of the head box the area below the removeable plate must be free accessible (see picture 3.1 head box). If the head box is installed above a suspended ceiling a constant possibility for access to the wall is to be ensured. It is imperative that the head box is installed exactly in level. Otherwise the fabric may travel.

4. Installation and assembling Page 10/18 4.3 Installation of the roller The fabric is furled on the roller by the supplier. Please ensure that the fabric is fixed with a strip or else. The fabric must not drop during installation. The istallation of the roller should be done with two people. For the installation please see picture 4.2 a and 4.3 a. There are two cable bushings on the motor end side to pass the cable through the head box (see picture 4.3 b and c). Attention! Please operate the roller motor only in combination with the control panel RSV-500. Otherwise the roller motor could be destroyed. Up Roller Cable outlet Head box Roller fixing bolt Roller fixing Side guide Side guide Bottom bar Picture 4.3 a Picture 4.3 b Roller bearing Bushing 1 Bushing 2 Picture 4.3 c

4. Installation and assembling Page 11/18 4.4 Side guides There are different options to install the side guides, depending on site situation. For the installation in the reveal please use the drillings in the backside of the side guides (see picture 4.4 a). max. 15 mm Insert the socket key from the top of the side guide! Picture 4.4 a For face installation angle plates are available optionally (see picture 4.4b). Picture 4.4 b The side guides must be installed flush with the bottom edge and the outside edge of the head box (see picture 4.4 c-e). Head box Flush Flush Side guides 90 90 Flush Picture 4.4 c Picture 4.4 d Picture 4.4 e Attention! Please check the 90 angle of the side guides / head box after installation. The side guides must be installed absolutely vertically. Please remove the saving strip of fabric after finishing of all mechanical installations and drop the fabric carefully. Please drop the fabric complete to see if there is any problem with srews or other fixing material e.g. in the head box. Attention! There is no speed control as the panel RSV-500 is not operating yet. Please hold the roller to control the drop speed. Finally please install the removeable plate to the bottom of the head box.

OK 4.5 Control panel RSV-500 4.5.1 Wiring diagram BMZ 230 V/50 Hz NYM-J 3x 1.5mm² by others Connecting cable 5x0,75 mm, length 2 m (by the supplier) 2 230 V/50 Hz NYM-J 3x 1.5mm² by others RSV-500 M Smoke/Fire curtain (single roller) RSV-500 Control panelrsv-500 BMZ Fire alarm signal (Volt-free contact NC with auto reset) ST - UP/AP RAUCHSCHÜRZE OK SIMON RWA R Systeme SIMON RWA R Systeme 4. Installation and assembling Page 12/18 RAUCHSCHÜRZE E.g. J-Y(St) Y-BMK 2x 2x 0.8mm² E.g. J-Y(St) Y-BMK 2x 2x 0.8mm² Optional connecting cable for e.g. Multiple roller or curtains with 2 motors RSV-500 E.g. J-Y(St) Y-BMK 4x 2x 0.8mm² E.g. J-Y(St) Y-BMK 2x 2x 0.8mm² Emergency button Key switch (for testing) ST - UP/AP Smoke detector RM 3000 The roller motor will be supplied with a2msilicone cable (5x0,75 m 2 ). If you install control panel more than 2 m from the motor please calculate the cable cross section according to the below formula. We recommend to use fire rated cable. Cable cross section [mm²] = Cable length [m] x 0,05 Fire alarm with Autoreset: Contact open: Alarm Contact close: Curtain rewinds automatically

4. Installation and assembling Page 13/18 4.5.2 General information Attention! Please install the battery after finishing all wirings, connections and programming in the RSV-500. The installer must have the necessary experience and knowledge. The control panel contencts of senitive electronic components and a micro controller. Please avoid wrong connections and take care regarding ESD, otherwise the panel could be damaged. Please read the manual and wiring schematic carefully. The installation should be done in the proximity of the roller motor (distance max. 5 m). The control panel must be programmed. Therefor please read the information in the product information. Each roller motor has one control panel RSV-500. For fire curtains with 2 motors per roller the control panels must be connected together for (2) synchronizing. Please find details in the product information of the panel. (1) ESD = Electrostatic discharge (2) See wiring schematic (4.5.1) 4.5.3 Connection Attention! All connections must be done without mains! Put out the fuses! Attention! Please note that the curtain will rewind automatically when 230 V mains are connected. You can switch off this function by activate the service mode (see DIP-switches). Please insert the cables into the housing and connect the roller motor and all other peripheral systems like emergency button, smoke detector or fire alarm signal. If there is a fire alarm signal please test if it is volt-free. Otherwise it could damage the panel. After finishing all connections please connect the mains (230 V) and insert the mains fuse. The smoke/fire curtain will rewind automatically and stay in the top position. Control panel RSV-500

4.5.4 Wiring schematic Attention! Service switches or external signals for testing/service must be impulses and no permanent signal. Fire alarm with Autoreset: Contact open: Alarm Contact close: Curtain rewinds automatically Contact FAS General Emergency switch HE 07* +EXT -RRWA1.N Loop resistor +EXT -RWA1.N Last Emergency switch HE 076 RD 4 5 RESET +EXT -RWA1.1 First Emergency switch HE 075 GN YE RD 1 2 3 4 5 RESET 15 k 9 9 AUF 7 6 8 AUF 7 6 8 15 k Service down Service UP RM 3000 Contact failure Fuse (1A slow) +EXT -RBMZ1.N Loop resistor +EXT -BMZ1.N Last FAS 2 1 NC 4 NO 3 +EXT -BMZ1.1 first FAS 2 1 NC 4 NO 3 rt +EXT -RRM.N Loop resistor -RM.N Last Smoke detector +EXT -RM.1 first smoke detector ge + - ALARM + Service button - yellow Service button - red Service functions: Service button yellow = Service up Service button red = Service down External service functions: Connection S2 = Service up Connection S3 = Service down - - - 4. Installation and assembling Page 14/18 Relay Option² ) 15k 1 3 2 1 3 Relay Option Option² ) B A Connecting cable Master / Slave (e. g. multiple roller) 2 DIP-switch Motor cable Rt = red gb = yellow sw = black bl = blue bn = brown Motor 230 V AC yellow red black blue brown

4. Installation and assembling Page 15/18 4.5.5 Programming final drop Programming instruction: The drop length of the curtain is factory adjusted to approx. 80 cm. To adjust the drop length to the required length, the RSV-500 has to be set into learning mode. In this learning mode the new drop length is trained by a test run. Procedure: 1. Let the curtain drop down for at least 40 cm by pushing the red service button when the curtain is still completely retracted. A short press on the red control button starts the drop procedure. When a drop length of approx. 40 cm is reached press again the red control button (short press) to stop the drop procedure. 2. After the curtain has stopped to drop down after approx. 40 cm, press both the yellow and red service button inside the RSV-500 for about 2-3 seconds at the same time (while you keep the buttons pressed the curtain will start to move for a short time in both directions). After releasing the control buttons the red signal inside the RSV-500 starts to blink. This signalizes that the RSV-500 is in the programming/learning mode and is ready for the test run. Please note: If the RSV-500 can not be put into programming mode, remove the mains fuse for approximately 10 seconds, then rescrew in the fuse and start again at step 1. If everything works you can go on with the following steps: 3. The test run is started by a short press on the red control button inside the RSV- 500. Now the curtain is rolled up automatically. After the curtain is completely rolled up, it automatically starts to descent. When the curtain has reached the required drop length press again the red service button (short press) in the RSV- 500. By doing this the control system will register this position as the future descending end position of the curtain and the curtain will also stop at once in this position. 4. After 1-2 seconds the curtain will roll up automatically. 5. After the curtain is rolled up, the control panel is put automatically into operation mode. Now the test run and the programming are finished. 6. Now you can insert the backup battery. You can repeat the test/learning run at any time following the above described steps to reprogram the drop position.

4. Installation and assembling Page 16/18 4.5.6 DIP switch applications Attention! Please program DIP-switches only without voltage (mains and battery). ON OFF 1 2 3 4 DIP switch 1: Programming Master/Slave DIP switch 1 OFF = Master DIP switch 1 ON = Slave Master/Slave configuration is used in multiple roller systems. One control panel has to be programmed as Master, all others are Slave panels. All signals (HE, smoke detector, FAS) are connected to the Master. These signals will be transmitted via the BUS intercace COM. The signal inputs (HE, smoke detector, FAS) of the slave pnaels are not active. DIP switches 2 and 4: The DIP-Schalter 2 and 4 are not used. DIP switch 3: Service mode DIP switch 3 OFF = Service mode OFF DIP switch 3 ON = Service mode ON In service mode (DIP switch 3 ON) the curtain does not rewind automatically in case of mains connection. The curtain can be driven up/down by the installer. 4.5.7 Direction of rotation for multiple rollers side by side To change the rotation direction you must change the polarity of the motor cable (blue and brown). Standard direction: Wind up Reverse direction: Wind up Motor cable Connect the motor cable as described in the wiring schematic: Blue core = terminal bl Brown core = terminal br Change polarity: Blau core = terminal bn Brown core = terminal bl Motor cable

5. Service and Maintenance Page 17/18 5.1 Service and maintenance, use 5.1.1 Operation test The operation of the fire curtains should be tested once a month. For doing this please follow the following steps: Make sure that the area where the curtain descends is always free of obstructions Let the curtain descend via the emergency or the key operated switch Make a visual check of the fixings and the fabric Let the curtain roll up again (via reset button of the emergency switch or the key operated switch) Check if the curtain rolls up properly and if it stays in this position 5.1.2 Maintenance Maintenances may only be carried out by qualified and spezialized staff, authorized by SIMON RWA Systeme GmbH. Fire curtains serve to protect human life and thus must be maintained regularly - at least once a year. Maintenance has to be carried out in accordance with a maintenance checklist defined by the manufacturer (download at ). 5.1.3 Terms for use The device must be used as normally intended. The switch-on duration and the ingress protection (IP) must be observed, please inquire in case of doubt. The device is subject to natural wear and tear. In case of material defect claims, these shall be asserted in writing, stating the source of supply of the device. Prescribed time limits and further provisions with regard to claims for material defects exclusively correspond with our General Terms and Conditions (download:, or they may be requested by sending an e-mail to, or by phone +49 851 988700).

5. Service and Maintenance Page 18/18 5.2 Maintenance check list Year of maintenance Date Building project System description Kind of mounting (e. g. ceiling / wall) Battery year of manufacture (1) Mounting staff Serial number / year of manufacture (1) The backup battery must be changed every four years! Name / Signature Test o.k. Notes No. Check points Optical inspection 1.0 Check the fire curtain for damaging, contamination, oxidation 1.1 Elektrical inspection 2.0 Check, if the electrical supply lines are connected properly and fixed well at the actuator 2.1 Check, if the wiring to the actuators has been laid according to the valid VDE-commandments and to the manufacturers instructions (wire cross section, etc.). 2.2 Functional inspection 3.0 Attention! Check the operating voltage (according to manufacturers instructions). 3.1 yes no Let the fire curtain move in its alarm position and check if the curtain descends completely. Ensure that the roll-off area is free of obstacles. yes no yes no yes no yes no yes no yes no yes no 3.2 Reset the curtain. Ensure that the curtain moves duly in its end position. 3.3 Inspection of the mechanical parts 4.0 Check the fastening of the head box and of the side guides (optional) Check the bearing of the roll shaft. 4.1 4.2