SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

Similar documents
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

New Construction Fire Inspection Process

AUTOMATIC FIRE SPRINKLER SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

FIRE SPRINKLER SYSTEMS POLICY

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

DIVISION 21 - FIRE SUPPRESSION

FIRE SPRINKLER SYSTEMS POLICY

CITY OF PASADENA FIRE DEPARTMENT

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

1 Exam Prep. Questions and Answers

DIVISION 21 - FIRE SUPPRESSION

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

Fire Sprinkler System Design and Installation Requirements

APPENDIX H (DESIGN SUBMISSION CRITERIA)

City of Vista Fire Department

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

A. This section includes design and performance information for fire protection and suppression systems.

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

PLAN REVIEW CHECKLIST

Orange Township Fire Department Fire Prevention Bureau

Brighton Area Fire Authority

Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:

FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Sprinkler Permit Applications

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

SECTION WET-PIPE SPRINKLER SYSTEMS

B. Related Sections: The following Sections contain requirements that relate to this Section.

MONTECITO FIRE PROTECTION DISTRICT

SECTION POLICY MANUAL

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

SECTION FIRE SUPPRESSION SYSTEMS

2016 California Building Code Adoption OC amendments Summary Title/Subject Justification/Comments Action

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET

4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.

RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

FIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS

Annual Water-Based Fire Protection Systems Inspection

Fire Sprinkler Submittal Requirements and Acceptance Testing

Fire Sprinkler Plan Submittal Form

FIRE SERVICE FEATURES

Fire Protection Coffee Break Training May 2016

FIRE INSPECTION CHECKLIST

DESIGN & CONSTRUCTION GUIDELINES

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

S000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM

Large Family Daycare Guideline

For additional information regarding R-3.1 residential care facilities please contact (951)

SECTION WET-PIPE SPRINKLER SYSTEMS

WALL ESCUTCHEON PIPE SEAL WITH APPROVED FIRE CAULKING (SEE SPECIFICATIONS) NOTE: 12" 12" 24"

VIOLET TOWNSHIP ZONING & BUILDING DEPARTMENT Rustic Drive Pickerington, Ohio (614) Fax (614)

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

SECTION : FIRE PROTECTION SYSTEMS

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

Design & Construction Standards, Revised January

DIVISION 21 FIRE SUPPRESSION

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

FIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

To expedite the plan review and inspection processes, please refer to the information below.

FIRE PREVENTION GUIDELINE

McMAHON FP200 OUTAGAMIE COUNTY ADMINISTRATION CENTER S. WALNUT & W. 8TH, APPLETON, WI ALTERATION / ADDITION

Checklist For Building Inspection & Fire Safety

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

ADDENDUM NO. 3 March 19, 2018

Access Aisle (Van) (Flow Test) Water Mains (Location & Sizes) Building Entrances. Building, Facilities, Element. Curb Ramps (Built-up)

DIVISION 21 FIRE SUPPRESSION

CONSTRUCTION REQUIREMENTS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 8 Annual Sprinkler System Inspection Revised

Transcription:

July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved; AC-Approved w/comments; I-Incomplete; D-Denied This Checklist outlines general requirements. Information contained herein applies to typical instances and may not address all circumstances. CODE REFERENCES 2007 California Fire Code (CFC), Chapter 9 Section 905 National Fire Protection Association (NFPA) 14 REQUIRED INSPECTIONS 1. Rough and Hydrostatic Inspection(s) 2. Sprinkler Final Inspection (including flow test) FILE REVIEW 1. Is there an alternate method application approved 2. Are there any special requirements or AM&M proposals? 3. Permit fees entered in Permits Plus. 4. Contractor shall provide, or have on file, a current Contractor s License. 5. Name and address of project 6. Contractor s name, address, and telephone number. 7. Three (3) sets of scaled plans and specifications MINIMUM INFORMATION 8. NFPA 14 - Class of standpipe system and the type of standpipe in accordance with 5.2 and 5.3. 9. NFPA 14 8.1 Scale: a common scale is used and the plan information shall be clear and legible, 8.1. 10. NFPA 14 - Plot plan showing supply piping and pipe size from the water source to the building. Page 1 of 5

11. NFPA 14 - Equipment symbol legend and compass point. 12. CFC 905 The correct standpipe class is provided for the occupancy and is in accordance with IFC 905. 13. NFPA 14 - Building dimensions, height, and the location of the fire department connection. PIPE 14. NFPA 14 4.2.3 The material standard and pipe wall thickness (schedule) for steel pipe assembled using welded or rolled groove method shall comply with the requirements in Section 4.2.3. 15. NFPA 14 4.2.4 Steel pipe assembled using threading shall comply with the material standard and pipe wall thickness requirements in Section 4.2.4. 16. Piping shall be supported and anchored in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, 6.4. VALVES 17. NFPA 14 4.5.1 Valve locations are detailed and data sheets are provided. 18. NFPA 14 4.5.1 The type of indicating or nonindicating shall comply with the design and operational requirements in section 4.5.1. 19. NFPA 14 6.2.1 Connection to the water supply is equipped with the appropriate valve(s) as specified in 6.2.1. 20. NFPA 14 6.2.2 Gate valves are provided to permit the isolation of standpipes without interrupting the supply to other standpipes from the same water source. 21. NFPA 14 6.2.5.1 Combined systems: connection from standpipe to sprinkler system has an individual control valve and check valve detailed. 22. CFC 905.9 Electric supervision of the valves for water supply, isolation control, and valves in feed mains is provided in accordance with IFC 905.9. 23. NFPA 14 6.2.8 All valves are marked or otherwise identified in accordance with the requirements of Section 6.2.8 to indicate the portion of the system they control. HOSE AND CABINETS 24. NFPA 14 4.6 Specification sheets for hose cabinets, racks and hose are provided. 25. NFPA 14 4.6.2 Hose for Class II and III systems is listed and complies with the diameter and length requirements of Section 4.6.2. 26. NFPA 14 4.6.4 Nozzles for Class II service are listed. 27. NFPA 14 4.7 Hose valves and connections comply with the requirements in Section. 28. NFPA 14 4.6.1.1.2 Hose cabinets are provided with signage and operating instructions. 29. NFPA 14 4.6.1.2 Cabinets with glass shall have a glass breaking device secured to the cabinet, which is detailed or noted on the plans. Page 2 of 5

30. NFPA 14 4.6.1.3 When a hose cabinet penetrates a fire-resistive assembly, the assembly shall be protected in accordance with CBC 712.3.2 requirements for membrane penetrations. HOSE CONNECTIONS 31. NFPA 14 7.2.1 Approved pressure regulating device is provided when the residual pressure exceeds the pressure specified in 7.2.1, detail and specification sheets are provided. 32. NFPA 14 7.3.1 Hose connections and hose stations are unobstructed and shall be located above the floor in compliance with. 33. CFC 905.4 The Class I standpipe is detailed showing outlets locations in compliance with 7.3.2 and CFC 905.4. 34. CFC 905.4 Each Class I standpipe has a roof outlet or an outlet at the highest landing of stairway that has roof access for a roof with less than a 4/12 slope. 35. NFPA 14 7.3.3 The Class II standpipe is detailed showing outlets locations in compliance with 7.3.3. 36. CFC 905.6 Class III standpipe outlets are located the same as Class I and II outlets, including the roof outlets, 7.3.4. 37. CFC 905 When required, Class II and III standpipe systems are auto- or semiautomatic-wet systems as specified in 5.4.3 and IFC 905. 38. CFC 904.5 An extra outlet is detailed and provided for the most hydraulically remote standpipe for testing purposes when the roof has less than a 4/12 slope. 39. NFPA 14 4.8.2 Each FDC has swivel fittings that comply with 4.8.2. 40. NFPA 14 6.3.5.2 Each fire department hose connection is provided signage in accordance with 6.3.5.2. 41. NFPA 14 6.3.5.2.2 If the FDC also supplies the sprinkler system then a sign indicating the system pressure and demand are detailed. 42. NFPA 14 6.3.5.3 When a portion of a building is served by an FDC, a sign is detailed to specify which part of the building is being served. 43. NFPA 14 6.3.2 Each FDC is provided with a listed check valve. 44. NFPA 14 6.3.3 FDC connections to a specific type of system are located and detailed relative to the control valves in accordance with the criteria listed in 6.3.3. 45. NFPA 14 6.3.4 For freezing environments, an automatic drip valve is detailed between the check valve and the FDC. 46. NFPA 14 6.3.5.1 FDC location is detailed on the street or response side of the building and signage detail complies with 6.3.5.1. 47. NFPA 14 6.3.6 The FDC height above finish grade is detailed and complies with 6.3.6. 48. NFPA 14 7.13.1 The number of FDCs required for Class I or III standpipe system shall comply with 7.13.1. Page 3 of 5

49. NFPA 14 7.13.2 Each high-rise building zone is provided the number of remotely located FDCs in accordance with 7.13.2. PROTECTION 50. CFC 905.4.1 Class I and III standpipes and lateral piping supplied from the standpipes are located in stairways or are protected in accordance with 6.1.2.2, CFC 905.4.1, and 905.6. 51. CFC 905.4.1 Class I and III lateral piping to hose connections need not be protected in sprinklered buildings, 6.1.2.2.1, CFC 905.4.1 and 905.6. 52. CFC 905.5.2 Class II standpipes and risers need not be protected. 53. NFPA 14 6.1.2.4 Piping exposed to corrosive conditions is corrosion-resistant pipe or provided a protective coating, coating information is provided. 54. NFPA 14 6.1.1 Dry standpipes are not concealed unless monitored in accordance with 6.1.1. 55. NFPA 14 6.1.2.6.1 If pipe must be installed under the building, details are provided to show method of protecting the pipe in accordance with 6.1.2.6.1. 56. NFPA 13 6.1.2.5 Earthquake bracing is provided and detailed in accordance with NFPA13, 6.1.2.5. INTERCONNECTION 57. NFPA 14 7.5.1 Interconnection between two or more standpipes in the same building is detailed. 58. NFPA 14 7.5.2 Interconnection at the top of the building is detailed when water supply tanks are at the top of the building and check valves are located and detailed in accordance with 7.5.2. DESIGN CRITERIA 59. NFPA 14 7.7.1 Each FDC for Class I and II standpipes are designed to provide the system demand, calculations are provided. 60. CFC 905 When automatic or semiautomatic water supply is required by 5.4 and CFC 905 the standpipe system demand shall comply with 7.7.2 and calculations are provided. 61. NFPA 14 7.10.1.3 Combination automatic sprinkler and standpipe systems shall be calculated in accordance with the requirements in Section 7.10.1.3. HYDRAULIC DEMAND 62. NFPA 14 7.10.1.2 Class I and III standpipes: Calculations based on the criteria in Section 7.10.1.2 shall be hydraulically calculated to verify the minimum flow rates specified in Sections 7.10.1.1.1, 7.10.1.1.2, 7.10.1.1.3, or 7.10.1.1.4.1 are satisfied. 63. NFPA 14 7.10.2.2 Class II standpipes: Calculations demonstrate the hydraulically most remote hose connection is supplied with the minimum water flow and pressure specified in 7.10.2.2. 64. NFPA 14 7.10.3 Maximum flow rate for each hose connection is in accordance with 7.10.3. 65. NFPA 14 7.8.2 Pipe schedule standpipe system complies with Table 7.8.2.1. Pipe schedule designs are limited to buildings not classified as a high-rise and equipped with wet standpipe systems, 7.8.2. Page 4 of 5

66. NFPA 14 7.12.1 A drain risers are detailed is provided in accordance with 7.12.1 for a standpipe equipped with pressure-regulating devices 7.12.1. 67. NFPA 14 7.12.1.1 The drain riser detail illustrates a tee as required in section 7.12.1.1. 68. NFPA 14 7.12.2.1 A drain valve and piping are detailed in accordance with 7.12.2.1. 69. NFPA 14 9.3 At least a 30 minute water supply is available for any class system. 70. NFPA 14 7.9 zoning is designed, detailed, and comply with 7.9. Page 5 of 5