Safety & Installation Instructions

Similar documents
Safety & Installation Instructions

Safety & Installation Instructions

Safety & Installation Instructions

EL-TSTAT-8820 Safety & Installation Instructions

Safety & Installation Instructions

Control4 Wireless Thermostat by Aprilaire. Safety and Installation Guide

Safety & Installation Instructions

Smart Temp. Model

TCONT602AF22MA. Programmable Comfort Control. Installation Instructions 18-HD37D1-1

Commercial Touchscreen Thermostat

ACONT600AF11MA Programmable Comfort Control

Owner s Manual. Model 8800 Universal Communicating Thermostat. Includes Operating Instructions and Warranty Information

Programmable Touchscreen Thermostats. Disconnect power before beginning installation.

PS4000 and PS5000 Touchscreen Programmable Thermostat Installation and Owners Manual Robertshaw 01/

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Detailed Installer Guide

Installer Guide. WARNING Important Safety Information. 1 Specifications

INSTALLATION MANUAL. This manual covers TopTech models: TT-S-755H. Need Help? Thermostat Applications Guide. Power Type. Table of Contents.

EWT-3102/EWT-3103 Touchscreen Programmable Thermostat

Indicates incorrect room temperature. No second stage or AUX heating. Emergency heat does not turn on

This thermostat provides electronic control of 24 VAC single-stage and multi-stage

VisionPRO 8000 with Wi-Fi

Model number is located on back of thermostat.

Detailed Installer Guide

T-32-TS Touchscreen Thermostat. Installation Manual

PerFormance Pro t12000 series InstallatIon GUIDe

Installation and Setup Guide

CT1001/CT1002 Touchscreen Programmable Thermostat

PerFormance Pro t4900 school series InstallatIon GUIDe

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.

6 Setting Your Program Schedule 7 Operating Your Thermostat 8 Additional Operation Features 9 Thermostat Maintenance

RTH8500 Series. Quick Installation Guide. Included in your box. Programmable Thermostat. Quick Install Guide Screws and anchors. RTH8500 Thermostat

Installer Guide. WARNING Important Safety Information. 1 Specifications

Programmable Thermostat

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

6 Setting Your Program Schedule 7 Operating Your Thermostat 8 Additional Operation Features 9 Thermostat Maintenance

PRO Installation. Thermostat Wi-Fi

Safety & Installation Instructions

(-)HC-TST213UNMS 5/1/1 Day 5/2 Day Non-Programmable. Yes

RC-2000 Thermostat Installation Instructions

T7200D,E Series 2000 Commercial Microelectronic Thermostats

1F98EZ-1421, Easy Install

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

Comfort System T-21-P Touchscreen Thermostat Installation Manual

heat (2 heat/1 cool).

WARNING Important Safety Information

CT2800 Programmable Thermostat

P200 Programmable Thermostat Installation Instructions & User Guide. For Installation Help. White-Rodgers.com

Smart Temp. ApolloP/n Installation Manual. Version 1.0

MagicStat CT3300 Programmable Thermostat

Emerson Blue Easy Set 1H/1C

No fan function in heat mode. Fan ON continuously. Indicates incorrect room temperature

Installation Instructions

User s Manual

PECO. WavePRO Wireless System INSTALLATION GUIDE: T2500 THERMOSTAT AND R2500 RECEIVER. The Peco WavePRO Wireless System

PRO Installation. Touch Wi-Fi Thermostat

HEAT PUMP PROGRAMMABLE THERMOSTAT

CAUTION: ELECTRICAL HAZARD

T8611M Deluxe Programmable Heat Pump Thermostats

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

Must be installed by a trained, experienced technician

Universal Programmable Smart Wi-Fi Thermostat Up to 3 Heat / 2 Cool Heat Pump Up to 2 Heat / 2 Cool Conventional with wireless Humidity Control*

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins

Programmable Thermostat

WARNING Important Safety Information

1F Day 5/1/1 Day Non-Programmable. W/ Economizer Max. Stage Heat/Cool 1/1 1/2 2/2 2/3 3/1 3/2 4/2 4/3

1F80ST /2 Day 5/1/1 Day Non-Programmable 1F86ST-0471

WARNING Important Safety Information

USER MANUAL MODEL READ ALL INSTRUCTIONS BEFORE PROCEEDING. 5-2 Day Programmable Multi-Stage 2 Heat/1 Cool Heat Pump Digital Thermostat

OWNER S MANUAL Venstar Inc. 08/07

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat:

1F Non-Programmable 5/1/1 Day 7 Day

1F95EZ-0671 Non-Programmable 7 Day. Maximum Stages Heat/Cool 1/1 2/2 3/1 4/2

WARNING Important Safety Information

Install Guide CT100. Caution. Caution

Lyric T6 Pro Wi-Fi. Professional Install Guide. Compatibility. Customer assistance. Programmable Thermostat

Operator: Save these instructions for future use!

HEAT HEAT HEAT COOL COOL

Digital Programmable

HAI Omni-Bus Network Installation. 5. Typical Application

TH146-N-2H1C. 1. Introduction. 2. Installation. 1.1 Applications. 2.1 Control Module (CT280-2H1C) 1.2 Supplied Parts. 1.

USER MANUAL 2000NC MODEL READ ALL INSTRUCTIONS BEFORE PROCEEDING. Builder Series 5-2 Day Programmable Single Stage Heat/Cool Digital Thermostat

SAS6000UTK-7 UNIVERSAL THERMOSTAT

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE

Deluxe Programmable Thermostats

T8624D Chronotherm IV Deluxe Programmable Multistage Thermostats

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION. Premier Series

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

WARNING Important Safety Information

Small Digital Thermostat Controller Temperature Control

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

PRO Installation. Touch Wi-Fi Thermostat

1F Day Day Non-Programmable. Maximum Stages Heat/Cool

T8602C Chronotherm IV Deluxe Programmable Thermostats

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.

Auto-Changeover: A mode in which the thermostat will turn on the heating or cooling based on room temperature demand.

Set & $ave. Model Programmable Thermostat. installation and operation manual

Deluxe Programmable Heat Pump Thermostat T8611M

INSTALLATION INSTRUCTIONS

Universal Wireless Thermostat Kit. * Wireless Humidity Control requires accessory model 7330.

Transcription:

8400 Series Thermostats Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61000652C 8400 Tstat Install.indd 1 10/13/09 11:08:56 AM

Table of contents Installation Installation location recommendations... 3 Outdoor temperature sensor (optional)... 4 Thermostat mounting... 5 Power & reset options... 5 Wiring terminal... 6 Wiring diagrams... 7 Setup & Testing System setup instructions... 11 System test mode... 16 References Quick reference to controls & display Non-programmable models (8444, 8446, 8448).... 22 Programmable models (8463, 8465, 8466).... 23 Thermostat features... 24 Troubleshooting... 25 Specifications... 27 2 61000652C 8400 Tstat Install.indd 2 10/13/09 11:08:56 AM

Installation Installation location recommendations Thermostat should be mounted: On an interior wall, in a frequently occupied space. Approximately 5 above floor. At least 18 from outside wall. Thermostat can be mounted to a vertical junction box. Do not mount thermostat: Behind doors, in corners, or other dead air spaces. In direct sunlight, near lighting fixtures, or other appliances that give off heat. On an outside or unconditioned area wall. In the flow of a supply register, in stairwells, or near outside doors. On a wall with concealed pipes or ductwork. 3 61000652C 8400 Tstat Install.indd 3 10/13/09 11:08:57 AM

Installation Outdoor temperature sensor (optional) Outdoor temperature can be measured by attaching an 8052 sensor to the S1 and S2 terminals. System setting #05 (Remote sensor) is used to enable sensor. Heat pump models can use the outdoor temperature to effectively utilize the heat pump: When the outdoor temperature is less than the Low Balance Point, the heat pump will be locked out and only auxiliary heating will be used. When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and only the heat pump will be used to provide heating. Install on side of building out of direct sunlight (north side recommended). Mount above snow line. Mount at least 3 away from exhaust vents and condensing lines. Maximum wire length is 300. Do not route wires along 120 VAC lines. RC R W Y G C S1 S2 O/B L W2 Y2 4 61000652C 8400 Tstat Install.indd 4 10/13/09 11:08:57 AM

Installation Thermostat mounting 1. Remove the back of the thermostat, by pressing the tab on the bottom of the unit. 2. Pull wires through the opening on the back of the thermostat. 3. Position and level the back of the thermostat on wall and mark the hole locations with a pencil. 4. Drill 1/4 holes & insert supplied anchors (drywall only). 5. Place back over anchors, insert and tighten screws. 6. Seal wire entry holes to prevent drafts affecting temperature readings. Power & Reset options The thermostat is dual power. It can either be AC or battery powered, or both (to provide backup power for the clock). Batteries are optional if the thermostat was connected to AC power when installed. For heat pump models (8446, 8448HP, 8465, 8466HP) 24 VAC must be connected in order for the system fault and emergency heat indicators to operate. The thermostat has a memory backup that saves the thermostat s settings in case of a power interruption. The reset button located under the battery cover can be used to reset the thermostat back to factory defaults. The system settings will also be reset back to defaults. 5 61000652C 8400 Tstat Install.indd 5 10/13/09 11:08:58 AM

Installation Wiring terminal Wire specifications 18-24 gauge thermostat wire Installation notes Ensure power at the HVAC equipment is off. Loosen screw terminals, insert stripped wire and re-tighten. Push the excess wire back into the opening and plug the wall opening to prevent drafts. RC 24 VAC supply cooling* R 24 VAC supply heating* W 1st stage heat / auxiliary Y 1st stage cooling / compressor G Fan C Common (optional when powered by batteries) S1 & S2 outdoor temperature sensor (optional) O/B Reversing valve L System fault indicator W2 2nd stage heat / auxiliary Y2 2nd stage cooling / compressor * Jumper between RC & R is used in single transformer systems (see wiring diagrams). RC R W Y G C S1 S2 O/B L W2 Y2 6 61000652C 8400 Tstat Install.indd 6 10/13/09 11:08:58 AM

Installation Wiring Model 8463 & 8444 Single Transformer (use jumper wire) Wiring Model 8463 & 8444 Two Transformers (Remove Jumper Wire) JUMPER TRANSFORMER HEATING COOLING FAN OUTDOOR TEMP SENSOR COOLING TRANSFORMER HEATING COOLING FAN OUTDOOR TEMP SENSOR HEATING TRANSFORMER RC R W Y G C S1 S2 RC R W Y G C S1 S2 7 61000652C 8400 Tstat Install.indd 7 10/13/09 11:08:58 AM

Installation Wiring Model 8465 & 8446 single Transformer (use Jumper Wire) Wiring Model 8465 & 8446 Two Transformers (Remove Jumper Wire) JUMPER AUX HEATING COMPRESSOR FAN OUTDOOR TEMP SENSOR REVERSE VALVE FAULT DETECT AUX HEATING COMPRESSOR FAN OUTDOOR TEMP SENSOR REVERSE VALVE FAULT DETECT TRANSFORMER HEAT PUMP TRANSFORMER AUX HEATING TRANSFORMER RC R W Y G C S1 S2 O/B L RC R W Y G C S1 S2 O/B L 8 61000652C 8400 Tstat Install.indd 8 10/13/09 11:08:58 AM

Installation Wiring Model 8466 & 8448 single Transformer (use Jumper Wire) for HEAT/COOL System Wiring Model 8466 & 8448 TWO TransformerS (REMOVE Jumper Wire) for HEAT/COOL System TRANSFORMER JUMPER 1st HEATING 1st COOLING FAN OUTDOOR TEMP SENSOR NOT USED NOT USED 2nd HEATING 2nd COOLING COOLING TRANSFORMER 1st HEATING 1st COOLING FAN OUTDOOR TEMP SENSOR NOT USED NOT USED 2nd HEATING 2nd COOLING HEATING TRANSFORMER RC R W Y G C S1 S2 O/B L W2 Y2 RC R W Y G C S1 S2 O/B L W2 Y2 9 61000652C 8400 Tstat Install.indd 9 10/13/09 11:08:58 AM

Installation Wiring Model 8466 & 8448 single Transformer (use Jumper Wire) for HEAT PUMP System Wiring Model 8466 & 8448 TWO TransformerS (REMOVE Jumper Wire) for HEAT Pump System HEAT PUMP TRANSFORMER JUMPER 1st AUX HEATING 1st COMPRESSOR FAN OUTDOOR TEMP SENSOR REVERSE VALVE FAULT DETECT 2nd AUX HEATING 2nd COMPRESSOR HEAT PUMP TRANSFORMER 1st AUX HEATING 1st COMPRESSOR FAN OUTDOOR TEMP SENSOR REVERSE VALVE FAULT DETECT 2nd AUX HEATING 2nd COMPRESSOR HEATING TRANSFORMER RC R W Y G C S1 S2 O/B L W2 Y2 RC R W Y G C S1 S2 O/B L W2 Y2 10 61000652C 8400 Tstat Install.indd 10 10/13/09 11:08:59 AM

Setup & Testing System setup instructions The following instructions show how to enter the system setup menu and change settings. The table on the following pages lists the settings and their details. Default settings are shown in bold. Some settings are only available to certain models, and some are specific to thermostats set to heat pump mode. How to enter the system setup menu to change system settings Press repeatedly until system is set to OFF. Press and hold and for three seconds. The screen of the first setting will be displayed. Press or to change the setting. Press to change to the next option. Press after the last setting. DONE will be displayed. The thermostat will return to Normal mode if no key is pressed in 3 seconds. To reset all system settings back to default, press the RESET button located under the battery door. SETTING VALUE SYSTEM SETTING NUMBER 11 61000652C 8400 Tstat Install.indd 11 10/13/09 11:08:59 AM

Setup & Testing System setup instructions (continued) Thermostat models 8448 & 8466 have the option of being used in heat pump or heat/cool systems. Switch SW1 located on the back of the thermostat s face is used to select this. System setting number 00 will only be shown on these models to display the position of SW1. SW1 HEAT PUMP HEAT/COOL 12 61000652C 8400 Tstat Install.indd 12 10/13/09 11:08:59 AM

Setup & Testing System setup instructions (continued) System setting 00 Equipment type (8466, 8448) (Set by SW1) 01 Temperature scale 02 Fan control in heating 03 Offset temperature for internal sensor 04 Auto mode 05 Outdoor temperature sensor 06 Compressor minimum off time 07 Heating minimum off time 08 Equipment minimum on time Setting range, default in bold 0 : heat/cool 1 : heat pump 0 : Fahrenheit 1 : Celsius 0 : Gas or oil furnace (Equipment controls fan) 1 : Electric (Thermostat controls fan) 0 : No offset applied 4 F to +4 F ( 2 C to +2 C) 0 : Auto mode is disabled 1 : Auto mode is enabled 0 : No outdoor temperature sensor attached 1 : Outdoor temperature sensor attached 5 minutes 1 to 5 minutes in 1 minute steps 2 minutes 1 to 5 minutes 2 minutes 1 to 5 minutes 13 61000652C 8400 Tstat Install.indd 13 10/13/09 11:08:59 AM

Setup & Testing System setup instructions (continued) System setting 09 1st stage differential 10 2nd stage differential (8448, 8466) 11 3rd stage differential (8448HP, 8466HP) 12 Reverse valve (8446, 8466HP, 8465, 8466HP) 13 Integral factor period (P+I control)* Set to OFF for proportional control only 14 Deadband (auto mode) 15 Progressive recovery (8463, 8465, 8466) Setting range, default in bold 1 F (0.5 C) 1 F to 4 F (0.5 C to 2 C) 1 F (0.5 C) 1 F to 4 F (0.5 C to 2 C) 1 F (0.5 C) 1 F to 4 F (0.5 C to 2 C) 0 O/B energized in cooling (O) 1 O/B energized in heating (B) 4 minutes 1 to 5 minutes or OFF to disable 3 F (2 C) 2 F to 5 F (1 C to 3 C) 0 : Progressive recovery is disabled 1 : Progressive recovery is enabled * The integral factor is used in the equipment control algorithm to maintain the space temperature at set point. A short integral factor period will increase the number of cycles per hour. (A short integral factor period will be more comfortable.) A long integral factor period will lower the number of cycles per hour. (A long integral factor period will be more economical.) 14 61000652C 8400 Tstat Install.indd 14 10/13/09 11:09:00 AM

Setup & Testing System setup instructions (continued) System setting 16 Low Balance Pt. (8446, 8448HP, 8465, 8466HP) System setting 05 must be enabled 17 High Balance Pt. (8446, 8448HP, 8465, 8466HP) System setting 05 must be enabled 19 Program format (8463, 8465, 8466) 20 Change air filter 21 Change water panel** Set number of months until reminder is required 22 Humidifier type** 23 Service dehumidifier 24 Service HVAC Setting range, default in bold 20 F ( 7 C) 1 F to 35 F ( 17 C to 1 C) or OFF to disable 60 F (16 C) 40 F to 80 F (4 C to 27 C) or OFF to disable 0 5/2 program (Weekdays and Weekends) 1 5/1/1 program (Weekdays, Sat. and Sun.) OFF 1, 3, 6, 12 months or OFF to disable OFF 1 to 12 months or OFF to disable 0 : Flow through type humidifier (1 reminder per season) 1 : Drain-less type humidifier (2 reminders per season) OFF 1 to 12 months or OFF to disable OFF 1 to 12 months or OFF to disable ** If humidifier type is set to Drain-less, then the first reminder is based on the system setting 21, second reminder will activate 3 months later. If humidifier type is set to Flow through, then the first reminder is based on system setting 21, second reminder will activate 12 months later. 15 61000652C 8400 Tstat Install.indd 15 10/13/09 11:09:00 AM

Setup & Testing System test mode The system test mode is used to test a system after installation. The outputs of the thermostat can be manually activated one at a time to test their function. The following instructions show how to enter the test mode and turn outputs on and off. The charts on the following pages show all of the options for each model. The test steps are: Test Number Heat/Cool Models 8444, 8463, 8448HC, 8466HC Heat Pump Models 8446, 8465, 8448HP, 8466HP 50 Heating (W) (W2) Aux Heating (W) (W2) 51 Cooling (Y) (Y2) Compressor Cooling (Y) (Y2) 52 Fan (G) Compressor Heating (Y) (Y2) 53 Fan (G) 16 61000652C 8400 Tstat Install.indd 16 10/13/09 11:09:00 AM

Setup & Testing System test mode (continued) How to enter the system test menu Press repeatedly until system is set to OFF. Press and hold and for three seconds. The screen of the first test step #50 is displayed: Press to turn on the output (01). For multi stage output, press again to turn on the 2nd stage (02). Press to turn off the output (00). Press to change to the next test step. Press after the last test step. DONE will be displayed. The thermostat will return to Normal mode if no key is pressed in 3 seconds. SYSTEM TEST NUMBER OUTPUT STATUS FLASHES IF 24VAC IS NOT PRESENT MODE (SW1 SETTING 8448 & 8466 ONLY) 17 61000652C 8400 Tstat Install.indd 17 10/13/09 11:09:00 AM

Setup & Testing Step #50 Heat #51 Cool #52 Fan Key Input Test steps for 8444 & 8463 System Setting Display (Output) #2 01 HEATING ON (W) 01 COOLING ON (Y) 01 FAN ON (G) [UP] 0 : Gas ON 1 : Elec ON ON [DOWN] [UP] ON ON [DOWN] [UP] ON [DOWN] 18 61000652C 8400 Tstat Install.indd 18 10/13/09 11:09:01 AM

Setup & Testing Step #50 Heat #51 Cool #52 Fan Key Input Test steps for 8448HC & 8466HC System Setting Display (Output) #2 01 HEATING ON (W) 02 HEATING ON (W2) 01 COOLING ON (Y) 02 COOLING ON (Y2) 01 FAN ON (G) 1st [UP] 0 : Gas ON 1 : Elec ON ON 2nd [UP] 0 : Gas ON ON 1 : Elec ON ON ON [DOWN] 1st [UP] ON ON 2nd [UP] ON ON ON [DOWN] [UP] ON [DOWN] 19 61000652C 8400 Tstat Install.indd 19 10/13/09 11:09:01 AM

Setup & Testing Step #50 Aux #51 Cool #52 Heat #53 Fan Key Input Test steps for 8446 & 8465 System Setting Display (Output) #2 #12 01 AUX HEATING ON (W) 01 COOL/HEAT ON (Y) 01 FAN ON (G) [UP] 0 : Gas ON 1 : Elec ON ON [DOWN] [UP] 0 : O ON ON ON 1 : B ON ON [DOWN] 0 : O ON 1 : B [UP] 0 : O ON ON 1 : B ON ON ON [DOWN] 0 : O 1 : B ON [UP] ON [DOWN] O/B 20 61000652C 8400 Tstat Install.indd 20 10/13/09 11:09:01 AM

Setup & Testing Step #50 Aux #51 Cool #52 Heat #53 Fan Key Input Test steps for 8448HP & 8466HP System Setting Display (Output) #2 #12 01 AUX HEATING ON (W) 02 AUX HEATING ON (W2) 01 COOL/HEAT ON (Y) 02 COOL/HEAT ON (Y2) 01 FAN ON (G) 1st [UP] 0 : Gas ON 1 : Elec ON ON 2nd [UP] 0 : Gas ON ON 1 : Elec ON ON ON [DOWN] 1st [UP] 0 : O ON ON ON 1 : B ON ON 2nd [UP] 0 : O ON ON ON ON 1 : B ON ON ON [DOWN] 0 : O ON 1 : B 1st [UP] 0 : O ON ON 1 : B ON ON ON 2nd [UP] 0 : O ON ON ON 1 : B ON ON ON ON [DOWN] 0 : O 1 : B ON [UP] ON [DOWN] O/B 21 61000652C 8400 Tstat Install.indd 21 10/13/09 11:09:02 AM

Quick Reference to controls & Display Non-Programmable models (8444, 8446, 8448) System Mode Setting Current Indoor Temperature Outdoor Temperature (OPTIONAL) Temperature SetTING Equipment Status System Mode Fan Setting UP down Fan Setting Heat pump models only Emergency heat (RED) System FAULT (YELLOW) Indicator shows through housing Quick Reference Card Battery Door Message Center Low Battery Warning 22 Note: BACKLIGHT IS ACTIVATED WITH FIRST BUTTON PRESS AND AUTOMATICALLY TURNS OFF. 61000652C 8400 Tstat Install.indd 22 10/13/09 11:09:02 AM

Quick Reference to controls & Display Programmable models (8463, 8465, 8466) System Mode Setting Fan Setting System Mode Fan Setting Program Current Schedule Period Current Indoor Temperature Current Time Outdoor Temperature (OPTIONAL) Temperature SetTING Equipment Status UP down Hold Heat pump models only Emergency heat (RED) System FAULT (YELLOW) Indicator shows through housing Quick Reference Card Battery Door Message Center Low Battery Warning Note: BACKLIGHT IS ACTIVATED WITH FIRST BUTTON PRESS AND AUTOMATICALLY TURNS OFF. 23 61000652C 8400 Tstat Install.indd 23 10/13/09 11:09:02 AM

Thermostat Features All 8400 series thermostats Large, clear, backlit display is easy to read even in the dark. Displays room temperature, temperature setting, and optional outdoor temperature. Dual power option (Battery or 24 VAC). Front battery door access for fast, easy replacement. Built in compressor protection. Circulation fan mode for air cleaning. Water panel, dehumidifier, air filter, and HVAC service indicators. System test mode. Programmable models only (8463, 8465, 8466) Separately programmable weekday/weekend schedules. Easy to use temperature control can override program schedule at any time. Progressive recovery. Progressive Recovery feature allows the thermostat to activate the heating and cooling equipment prior to an event in order to reach the desired temperature at the start of the next scheduled event. 24 61000652C 8400 Tstat Install.indd 24 10/13/09 11:09:02 AM

Troubleshooting Display is blank Check circuit breaker and reset if necessary. Make sure power switch at heating & cooling system is on. Make sure furnace door is closed securely. If thermostat is battery powered, make sure fresh AA alkaline batteries are correctly installed. Temperature settings do not change Make sure heating and cooling temperatures are set to acceptable ranges: Heat: 45 to 90 F (7 to 32 C). Cool: 50 to 99 F (10 to 37 C). Heating system does not respond ( HEATING appears on screen) Check for 24 VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem. Check for 24 VAC between the heat terminal (W) and the transformer common. If 24 VAC is present, the thermostat is functional. Check the heating equipment to find the cause of the problem. Check for loose or broken wires between the thermostat and the heating equipment. 25 61000652C 8400 Tstat Install.indd 25 10/13/09 11:09:03 AM

Troubleshooting 26 Cooling system does not respond ( COOLING appears on screen) Check for 24 VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem. Check for 24 VAC between the cooling terminal (Y) and the transformer common. If 24 VAC is present, the thermostat is functional. Check the cooling system to find the cause of the problem. Check for loose or broken wires between the thermostat and the cooling equipment. Fan does not turn on in a call for heat Check System Setting #02 (Fan Control), to make sure the fan control is properly set to match the type of system (see page 11). Heat pump issues cool air in heat mode, or warm air in cool mode Check System Setting #12 (Reversing Valve), to make sure it is properly configured for your system (see page 11). Heat/cool both on at same time Check SW1 (Equipment Type), to make sure it is set to match the installed heating/cooling equipment (see page 12). Check to make sure heating and cooling wires are not shorted together. Heating equipment is running in cool mode Check SW1 (Equipment Type), to make sure it is set to match the installed heating/cooling equipment (see page 12). HEATING is not displayed Change the System Mode to Heat, and set the temperature level above the current room temperature. COOLING is not displayed Change the System Mode to Cool, and set the temperature level below the current room temperature. 61000652C 8400 Tstat Install.indd 26 10/13/09 11:09:03 AM

Specifications Environment Temperature Relative humidity Operating: 32 to 120 F (0 to 48.9 C) Shipping: -30 to 140 F (-34.4 to 60 C) Operating: 5% to 90% R.H. (non-condensing) Electrical Operating voltage Current Power supply Battery power 24 VAC (18 30 VAC) Maximum: 2.5A (total), 1.0A (single output) Maximum surge current: 5A Dual power. Can be battery or 24 VAC powered. When both the sources are available, battery will be used as back up power. Battery power: AA size alkaline battery x 2 Battery life: Approximately 1 year 27 61000652C 8400 Tstat Install.indd 27 10/13/09 11:09:03 AM

Specifications Thermal Outdoor temperature sensor Room temperature measurement Outdoor temperature measurement Temperature setting range Maximum distance: 300 feet Display range: 32 to 99 F (0 to 40 C) Display range: -20 to 130 F (-30 to 55 C) Heat: 45 to 90 F (7 to 32 C) Cool: 50 to 99 F (10 to 37 C) RESEARCH PRODUCTS CORPORATION P.O. BOX 1467 MADISON, WI 53701-1467 www.aprilaire.com 61000652 10.09 B2204777C 28 61000652C 8400 Tstat Install.indd 28 10/13/09 11:09:03 AM