ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

Similar documents
ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon Boiler Controller Commissioning Quick Reference Guide

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

G a

Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range.

Contents. 1 General Appliance Type Single Units Cascade Manager Units Cascade Slave Units...

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

Appliance and Controller Electrical Installation Guide.

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range.

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

RVL470. Heating Controller. Use. Functions. Series B

RVL481. Heating Controller. including d.h.w. heating

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

Quickheat 30 weather compensated boiler control

Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled**

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

RVL480. Heating Controller

INSTRUCTION FOR THE USER THC V E OIL BLU

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

prestige Control Application Supplement WARNING

RVL47. Heating Controller. Installations Instructions. Installation

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

COnDEnSInG BOIlERS TAU UNIT OIL USER parameters manual

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

Settings and Maintenance of the CombinAir

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Operating Instructions

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

1.1 Controller General Information

Operating Instructions

Electronic Pellet Burner Controller NPBC-V3M

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

Service Manual. w/con X US Interface Models: Series: & WARNING

Electronic Pellet Burner Controller NPBC-V3-1

Room Unit for Boiler Control QAA User manual. Building Technologies. With OpenTherm Interface

Control Application. Supplement - ACVMax

Service Manual Models:

RVL479. Heating Controller. for use with a partner unit

Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range

prestige Control Application Supplement - Type 5 MCBA WARNING

Service Manual. w/con X US Interface Models: WARNING

Type summary Albatros 2

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

prestige Control Application Supplement - ACVMax

Boiler controller S-Tronic Plus

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

- Data Brochure Steam Control 279

Service Manual Models: 1.0, 1.3, and 1.5

Service Manual Models:

Service Manual Models:

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

DOMESTIC HOT WATER Follow operational sequence

Service Manual Models:

Boiler controller Lambdatronic S 3200

CEM-24 Series. Owner's Manual - Installation and Operating Instructions

Service Manual Models: Series 100 & 101

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date:

Installation & Operation Manual

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

Service Manual. w/con X US Interface Models: Beginning with Serial # WARNING

prestige Control Application Supplement - Type 5 MCBA WARNING

PRELIMINARY EDITION

RVP310. Heating Controller. Building Technologies HVAC Products

Condensing Boiler RS100 Controller Training Program

Parameter guide 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER WARNING WARNING

THERMAX Efficiency Monitor

District heating controller

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

prestige Control Application Supplement - TriMax

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

B-40/B-41 Modulating Temperature Controller

User Instructions For TopTronic RS-30

Q - Series Boiler. Troubleshooting Manual

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

Local Process Bus LPB

ADI LT CONDENSING LOW TEMPERATURE BOILER

GH10PA USER MANUAL. Program version 01 MANUAL FOR CONTROLLER FOR CONTROLLING CENTRAL HEATING BOILERS FIRED WITH PELLETS AND OATS

SYX660 Commissioning Guide V Page 1 of 55

District heating controller

- Data Brochure Universal Reset Module 422

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

Service Manual Models: 1.0, 1.3, and 1.5

Installation and Operating Manual for the EcoStar 500 Oil Condensing Floor Standing Range Output Range kw

- Data Brochure Universal Reset Module 423

- Data Brochure D 260. Boiler Control /09

O CRC100. Comfort Room Controller (2015/01) en

INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT

Weather compensated flow temperature control of heating and boiler systems

Transcription:

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. The RVA 46 Zone Controller can only be used in conjunction with a RVA47 controlled boiler installation. The RVA46 controller must be connected to a LPB network utilized by the RVA47 controllers. Dedicated connections points can be found in the wiring looms supplied within the housing for the RVA 47 and RVA46. Separate wiring looms are available if the controllers are to be panel mounted. The RVA 46 controller can control it dedicated heating zone in one of two methods. Fixed flow temperature controlled by the master RVA47. A flow sensor is NOT required. The controller will use the outside air temperature reading obtained by the master RVA47. The controller will control the operation of the zone pump. The temperature control of the respective area can be enhance by the application of a dedicated room unit. QAA70, QAA50 or QAA10. Variable flow temperature controlled via a combination of the following. A flow sensor positioned on the respective zone s flow pipe after the three port mixing valve and pump. (QAD21 or QAD26) The controller can utilize the outside air temperature information obtained by the master RVA47, however if the heating zone is effected by adverse outside temperature that is different from that sensed by the masters RVA47 sensor a dedicated zone sensor can be installed and wired to the RVA46 controller.(qac32) The controller will control the operation of a three port mixing valve (230Volt) (supplied by others.) The controller will control the operation of the zone pump. The temperature control of the respective area can be enhanced by the application of a dedicated room unit. QAA70, QAA50 or QAA10.

RVA 46 Fault Indication If the sensors and communication wiring connected to the RVA46 controller fail or are removed from circuit, an error message will be displayed on the left of the LCD screen. Error Message Notation Er. Once an error message is present the cause of the error can be traced by accessing function [50]. To access function [50], Open the flap of the controller and press the down Prog button twice. [50] Should appear in the left-hand side of the LCD display. The figure shown in the center of the screen is the fault identification number. The display can hold a number of faults but will only display 2 at any one time. The second error can be accessed by pressing the + or buttons. Once a fault has been rectified the error number will disappear or be replaced with another fault number if further attention is required. The fault identification numbers are detailed below. Blank No Fault. 10 Outside Air Temperature Sensor. 30 Flow Temperature Sensor 61 Fault Room unit. 81 Short Circuit on LPB Connection. 100 Two Clock Masters Present. 140 Incorrect Device or Segment Address 145 Wrong Device Connected to PPS Circuit. 150 General Burner Module Fault.

ProCon Fault Indication. MHG Heating Ltd The following codes will be displayed on both the Boiler control panel and the RVA46 Unit. Boiler Control Panel: If the Boiler LMU64 Controller or RVA46 Unit detects an operational fault a relevant code is flashed alternately with the Time of Day display. If the fault prevents the boiler from operating the appears at the lower left corners of the display. By pressing the INFO button on the display a full screen display will indicate the fault code. By opening the opening the side-hinged cover / flap on the RVA46 unit and pressing the PROG button twice Line # 50 will indicate the fault code and give a brief description of the fault. Faults can only be rest at the boiler by pressing the RESET button. Prior to pressing the RESET button a note should be made of the fault code for future reference.

Fault Code Description E-0 No Error Detected E-10 Outside Air Sensor Fault / Not Detected E-20 Flow Water Sensor Fault / Not Detected E-26 System Flow Sensor Faulty / Not Detected E-28 Flue Gas Sensor Fault / Not Detected E-40 Return Water Sensor Fault / Not Detected E-46 System Return Water Sensor Fault / Not Detected E-50 HWS Sensor Short Circuit 1 E-52 HWS Sensor Short Circuit 2 (Not Used) E-58 HWS Volt Free Switch Fault / Not Detected E-60 Faulty Room Sensor E-61 Faulty Room Sensor E-62 Incorrect Room Unit Connected E-77 Air Pressure Sensor Not Detected (Not Used) E-78 Water Pressure Sensor Defective (Not Used) E-81 LPB Short Circuit (Boiler Cascade Wiring) E-82 LPB Address Conflict (Boiler Cascade Settings) E-86 Short Circuit on PPS Connection (Not Used in ProCon Configuration) E-91 EEPROM E-92 Hardware Malfunction E-100 Conflict Between Time of Day Master Control (Boiler / QAA73 / RVA47) E-105 Annual Service Due (QAA73 Service Tool Required to Rest Timer on HT Range) E-110 Boiler Water Temperature Overheat E-111 Boiler Temperature Too High (Auto Resetting) E-113 Flue Gas Temperature overheat (Not Used) E-117 High System Water Pressure Sensor (Not Used) E-118 Low System Water Pressure Sensor (Not Used) E-119 System Water Pressure Switch Activated (Below 0.8 bar) E-124 Boiler Temperature Too High (Auto Resetting) E128 Flame Extinguished During Operation (LMU Version D) E129 Air Supply Error. Fan speed incorrect during operation. (LMU Version D) E-130 Flue Temperature Too High (Auto Resetting) E-131 Fault With Burner E-132 External Safety Interlock Activated (Open Circuit) E-133 No Flame Detected After Final Ignition Attempt E-134 Flame Extinguished During Operation LMU Version C) E-135 Air Supply Error. Fan speed incorrect during operation. (LMU Version C) E-140 LPB Segment / Address Not Recognized (Boiler Cascade Settings) E-142 LPB Missing Partner (Boiler Cascade Settings) E-145 Wrong Device Connected to PPS Circuit (Not Used in ProCon Configuration) E-146 Unrecognized Plant Configuration E-147 Burner Modules Not Connected (PPS Circuit Not Used in ProCon Configuration ) E-148 LPB Interface Not Configured (Boiler Cascade Settings) E-150 General Boiler Fault E-151 Boiler LMU64 Controller Malfunction E-152 Boiler LMU64 Controller Parameter Programming Error E-153 Boiler Control Interlocked E-154 Boiler Operating Outside of Predefined Parameters. (System Hydraulic Error.) E-160 Fan Not Reaching Set Point E-161 Combustion Fan Speed Too High E-162 Air Pressure Switch Fault (Not Used) E-164 Flow Switch / Pressure Switch Open (Not Used) E-166 Air Pressure Switch Fault (Not Used) E-180 Boiler Operating in Chimney Mode 100% Output E-181 Boiler Operating in Commissioning Mode E-183 Boiler Controller / QAA73 Room Unit in Parameter Setting Mode

End User Parameter Setting. To enter the End User Parameter Program, the door must be opened and one of the UP or DOWN Prog buttons must be depressed. A number between 1 & 50. Will appear in a bracket on the left of the display window. These can be paged through by using the UP or DOWN buttons. To alter or input the required data in the selected program line # use the + or - buttons. To leave the End User Parameter Setting Menu press the AUTO button. The defaults indicated below are for standard systems. If additional control features are required alteration will have to be made. Please refer to the RVA46 manual for additional details. #, -, --- Indicates where an input can be made if required. -- Indicates where an input can not be made and a sensed / attenuated figure is displayed. OFF will be displayed if the +/- buttons are used. [Prog #] Description of Prog # Range Inputs Preset Time of Day. 1 Time of day 0-23:59 Hr/Min 00:00 2 Weekday 1 7 Day 1 Time Switch Program Heating 5 Every day the same. 1-7 Day - Every day different. 1 7 Day 6 1 st On time. - 24:00 Hr/Min 06:00 7 1 st Off time. - 24:00 Hr/Min 22:00 8 2 nd On time - 24:00 Hr/Min - 9 2 nd Off time - 24:00 Hr/Min - 10 3 rd On time - 24:00 Hr/Min - 11 3 rd Off time - 24:00 Hr/Min -

Hot Water Service 12 HWS Operating Mode 0/1 1 0 HWS OFF 1 HWS ON 13 Required HWS temperature 40-60 C 55 Heating Circuit 14 Night set back temperature 10-30 C 16 15 Frost Protection temp 4-15 C 10 16 Summer/Winter switching 8-30 C 17 17 Slope of heating curve -/2.5.40-32 Actual Values 18 Actual Room temperature 0-50 C -- 19 Actual outside temperature -50. +50 C -- Maintenance 23 Restore factory presets 0/1-0 Press +&- together for 3 seconds 50 Indication of faults 0 255 --

Heating Engineer Parameter Setting. To enter the Heating Engineer Parameter Program, the door must be opened and the UP & DOWN Prog buttons must be depressed for at least 3 seconds until # 51 appears in the window. A # between 51 & 95. will appear in a bracket on the left of the display window. These can be paged through by using the UP or DOWN buttons. To alter or input the required data in the selected program line # use the + or - buttons. To leave the Heating Engineer Parameter Setting Menu press the AUTO button. [Prog #] Description of Prog # Range Preferred Setting Service Values 51 Output Test 0 Automatic control 0 4 0 1 All outputs off 2 Circulating pump on 3 Mixing Valve Open 4 Mixing Valve Closed 52 Input Test 0 Flow temperature value 0.2 0 1 Outside temperature value 2 Room temperature value 53 Plant Type # refer to drawings at rear 1 16 -- of manual (System Specific) 54 Display of nominal room temp set point. 1..12/0255 -- Actual Values 55 Actual value of flow temperature 1..4/0..140 -- 56 Actual value of HWS temperature 0 140 -- 57 Actual value of boiler flow temperature. 0 140 -- (Not always available.) 60 Display of boiler error codes 1 255 --

62 Display of PPS communication 0 15 0 255 -- 0000 PPS Short Circuit --- No communication 0 15 Address Display on Left 0 255 Device Identification Display on Right Space Heating 63 Room Unit Type 0 / 1 1 0 Analog 1 Digital (RE3231 [QAA70] or QAA50) 63 Parallel displacement of heating curve -4.5- +4.5 0 65 Room temperature Influence 0 / 1 1 0 Inactive 1 Active 67 Room temperature pump switching differential Higher = Less stable temperature ---/0.5..4 1 Lower = More stable temperature ----- Inactive. 68 Minimum limitation of flow temperature. 8 95 8 69 Maximum limitation of flow temperature. 8 95 82 70 Type of build construction 0/1 1 0 Heavy 1 Light 71 Automatic adaptation of heating curve. 0/1 0 0 Inactive 1 Active HWS 80 Reduced HWS temperature set point 8..70 40 81 HWS time control 0..3 1 0. 24 hours per day. 1. As local heating times. 2. As local heating times with 1 hour shift. 3. As system heating times with 1 hour shift

LPB Communication Setting 85 LPB control device address 0..16 2 0. Standalone single RVA46 1. Master RVA47 cascade manager with sensors attached. 2 16 Slave RVA46s operating from master RVA47.(House Number.) (Each subsequent RVA46 should be given consecutive numbers.) 86 LPB control segment address 0..14 1 0. Heat generator. (Street Name.) 1.14 Heat consumer. 87 Clock mode. 1..2 2 1 System time, 2 System time with adjustment. 88 Summer / Winter change over function. 0..1 0 0. Inactive. 1. Central change over of all heating circuits 92 LPB Bus power supply. 0..1 1 0. Off. 1. On. 93 Operation of LPB power supply. On / Off -- 94 Display of LPB communication. On / Off -- 95 Source of Outside air temperature 00.01..14.16 -- --. -- No Signal. 00.01..14.16. Address

OEM Parameter Setting. To enter the OEM Parameter Program, the door must be opened and the UP & DOWN Prog buttons must be depressed for at least 10 seconds until 00000 appears in the window. The 00000 display must be changed to 11111 by inputting a password. The password for the RVA 46 is DOWN, DOWN, PLUS, MINUS, UP. (Older units DOWN, UP, PLUS, MINUS, PLUS.) A # between 22 & 91. will appear in a bracket on the left of the display window. These can be paged through by using the UP or DOWN buttons. To alter or input the required data in the selected program line # use the + or - buttons. To leave the OEM Parameter Setting Menu press the AUTO button. [Prog #] Description of Prog # Range. Preferred Setting Space Heating OEM 22 Room influence gain factor. 0..20 4 23 Quick setback constant. 0..20 8 (Room sensor dependant) Increase. Setback will become longer Decrease. Setback time will become shorter 24 Boost of room temperature set point. 0..20 5 (Room sensor dependant) Increase. Heat up time reduced. Decreased. Heat up time increased. 25 Frost protection program 0..1 1 0. Frost protection program switched. Off 1. Frost protection program switched. On 26 Boost of boiler temperature Set point 0 50 10 HWS 31 Maximum HWS set point 8 80 60

35 HWS Priority. 0..2 1 0 Absolute 1 Shifting 2 None (Parallel operation with heating.) General 41 Display default 0..1 0 0. Day # Time of Day. 1. VT Circuit flow temperature. 42 Heat gains -2 +4 0 Increase. If gains are high. Decrease If gains are low. 43 Curve Adaptation 1 sensitivity 1 15 15 Outside air range between 4-12 0 C 44 Curve Adaptation 2 sensitivity 1 15 15 Outside air range below 4 0 C 91 Software Version 00.0 99.9 --