Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

Similar documents
Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

Analysis of the Design of an HVAC System in a Public Building

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Daikin Blueprint: Delivering Hot Water with a Chiller

State Grid Zhejiang Electric Power Corporation Electric Power Research Institute, Hangzhou, , China

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

The Mode of Urban Renewal Base on the Smart City Theory under the Background of New Urbanization

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Design of Humidity Monitoring System Based on Virtual Instrument

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Development and Application of Micro Channel Heat Exchanger for Heat Pump

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Research on the Monitor and Control System of Granary Temperature and Humidity Based on ARM

Computing Services Center

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

A study of Transient Performance of A Cascade Heat Pump System

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

2012 International Symposium on Safety Science and Technology Factor analysis of high-rise building fires reasons and fire protection measures

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

The Low-Temperature Radiant Floor Heating System Design and Experimental Study on its Thermal Comfort

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

Modeling and Simulation on Temperature Control System of Farm Products Baking Equipment. Liu Jun, Jia Zhenwei, Guo Rongxing

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Temperature. In the HVAC area, we talk about two kinds of temperatures.

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

A New Dedicated Outdoor Air System with Exhaust Air heat recovery

Development of Small-diameter Tube Heat Exchanger: Circuit Design and Performance Simulation

Appendix 13. Categories of Cooling and Heating systems

Vapor-Compression Refrigeration

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

b.) Technical Information:

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Research on Fault Detection and Diagnosis of Scrolling Chiller with ANN 1

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Design of an Infusion Rate Control System Based on Single Chip Microcomputer

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

CHAPTER 4. HVAC DELIVERY SYSTEMS

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

APPLICABILITY OF VRV/VRF HVAC SYSTEM A JUDICIOUS AND RATIONAL APPROACH

Purdue e-pubs. Purdue University

General HVAC Recommendations

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

VRV The total solution. Integrated Climate Control

Design of Cold Light Source System for Medical LED Endoscope

DESIGN AND FABRICATION OF A PORTABLE REFRIGERATOR BASED ON PELTIER EFFECT

Study on the North China Rural Water Supply Project O&M Cost Standard Rating

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

A REVIEW ON GREEN TECHNOLOGY IN HVAC

Construction of Wireless Fire Alarm System Based on ZigBee Technology

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

4.0 Mechanical Redesign

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

The Application of Double-deck Inorganic Composite Fire Resisting Shutters in Constructional Engineering Bai-Xia ZHOU*

Study on an environmental simulation system of low/high temperature. for great space

Design of the Fiber-optic Fence Warning System with Distributed Video Real-Time Display Function Qiang-yi YI and Zheng-hong YU *

European Researcher, 2014, Vol.(75), 5-2

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

ENGINEERING. Edition No. 13 October 2002

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Application of Fuzzy Control in Central Air-conditioning Terminal Units Energy-saving

ErP. ErP READY. The Eco-Design Directive ErP for refrigerator systems and heat pumps. READY

Research on Public Space Renewal Strategy of Small and Medium-sized Towns Based on Spatial Syntax--Taking Liulin Liaoyuan Square as an Example

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

International Engineering Research Journal Performance assessment of multistage thermoelectric cooling module based refrigerator

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Indoor thermal comfort by controlling heat transfer through building envelope

An Eco- economics Analysis on Construction and Development of New Urban Areas

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Adsorption refrigeration system using waste heat

Description of All Alternatives Considered-

SIMULATION OF A NEW TYPE GAS-FIRED AIR-COOLED AIR-CONDITIONER. Lin Wang, Xing Xu, Aihua Ma, Yonghui Guo and Xiwen Zhou

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

ADVANCED TRAINING INSTITUTE, HYDERABAD PR04/F01

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

Transcription:

Application of the VRV Air-Conditioning System Heat Recovery Series in Interior Zone and Analysis of its Energy Saving Qiang Zhang Deying Li Jiandong Zhang Master Student Professor Engineer Key Laboratory of Heating, Gas Supply, Ventilating & Conditioning Engineering Beijing Institute of Civil Engineering and Architecture, 100044 Beijing & China E-mail: zhangqiang1980@126.com Abstract: To reduce the energy consumption of air conditioning systems, we can use the VRV air conditioning system to supply cold loads in the winter for rooms in the construction inner zone where cold loads need to be supplied. The VRV air-conditioning system of variable frequency technology can achieve the effect of energy conservation. In this article, we analyze the application of the VRV air conditioning system heat recovery series in the construction inner zone and its energy saving characteristics via a project example. Key words: VRV air-conditioning system; heat recovery series; construction inner zone; energy saving 1. INTRODUCTION With the continuous development of national economy, the size and volume of modern architectures are constantly growing in many large and medium-sized cities emerged lots of office buildings and shopping centers and other buildings, which have a common feature of a larger presence within the district. In such buildings, it was possible that some rooms need to be heated up at the same time; some other rooms need to be cooled down. But the traditional air conditioning and traditional forms can only heat up or cool down at a time.thus the indoor heat and cold sinks haven t been fully utilized. Not only can this substantially increase the capacity of air conditioners, but also enormous waste of energy would be caused. Theoretical analysis and practical tests [1~3] show us that failing to set air conditioning system in light of the differences between the building inner and outer zone in a building with inner zone would not meet the requirements of environmental comfort, but would cause the serious mixed loss of heat and cold energy as well as the great difficulties to the reconstruction. For the design of air conditioning in a building with inner zone, the new added No.5.2.3 regulation of Code for design of heating ventilation and air conditioning 2001 edition requests that in the inner zone and the surrounding areas of the buildings with large discrepancy of load characteristics, in the rooms which must be heated and cooled respectively at the same time, the air conditioning system should be installed respectively. Engineers have put forward some different modes of air conditioning system, some of which have been applied for buildings with inner zone [4]. Such as setting the heating system alone in outer zone, and CAV air conditioning system with a variable fresh air volume in the inner zone; setting heating system in outer zone and VAV air conditioning system in inner zone; closed-loop water source heat pump system; VRV air conditioning system heat recovery series; multi-zone air conditioning system, and so on. The different air conditioning systems have their own advantages and disadvantages. In this paper, we will only introduce the application of VRV air conditioning system heat recovery series in interior zone, and analyzes its energy saving efficiency. 2. SYSTEM STRUCTURE AND RUNNING PATTERN VRV air conditioning system heat recovery series is composed of several indoor units and several

Fig. 1 The principle diagram of VRV air conditioning system heat recovery series Fig. 2 The principle diagram of refrigerant s current direction in the system outdoor units. This paper will analyze the most typical system of one outdoor unit. Fig.1 shows the system s structure and the principle diagram. The outdoor unit is composed of variable frequency compressor, heat exchanger module and etc. The indoor unit is just a heat exchanger module. The heat exchanger module is composed of electronic expansion valve, heat exchanger, two position three way electromagnetic valve and three tubes (the high pressure air tube, the high pressure liquid tube and low pressure air tube). The outdoor unit module s structure is the same as the indoor unit module, the indoor unit connects the heat exchanger module with the system through the switches between the two position three way electromagnetic valve and the electronic expansion valve. [5] The controllers were fixed between the indoor and outdoor units, and they would switch the tubes automatically according to the signals (to heat or to cool) from each room. When the rooms need to be cooled, the three tubes would be switched to the sucking tube and the liquid tube, then the high pressure refrigerant would evaporate and return vapor after throttle. Then the coils of indoor unit would function/work as evaporator and make the room cool. When the rooms need to be heated, the tubes would be switched to the air exhaust tube and the liquid tube, then the high pressure refrigerant vapor would emit heat in heat exchanger (condenser) inside room and would be congealed to liquid. The outdoor units can run the refrigerating circulation up to snuff for -5~40 scope of the outdoor temperature (the indoor wet-bulb temperature 15~25 ); running the heating circulation up to snuff for -10~15 scope of the outdoor temperature (the indoor dry-bulb temperature 16~27 ).

Fig. 3 The distribution of the De Bao hotel Through the above analysis, we can tell that the structure of modules of the indoor and outdoor heat exchanger can match each other. Any module can convert their circulate mode freely through the appropriate conversion of the electronic expansion valve and the two position three way electromagnetic valve. The system can also convert cooling into heating or vice versa and meet the request of being cooled down or heated up respectively at the same time in indifferent rooms. We can select a system with two indoor units to analyses the circulate mode of VRV air conditioning system heat recovery series. When the system is cooling and heating at the same time with one indoor unit (such as No.2 indoor unit) in the condition of cooling, then the heat exchanger (HE2) of it is evaporator; while the other indoor unit (No.1 indoor unit) is in the condition of heating. At that time the heat exchanger (HE1) of the No.1 indoor unit is condenser. The refrigerant that No.1 indoor unit needed is equal to the flux of the No.2 indoor unit. The outdoor heat exchanger is closed. Fig.2 shows the refrigerant s current direction in the systems. 3. ACTUAL ENGINEERING INSTANCE [6] The Peking De Bao Hotel s building area is 27000 square meters, and the air conditioning area of it is 25000 square meters. The hotel meeting room, which is surrounded by the guest rooms, still needs to be cooled while in the transfer reasons and winter, because the heating load of it is big. Fig. 3 shows the distribution of the guest rooms area and the meeting room in the hotel. We can know from Fig. 3 that the meeting room is in the inner zone of the hotel and the distance between it and the exterior protected construction is 8.2 meters. Fig.4 shows the distribution of temperature in the inner and outer zone of the guest rooms area. It shows that the air conditioning must provide cooling for the meeting room to eliminate the heating load and to assurance the normal temperature of the meeting room.

Fig.4 The temperature recording of De Bao hotel inner zone and outer zone in January 18 When the hotel was designed, the differences According to experiment [7], the VRV air between the inner and outer zone s load hadn t been conditioning system s SEER has a high numerical considered and the air conditioning system hadn t value when the part load rate varies between 45% and been designed separately. The air conditioning 70%.The max figure of some part load COP can adopted two-pipe water system, which resulted in the achieve as high as 4.1. However, the COP of normal comfortable temperature in the guest rooms however, Air-Source Heat Pump Chiller is only under3.0 the meeting room s temperature is very high and the following the whole load operation and in the guest feels uncomfortable and the complaint rate is condition of part load operation [5], even under 2.0. rather high. Thus the task of the reception of the According to the annual air conditioning load meeting can t be guaranteed. After the market distributed data of the ASHRAE criterion 880-56 investigation and on-the-spot inspection, it was (shows in the table 1), the time that air conditioning decided that to adopt the fresh air and VRV air load exceeds 80% only occupies less than 10% of conditioning system heat recovery series to solve the total annual operation time. In other wards, the heating load problem of the hotel inner zone in the operation time of air conditioning system with part transfer seasons and winter. The inner zone air load exceeds more than 90% of total annual operation conditioning area is 800 square meters. The design time. Thus, we can say that the application of the load is 84 kilowatts. The equipment is the product of VRV air conditioning unit applies in buildings has the the Shanghai Daikin Industries Co. Ltd. extremely good energy saving characteristic. The heating load problem of the inner zone at Tab.1 The annual air conditioning load transfer seasons and winter were solved by the distributed data operation of VRV air conditioning system heat Cold load rate (%) 75~100 50~75 25~50 0~25 recovery series. At the same time, because the new system has sets the fresh air duct solo, the outdoor air Running time rate load can resolve the inner zone heating load problem 10 50 30 10 (%) when there are not too many persons in some of the The VRV air conditioning system heat recovery meeting rooms. Compared with the two pipe fan-coil series is the very refinement of the air conditioning with fresh air system, the single system can save unit that the air-to air total heat exchanger has been about 40% of the power consumption a year. The added to the ordinary VRV air conditioning unit. It reformation of this system is successful and energy could choose heating or cooling each room freely saving. according to the whole year heat load, and also could use the excess heat of the building effectively during 4. ENERGY SAVING ANALYSIS the cooling and heating simultaneously.

Through the construction instance analysis, this kind of systems is obviously the energy saving, highly effective and complete heat heating/cooling system. It achieves the low load operation through the total heat recycling operation during the cool and heat operating condition simultaneously, and also causes the refrigerant to transmit the heat from the low load place to the high load place. For the building with the inner zone with big calorific which also need for cold capacity in transfer season or winter, compared to single heating and cooling operation,this operation can save about 15% to 20% energy. And compared to the fresh air system, it can save about 28% energy [7]. 5. CONCLUSION This article describes the application of VRV air conditioning system heat recovery series in the construction inner zone, and has analyzed the energy saving characteristic of it with a construction instance. From the analysis, it can be clearly judged that this system has the following merit: 1) It could operate like the closed water loop heat pump system whose terminal units can realize the result of cooling and heating simultaneously and obtaining an optimal balance of the cold and heat energy in the construction. So the energy saving effect is remarkable; 2) It does not need a big refrigerating plant room or supplementary heat source. Thus it could save the construction area; 3) The diameter of refrigerant tubes is small, so it could be arranged easily and it is free from the restriction of the building store height; 4) The cold (heat) energy of the terminal units is not too large, therefore especially, it suits the building such as office building which has many rooms in the inner and outer zone; 5) The system independence is so good that in the case that any outdoor machine breaks down it was but the connected terminal with it could be affected, not the normal work of the whole system; 6) The time cycle of the designing and installation of the system is short. So especially it suits the reconstruction of old project. The above analysis shows that the VRV air conditioning system heat recovery series can satisfy the heating and cooling request of many rooms while at the same time maintain a high energy using efficiency. This system reduces thermal pollution for the outdoor environment greatly. It is one kind of highly effective conversion and utilization mode of energy. REFERENCES [1] Cunyang Fan, Xiaoping Li. Improvement of Window Side Thermal Environment and Energy Saving in office buildings[j]. HV&AC, 1997, 27(2):18-24. (In Chinese) [2] Weicheng Yang. Application of Multizone Air Conditioning System in Modem Office Buildings[J]. HV&AC, 1996, 26(2):60-64. (In Chinese) [3] Xiaomei Zheng. Exploration of Heat Removal from The Air-conditioned Inner Zone[J]. HV&AC, 2001.31(5):61-63. (In Chinese) [4] Wei Zhao. Air Conditioning Schemes for Buildings With Inner Zones[J]. HV&AC, 2005.35(1):73-76. (In Chinese) [5] Xiaojing Ni, Zhaofeng Zhou, Hua Chen. An Analysis of Energy Saving by Employing Variable Frequency Technology in Air Conditioning: Heat Recovery Multiple VRV Air Conditioning System[J]. JOURNAL OF ZHEJIANG SHUREN UNIVERSITY, 2004, 4(3):79-82. (In Chinese) [6] Jiandong Zhang. The Energy Saving Technology of Optimum Operation for Air Conditioning System in Hotel[D].Beijing: Beijing Institute of Engineering and Architecture, 2004. (In Chinese) [7] Weihua Xue. Analysis of Heat in Energy Consumption of The VRV Air Conditioning System and Its Influencing Factors[J]. HV&AC, 2001.31(4):7-9. (In Chinese)