Flame Spread Monitoring and Estimation of the Heat Release Rate from a Cable Tray Fire using Video Fire Analysis (VFA)

Similar documents
Overview of the PRISME project Technical Description and Main Outcomes

CABLE TRAY FIRE IN OPEN ATMOSPHERE

Collaboration on fire code benchmark activities around the international fire research program PRISME

Test One: The Uncontrolled Compartment Fire

Video Smoke Detection using Deep Domain Adaptation Enhanced with Synthetic Smoke Images

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Electrical failure during NPP cable fires

Advantages and Disadvantages of Fire Modelling

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications

PRISME Seminar 2012 Aix en Provence, France 30 May Hosted by Institut de Radioprotection et de Sûreté Nucléaire (IRSN) PROGRAMME

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

Data collection in Fire PSA. Institut de Radioprotection et de sûreté Nucléaire (IRSN), BP 68, 91192, Gif-sur-Yvette, France,

Sprinklers Modeling for Tunnel Road Fire Fighting

In: Conference proceedings fourteenth international Interflam conference, 1, , 2016.

A Priori Modelling of Fire Test One

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

A study for a fire spread mechanism of residential buildings with numerical modeling

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

Modeling a real backdraft incident fire

Geographic Reasoning on Multi-Modal Fire Spread Data

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Considerations in the Design of Smoke Management Systems for Atriums

Fire propagation over combustible exterior facades exposed to intensified flame in Japan

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

PERFORMANCE-BASED FIRE PROTECTION OF NUCLEAR PLANTS

Fire Risks of Loviisa NPP During Shutdown States

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

CFD Model of a Specific Fire Scenario

An experimental study of the impact of tunnel suppression on tunnel ventilation

Travelling Fires for CFD

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Development and Full-Scale Tests of a Water Mist System inside High Speed Trains

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Compression of Fins pipe and simple Heat pipe Using CFD

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

FLIGHT UNLOADING IN ROTARY SUGAR DRYERS. P.F. BRITTON, P.A. SCHNEIDER and M.E. SHEEHAN. James Cook University

Event Tree Methodology as Analytical Tool for Fire Events

Determination of Fire Exposure Heat Flux in Cable Fire Tests

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

Edinburgh Research Explorer

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

How design fires can be used in fire hazard analysis

Thick-Film Heater achieves Superior Performance in Thermal Response, Uniformity and Efficiency.

STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies

INSIGHTS GAINED FROM A REVIEW OF FIRE PRA RISK CONTRIBUTION BY IGNITION FREQUENCY BINS

Steam condensation in a 2D model of an annular gap steam injector

REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM

MINISTERIO DE FOMENTO

Available online at ScienceDirect. Procedia Engineering 84 (2014 )

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Development of Seismic-induced Fire Risk Assessment Method for a Building

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

Fire Patterns. Introduction. Skills Objectives. Fire Effects and Fire Patterns (2 of 2) 12/20/ Knowledge Objectives

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Fire Test Evaluation using the Kerosene and Aviation Fuel

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

Fire safety engineering applied to high-rise building facades

Firefighter Safety in Battery Energy Storage System Fires

Heat and Smoke Release of a Ceiling-Installed Speaker

The Effect of Model Parameters on the Simulation of Fire Dynamics

Fike set out to develop a better understanding of the power density trends in data centers around the world.

Risk Management of Fire using Video Based Detection

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

Adrian Milford Sereca - a Jensen Hughes Company, Project Engineer Vancouver, BC, Canada

ISO/TR TECHNICAL REPORT. Reaction-to-fire tests Full-scale room tests for surface products Part 2: Technical background and guidance

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony

PREDICTING LARGE-SCALE FIRE PERFORMANCE FROM SMALL- SCALE FIRE TEST DATA

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Fire Scenario Influence of Material of Boundary Condition on Results

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Investigating Heat and Smoke

Fire Spread in Large Industrial Premises and Warehouses

OIL AND GAS INDUSTRY

The Dalmarnock Fire Tests: Experiments and Modelling Edited by G. Rein, C. Abecassis Empis and R. Carvel

Transcription:

Noname manuscript No. (will be inserted by the editor) Flame Spread Monitoring and Estimation of the Heat Release Rate from a Cable Tray Fire using Video Fire Analysis (VFA) First Author Second Author Received: date / Accepted: date Abstract The paper presents an application of Video Fire Analysis (VFA) to a cable tray fire scenario, a scenario of interest to Nuclear Power Plants (NPPs) where cables constitute a substantial part of the combustible load. Five horizontal trays, each 2.4 m long and 0.45 m wide, are positioned with a 0.3 m spacing (in the vertical direction) and set-up against an insulated wall. Each tray contains 49 power PVC cables of 13 mm outer diameter. Ignition is performed with an 80 kw propane burner centrally positioned at 0.2 m below the first (i.e. lowest) tray. Thanks to a flame detection algorithm, the VFA technique allows a reconstruction of the heat release rate (HRR) profile based on the estimated temporal evolution of flame and extinction fronts at the level of each tray. The obtained profile is generally in good agreement with the HRR measurements (from oxygen depletion calorimetry). However, the time to reach the peak HRR is overestimated by approximately 100 s and the peak HRR of 3 MW is underestimated by 17%. These results are nevertheless encouraging because they provide confidence in the flame spread measurements (which are estimated for the case at hand between 2 and 5 mm/s). Therefore, a systematic application of VFA to real-scale experiments is believed to generate a valuable set of data (e.g. flame spread rates) for the development of simplified modelling. Keywords Cable Fire Spread (CFS) Video Fire Analysis (VFA) F. Author first address Tel.: +123-45-678910 Fax: +123-45-678910 E-mail: fauthor@example.com S. Author second address

2 First Author, Second Author 1 Introduction Fire analysis efforts in Nuclear Power Plants (NPPs) have particularly focused on cable trays because they constitute a substantial part of the combustible load in NPPs. These efforts have resulted in a large set of experimental data that allowed the development of models with several degrees of complexity. However, there is still no consensus on the best approach for the prediction of the heat release rate (HRR) from a stack of cable trays. The methodology suggested in [2,3] for the HRR prediction from a stack of horizontal cable trays, and referred to as the FLASH-CAT model, addresses an overall description of the fire development in the framework of a simplified modelling approach (in comparison for instance to the Computational Fluid Dynamics (CFD) technique). The FLASH-CAT model assumes that, for an ignition below the centre of the lowest tray, the fire produces a V-shaped pattern with a given constant angle and spreads laterally at a constant rate. It is stated nevertheless in [3] that it is difficult to measure experimentally the spreading rate and that there is not enough new data to suggest that the horizontal spread rates used in the simplified approach are inappropriate. The work presented in this paper seeks to fill this gap by applying the Video Fire Analysis (VFA) technique described in [4] to the case of five horizontal trays. The temporal evolutions of flame and extinction fronts are tracked at the level of each tray and estimates of the HRR, flame spread rates and fire development pattern (e.g., flame spread angle) are produced. 2 Description of the fire scenario The experimental test considered in this work has been performed by the French institute IRSN (Institut de Radioprotection et de Sûreté Nucléaire) in the context of two large international collaborative research projects, called PRISME and PRISME 2 [5,6]. The burning behaviour of cable trays in open atmosphere conditions is characterized in [7]. The test considered here is called CFSS1. The fire source, as shown in Fig. 1, is composed of five horizontal trays 2.4 m long and 0.45 m wide, with a 0.3 m spacing. The trays are set-up against an insulated side wall. Each tray contains 49 power PVC cables of 13 mm outer diameter provided by one of the PRISME partners, the technical research center of Finland (VTT). Each cable is composed of: (1) a metallic material with a linear mass of 85 g/m, (2) a sheath layer with a linear mass of 85 g/m, (3) a filler layer with a linear mass of 35 g/m, and (4) an insulation layer of 30 g/m. Chemical analyses have identified mainly three elements in the composition of each cable: P V C, CaCO 3 and phthalates. The ignition source is a sand burner of 0.3 0.3 m 2 located 0.2 m below the first tray at the centre. The gas burner supplied with propane delivers a fire power of 80 kw. The supply is stopped when the total HRR reaches 400 kw. This time is considered as the ignition time of the cable trays. In other words, it is the time

Title Suppressed Due to Excessive Length 3 Fig. 1 The five horizontal cable tray device used for the CFSS fire tests after which self-sustained burning occurs. For the considered test, the ignition time is 80 s. 3 Application of the VFA technique: Flame spread monitoring and HRR profile reconstruction Video Fire Analysis (VFA) consists of analyzing video camera footages from a fire scene using image processing techniques [4]. The main objective in the development of the VFA technique is to provide a reliable fire sensing tool for fire detection [8] and fire scene analysis. If such analysis is performed fast enough, real-time predictions of the fire development [9 11] can be produced to help the decision making process for example for firefighting or evacuation [12]. In this paper, the primary objective is to demonstrate that, thanks to a Flame Detection Algorithm (FDA), reliable data for flame spread could be obtained and used later in simplified modelling of cable tray fire. The reliability of the flame spread data is assessed by comparing a reconstructed HRR (from such data) to the HRR measured by oxygen calorimetry. 3.1 Flame front and extinction front measurements The flame detection algorithm developed in [4] has been applied to track the temporal evolution of the flame front, r f, and extinction front, r ex, at the level of each tray, i, as shown in Fig. 2. The trays are numbered from bottom up. The measurements are explained in Fig. 3 and displayed in Figs. 4 and 5. Figure 4 shows, in the initial stages of the fire (between 40 and 80 s), a very sharp increase in the location of the flame front up to r f = 400 mm, which is due to the fire plume generated by the burner of 300 mm 300 mm. After approximately 120 s, the flame front is observed to increase at lower rates.

4 First Author, Second Author Fig. 2 Illustration of the flame detection algorithm used in the VFA performed in this work. The top images are extracted video images. The bottom ones are processed using the FDA Fig. 3 Time sequence of video images and illustration of the FDA measurements (The variable r f5 denotes the flame front at the level of the fifth tray. The variables r f1 and r ex1 denote respectively the flame front and extinction front at the level of the first tray )

Title Suppressed Due to Excessive Length 5 Fig. 4 Measured temporal evolution of the flame front at the level of each tray Flame spread at the level of trays 1 and 2 is clearly lower than for the group of trays 3 to 5. A more detailed discussion on the spread rates will be provided further in a separate section. The flame front reaches the end of all the trays at approximately 400 s, which is the expected time for the occurrence of the HRR peak, since the full combustible load area is burning. One can clearly see that the flame front position may exceed the tray half length. This is due to the high flow rates of pyrolized fuel that is partially transported up to certain radial distance from the sides of the trays. The slight decrease in the flame front positions after 400 s is due to a decrease in the flow rates of pyrolized fuel and the induced change in the flame shape. The sharp decrease (after a slight decrease in the flame front position) is attributed to the fact that the extinction front reaches the flame front. Figure 5 shows some noise in the measured profile of the temporal evolution of the extinction front. For example, the extinction front measured between 0 and 200 s can be attributed to holes in the flame envelope (indicated with a circle in the bottom left picture of Fig.2). A persistent extinction front is recorded first at the level of the 5th tray at approximately 500 s. The extinction front reached the tray end for trays 2 to 5 between 800 and 900 s. Full extinction at the level of the first tray occurred only around 500 s later. This can be explained by the lower spread rate for the first tray.

6 First Author, Second Author Fig. 5 Measured temporal evolution of the extinction front at the level of each tray 3.2 HRR reconstruction The fire HRR is estimated as follows: n Q f (t) = 2 [r f,i (t) r ex,i (t)] A cbl i=1 Q f (1) where t is the time, n the number of trays, A cbl the cable burning area per unit length [m 2 /m] and Q f is the Heat Release Rate per Unit Area (HRRPUA), which is assumed to be constant. The coefficient 2 refers to the fact that measurements were performed on only one half of the trays. Flame spread is assumed to be symmetric. This was not a premeditated choice but rather a constraint due to the positioning of the camera that did not allow a clear monitoring over the full length of the trays. Cables are arranged loosely along the trays. Therefore, it is assumed that all the cable surface per unit length may burn at the same time. So, the cable burning area per unit length is calculated as: A cbl = n cbl/tray πd cbl (2) where n cbl/tray is the number of cables per tray (49 in this case) and d cbl the cable diameter (d cbl = 13mm).

Title Suppressed Due to Excessive Length 7 Fig. 6 HRRPUA from standard cone calorimeter experiments at 50 and 60 kw/m 2 heat flux (data taken from [13] and recalculated based on an exposed area computed from Eq.(3)) In Eqs.(1) and (2), it is assumed that the burning is two dimensional and that the burning area can be estimated by multiplying the cumulative perimeter of all the cables by the burning length. The remaining unknown in Eq. (1) is the HRRPUA, Q f. It is estimated by performing small-scale cone calorimetry measurements under a a constant external heat flux, Q E. The HRRPUA is calculated then by dividing the HRR by the exposed area. The exposed area is typically taken as the area of the sample holder (88.4 cm 2 ). However, in order to be consistent with Eq. (2), the exposed area of the cables in the cone sample is calculated here as: A sample = n sample πd cbl 2 L sample (3) where n sample is the number of cables placed in the sample holder (in this case n sample = 7) and L sample the length of each cable, taken as L sample = 0.1m. Note that, contrary to Eq.(2) for the full-scale, only half of the cable circumference of the cables is exposed (and thus considered) in the cone calorimetry tests. The cone calorimetry results displayed in Fig. 6 show a good repeatability for the 50 kw/m 2 tests and an average HRRPUA of 100 kw/m 2 at the

8 First Author, Second Author Fig. 7 Measured (using oxygen depletion calorimetry) and predicted (using VFA) HRR profiles steady-state stage. Figure 7 shows an overall good agreement between the reconstructed HRR profile based on Eq. (1) in conjunction with the flame spread measurements (using VFA) and the measured profile (using oxygen depletion calorimetry). As expected from the flame front measurements, the time to reach the peak HRR is overestimated by approximately 100 s. Furthermore, the peak HRR is underestimated by approximately 17%. 3.3 Discussion on flame spread Spread rates The flame front results displayed in Fig. 8 show that flame spread rates vary between 2 and 5 mm/s. Furthermore, there are two distinct flame spread rates. Flame spread at the level of trays 1 and 2 occurs at an average rate of 2.35 mm/s. The average rate for trays 3, 4 and 5 is significantly higher, v f = 4.68 mm/s. This could be explained as the following. For the higher trays, radiation comes from all sides, whereas for the lower trays it comes rather essentially form the top. Furthermore, it is well known that the width of a smoke plume increases with height, which enhances the convective heat transfer for the higher trays and results in a larger surface area for flame

Title Suppressed Due to Excessive Length 9 Fig. 8 Measured temporal evolution of flame front at the level of each tray between 90 and 300 s and corresponding estimated flame spread rates impingement. Cables of the upper trays are more pre-heated than the ones of the lower trays, which results in higher spread rates. Flame spread angle Figure 9 shows that flame spread could be further characterized by estimating the angle of the V-shaped pattern produced in the configuration of interest. An analysis of the flame front positioning at three instants during the fire stage shows that the obtained pattern is not readily characterized by a V-shape. However, if one assumes that it is the case and performs a linear regression (as shown in Fig. 9), the angle θ can be estimated to be within a range of 13 to 21. 4 Conclusions The work presented in this paper showed a detailed application of Video Fire Analysis (VFA) to a cable fire spread (CFS) scenario investigated experimentally in the framework of a large international collaborative research project, namely the PRISME 2 project. Thanks to a flame detection algorithm, important information was obtained on the flame spread process for a stack of five horizontal trays. The information consists primarily of the temporal evolution of flame front and extinction front at the level of each tray. It has been

10 First Author, Second Author Fig. 9 Estimated flame spread angle from flame front measurements at different instants during the fire growth stage (the variable r f1 denotes the flame front at the level of the first tray) shown that by processing further this data, one can obtain additional information such as: (1) the temporal evolution of the HRR profile, (2) lateral flame spread rates, and (3) the flame spread pattern (e.g., V-shape and corresponding angle). A good agreement was obtained between the reconstructed HRR profile and the profile measured by oxygen depletion calorimetry. The VFA technique is shown thus (thanks to the good HRR prediction) to provide valuable and reliable lateral flame spread data in the case of cable tray fires. The latter remain very scarce in the literature. The measurements performed in this work show that the flame spread rate can be assumed to be constant as suggested in earlier studies. However, it has been found that there was a distinct difference in the rates between the trays. For instance, for the case at hand, the spread rate in trays 1 and 2 (lowest positions) is similar but significantly lower than the average velocity for the remaining top three trays. Further investigation on the flame front positioning at the level of each tray at several instants during the fire growth stage showed that the V-shaped pattern cannot be readily characterized by a constant angle. If the constant angle assumption is adhered anyway, the value varies between 13 and 21 for the case at hand. In a nutshell, the application of VFA to real-scale experiments is shown here to generate a valuable set of data (e.g. flame spread rates) for the development

Title Suppressed Due to Excessive Length 11 of simplified modelling that allows the prediction of the HRR from a stack of cable trays. Acknowledgements The research carried out in this work has mainly been funded by Bel V through a post-doctoral research grant (contract number A12/TT/0617). The video fire analysis research was funded by Ghent University iminds. The authors are also grateful for the financial support of the participating OECD/NEA member countries (Belgium, Canada, Finland, France, Germany, Japan, Spain, Sweden, United Kingdom) to the joint OECD PRISME 2 project. Thanks also to Prof. Simo Hostikka (Aalto University, Finland) and dr. Anna Matala (VTT, Finland) for providing us with the cone calorimetry data. References 1. Electric Power Research Institute (EPRI), Palo Alto, CA, and U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research (RES), Rockville, MD (2005) EPRI/NRC-RES Fire PRA Methodology for Nuclear Power Facilities: Volume 1: Summary and Overview. EPRI-1011989 and NUREG/CR-6850. http://www.nrc.gov/readingrm/doc-collections/nuregs/contract/cr6850/v1/cr6850v1.pdf 2. Electric Power Research Institute (EPRI), Palo Alto, CA, and U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research (RES), Rockville, MD (2005) EPRI/NRC-RES Fire PRA Methodology for Nuclear Power Facilities: Volume 2: Detailed Methodology. EPRI-1011989 and NUREG/CR-6850. http://www.nrc.gov/readingrm/doc-collections/nuregs/contract/cr6850/v2/cr6850v2.pdf 3. McGrattan K, Lock A, Marsh N, Nyden M, Price M, Morgan AB, Galaska M, Schenk K (2010) Cable Heat Release, Ignition, and Spread in Tray Installations During Fire (CHRISTIFIRE), Phase 1: Horizontal Trays. Report NUREG/CR-7010, Vol. 1. http://www.nrc.gov/reading-rm/doc-collections/nuregs/contract/cr7010/cr7010v1.pdf 4. Verstockt S, Hoecke S, Tilley N, Merci B, Sette B, Lambert P, Hollemeersch CFJ, Van de Walle R (2011) FireCube: A multi-view localization framework for 3D fire analysis. Fire Safety J. 46:262-275. doi:10.1016/j.firesaf.2011.03.001 5. Audouin L, Rigollet L, Prétrel H, Le Saux W, Röwekamp M (2013) OECD PRISME project: Fires in confined and ventilated nuclear-type multi-compartments - Overview and main experimental results. Fire Safety J. 62:80-101. doi:10.1016/j.firesaf.2013.07.008 6. Audouin L, Prétrel H, Zavaleta P (2013) OECD PRISME 2 Fire Research Project (2011-2016) Current Status and Perspectives, 13th International Post-Conference Seminar on Fire Safety in Nuclear Power Plants and Installations (SMiRT-22), Columbia, South Carolina, USA. 7. Zavaleta P, Charbaut S, Basso G, Audouin L (2013) Multiple Horizontal Cable Tray Fire in Open Atmosphere, Thirteenth international conference of the Fire and Materials, San Francisco, USA, pp 57-68. 8. Cetin A, Dimitropoulos K, Gouverneur B, Grammalidis N, Günay O, Y.H. Habiboglu YH, Ugur Töreyin B, Verstockt S (2013) Video fire detection Review. Digital Signal Processing 23:1827-1843. doi:10.1016/j.dsp.2013.07.003 9. Beji T, Merci B, Verstockt S, Van de Walle R (2014) On the Use of Real-Time Video to Forecast Fire Growth in Enclosures, Fire Technol. 50:1021-1040. doi:10.1007/s10694-012- 0262-0 10. Beji T, Vertockt S, Van de Walle R, Merci B (2013) Experimental and numerical study of furniture fires in an ISO-room for use in a fire forecasting framework, J Fire Sci. 31:449-468. doi:10.1177/0734904113479774 11. Jahn W, Rein G, Torero JL (2010) Forecasting fire growth using an inverse zone modelling approach. Fire Safety J. 46:81-88. doi: 10.1016/j.firesaf.2010.10.001 12. Cowlard A, Jahn W, Abecassis-Empis C, Rein G (2010) Sensor assisted firefighting. Fire Technol. 46:719-741. doi:10.1007/s10694-008-0069-1 13. Mangs J, Hostikka S (2013) Experimental characterization of the MCMK cable for fire safety assessment. Research report VTT-R-06873-12, VTT, Finland. http://www.vtt.fi/inf/julkaisut/muut/2012/vtt-r-06873-12.pdf