Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Similar documents
Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

BS EN : 2001 & IEC :2000

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

BS 476: Part 6: 1989+A1:2009

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

25 th November Title:

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BS 476: Part 6: 1989+A1:2009

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

BS EN ISO : 2010

BS EN ISO : 2010

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

BS EN ISO : 2010

NF X : Parts 1, 2, 3, 4 & 5

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

Review Fire Test Report

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.

IMO Resolution MSC 61(67): Annex 1: Part 2

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

CERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC

Certifikat och provningsprotokoll för art och 4511

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

Fire resistance test on fire collars protecting a concrete slab penetrated by services

CERTIFICATE OF APPROVAL No ME 5085

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

WARNING: DOWNLIGHTS MUST BE FITTED CORRECTLY IN FIRE RATED CEILINGS

Report Number BTC 15450A

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

Fire Test Reports for Interpon D Powder Coatings

BCTC CARPET TECHNICAL CENTRE

EN 1155:1997 TESTS OF : PERKO R106 FS CONCEALED FIXED ELECTRICALLY POWERED FREE SWING DEVICES FOR SWING DOORS. Leopold Street, Birmingham.

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

The Radiators With Brains

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Life Safety and Fire Resistant Glazing Systems

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

FUNDERMAX GMBH FIRE TEST REPORT

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

Test Report: ICL/CR15/11/087

CERTIFICATE OF APPROVAL No CF 5635 P3 SRL

SIGMADEK, LTD. FIRE TEST REPORT

CAN/ULC-S109 Flame Resistance of "Argo" Fabric

FACADES AND FIRE The Essential Elements

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

FTSG RESOLUTIONS. This document of FTSG resolutions was issued by the Company Secretary 20 July 2012.

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

Exova Warringtonfire - Expert Witness Directory 2018

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

CAN/ULC-S109 Flame Resistance of "Xanadu" Material

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F

Test Report: ICL/H18/9039 Rev 1

The Train Now Arriving At... Harmonised Fire Safety For European Rolling Stock

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

C-01 FIRE DECKS AND BULKHEADS

Loss Prevention Standard

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

CERTIFICATE OF APPROVAL No. ME 5008 EMIRATES FIRE FIGHTING EQUIPMENT FACTORY LLC (FIREX)

Contact person Date Reference Page Richard Johansson P (2) Fire Research

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

2 Examination of Cladding Panels (Laboratory)

CERTIFICATE OF COMPLIANCE

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

CERTIFICATE OF FIRE APPROVAL

Department for Communities and Local Government Research Report:

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

GAS-FIRED ('INFRA-RED') HEATER FOR USE ON THE JOINTS

THE HOME OF REACTIVE PROTECTION SYSTEMS

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Classification of Fire Performance of Wall and Ceiling Lining Materials

Transcription:

Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report No: 332065/A Prepared for: Hoody Speaker Hoods Ltd Link House Knight Rider Court Knight Rider Street Maidstone Kent ME15 6LU Date: 12 th November 2013

Page 2 of 16 Indicative Fire Test We have pleasure in enclosing the information obtained from the indicative fire test conducted, on your behalf, on the 9 th August 2013. The test results relate to an investigation, which utilised the heating and pressure conditions specified in BS EN 1363-1: 2012. The information is provided for the test sponsor s information only and should not be used to demonstrate performance against any published fire test standard, nor compliance with a regulatory requirement. The test was not conducted under the requirement of UKAS accreditation. The purpose of the investigation was to provide an indication of the behaviour of a section of a timber floor protected on its underside by a plasterboard ceiling incorporating three speakers and associated covers, when subjected on its underside to the heating and pressure conditions specified by BS EN 1363-1: 2012. The test assembly had overall nominal dimensions of 1700 mm wide by 2200 mm long and briefly comprised three sections of softwood timber joist at nominally 600 mm centres. The ends of the joists were closed with a section of the same softwood joist fixed across the ends on both edges. The floor construction was faced on its upper surface with a single layer of nominally 22 mm thick chipboard flooring. The underside of the floor was provided with a direct fixed ceiling formed from two layers of 12.5mm thick Lafarge Firecheck plasterboard. Three speakers with associated covers were fitted into the ceiling. The speakers were referenced A to C for the purpose of the test and were described by the sponsor as follows: Specimen A was referenced Monitor Audio CT165 Ceiling Speaker (Hoody 1). The specimen had a nominal diameter of 265 mm by 160 mm high and was installed within a cut out aperture within the ceiling 211 mm diameter by 114 mm high. Specimen B was referenced Monitor Audio CT180 Ceiling Speaker (Hoody 2). The specimen had a nominal diameter of 335 mm by 180 mm high and was installed within a cut out aperture within the ceiling 247 mm diameter by 121 mm high. Specimen C was referenced Monitor Audio CWT140R Ceiling Speaker (Hoody 5). The specimen had a nominal diameter of 185 mm by 145 mm high and was installed within a cut out aperture within the ceiling 149 mm diameter by 98.6 mm high. All three speakers were fitted with an Acoustic Fireproof Cover, provided by Hoody Speaker Hoods Ltd. The floor assembly was mounted such that it formed the top horizontal face of a 1.5 m by 2.0 m gas fired furnace chamber, the temperature rise of which was controlled to conform with the heating and pressure conditions specified in BS EN 1363-1: 2012. The following information relating to the test is enclosed: Table 1 - Specified and actual furnace temperatures and percentage tolerances Table 2 - Individual and mean temperatures recorded on the unexposed surface of the floor (Thermocouples 20 to 24) Table 3 - Individual temperatures recorded on the unexposed surface of the floor adjacent to joints. (Thermocouples 25 and 26) Table 4 - At three positions mid-height of the air cavity, adjacent to the speaker assemblies (Thermocouples 27 to 29) Graph 1 - Graph showing the specified and actual furnace temperatures

Page 3 of 16 Graph 2 - Graph showing the individual and mean temperatures recorded on the unexposed surface of the floor. Observations on the general behaviour of the specimens during the test. Photographs taken before and after the test. The test was discontinued after a period of 90 minutes. We trust that the information obtained from the test will be useful to you. Yours faithfully, Responsible Officer D. Yates Testing Officer Fire Resistance Department Exova Warringtonfire This copy has been produced from a.pdf format electronic file that has been provided by Exova Warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Exova Warringtonfire. The pdf copy supplied is the sole authentic version of this document. All pdf versions of this report bear authentic signatures of the responsible Exova Warringtonfire staff.

Page 4 of 16 Table 1 Time Specified Actual Furnace Furnace Minutes Temperature Temperature Deg. C Deg. C 0 20 26 3 502 481 6 603 595 9 663 653 12 705 698 15 739 741 18 766 766 21 789 785 24 809 806 27 826 827 30 842 843 33 856 857 36 869 870 39 881 880 42 892 892 45 902 902 48 912 912 51 921 922 54 930 931 57 938 941 60 945 945 63 953 956 66 960 964 69 966 967 72 973 970 75 979 981 78 985 986 81 990 991 84 996 994 87 1001 999 90 1006 1004

Page 5 of 16 Table 2 Time T/C T/C T/C T/C T/C Mean Number Number Number Number Number Minutes 20 21 22 23 24 Temp Deg. C Deg. C Deg. C Deg. C Deg. C Deg. C 0 21 21 22 23 22 22 3 21 21 22 23 22 22 6 21 21 22 22 22 22 9 21 21 22 23 22 22 12 21 22 23 23 23 22 15 22 22 25 24 23 23 18 23 24 28 25 25 25 21 24 25 34 26 26 27 24 26 27 45 28 28 31 27 28 28 59 29 30 35 30 29 30 71 31 31 38 33 31 32 78 32 33 41 36 32 33 84 34 34 43 39 34 35 85 35 36 45 42 36 37 87 37 38 47 45 38 39 90 38 39 49 48 39 40 92 40 41 50 51 41 42 95 41 42 52 54 42 43 98 42 43 54 57 44 45 102 43 45 56 60 46 47 108 45 47 59 63 48 52 119 48 51 64 66 52 57 130 53 56 70 69 57 62 141 58 61 76 72 62 66 151 62 65 81 75 66 70 159 66 69 86 78 69 72 166 69 71 89 81 72 74 170 72 73 92 84 74 76 176 74 75 95 87 75 77 181 76 76 97 90 78 79 191 78 79 101

Page 6 of 16 Table 3 Time T/C T/C Number Number Minutes 25 26 Deg. C Deg. C 0 21 22 3 21 22 6 21 22 9 21 22 12 21 22 15 22 23 18 22 23 21 23 24 24 24 26 27 26 27 30 27 28 33 29 30 36 30 31 39 32 33 42 34 35 45 36 39 48 38 43 51 41 46 54 48 49 57 54 52 60 60 57 63 64 61 66 67 63 69 70 66 72 72 67 75 74 69 78 74 71 81 74 73 84 76 74 87 76 76 90 79 78

Page 7 of 16 Table 4 Time T/C T/C T/C Number Number Number Minutes 27 28 29 Deg. C Deg. C Deg. C 0 23 23 24 3 24 24 26 6 32 33 48 9 47 56 74 12 70 91 92 15 88 129 109 18 127 178 116 21 164 217 132 24 200 250 151 27 230 257 165 30 255 286 177 33 264 352 189 36 273 412 197 39 290 463 207 42 334 494 217 45 375 516 230 48 405 530 245 51 421 538 256 54 430 542 262 57 437 541 272 60 448 535 302 63 471 542 338 66 491 549 382 69 504 551 423 72 517 558 450 75 532 567 475 78 548 576 493 81 561 586 514 84 581 607 540 87 617 661 563 90 652 675 587

Page 8 of 16 Graph 1 1000 900 800 Temperature - Deg. C 700 600 500 400 Specified Furnace Temperature Deg. C Actual Furnace Temperature Deg. C 300 200 100 0 0 10 20 30 40 50 60 70 Time - Minutes

Graph 2 WF Test Report Page 9 of 16

Page 10 of 16 Test Observations Time All observations are from the unexposed face unless noted otherwise. mins secs The ambient air temperature in the vicinity of the test construction was 21ºC at the start of the test with a maximum variation of +4, -1ºC during the test. 00 00 The test commences. 04 30 Slight smoke release begins from the joints within the timber deck. 05 30 Viewed from the exposed face, the paper face of the plaster board ceiling has begun to burn away. The plastic speaker facing of Specimens A and B appears to have melted and fallen away. 06 00 Viewed from the exposed face, the plastic speaker facing of Specimen C appears to have melted and fallen into the furnace. 11 20 Slight smoke release continues from along the joints within the timber deck. Slight discolouration is evident at the same locations. 30 00 The ceiling board joints appear black in colour and slightly charred. The circular apertures within the ceiling appear blackened and slightly charred also. 50 00 The board joints within the first layer of ceiling board have opened up by approximately 20 25 mm. 58 40 Viewed from the exposed face, a large section of the first layer of ceiling board has dropped downwards by approximately 30 35 mm as it begins to detach from the ceiling along the joint. 62 10 Smoke release from the joints within the timber floor has increased slightly. Discolouration has become more evident at the same location. 64 30 Viewed from the exposed face, flames issue from the circular openings within the ceiling. The first layer of the ceiling board has dropped down further along the joint now by approximately 50 mm. 71 30 Smoke release from the joints within the timber deck has increased further. 72 10 Viewed from the exposed face, a large section of the first layer of ceiling board continued to pull away from the ceiling now by approximately 150 200 mm. 73 10 A large section of the first layer of ceiling board has detached and fallen into the furnace chamber. 75 00 Smoke release has increased further along the timber deck joints. 78 55 A cotton pad is applied at the mid span of a timber deck joint but fails to ignite. 83 20 Viewed from the exposed face, large amounts of flaming issue from the circular apertures within the ceiling.

Page 11 of 16 Time mins secs 84 40 Smoke release from the joints within the timber deck has increased significantly. 89 50 A large section of the second layer of board begins to drop downwards at the approximate centre of the ceiling. 90 00 Smoke release from the ceiling increases significantly and the test is discontinued at the sponsor s request.

Page 12 of 16 Test Photographs The exposed face of the ceiling prior to the test. The unexposed face of the ceiling prior to the test.

Page 13 of 16 The unexposed face of the ceiling after a test duration of 30 minutes The exposed face of the ceiling after a test duration of 30 minutes

Page 14 of 16 The unexposed face of the ceiling after a test duration of 60 minutes The exposed face of the ceiling after a test duration of 60 minutes

Page 15 of 16 The unexposed face of the ceiling after a test duration of 90 minutes The exposed face of the ceiling after a test duration of 90 minutes

The exposed face of the ceiling immediately after the test WF Test Report Page 16 of 16