Technical Committee on Fluidized Bed Boilers

Similar documents
Technical Committee on Fluidized Bed Boilers

Technical Committee on Multiple Burner Boilers

Committee on NFPA 85

Technical Committee on Fundamentals of Combustion Systems Hazards

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

Technical Committee on Incinerators and Waste Handling Systems

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

NFPA 101 SAF-RES PUBLIC COMMENTS

M E M O R A N D U M. The Technical Correlating Committee on Boiler and Combustion Systems Hazards

TECHNICAL COMMITTEE ON WATER-COOLING TOWERS. First Draft Meeting Agenda. February 7, :00 AM - 5:00 PM EST Web/Teleconference Meeting

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input


SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

Public Comment No. 7-NFPA 30A-2013 [ Section No ]


DIRECTIVE NO: D-B

Changes for the New Edition. Senior Engineer, NFPA NFPA

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

NFPA 85 COMPLIANCES OF BMS: A CASE STUDY OF BOILER CONTROL AT SBM OFFSHORE MALAYSIA COMPANY 1. AHMED ABOUELRISH 2 Universiti Teknologi Petronas

1. Welcome. Robert Smith, Chair. 2. Introductions and Update of Committee Roster. (attached)

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

First Revision No. 20-NFPA [ Section No ]

Technical Committee on Mining Facilities First Draft Meeting - NFPA 120 and 122

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on


REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing


Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc.

Low pressure boiler* inspection and maintenance

NFPA 86 Commitee Inputs Page 1 of 45

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

3. Approval of Meeting Minutes from January 21, 2014 (Attachment A). Fall 2018 revision cycle schedule. (Attachment C)

Public Comment No. 13-NFPA [ Section No ]

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

NFPA 79 - Second Draft Meeting July 8-10, DoubleTree Hotel, Portland, ME

National Fire Protection Association

TECHNICAL COMMITTEE ON FIRE PUMPS

TECHNICAL COMMITTEE ON FIRE CODE

Public Comment No. 2-NFPA [ Section No ]

First Revision No. 106-NFPA [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

MINUTES OF MEETING. Technical Committee on Fundamentals of Combustion Systems Hazards

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

FIF AAA (F2014) Second Draft Meeting Web/Teleconference Meeting Agenda March 18, :00 5:00 p.m. ET

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Committee on NFPA 85

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Technical Committee on Fluid Heaters


The Committee updated the edition dates for the reference sources for extracted text within the standard per the NFPA Manual of Style.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Revitalize Building Mechanical Systems (4619)

4.6 Advanced Propane Appliance Service and Troubleshooting Performance-Based Skills Assessment 2019

AGENDA First Draft Meeting for the 2016 Edition of NFPA 70B March 12-14, 2014 San Antonio, TX

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

NFPA s Standards Development Process

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

Public Input No. 3-NFPA [ Chapter 2 ]

TECHNICAL COMMITTEE ON WASTEWATER TREATMENT PLANTS First Draft Meeting Agenda September 10-12, 2013 Hampton Inn, Columbus, Ohio

SAFETY CONTROL REQUIREMENTS FOR OVENS AND FURNACES

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on

SECTION HEATING BOILERS

NFPA Technical Committee on Fire Tests

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Technical Committee on Gas Process Safety

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.


National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Public Comment No. 2-NFPA [ Section No ]

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Rental Boiler Specifications (Nebraska Boiler)

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

26 of 128 9/23/2014 9:25 AM

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Industrial furnaces and associated processing equipment Safety. Part 2: Combustion and fuel handling systems

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Document Code: 1 (15) Issuing date: Status:

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Public Input No. 23-NFPA [ Section No. 1.1 [Excluding any

Second Revision No. 14-NFPA [ Global Comment ] Submitter Information Verification. Committee Statement 8/25/ :39 AM

TECHNICAL COMMITTEE ON INTERNAL COMBUSTION ENGINES

Compliance Guidance for non-technical managers

REFERENCE SYLLABUS. For FIRED PROCESS HEATER OPERATOR S. CERTIFICATE of COMPETENCY EXAMINATION AB-239. Edition 3, Revision 1, Issued

Transcription:

Technical Committee on Fluidized Bed Boilers AGENDA NFPA Headquarters 1 Batterymarch Park Quincy, MA 02169 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Committee Members and Guests 3. Approval of Minutes from the April 5, 2010 Meeting via teleconference. See www.nfpa.org/85. 4. Staff Liaison Report A. Committee membership update (For the period April 5, 2010 Feb. 5, 2013) Name Category Change Date William George U (Principal) Resign 4/6/2010 David Habenicht SE (Principal) Resign 6/8/2011 David Pickles U (Principal) Appoint 8/2/2010 (Total Voting Members 13; M=38%, SE=23%, U=23%; I=8%; IM = 8%) B. Revision Cycle Review and timeline (Attachment A) 5. Old Business A. Gasifiers. The TC discussed adding coverage for gasifiers but determined that interest is limited. The TC requested that gasifiers remain on the agenda for periodic review as the technology matures. 6. New Business A. Create First Revision of Chapter 7. The committee should review the Public Input (Attachment B) and revise chapter 7 of NFPA 85 as appropriate. B. Review BCS-FUN actions. The committee members are asked to review the actions of the Fundamentals committee (sent under separate cover) and bring forward any items warranting further dicussion. C. Industry Update. The committee should discuss current projects, new technology, and any other items related to fluidized bed boilers that may be of general interest. 7. Other Items? 8. Date/Location of Next Meeting. The Second Draft meeting must take place between Nov. 15, 2013 and January 24, 2014. The BCS-FUN meeting is tentatively scheduled for Dec 4-5, 2013 in Atlanta, GA. 9. Adjournment.

Attachment A: Fall 2014 Revision Cycle

2014 FALL REVISION CYCLE *Public Input Dates may vary according to documents and schedules for Revision Cycles may change. Please check the NFPA Website for the most up to date information on Public Input Closing Dates and schedules at www.nfpa.org/document # (i.e. www.nfpa.org/101) and click on the Next Edition tab Process Stage Public Input Stage (First Draft) Process Step Dates for TC Dates for TC with CC Public Input Closing Date* 1/4/2013 1/4/2013 Final date for TC First Draft Meeting 6/14/2013 3/15/2013 Posting of First Draft and TC Ballot 8/2/2013 4/26/2013 Final date for Receipt of TC First Draft ballot 8/23/2013 5/17/2013 Final date for Receipt of TC First Draft ballot recirc 8/30/2013 5/24/2013 Posting of First Draft for CC Meeting 5/31/2013 Final date for CC First Draft Meeting 7/12/2013 Posting of First Draft and CC Ballot 8/2/2013 Final date for Receipt of CC First Draft ballot 8/23/2013 Final date for Receipt of CC First Draft ballot recirc 8/30/2013 Post Final First Draft for Public Comment 9/6/2013 9/6/2013 Public Comment closing date 11/15/2013 11/15/2013 Final Date to Publish Notice of Consent Documents (Documents That Received No Comments) 11/22/2013 11/22/2013 Appeal Closing Date for Consent Documents (15 Days) (Documents That Received No Comments) 12/7/2013 12/7/2013 Final date for TC Second Draft Meeting 5/2/2014 1/24/2014 Posting of Second Draft and TC Ballot 6/13/2014 3/7/2014 Comment Stage Final date for Receipt of TC Second Draft Ballot 7/7/2014 3/28/2014 (Second Draft) Final date for receipt of TC Second Draft ballot recirc 7/14/2014 4/4/2014 Posting of Second Draft for CC Mtg 4/11/2014 Final date for CC Second Draft Meeting 5/23/2014 Posting of Second Draft for CC Ballot 6/13/2014 Final date for Receipt of CC Second Draft ballot 7/7/2014 Final date for Receipt of CC Second Draft ballot recirc 7/14/2014 Post Final Second Draft for NITMAM Review 7/18/2014 7/18/2014 Tech Session Preparation (& Issuance) Notice of Intent to Make a Motion (NITMAM) Closing Date 8/22/2014 8/22/2014 Posting of Certified Amending Motions and Consent Documents 10/17/2014 10/17/2014 Appeal Closing Date for Consent Documents (15 Days) 11/1/2014 11/1/2014 SC Issuance Date for Consent Documents (25 Days) 11/11/2014 11/11/2014 Tech Session Association Meeting for Documents with CAMs 6/22 25/2015 6/22 25/2015 Appeals and Issuance Appeal Closing Date for Documents with CAMs (20 Days) 7/15/2015 7/15/2015 SC Issuance Dates for Documents with CAMs 8/27/2015 8/27/2015

Attachment B: Public Input

04 of 171 2/6/2013 3:15 PM Public Input No. 223-NFPA 85-2013 [ Section No. 7.2 ] 7.2 Purpose. The purpose of this chapter is to establish minimum standards for the design, installation, operation, and maintenance of atmospheric fluidized bed boilers, associated fuel-burning systems, and related systems to contribute to safe operation to the design operation and, in particular, to the prevention of furnace explosions and pressure excursions. The objective of this suggested change is to replace "safe operation" as it may not be unenforceable language. Related Public Inputs for This Document Related Input Public Input No. 222-NFPA 85-2013 [Section No. 5.2] Relationship Submitter Full Name: Ted Jablkowski Organization: Fives North American Combustion Submittal Date: Thu Jan 03 16:51:05 EST 2013 I, Ted Jablkowski, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Ted Jablkowski, and I agree to be legally bound by the above and the terms and

05 of 171 2/6/2013 3:15 PM Public Input No. 153-NFPA 85-2013 [ Section No. 7.3.3.8.2.1 ] 7.3.3.8.2.1 The procedure shall include inspections by the owner/operator that start from the upper elevations of the hot cyclone(s) and other equipment and proceed to each space or chute below. As written, this paragraph is open to misinterpretation as to who should do the inspection. Jurisdictional authorities (AHJ) have for many years been inappropriately interpreting NFPA 85 as containing in-service inspection responsibilities for the National Board Commissioned Boiler Inspectors employed by Authorized Inspection Agencies as defined by the National Board document NB-369 Qualifications and Duties for Authorized Inspection Agencies (AIAs) Performing Inservice Inspection Activities and Qualifications for Inspectors of Boilers and Pressure Vessels. This has caused significant legal issues for Authorized Inspection Agencies. The proposed change is intended to make it clear that NFPA 85 does not contain any requirements.for in-service inspections for these agencies. Related Public Inputs for This Document Related Input Public Input No. 132-NFPA 85-2013 [Section No. 3.2.2] Relationship Submitter Full Name: Brian Moore Organization: Hartford Steam Boiler Inspecti Submittal Date: Wed Jan 02 14:04:37 EST 2013 I, Brian Moore, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Brian Moore, and I agree to be legally bound by the above and the terms and

06 of 171 2/6/2013 3:15 PM Public Input No. 155-NFPA 85-2013 [ Section No. 7.4.2.1.3.1(C) ] (C) Observation ports shall be provided to allow owner/operator inspection of the duct and warm-up burners. As written, this paragraph is open to misinterpretation as to who should do the inspection. Jurisdictional authorities (AHJ) have for many years been inappropriately interpreting NFPA 85 as containing in-service inspection responsibilities for the National Board Commissioned Boiler Inspectors employed by Authorized Inspection Agencies as defined by the National Board document NB-369 Qualifications and Duties for Authorized Inspection Agencies (AIAs) Performing Inservice Inspection Activities and Qualifications for Inspectors of Boilers and Pressure Vessels. This has caused significant legal issues for Authorized Inspection Agencies. The proposed change is intended to make it clear that NFPA 85 does not contain any requirements.for in-service inspections for these agencies. Related Public Inputs for This Document Related Input Public Input No. 132-NFPA 85-2013 [Section No. 3.2.2] Relationship Submitter Full Name: Brian Moore Organization: Hartford Steam Boiler Inspecti Submittal Date: Wed Jan 02 14:16:37 EST 2013 I, Brian Moore, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Brian Moore, and I agree to be legally bound by the above and the terms and

07 of 171 2/6/2013 3:15 PM Public Input No. 156-NFPA 85-2013 [ Section No. 7.6.2.1.1 ] 7.6.2.1.1 Preparation for starting shall include a thorough inspection by the owner/operator and shall verify the following: (1) The furnace and gas passages are in good repair and free of foreign material. (2) All personnel are evacuated from the unit and associated equipment, all access and inspection doors are closed, and all equipment and instrumentation are ready for operation. (3) All airflow and flue gas flow control dampers have been operated through their full range to check the operating mechanism. (4) All adjustable individual burner dampers or registers have been operated through their full range to check the operating mechanism. (5) All safety shutoff valves are operational and closed, and ignition sparks are de-energized. (6) The feeder equipment is effectively isolated to prevent the leakage of fuel or sorbent into the furnace and to prevent hot air or flue gas from the fluidized bed from leaking back into the feed system. (7) The drum water level is established in drum-type boilers, circulating flow is established in forced circulation boilers, or minimum water flow is established in once-through boilers. (8) The feeders and associated equipment are calibrated and ready for operation. (9) Energy is supplied to the control system and to the safety interlocks. (10)* The oxygen analyzer and carbon monoxide or combustibles analyzer, if provided, are operating, the carbon monoxide or combustibles indication is at zero, and oxygen indication is at maximum. (11) A complete functional check of the safety interlocks has been made, at minimum, after system maintenance. (12) A complete periodic operational test of each igniter has been made as follows: (a) (b) (c) Frequency of testing is dependent on the design and operating history of each individual unit and ignition system. As a minimum, a test shall be performed during every start-up following overhaul or other maintenance. A test shall be integrated into the starting sequence and shall follow the unit purge and precede the admission of any burner fuel. (13) Individual igniters or groups of igniters shall be permitted to be tested while the unit is in service as follows: (a) (b) Such tests shall be made with no main fuel present in the igniter's associated burner. The burner air register shall be in its start-up or light-off position as described in the established operating procedure. (14)* The furnace contains the required bed inventory as defined by the manufacturer or determined by test. As written, this paragraph is open to mininterpretation as to who should do the inspection. Jurisdictional authorities (AHJ) have for many years been inappropriately interpreting NFPA 85 as containing in-service inspection responsibilities for the National Board Commissioned Boiler Inspectors employed by Authorized Inspection Agencies as defined by the National Board document NB-369 Qualifications and Duties for Authorized Inspection Agencies (AIAs) Performing Inservice Inspection Activities and Qualifications for Inspectors of Boilers and Pressure Vessels. This has caused significant legal issues for Authorized Inspection Agencies. The proposed change is intended to make it clear that NFPA 85 does not contain any requirements.for in-service inspections for these agencies.

08 of 171 2/6/2013 3:15 PM Related Public Inputs for This Document Related Input Public Input No. 132-NFPA 85-2013 [Section No. 3.2.2] Relationship Submitter Full Name: Brian Moore Organization: Hartford Steam Boiler Inspecti Submittal Date: Wed Jan 02 14:22:09 EST 2013 I, Brian Moore, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Brian Moore, and I agree to be legally bound by the above and the terms and

09 of 171 2/6/2013 3:15 PM Public Input No. 158-NFPA 85-2013 [ Section No. 7.7.5.2.1.1 ] 7.7.5.2.1.1 Preparation for starting shall include a thorough inspection by the owner/operator and shall verify the following: (1) All safety shutoff valves are closed, and all sparks are de-energized. (2) Oil ignition systems meet the requirements of Section 7.8. (3) Fuel system vents are open and venting to atmosphere outside the boiler room; lines are drained and cleared of condensate and other foreign material. (4) The correct drum water level is established in drum-type boilers, circulating flow is established in forced circulation boilers, or minimum water flow is established in once-through boilers as established by the boiler manufacturer. (5) Burner elements and igniters are positioned in accordance with the manufacturer's specification. (6) Energy is supplied to the control and interlock systems. (7) Meters or gauges are indicating fuel header pressure to the unit. As written, this paragraph is open to misinterpretation as to who should do the inspection. Jurisdictional authorities (AHJ) have for many years been inappropriately interpreting NFPA 85 as containing in-service inspection responsibilities for the National Board Commissioned Boiler Inspectors employed by Authorized Inspection Agencies as defined by the National Board document NB-369 Qualifications and Duties for Authorized Inspection Agencies (AIAs) Performing Inservice Inspection Activities and Qualifications for Inspectors of Boilers and Pressure Vessels. This has caused significant legal issues for Authorized Inspection Agencies. The proposed change is intended to make it clear that NFPA 85 does not contain any requirements.for in-service inspections for these agencies. Related Public Inputs for This Document Related Input Public Input No. 132-NFPA 85-2013 [Section No. 3.2.2] Relationship Submitter Full Name: Brian Moore Organization: Hartford Steam Boiler Inspecti Submittal Date: Wed Jan 02 14:30:59 EST 2013 I, Brian Moore, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Brian Moore, and I agree to be legally bound by the above and the terms and

10 of 171 2/6/2013 3:15 PM Public Input No. 159-NFPA 85-2013 [ Section No. 7.8.5.2.1.1 ] 7.8.5.2.1.1 Preparation for start-up shall include a thorough inspection by the owner/operator and shall verify the following: (1) Energy is supplied to the control system and to the interlock systems. (2) All safety shutoff valves are closed; all sparks are de-energized. (3) Gas ignition systems meet the requirements of Section 7.7. (4) Circulating valves are open to provide and maintain hot oil in the burner headers. (5) The proper drum water level is established in drum-type boilers, circulating flow is established in forced circulation boilers, or minimum water flow is established in once-through boilers. (6) Burner guns have been checked to ensure that the correct burner tips and sprayer plates and gaskets are in place to ensure a safe operating condition. (7) Burner elements and igniters are positioned in accordance with the manufacturer's specifications. (8) Meters or gauges indicate fuel header pressure to the unit. As written, this paragraph is open to misinterpretation as to who should do the inspection. Jurisdictional authorities (AHJ) have for many years been inappropriately interpreting NFPA 85 as containing in-service inspection responsibilities for the National Board Commissioned Boiler Inspectors employed by Authorized Inspection Agencies as defined by the National Board document NB-369 Qualifications and Duties for Authorized Inspection Agencies (AIAs) Performing Inservice Inspection Activities and Qualifications for Inspectors of Boilers and Pressure Vessels. This has caused significant legal issues for Authorized Inspection Agencies. The proposed change is intended to make it clear that NFPA 85 does not contain any requirements.for in-service inspections for these agencies. Related Public Inputs for This Document Related Input Public Input No. 132-NFPA 85-2013 [Section No. 3.2.2] Relationship Submitter Full Name: Brian Moore Organization: Hartford Steam Boiler Inspecti Submittal Date: Wed Jan 02 14:35:36 EST 2013 I, Brian Moore, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Brian Moore, and I agree to be legally bound by the above and the terms and

50 of 171 2/6/2013 3:15 PM Public Input No. 171-NFPA 85-2013 [ Section No. A.7.3.3.8.2.2 ] A.7.3.3.8.2.2 One method by which the absence of solids can be confirmed is by soundings. Soundings are accomplished by lowering a weighted cable from the top of the cyclone to the base of the loop seal. Visual inspections inspections by the owner/operator are also feasible if light from an opening in the loop seal can be seen from the top of the cyclone. It should be noted that these methods may not indicate the presence of solids adhering to the sides of the cyclone, the loop seal, or the connecting pipe. [See L.2.2 (10).] As written, this paragraph is open to misinterpretation as to who should do the inspection. Jurisdictional authorities (AHJ) have for many years been inappropriately interpreting NFPA 85 as containing in-service inspection responsibilities for the National Board Commissioned Boiler Inspectors employed by Authorized Inspection Agencies as defined by the National Board document NB-369 Qualifications and Duties for Authorized Inspection Agencies (AIAs) Performing Inservice Inspection Activities and Qualifications for Inspectors of Boilers and Pressure Vessels. This has caused significant legal issues for Authorized Inspection Agencies. The proposed change is intended to make it clear that NFPA 85 does not contain any requirements.for in-service inspections for these agencies. Related Public Inputs for This Document Related Input Public Input No. 132-NFPA 85-2013 [Section No. 3.2.2] Relationship Submitter Full Name: Brian Moore Organization: Hartford Steam Boiler Inspecti Submittal Date: Wed Jan 02 15:30:34 EST 2013 I, Brian Moore, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Brian Moore, and I agree to be legally bound by the above and the terms and

51 of 171 2/6/2013 3:15 PM Public Input No. 11-NFPA 85-2012 [ New Section after A.7.3.3.9(1) ] A.7.3.3.9(6) Bed solidification can occur as a result of agglomeration. Alkali compounds can attach to bed material particles. These alkali compounds can have low melting points and can cause the bed particles to stick to each other to form agglomerates. In discussions with the BCS-FUN-TC the definition for agglomeration (3.3.2) is being deleted from the first draft. Defining agglomeration for this specific case precludes the use of the term in other cases within the code where agglomeration is a concern. This public comment offers annex materail to 7.3.3.9(6) to capture and explain how agglomeration occurs in this particular case. Submitter Full Name: Richard Gallagher Organization: Zurich Services Corporation Submittal Date: Tue May 29 09:47:30 EDT 2012 I, Richard Gallagher, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Richard Gallagher, and I agree to be legally bound by the above and the terms and

52 of 171 2/6/2013 3:15 PM Public Input No. 67-NFPA 85-2012 [ Section No. A.7.6.2.1.1(10) ] A.7.6.2.1.1(10) Analyzers could contain heated elements that exceed the autoignition temperature of some fuels. Zirconium oxide analyzers, commonly used for oxygen analysis, contain an element heated to 704 C (1300 F). This high temperature element presents a potential ignition source to unburned fuel that could be present at start-up. Some analyzers are designed to protect the sampled space from the ignition source by providing flashback protection (such as flame arresters in the sample gas path). Analyzers that have that protection or that are not heated to autoignition temperature do not present an ignition hazard It should be noted, however, that flame arrestors may only work below a certain temperature which is usually not quantified, may not quench a flame as well once it becomes corroded and may induce a speed of response delay that could be detrimental to the control or protection strategy. Consideration should be given to powering down analyzers during boiler or fuel trip situations if they can exceed the autoignition temperature of the fuel being fired. Discussions with a major supplier of zirconium oxide based oxygen analyzers revealed the stated limitations of flame arrestors and those limitations need to be understood by users of the Code. This same change is being proposed against identical annex material in A.5.3.4.6.3, A.6.4.2.3.4.6(2) and A.7.6.2.1.1(10). Submitter Full Name: Dale Evely Organization: Southern Company Services, Inc Submittal Date: Thu Nov 29 09:28:01 EST 2012 I, Dale Evely, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Dale Evely, and I agree to be legally bound by the above and the terms and

70 of 171 2/6/2013 3:15 PM Public Input No. 157-NFPA 85-2013 [ Section No. L.2.2 ] L.2.2 Recommendations. Recommendations are as follows: (1) The designers of the boiler and related plant equipment should identify the potential sources of hot solids and associated hazards and make recommendations for personnel safety. (2) The designer should give careful consideration to the selection of materials that come into direct contact with hot solids. (3) Clean-out ports, fittings that might be used as clean-out ports, and spool pieces that might be removed for rodding out blockages should be positioned so that a sudden rush of hot solids does not lead to personnel injury. Components that are removable for maintenance when the plant is out of service but that should not be removed when the plant is in service because of the risk of hot spills should be marked clearly. (4) Instrumentation and wiring needed for the safe operation of the plant should not be routed near potential sources of hot solids. If such routing is necessary, the wiring should be protected from the direct flow of the solids. (5) Fuel lines should not be located near potential sources of hot solids. The fuel lines should be protected from the direct flow of the solids. (6) Plant personnel should be trained in the potential sources of hot solids, associated hazards, and the corresponding safety procedures. (7) Procedures should be developed for cleaning obstructions that provide safety to personnel and equipment. Protective clothing and eye protection should be provided for personnel who rod out obstructions. (8) Components that might contain hot solids should be inspected frequently by the owner/operator. (9) Water-cooled screws have failed when suddenly flooded with hot bed material following the removal of an upstream blockage. The sudden transfer of large amounts of heat has resulted in overpressurizing the cooling water passages. The operators should be trained adequately and the systems designed with appropriate instrumentation, interlocks, and pressure relief devices to mitigate the risks associated with this type of event. (10) An FBC system's furnace and connected components will contain substantial quantities of hot solids for some time after a master fuel trip (MFT). Personnel should be aware of and trained to deal with the following possible results: (a) (b) (c) (d) (e) (f) Hot solids stored in a furnace-connected space may suddenly flow into another space. Care should be taken to ensure that personnel do not enter a furnace or connected space that could still contain hot solids or be connected to a space that contains hot solids. Solids stored in the cyclone or loop seal for example, due to blockage could suddenly be released and flow into another space when the blockage fails or the solids cool and their fluidization characteristics change. Operation of an FD fan, an ID fan, or other fans might not rapidly cool stored solids because the moving air could bypass the bulk of a heap of hot particles. While a surface could appear cool because of rapid heat loss due to radiation, the bulk of the heap could still be hot due to self-insulation. A large heap of solids could require many hours to cool to a safe temperature. Water might enter a body of hot solids from any of a number of sources, including a boiler tube leak. Water pouring onto the solids might not immediately wet the hot solids (much like a drop of water on a hot griddle). When the solids suddenly become wet, rapid generation of steam (steam explosion) could occur. In the event of a steam explosion, hot solids could flow upward as well as in other directions. Large hot clinkers or hot refractory could suddenly be released from the cyclone and flow into the loop seal and connected spaces with the assistance of smaller fluidizable particles. As written, paragraph (8) is open to misinterpretation as to who should do the inspection.

71 of 171 2/6/2013 3:15 PM Jurisdictional authorities (AHJ) have for many years been inappropriately interpreting NFPA 85 as containing in-service inspection responsibilities for the National Board Commissioned Boiler Inspectors employed by Authorized Inspection Agencies as defined by the National Board document NB-369 Qualifications and Duties for Authorized Inspection Agencies (AIAs) Performing Inservice Inspection Activities and Qualifications for Inspectors of Boilers and Pressure Vessels. This has caused significant legal issues for Authorized Inspection Agencies. The proposed change is intended to make it clear that NFPA 85 does not contain any requirements.for in-service inspections for these agencies. Related Public Inputs for This Document Related Input Public Input No. 132-NFPA 85-2013 [Section No. 3.2.2] Relationship Submitter Full Name: Brian Moore Organization: Hartford Steam Boiler Inspecti Submittal Date: Wed Jan 02 14:26:27 EST 2013 I, Brian Moore, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this By checking this box I affirm that I am Brian Moore, and I agree to be legally bound by the above and the terms and