EarthLinked Model DSH-1872 Desuperheater Kit

Similar documents
Heat Recovery Module Installation Manual for

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions

EarthLinked Freeze Protection Kit Model FP-1872 Installation Manual

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

EarthLinked CC Series Compressor Unit R-410A Quik-Start Instructions

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked STORAGE WATER HEATER / HYDRONIC BUFFER TANK MODELS GSTE-60, GSTE-80 & GSTE-119

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked Series PHXTI Pool Heat Exchangers Installation Manual

EarthLinked HC Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked AFN Series Air Handlers Installation Manual

EarthLinked AVN Series Air Handlers Installation Manual

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

AVS Air Handlers Prime PSC, PSD, PSDH and Classic SC, SD, and SDH

Temperature Control Kit Model HHK/CWK-1872

EarthLinked SD(A) Series

Model R060 Installation - Operation Manual

EARTHLINKED GEOTHERMAL RENEWABLE ENERGY SYSTEMS MAINTENANCE GUIDE

INSTALLATION INSTRUCTIONS

Prime Series PSC Geothermal Heating and Cooling System

MACH N-407 Heat Pump Air-Cooled Chiller

Prime Series PSDH Geothermal Heating and Cooling System

Prime Series PSDH Geothermal Heating and Cooling System

Classic Series SD Geothermal Heating and Cooling System

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

MAC N-407 Air-Cooled Chiller

INSTALLATION INSTRUCTIONS

AHWG Remote Mount Hot Water Generator Module

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

AHWG Remote Mount Hot Water Generator Module for TTP Series Outdoor Split Unit

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Owner s Manual Therma-Stor II Heat Recovery System

SECTION AIR COILS

TABLE 1. Specifications: Dimensions: 6¼ x 9 5/8 x 2 ¾

Liebert CSU3000 Chiller

Commercial High-Efficiency Condensing Units

PACKAGE AIR CONDITIONER

Electric Duct Heaters

Split System Cooling Product & Performance Data

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

3 TON Heating Performance Data TON Cooling Performance Data TON Heating Performance Data TON Cooling Performance Data...

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

APPLICATION DATA SHEET

SERVICE MANUAL FOR MODEL RM-10

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions.

WCH5**4. Product Specifications

Installation Instructions

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

Cavitator Ultrasonic Cleaners

SPLIT SYSTEM HEAT PUMP 1½ 5 TON HERITAGE 13 MODELS 2A6H A American Standard Heating & Air Conditioning

MAC-120HE-03 Air-Cooled Chiller

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Residential Piping and Long Line Guideline

30GXN,R AIR-COOLED LIQUID CHILLERS WITH COMFORTLINK CONTROLS 50/60 Hz

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

CENTRAL SPLIT UNIT UNIC

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

Instruction Manual for HX-DX and HX-DXHP Heat Exchangers 3 / 2017

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

pyxis pyxisa NEW rcgroupairconditioning

Air-Cooled Condenser. Installation Instructions. Revision Date: 12/21/98

INSTRUCTIONS! DO NOT DISCARD!

SECTION PLUMBING EQUIPMENT

Commercial High-Efficiency Condensing Units

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

Split System Cooling Product Data

Classic Series SC Geothermal Heating and Cooling System

SECTION (15530) - REFRIGERANT PIPING

INSTALLATION INSTRUCTIONS

COMPRESSOR SERVICE REPLACEMENT KIT P/N (WCC 500A, 115/60, AIR COOLED)

Jr. Tech (JT-1, 2, 3) Knowledge Areas

THE PRODUCTS YOU NEED. THE QUALITY YOU WANT. THE INNOVATION YOU DESERVE.

Split System Cooling Product Data

Portable Roller Oven. Features

pyxis u pyxis ua NEW rcgroupairconditioning

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SM Field Installed Electric Heat Kit

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz)

RDT Refrigeration Book

13 SEER CONDENSING UNITS

SPLIT SYSTEM COOLING 1½ 5 TON ALLEGIANCE 14 MODELS 4A7A C/30-060B American Standard Heating & Air Conditioning

Split System Cooling Product Data

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning

SECTION DOMESTIC WATER HEATERS

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

TECHNICAL DATA & SERVICE MANUAL

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

Transcription:

EarthLinked Model DSH-1872 Desuperheater Kit for SC and CC Compressor Units CONTENTS PAGE Desuperheater Kit Information 3 Desuperheater Mechanical Installation 9 Desuperheater Electrical Installation 17 System Start-Up 20 DSH KIT (04/13) Copyright 2013 Earthlinked Technologies, Inc.

Disclaimer Proper installation and servicing of this EarthLinked Kit is essential to the Heating and Cooling Systems reliable performance. All EarthLinked systems and kits must be installed and serviced by an authorized, trained technician who has successfully completed the training class and passed the final examination. Installation and service must be made in accordance with the instructions set forth in this manual. Failure to provide installation and service by an authorized, trained installer in a manner consistent with this manual will nullify the limited warranty coverage for the system. EarthLinked Technologies shall not be liable for any defect, unsatisfactory performance, damage or loss, whether direct or consequential, relative to the design, manufacture, construction, application or installation of the field specified components. Earthlinked Technologies, Inc. 4151 South Pipkin Road Lakeland, Florida 33811 tel. 863-701-0096 fax 863-701-7796 info@earthlinked.com www.earthlinked.com CSI # 23 80 00 DSH KIT (04/13) Page 2

Desuperheater Kit Information For SC Compressor Units: The field installed ETI Desuperheater Kit Model DSH-1872 equips the SC Series Compressor Unit with supplemental water heating capability during (1) heating and cooling mode operation or (2) cooling mode operation for the ETI Heating and Cooling System. Use of the desuperheater to heat water during the heating season will increase the heating load on the space heating equipment by 2,000 BTUH for each adult and teenager occupant. For CC Compressor Units: The field installed ETI Desuperheater Kit Model DSH-1872 equips the CC Series Compressor Unit with supplemental water heating capability during cooling mode operation. For SC and CC Compressor Units: Typical water piping installed with an existing or new standard storage water heater is illustrated in Figure 1. Water piping for the desuperheater installed with an ETI Model GSTE Storage Water Heater is illustrated in Figure 2. The GSTE Series Storage Water Heater is available in 60, 80 and 119 gallon capacities with water piping connections built into the top of the storage water heater specifically for use with the desuperheater. All GSTE Series models are equipped with a 4.5 kw electric heater and provide the following hot water recovery rates in gallons per hour, for a range of water temperature increases, in degrees Fahrenheit. ΔT 30 40 50 60 70 80 90 GPH 62 46 37 31 26 23 21 *ΔT in ºF; GPH in U.S. Gallons per hour. DSH KIT (04/13) Page 3

Field wiring for the DSH-1872 Kit applied to the SC Compressor Unit is illustrated in Figure 3a for water heating during (1) heating and cooling system operation and (2) cooling system operation only. Field wiring DSH-1872 Kit applied to the CC Compressor Unit is illustrated in Figure 3b for water heating during cooling system operation. Figure 1. Desuperheater Installed with Existing or New Standard Storage Water Heater DSH KIT (04/13) Page 4

Figure 2. Desuperheater installed with GSTE Storage Water Heater. DSH KIT (04/13) Page 5

Figure 3a. SC Field Wiring for Desuperheater Kit DSH KIT (04/13) Page 6

Figure 3b. CC Compressor Unit Field Wiring DSH KIT (04/13) Page 7

Mounting/Location The Desuperheater is mounted vertically on a solid surface indoors in a space with ambient temperatures of 40 F or above. The Desuperheater is to be located within 10 feet of the compressor unit and as close as possible to the storage water heater (not to exceed 25 feet), with interconnecting water lines insulated. Controls As illustrated in Figures 3a and 3b, the Desuperheater contains a water high limit control. It is factory set to 140 F. It also contains a refrigerant gas low limit, which is factory set to 125 F. The freeze protection control is designed to operate the circulating pump when water temperatures of 40 F or less are detected, in order to provide water circulation independent of compressor operation. Heat Exchanger The Model DSH-1872 Desuperheater contains a corrosion resistant all-copper double wall heat exchanger of counterflow twin tube design. The heat exchanger is continuously vented along its entire length and meets IAPMO safety requirements and exceeds applicable UL requirements. Circulator Pump The Desuperheater contains a Taco 006 series low wattage wet rotor in-line single stage circulator. The water cooled pump is rated at 60 watts, 230 volts and 0.40 amperes. It is designed for 125 psig working pressure and up to 220 F fluid temperature. The pump housing is bronze and the bearings are ceramic. DSH KIT (04/13) Page 8

Desuperheater Mechanical Installation Before initiating mechanical or electrical installation of the Desuperheater, read, understand and execute the following: When brazing copper tubing, always utilize the nitrogen brazing process as described here: DSH KIT (04/13) Page 9

Two refrigerant lines must be run from inside the compressor unit cabinet to the Desuperheater. The available holes (marked plugged ) in the cabinet for the SC compressor units are shown in Figure 4. For the CC compressor unit, shown in Figure 5, two additional holes of at least 1 diameter are to be field drilled in the plumbed panel of the cabinet to accommodate the interconnecting refrigerant tubing. See Kit Contents in Desuperheater Electrical Installation section. Desuperheater piping and connections to the compressor units are illustrated as follows: SC: Figures 6 & 7 CC: Figures 8 & 9 Water piping for all compressor unit sizes is 1/2 OD copper with insulation on both water lines and the storage water heater located as close as practical to the Desuperheater, within 25 feet maximum. Figures 1 and 2 illustrate typical water piping, fittings and connections for the Desuperheater and storage water heater. DSH KIT (04/13) Page 10

Figure 4. SC Cabinet Dimensions and Connections DSH KIT (04/13) Page 11

Figure 5. CC Cabinet Dimensions and Connections DSH KIT (04/13) Page 12

Figure 6. SC Internal Flow Schematic with Desuperheater DSH KIT (04/13) Page 13

Figure 7. SC Piping with Desuperheater DSH KIT (04/13) Page 14

Figure 8. CC Internal Flow Schematic with Desuperheater DSH KIT (04/13) Page 15

Figure 9. CC Piping with Desuperheater DSH KIT (04/13) Page 16

DESUPERHEATER ELECTRICAL INSTALLATION Kit Contents In addition to 4 Ft. of 1/2 Type ACR soft copper tubing and two 1/2 90 o copper ells, the DSH-1872 kit contains the following items for electrical installation. Figure 10 lists the kit items and which are utilized in the installation on SC and CC compressor units. Used with Kit Components SC Compressor CC Compressor Fuse Holder (2) Yes Yes Fuses (2) Yes Yes Screws (8) Yes- 8 Yes- 5 2 Block Term. Strip Yes Yes Pink Wire Yes Yes Gray Wire Yes Yes 3 Block Term. Strip Yes No DPDT Relay Yes No Red Wire Yes No Black Wire Yes No Blue Wire Yes No Yellow/Green Wire Yes No Yellow/Blue Wire Yes No Red/White Wire Yes No Figure 10. DSH-1872 Kit Electrical Components DSH KIT (04/13) Page 17

SC Compressor Unit Figure 11. SC Compressor Unit Field Wiring 1. Turn OFF all electrical power to the EarthLinked system. 2. Install fuse holders, fuses, three pole terminal strip, two pole terminal strip and water. heater relay in electrical box with fasteners, as shown in Figure 11. 3. Connect wires as shown in Figure 11. 4. Install fuses. 5. Check all wiring for proper routing and ensure good connections at all terminals. DSH KIT (04/13) Page 18

CC Compressor Unit Figure 12. CC Compressor Unit Field Wiring 1. Turn OFF all electrical power to the EarthLinked system. 2. Drill holes in electrical box as necessary to install fuse holders and terminal strips as shown in Figure 12. 3. Connect wires as shown in Figure 12. 4. Field wire DSH to terminal strips. 5. Install fuses. 6. Check all wiring for proper routing and ensure good connections at all terminals, prior to restoring electric power to the system components. 7. Test system for functionality. DSH KIT (04/13) Page 19

SYSTEM START-UP 1. Braze and check all field-made refrigerant joints for leaks and repair as necessary. See the EarthLinked Heating and Cooling System Installation, Operation and Maintenance Manual, or the appropriate SC Quik-Start Manual or CC Quik-Start Manual for the proper procedure. 2. Evacuate and charge the refrigerant system in accordance with the appropriate EarthLinked Heating and Cooling System Installation, Operation and Maintenance Manual, or the appropriate SC Quik-Start Manual or CC Quik-Start Manual. 3. Fill the water system and ensure that all air has been eliminated from the desuperheater, to prevent pump cavitation and bearing damage. 4. Check and repair all field-made water system joints to ensure there are no leaks. 5. Start system and check for functionality. DSH KIT (04/13) Page 20