K 60 D 068 Z KIT RÉGULATION POUR POMPE À CHALEUR EN RELÈVE DE CHAUDIÈRE APPLICATIONS 2 ZONES MIXTE (PLANCHER + RADIATEURS) OU 2 ZONES PLANCHER

Similar documents
K 60 D 067 Z KIT RÉGULATION POUR POMPE À CHALEUR EN RELÈVE DE CHAUDIÈRE APPLICATION 1 ZONE RADIATEURS OU PLANCHER - ACTION PROPORTIONNELLE

K 60 D 066 Z KIT RÉGULATION POUR POMPE À CHALEUR EN RELÈVE DE CHAUDIÈRE APPLICATION 1 ZONE RADIATEURS / ACTION TOUT OU RIEN

ENSEMBLE DE CONTRÔLE ET RÉGULATION POUR SYSTÈMES DE CHAUFFAGE / CLIMATISATION AVEC POMPE À CHALEUR INVERTER ET APPOINT ÉLECTRIQUE.

CONTROL UNIT FOR HEATING/COOLING SYSTEMS WITH INVERTER SPLIT HEAT PUMP AND ELECTRICAL BACK UP. APPLICATIONS:

M2Z M NOTICE D INSTALLATION INSTALLATION INSTRUCTION MANUALE D INSTALLAZIONE MANUAL DE INSTALACIÓN AUFSTELLUNGS- HANDBUCH INSTRUÇÕES DE INSTALAÇÃO

Installer Manual KNX Touchscreen Thermostat

K 60 D 070 Z KIT RÉGULATION SYSTÈME POUR POMPE À CHALEUR INVERTER AVEC CHAUFFAGE D APPOINT ÉLECTRIQUE

Programmable Towel Radiator Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

TIREE FAN COIL CONTROLLER - T6580

INSTRUCTION MANUAL REMOTE CONTROL DEVICE EASYREMOTE

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

N M AirControl AHU. Control manual

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

REMOTE CONTROL FOR CHILLER MYCHILLER

Semi flush-mount room thermostats

PROGRAMMABLE 7-DAY RF THERMOSTAT

T6580 FAN COIL CONTROLLER

G a

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control

RVL481. Heating Controller. including d.h.w. heating

PROGRAMMABLE 7-DAY THERMOSTAT

Installation Guide. ECL Comfort 210, application A Table of Contents

INSTRUCTION FOR THE USER THC V E OIL BLU

ETO 2 - Controller for ice and snow melting

Easy-Stat. Wireless Programmable Room Thermostat Pt No

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

RC-101 Heat Pump Real Time Pricing System 2 Stage Heat / 1 Stage Cool

HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

Control solutions Biofloor

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

Room thermostats with LCD for wall mounting

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

Condensing Boiler RS100 Controller Training Program

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

SCHMIDT LED Measured Value Display MD Instructions for Use

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

Connections, displays and operating elements C D E G H. Installing the control unit

Tebis application software

OPERATING INSTRUCTIONS

UV - Monitor UVT 16. Use. Description

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

PHRT 9 / 18 PHRT 12 PHRT 16 PHRT 18. Pompe à chaleur avec équipement hydraulique - Fluide réfrigérant R 410 A

Wireless room thermostat with LCD

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

Self-learning Room Temperature Controller

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: /

1. Information before installation General terms of delivery, storage and transport

FIL-SPL Flow-through heater for central heating USER MANUAL

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

UM PAC HT 01-N1GB Part number / Code / Teil Nummer / Codice / Código : GBSupersedes / Annule et

RVL479. Heating Controller. for use with a partner unit

BSR Addressable Fire Detection control panel. Installation operation manual

Room thermostat with Auto Timer, Option External Input

DC 60 & DM 60 displays

Wall Hung Boiler Room Thermostat OR30 OT Thermostat

RVL480. Heating Controller

Room thermostat with Auto Timer, Option External Input

Model: RT310RF. Installation Manual

Products no longer available

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

OPERATION MANUAL. Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB

B-40/B-41 Modulating Temperature Controller

Rev Pulse Modulating and Anti- Sweat Control (PMAC II Solo) Installation and Operation Manual

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

* _rev1* User guide DRIVER 230 CPL. 3 zone weekly programmer using power line carriers

Room thermostat with Auto Timer, Option External Input

Programmable Electronic Thermostat

Regulation EASY CLIMA VERSION 1.6 TECHNICAL MANUAL

Application description

NA G µair CONNECT 2

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Room thermostat with Auto Timer, independent DHW

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Sensor Control Panel

RVL470. Heating Controller. Use. Functions. Series B

Model: Touch-RS. 1 Touch-RS

Type ETO2. Controller for ice and snow melting 67222A 04/14 (JRK) GREEN COMFORT Maximum comfort with low energy consumption OJ Electronics A/S

- Data Brochure D 260. Boiler Control /09

Tri-Stack Smart System

ELECTRONIC COMMUNICATING THERMOSTAT

PRELIMINARY EDITION

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

ENGLISH. REMOTE CONTROL / ROOM THERMOSTAT Wireless INSTALLATION SERVICING AND USER MANUAL

ERV-24. Technician Settings & Operating Manual. Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135

Analog Room Pressure Monitor RPC Series

Digital Thermostat. Models: VS35W and VS35B INSTALLER / USER MANUAL

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

5, SE GÅNGHESTER,

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Transcription:

(Etiquette signalétique) NOTICE D INSTALLATION INSTALLATION INSTRUCTION MANUALE D INSTALLAZIONE MANUAL DE INSTALACIÓN AUFSTELLUNGS- HANDBUCH F I E D K 60 D 068 Z KIT RÉGULATION POUR POMPE À CHALEUR EN RELÈVE DE CHAUDIÈRE APPLICATIONS 2 ZONES MIXTE (PLANCHER + RADIATEURS) OU 2 ZONES PLANCHER CONTROL KIT FOR HEAT PUMP IN CONJUNCTION WITH EXISTING BOILER MIXED 2-ZONE APPLICATIONS (FLOOR + RADIATORS) OR 2-FLOOR ZONES KIT REGOLAZIONE PER REFRIGERATORE IN POMPA CALORE CON CALDAIA DI INTEGRAZIONE APPLICAZIONI 2 ZONE MISTO (PAVIMENTO + RADIATORI) O 2 ZONE PAVIMENTO KIT DE REGULACIÓN PARA BOMBA DE CALOR CON CONEXIÓN DE CALDERA APLICACIONES 2 ZONAS MIXTA (SUELO + RADIADORES) O 2 ZONAS SUELO SET - STEUERMODUL UND SCHALTKASTEN FÜR WÄRMEPUMPE PLUS BAUSEITIGE HEIZQUELLE ANWENDUNGEN 2 ZONEN GEMISCHT (FUßBODEN + HEIZKÖRPER) ODER 2 ZONEN FUßBODEN Septembre 2008 10 11 486 - F..I.E.D - 01

MARKING This product, marked with the symbol, complies with the essential requirements of the following Directives: - Low voltage No. 2006/95/EC. - Electromagnetic Compatibility No. 89/336 EEC, modified 92/31 and 93/68 EEC. CONTENTS 1 - Purpose - Use........................................ 2 2 - Precautions.......................................... 2 3 - Composition......................................... 2 4 - Operating principle.................................... 3 5 - Installation........................................... 5 6 - Connections......................................... 6 7 - Presentation of electronic control elements................ 10 8 - Operation.......................................... 12 9 - Starting - Maintenance................................ 22 10 - Electrical diagram.................................... 23 1 - PURPOSE - USE This control kit is designed to control heating installations with a heat pump for relieving a boiler in residential applications. Application: - 2 Mixed zones (Floor + Radiators). - 2 Floor zones. Note: The floor system can be of heating / cooling type. 2 - PRECAUTIONS IMPORTANT Installation, commissioning and maintenance of this kit must be performed by qualified and authorised personnel, in accordance with current standards and recognized trade practices. Before doing any work on the installation, make sure it is switched off and all power supplies locked out. Consult the manuals of the system's various components: - Generator. - Boiler. CAUTION Before each start-up operation, make sure that the it is properly configured for the application. See paragraph 8.7. 3 - COMPOSITION The kit includes: - A control box to be installed in the comfort zone (see paragraph 5.1). - An electrical control box is to be placed in the equipment room (see paragraph 5.4). - An outside temperature sensor unit placed on the facade of the building (see paragraph 5.2). - 2 outgoing water temperature probes for zones 1 and 2, with their retaining clamp, to be placed on the piping (see paragraph 5.3). - An installation return water temperature sensor, with its retaining clamp, is to be placed on the piping (see paragraph 5.3). - An ambiance sensor to be placed in zone 2 (see paragraph 5.1). 2 Control unit: - Plastic wall-mounted control unit. - Dimensions: height = 128 mm width = 86 mm - Colour: White - Class lll - IP 30 depth = 34 mm

04 05 21 22 23 24 25 A 01 02 03 11 12 13 14 15 S1 C S2 C S3 4 3 2 1 A1 C A2 C A3 H1 H2 H3 CN8 CN7 CN6 CN5 CN1 CN2 CN3 CN4 230V N U FP R1 R2 R3 C E1 E2 T+ T- D1 D2 + - B C + - CN3 Y2 CN2 Y1 U N CN1 CN4 CN5 CN6 S5 C S4 C A4 P2 P1 N 230V CN3 Y2 CN2 Y1 U CN1 N N + - 230V CN4 CN5 CN6 S5 C S4 C A4 P2 P1 Outside temperature sensor: - Installed in a box with cable gland. Note: This sensor must be installed in a location that is sheltered from inclement weather. See details in paragraph 5.2. Water temperature sensor: - Metal cap: length: 41 mm max. diameter: 8 mm - With 3.5 meters of cable and retaining clamp. Zone 2 ambiance sensor: - Designed to be installed in Mosaic type flushmounted boxes (size 45 x 45). x 3 Electrical control box: - plastic box with transparent door + lock and wall mounting lugs + screws. - grey colour, RAL 7035. - IP 22, once installed. - weight: 4.7 Kg. 1 - Equipment: 1 - Heating control electronic board 2 - Boiler authorisation relay 2 N U KA1 N 1 A1 Carte BI PAC (accessoire) 8 3 - Control system circuit breaker 4 - Terminal strip 5 - Zone 1 electronic control board 3 2 Q1 BORNIER XC1 Twin heat pumps Ctrl kit (accessory) 6 6 - Zone 2 electronic control board A2 A3 7 - BUS terminal strip 8 - Control board accessory location Bi-PAC (see specific installation manual) 4 5 BARRETTE DE TERRE BORNIER XC2 + - 7 4 - OPERATING PRINCIPLE The kit is designed allow complete installation control from the parameterable control box. The orders given by the control box are sent (via a 2-wire BUS) to the installation elements via a control unit which manages the generator, the boiler make-up valve, circulators and the zone valves. The generator and the make-up unit are driven based on a resulting water temperature setpoint calculated according to a water law (according to the outside temperature). Priority is given to thermodynamic heating. A temperature sensor to be placed on each zone outgoing line allows the water temperature of each zone to be controlled by means of a control valve (not included). A water temperature sensor on the installation's return line is used to control the generator and the make-up unit, if any. 3

Installation diagram: Accessory 70250065 Ambiance sensor (of control box outside zone) Zone 1 Ambiance sensor Zone 2 Control box with ambient temperature sensor OR Outside sensor Boiler 230 VAC power supply, control box 3-way On/Off valve, 230 VAC 70600116 Heating board Control kit K60D068Z Zone board Outgoing sensor 3-way proportional valve, 230 VAC Zone board Outgoing sensor Do not place the thermostatic valve on the radiator(s) located in the room where the ambiance sensor Water return probe 3-way proportional valve, 230 VAC Decoupling bottle Installation according to current standards and recognised trade practices Output control valve Decoupling bottle kit 70600112 Mixing tank 70600118 Dirt separator 70600114 Generator Note: install the strainer filter, supplied with the generator, on the water inlet Installation diagram for indication Not contractual. 4

5 - INSTALLATION 5.1 - CONTROL BOX AND AMBIANCE SENSOR INSTALLATION As the control unit is equipped with a temperature sensor, it must be installed in a location that is representative of the temperature of the comfort zone No. 1 (Floor). Wall mounting: the control unit (or the ambiance sensor) not be installed in corners, on shelves or behind curtains, near sources or heat or directly exposed to sunlight. The unit should be installed approximately 1.5 m above the floor. Open the box by removing the lower screw and secure the base to the wall (mounting holes, item 1). Open the protective cover (screw 2) and connect the BUS link to the control board (see chapter 6). Mini. 20 cm 1.50 m Base 1 Control unit 2 Rear view Fit the control unit back on its base. Note: If this ambiance installation is not possible, use the ambiance sensor accessory 70250065. This ambiance sensor is intended to be installed in Mosaic type flush-mounted boxes (size: 45 x 45). It is connected to the valve control board. The ambience sensor supplied with the kit is to be installed in a location that is representative of the temperature in comfort zone No. 2 (Radiators or floor). Respect the same precautions as for the control box. Ambiance sensor 5.2 - INSTALLATION OF THE OUTSIDE TEMPERATURE SENSOR This sensor must be located outside in a location that is representative of the temperature to be measured (on a wall facing North/North-west) and located away from parasitic heat sources (chimney, thermal bridge, etc..) and sheltered from inclement weather (under a roof overhand, for example). Connection as per paragraph 6. 5.3 - INSTALLATION OF THE WATER TEMPERATURE SENSOR To ensure proper operation: - Ensure that the sensor is correctly secured to the piping. Use the metal retaining clamp supplied with this kit. - Use thermoconductive paste to improve conductivity (not supplied). - Insulate the assembly with insulating foam (not supplied). 5.4 - INSTALLATION OF THE ELECTRICAL CONTROL BOX To be installed in the equipment room (ambient temperature between 0 and 40 C). IP 22, once installed. Plastic wall-mounted control box. - Install the mounting lugs, supplied with the kit, on the box. - Secure the box to the wall using the screws / anchors supplied with the kit. Electrical connections: see paragraph 6. Note: The box must be supplied with 230 V / 1 / 50Hz. 322 322 5

6 - CONNECTIONS 6.1 - GENERALITIES Electrical cabinet according EN 60 439-3. The electrical installation must comply with the standards and regulations applicable where the device is being installed (in particular NF C 15-100 = IEC 364). Power supply for the cabinet: 230V/1/50Hz. The acceptable voltage variation is +/- 10 % during operation. Class 1 device. Short circuit current: 4.5 ka (according EN 60 898). Device designed to be connected to a mains supply with a TT neutral point connection (Neutral connected to earth - according NF C 15-100). The electrical connections must be fixed. Use grommets for passing cables into the cabinet. 6.2 - PRINCIPLE See diagrams in paragraph 6.3. The connecting cables are not supplied. Caution: To avoid problems related to electromagnetic disturbances, do not route these cables near power cables. Control unit Outside air temperature D Power supply 230 V / 1 / 50Hz C B Generator load shedding A M Ambiance sensor Zone 1 accessory item 70250065 N Ambiance sensor Zone 2 E On/Off Heating/Cooling ALARM Control box Zone 1 board 1 - (A2) Zone 1 board 2 - (A3) GENERATOR F G H J L O Q S U P R T V Authorisation Alarm Supplementary heating Supplementary On/Off valve (230 V) Primary circulating pump (230 V) Proportional zone 1 valve (230 V) Closed position Zone 1 circulating pump (230 V) Proportional zone 2 valve (230 V) Closed position Zone 2 circulating pump (230 V) Installation outgoing water temperature Outlet water temperature, zone 1 Outlet water temperature, zone 2 : Possible link ZONE 1 Floor ZONE 2 Radiators or Floor system 6

A Generator load shedding signal (if required) - Two possibilities: 1) By a "remote info" signal coming from the electrical utility meter EDF (French electrical utility) (VLV "Very Low Voltage" signal): 1 twisted pair (6/10) cable with shielding (screen grounded box side). 2) By a good quality, potential-free external contact. - Contact closed = generator load shedding. - 2-conductor cable, min. size 0.5mm 2. - Maximum length 25 meters. - To be connected to the heating board A1. B BUS - 2-conductor cable, min. size 1 mm 2. - Total length of the BUS connection: 40 meters (heating board A1 / control box connection). - To be connected on the specific terminal strip (terminals + and -) placed in the service box. C Control box power supply - 230 V, single-phase, 50 Hz + ground (Class I). - It must be supplied from a protection and disconnect device in compliance with current regulations. - Cable 3G 1.5 mm 2. - To be connected directly on circuit breaker Q1 of the box (Terminals U and N). Note: The control box is supplied by the BUS. D Outside temperature sensor - 2-conductor cable, min. size 0.5 mm 2. - Maximum length 25 meters. - To be connected to the heating board A1. E Generator control - Shielded cable, 2-twisted pairs (for heating installation only) or 3-twisted pairs (for a reversible floor type installation). 1 pair for generator on. 1 pair for heating / cooling generator inversion (reversible floor). 1 pair for the generator alarm signal. - Min. cable size: 0.5 mm 2. - Maximum length 25 meters. - Shielding, generator side. - To be connected to the heating board A1. F Supplementary boiler authorisation (as required) - Potential-free changeover contact, available on the box's terminal strip (terminals A, B, C). - 2 A resitive at 230 Vac maximum. - Actuated contact = boiler authorised. - Not mandatory. To be used if boiler operation is to be slaved. G Boiler alarm unavailable (as required) - A contact from the boiler can possibly be connected on the heating board A1 for signalling on the control box and closure of the supplementary valve. - This contact must be potential-free and of good quality. - Contact open = alarm. - A maximum connection length of 25 meters and size 0.5 mm 2. H Boiler supplementary valve control - "On/Off" control signal, 230 V / 50 Hz (30 VA maximum) available on the box's terminal strip: - terminal 2 = common (connected to the Neutral) - terminal 1 = valve opening control - terminal 3 = valve closing control - It is possible to connect either a 3-point valve (3 wires) (available as an accessory), or a spring type return valve (2 wires). - Minimum cable size 0.75 mm 2. I Closed supplementary valve position (as required) - To be connected to the heating board A1 in the case of a reversible heating / cooling floor system. - Auxiliary contact of the supplementary valve closed when the supplementary valve is closed (generator operation is prohibited (cooling) if the valve remains open). - This contact must be potential-free and of good quality. - A maximum connection length of 25 meters and size 0.5 mm 2. J Primary circulator - It is possible to supply a circulator with 230 V / 1 / 50 Hz directly via the box's terminal strip (Terminals 5 - Phase / 4 - Neutral / Ground). - Maximum current 1.6 A (for a superior current strength, the signal must be relayed). - Cable 3G 1.5 mm 2. - The circulator must have its own thermal protection (not supplied). 7

L Water temperature sensors installation return - Sensors delivered with a cable measuring 3.5 m long. - This connection may be extended with a 2-conductor cable (minimum 0.5 mm 2 cross-section) and with a maximum length of 25 meters. - To be connected to the heating board A1. M N Ambient temperature probe (possible in zone 1 - mandatory in zone 2) - Required if the control box is not placed in a location that is representative of the temperature in zone 1. - The sensor of zone 2 is included in the kit. - 2-conductor cable, min. size 0.5 mm 2. - Maximum length 25 meters. - To be connected to the zone 1 board (identified A2) and on the zone 2 board (identified A3). Caution: Activate the zone 1 sensor by setting parameter 73 to 0. O P Water temperature sensors (zone 1 and zone 2 outgoing lines) - Sensors delivered with a cable measuring 3.5 m long. - This connection may be extended with a 2-conductor cable (minimum 0.5 mm 2 cross-section) and with a maximum length of 25 meters. - To be connected to the zone 1 board (identified A2) and on the zone 2 board (identified A3). Q R Zone valve control - Proportional action - 3-point control signal, 230 V / 50 Hz (30 VA maximum) available on the box's terminal strip: - For zone 1: - terminal 14 = common (connected to the Neutral) - terminal 13 = valve opening control - terminal 15 = valve closing control - Minimum cable size 0.75 mm 2. - For zone 2: - terminal 24 = common connected to the Neutral - terminal 23 = valve opening control - terminal 25 = valve closing control - Minimum cable size 0.75 mm 2. S U T Zone circulators - It is possible to supply the zone circulators with 230 V / 1 / 50 Hz directly via the terminals in the box: - For zone 1: - terminal 11 = Phase - terminal 12 = Neutral - Ground - For zone 2: - terminal 21 = Phase - terminal 22 = Neutral - Ground - Maximum current 1.6 A (for a superior current strength, the signal must be relayed). - Cable 3G 1.5 mm 2. - The circulator must have its own thermal protection (not supplied). V Zone valves in closed positions - To be connected to the zone 1 board (identified A2) and on the zone 2 board (identified A3). - Auxiliary contact of each zone valve, closed when the valve is closed. - This contact must be potential-free and of good quality. - A maximum connection length of 25 meters and size 0.5 mm. Note: ensure that the ground connections of the various system components are interconnected. 8

6.3 - BOX CONNECTING DETAILS Outside temperature sensor D Generator Printed Circuit Board (*) For reversible floor installation: remove the jumper between terminals 3 and 4 and connect these terminals to the control. N U Installation return sensor L (*) Cn/fr M/A 4 3 2 1 5 E S1 C S2 C S3 4 3 2 1 A1 C A2 C A3 H1 H2 H3 5 4 3 2 1 4 3 2 1 5 4 3 2 1 3 2 1 CN8 CN7 CN6 CN5 AL 6 Not used G Supplementary valve position contact closed (as required - for reversible floor system). Q1 KA1 230V A1 CN1 CN2 CN3 CN4 1 2 3 1 2 3 4 1 2 3 4 1 2 3 4 N U FP R1 R2 R3 C E1 E2 T+ T- D1 D2 + - Boiler fault contact unavailable (as required). Remove the bridge between C and A3. A Electrical utility meter Or Generator load shedding (if used) Micro-switch on Z1 Micro-switch on Z2 Terminal XC 1 + - Y2 N Y1 U N + - Y2 N Y1 U N 1 2 3 4 5 11 12 13 14 15 21 22 23 24 25 A B C R H Q F Z2 Z1 A2 Z2 Z1 A3 S5 C S4 C A4 P2 P1 S5 C S4 C A4 P2 P1 Ph N C Open Power supply 230 V / 1 / 50 Hz Common Close On/Off supplementary valve J Primary circulator S Circulator, zone 1 Open Common Close Proportional valve, zone 1 T Circulator, zone 2 Open Common Close Proportional valve, zone 2 Boiler heating authorisation (if used) M Ambiance sensor, zone 1 (possible accessory item) O U Valve contact, zone 1, closed Water outgoing sensor, zone 1 N Ambiance sensor, zone 2 P V Valve contact, zone 2, closed Water outgoing sensor, zone 2 Terminal XC 2 B BUS Control unit 6.4 - CABLE ROUTING Box top view Box 230 VAC power supply BUS 230 VAC connections Control signals and sensors 9

7 - PRESENTATION OF ELECTRONIC CONTROL ELEMENTS 7.1 - CONTROL UNIT 1 Rotary function selection knob (9 positions, left to right): - Cooling: Operation in cooling mode available only for the Reversible floor configuration. - Heating, anti-freeze: Anti-freeze mode operation - Heating, ECO: Heating mode operation with ECO setting - Heating, Auto: Heating mode operation with hourly programming - Heating, Confort: Heating mode operation with Comfort setting - Stop - Time setting - Prog. Z1: Zone 1 program control (hourly / weekly) - Prog. Z2: Zone 2 program control (hourly / weekly) 2 3 4 2 Push-button for setpoint and parameter modification 5 3 4 5 Push-button for setpoint and parameter modification "Z/OK" push-button Display selection zone 1 / zone 2 / outside temperature and validation Liquid crystal display (LCD) 1 6 6 Ambient temperature sensor Generator load shedding Day of the week or parameter level Zone 1 display Zone 2 display Override in progress Supplementary heating authorisation Outside temperature display Hourly programming Comfort / ECO / Anti-freeze indication Telephone override activated When off, the display indicates "OFF". When in operation, the normal reference display indicates: - the setpoint temperature of zone 1, - the current setting with the hourly program bar graph: = Comfort = ECO No indication - current day. = Anti-freeze (prolonged absence) 10

7.2 - HEATING BOARD A1 Allows control of the generator and to authorise boiler heating. It is connected to the control unit by the communication BUS. C (**) Boiler alarm input unavailable (***) Supplementary valve inlet closed (**) Generator fault input Not used (*) Generator On / Off output (***) (*) Generator Heating / Cooling output Outside temperature Installation return water temperature Not used S1 C S2 C S3 4 3 2 1 A1 C A2 C A3 H1 H2 H3 5 4 3 2 1 4 3 2 1 5 4 3 2 1 3 2 1 CN8 CN7 CN6 CN5 T G A CN3 CN4 1 2 3 4 1 2 3 4 1 2 3 4 3 CN1 1 2 T- D1 D2 + - N U FP R1 R2 R3 C E1 E2 T+ 230V BUS or EDF Not used Generator load shedding Primary circulator control Supplementary valve closure control Supplementary valve opening control Not used 230 VAC power supply A G C T = Boiler control LED = Generator control LED = Communication BUS LED = Elec. utility load shedding Téléinfo LED (flashes if not connected) EDF = (Electricité de France) - electrical utility (*) Potential-free, normally-open contact (**) Alarm on contact opening (***) For the reversible floor application 7.3 - BOARDS ZONE A2 AND A3 Enables control of the control valve (230 V output, 3 points - proportional action) and the circulating pump of each zone. Connected to the heating board and to the control box via the communication BUS. There is one board per zone. C BUS + - 3-point valve control output, 230 Vac Y2 N Y1 U N 230 VAC power supply C = Communication bus LED Y1 = Valve opening control LED Y2 = Valve closing control LED P = Circulating pump control LED Z2 Z1 Y2 Y1 P S5 C S4 C A4 P2 P1 Zone ambient temperature sensor Zone circulating pump control outlet Zone water outgoing sensor Zone valve contact (closed if the valve is closed) 7.4 - TEMPERATURE SENSORS Type CTN 10 KΩ at 25 C. Temperature ( C) Ohmic value (Ohm) Temperature ( C) Ohmic value (Ohm) -20 97 120 30 8 058-15 72 980 35 6 532-10 55 340 40 5 326-5 42 340 45 4 368 0 32 660 50 3 502 5 25 400 55 2 936 10 19 900 60 2 488 15 15 710 65 2 082 20 12 490 70 1 751 25 10 000 11

8 - OPERATION The operating modes are selected using the rotary knob on the front of the control unit (see chapter 7.1 and user's manual). 8.1 - HEATING MODE 8.1.1 - HEATING OPERATING DIAGRAM Water temperature setpoint A water rule is determined for each zone. An outside temperature X determines a water temperature resulting setpoint Y1 for zone 1 and Y2 for zone 2. The parameters determining this water rule can be set by the installer (see the table in paragraph 8.7). The resulting setpoint for zone 1 is displayed at parameter 4. The resulting setpoint for zone 2 is displayed at parameter 5. If required, each resulting setpoint can be corrected depending on the ambient temperature of the zone and the automatic slope correction (see paragraph 8.1.5). The generator is controlled according to the highest resulting setpoint. The control valve of each zone is controlled according to the resulting setpoint of the zone. Max. water temp. Z1 (parameter 30) Max. water temp. Z2 (parameter 31) Min. water temp. (parameter 32) Min. water temp. (parameter 33) Generator shutdown threshold (parameter 20) 2K Y1 Y2 Z1 Z2 Regional min. temperature (parameter 21) Supplementary heating authorization threshold (parameter 22) Generator authorization Supplementary heating authorization 2K Activation Zone 1 (pump + valve) Activation Zone 2 (pump + valve) X Water temperature resulting setpoint slope in Zone 1 2K Outside temperature No heating setpoint (parameter 23) If generator alarm or if generator prohibited due to excessively cold water Water temperature resulting setpoint slope in Zone 2 Primary pump 8.1.2 - "COMFORT" HEATING MODE Water temperature setpoint - The circulating pump of each zone is actuated and the control valve activated if the outside temperature is less than the non-heating temperature. - The heating can operate only if the outside temperature is less than the non-heating temperature. - A water rule is determined for each zone according to the settings that are specific to the zone. A resulting setpoint of the water temperature is calculated according to the outside temperature and the ambient temperature of the zone. The control valve is controlled by the zone board according to this resulting setpoint and the water temperature read by the sensor placed on the outlet of the zone considered. - The generator and the make-up unit, if installed, are thus controlled by the installation's water return temperature according to the following: the highest resulting setpoint of the 2 zones for the 2 floor zone application. the highest resulting setpoint of the 2 zones less 5 degrees for the 2 mixed zone application. For each zone, the water rule is determined by: - the non-heating temperature (parameter 23), - the regional minimum temperature (parameter 21), - the minimum temperature of the water circuit (parameters 32 for zone 1, 33 for zone 2), - the maximum temperature of the water circuit (parameters 30 for zone 1, 31 for zone 2). The resulting setpoint calculated in this manner can be corrected by the ambient temperature of the zone: A difference of +/- 1 degree of ambient temperature in relation to the heating setpoint temperature of the zone (adjustable from 15 to 25 C) causes the resulting setpoint (water temperature) to decrease or increase of 2 degrees, respectively. However, this variation cannot exceed +/- 4 degrees. 12

In addition, a self-adapting system (if activated by the parameter P74) automatically adjusts the heating slope of each zone according to the difference between the setpoint (ambiance) and ambient temperature. See details in paragraph 8.1.5. If the installation's water temperature exceeds the generator setpoint value, it shuts down and heating is provided by the boiler only. Caution: Make sure that the boiler setpoint allows the water temperature of the resulting setpoint to be obtained. Supplementary valve activation and boiler authorisation - The supplementary heating via the boiler is activated if the generator is not able to maintain the installation's water return temperature at the calculated value (resulting set point). - Caution: During normal operation, supplementary heating is authorised only if the outside temperature drops below the authorisation threshold (parameter 22). However, it may be authorised for higher temperatures if the generator is unavailable (due to an alarm, safety cut-out or load shedding). In case of an unavailable boiler alarm, the supplementary valve is closed and the boiler is not authorised. Alternative generator / boiler operation: If this type of operation is selected (parameter 72 = 0), simultaneous operation of the generator and supplementary heating is prohibited: if the outside temperature is below the authorisation threshold (parameter 22), the generator shuts down and heating is ensured only by the boiler. Supplementary heating control shift (parameter P40) Resulting setpoint Boiler supplementary activation Generator command Water temperature Generator operating safety features in heating mode - A safety device on the water temperature (installation return) prohibits generator operation if this temperature is below the thermodynamic heating authorization threshold (parameter 36). In this case, only the boiler is authorised to raise the water temperature and allow the generator to function, regardless of the outside temperature. The activation of this safety feature is indicated by the flashing of the display. - Generator operation is prohibited if the outside temperature is below the generator's shut-off threshold (parameter 20). Only the boiler is authorised. In order to guarantee a minimal thermal load, the generator can only operate if at least one zone is activated (circulating pump in operation and valve open). 8.1.3 - "ECONOMY" HEATING MODE The switch to "ECO" mode lowers the ambient temperature setpoint by a value than can be adjusted from 1 to 6 K (parameter 24). It can only be activated in heating mode (inactive in cooling mode). Switching from "Comfort" to "ECO" is accomplished either by hourly programming, weekly programming by zone or by actuating the rotary knob for the entire installation. In the case of hourly programming, the user can activate a temporary override (1 hour + periods of 1 hour during the current day) per zone. 8.1.4 - "ANTI-FREEZE" HEATING MODE (prolonged absence) Selection for the 2 zones is made using the rotary knob on the control unit. Anti-freeze mode ambient temperature setpoint The resulting water temperature setpoint shifts to an adjustable value through parameterisation: - for the 2 Mixed zone application: Zone activation. parameter 28 for zone 1, Floor (factory set at 25 C),. parameter 29 for zone 2, Radiators (factory set Ambient temperature at 35 C). - for the zone 2, Floor application:. parameter 29 for both zones (factory set at 25 C). Each zone can only be activated (circulating pump and control valve) if the ambient temperature of the zone is less than the anti-freeze ambiance setpoint, adjustable via parameter 25. If the ambient temperature of the zone rises above this threshold, the circulating pump stops (after a 1 minute delay) and the valve is closed. In order to guarantee a minimal thermal load, the generator can only operate if at least one zone is activated (circulating pump in operation and valve open). 13

8.1.5 - SELF-ADAPTING HEATING SLOPE System activated by parameter 74 = 1. Principle: the theoretical slope calculated according to the parameters of the control equipment is automatically corrected by the system by adding (or subtracting) a correcting coefficient (the value of which is displayed in parameter 90). This coefficient is determined by analysing, in terms of a 24-hour continuous operating period in "Comfort" heating mode, the behaviour of the ambient temperature in relation to the setpoint temperature (in "Comfort" mode). This analysis is also weighted by the difference between the setpoint and the outdoor temperature. The calculation of the correction coefficient is performed separately for each zone. Example: (P) = Theoretical slope (P + K) = Slope increased with ambient temperature below the setpoint (P - K) = Slope decreased with ambient temperature above the setpoint Note: Regardless of the slope, the resulting setpoint cannot exceed the maximum temperature value of the water (parameters 30 and 31) (possibly corrected according to the ambient temperature). Example: To adjust the following parameters:. Parameter 21 = 0 C. Parameter 23 = 20 C. Parameter 30 = 60 C. Parameter 32 = 30 C 60-30 Theoretic slope value P = = 1.50. 20-0 Max. water temperature (parameters 30 and 31) Min. water temperature (parameters 32 and 31) Water temperature If the value of the coefficient K read on parameter 90 is 10 (hundredths), the actual slope becomes: P + K = 1.50 + 0.10 = 1.60. The value of this coefficient is reset in the event of: - deactivation of the system by parameter 74, - re-initialisation of the parameters by parameter 60, - an application change by parameter 70. 8.2 - COOLING MODE Active only for the Heating / Cooling reversible Floor. - Parameter 71 set at 1 (reversible). Selection is made using the rotary knob on the control unit. During mode selection, the supplementary valve is closed (to isolate the boiler circuit). Furthermore, in the case of the Mixed application, zone 2, Radiators is deactivated (valve closed and zone circulator off) so as not to convey cold water into the radiators. The generator operates with its own water temperature setpoint (recommended setting: 22 C installation return). Each zone can only be activated (circulating pump and control valve) if the ambient temperature of the zone is greater than the Cooling ambient temperature setpoint zone's setpoint. At this moment, the zone valve adjusts the water temperature of the floor outgoing line according to an adjustable setpoint (parameter 34 is factory-set at 20 C). If the ambient temperature of the zone drops below this Zone activation threshold, the circulating pump stops (after a 1 minute delay) and the valve is closed. Ambient temperature In order to guarantee a minimal thermal load, the generator can only operate if at least one zone is activated (circulating pump in operation and valve open). Furthermore, in order to avoid unnecessary energy dissipation, the primary circuit's circulator is controlled only if at least one zone is activated. Generator operating safety features in cooling mode - Generator operation is prohibited if the installation return water temperature is above a threshold (parameter 35). The activation of this safety feature is indicated by the flashing of the display. - An "anti-condensation" device on the installation's return temperature prohibits generator operation if this temperature is below 18 C. - Generator operation is prohibited if the supplementary valve or the radiator zone valve are not closed. In this case, the "VA" alarm message is displayed. (P) (P-K) Regional min. temperature (parameter 21) Peak limiting (P+K) Outside temperature Heating authorisation threshold (parameter 23) 14

8.3 - FORCING OF CONTROL OUTPUTS Forcing: for maintenance operations only, when the system is "OFF", it is possible to force the control of the following outputs by setting to parameter to "1": - parameter 64: primary circulator - parameter 65: zone 1 (circulator pump on + valve open) - parameter 66: zone 2 (circulator pump on + valve open) - parameter 67: generator - parameter 68: heating / cooling inversion output shut down (for reversible floor only) - parameter 69: supplementary boiler Caution: At the end of the operation, forcing must be deactivated (by returning the parameters "0") before restarting the installation. 8.4 - GENERATOR LOAD SHEDDING This can be done: - either by a potential-free contact, - or from a " Tele-Info signal sent by the electrical utility meter (per specification EDF HN 44-S-81). Restricts the operation of the generator (in heating mode and in cooling mode). Signalled by icon on the display unit. 8.5 - ZONE VALVES CONTROL Ensured by zone A2 and A3 boards. - Valve in mixed operation (see hydraulic diagram, paragraph 4). - The control issues a 230 VAC chronoproportional 3-point control signal (opening/closing).. Time base = Valve action time (parameter 63) 10 Difference (setpoint/ water outlet temperature). Percentage of the control time = Proportional strip (parameter 38) This percentage is displayed at parameter 17 for zone 1 and 18 for zone 2, ("+" sign = open, " " sign = closed) In the neutral zone (parameter 39), the valve is not controlled. - Valve motors designed to accept opening and closing orders permanently. - The valves must be equipped with a limit switch detecting the "Valve closed" position. (Valve closed = contact closed - to be connected on the corresponding zone board). 8.6 - CIRCULATOR PUMPS 8.6.1 - GENERAL Circulator pump shutdown is delayed 1 minute. A degripping device allows the circulating pumps to start automatically, for 3 seconds, every 24 hours, if they are off. The circulators must have their own thermal protection (not supplied). 8.6.2 - PRIMARY CIRCULATOR PUMP In heating mode (Comfort / ECO / anti-freeze), the primary circulator is actuated if the outside temperature is below the non-heating threshold. In cooling mode, it is actuated if at least one zone is activated (zone pump in operation, zone valve open). 8.6.3 - ZONE CIRCULATORS In heating mode (Comfort / ECO), the circulators are actuated if the outside temperature is below the non-heating threshold. In anti-freeze heating mode and in cooling mode, the circulators are controlled according to the ambiance demand. 8.6.4 - GENERATOR CIRCULATOR The circulating pump built into the generator is factory-set to operate constantly as soon as generator power is on. It is possible to operate this circulating pump only when the generator is controlled by this system. To do this, on the generator's ECH regulator, change parameter H20 to 4 (see generator manual). 15

8.7 - PARAMETERS Access: - 2 access levels: - Level 1, read only, with direct access for parameters 1 to 19, - Level 2, ("technical level") accessible by password ("see last page"). This level is entered via parameter 20, although all parameters are accessible. Procedure: 1 ) Simultaneously press and hold the buttons and for 5 seconds, until the screen displays PArA. 1: User 2: Installer 2 ) Select the User menu = Level 1 or Installer = Level 2 using the and buttons. 3 )* To access level 1, press Z/OK. The display indicates the first parameter P01. Press the or keys to shift from one parameter to another. To know the value of the parameter, press Z/OK. To redisplay the value of the parameter, press Z/OK again. Access to the 1 st parameter (P01) Display of the parameter value 3Bis )* To access level 2, press Z/OK. The display shows. Enter the password digit by digit, by selecting the desired digit using the or buttons and by confirming with Z/OK. Once the password is entered, the display then indicates P20 which is the first parameter of this level. To display the value of a parameter, select it using the or keys and press Z/OK. To modify this parameter, if needed, press keys or. To redisplay the value of the parameter, press Z/OK again. 4 ) To exit the parameterisation procedure, press and hold Z/OK. In all cases, the display returns to normal automatically after a few minutes of inactivity. The parameters can be accessed and modified both in operation and when shut down, except for those for installation configuration and default parameterisation which can only be accessed and modified when the installation is shut down. Note: The flashing parameter values are those that can be modified. Otherwise, the display remains steady. Configuration of installation type IMPORTANT: THE FOLLOWING ELEMENTS MUST BE CARRIED OUT EACH TIME THE INSTALLATION IS PLACED INTO SERVICE - Set parameter 70 according to the application:. P70 = 4 for 2 Mixed Floor + Radiator zones application.. P70 = 5 for 2 Floor zone application. - Procedure: 1) Set the rotary knob on the control unit to the "Stop" position. 2) Go to parameter 70. Press the "Z/OK" button; the value of the parameter is displayed. This value may be read or modified using the and buttons if the system is in the "Stop" position. If parameters are modified, an initialisation process is launched automatically (the "init" message is displayed). When initialisation is completed, the display returns to parameter 70. Note: If this parameter is set in other than the "Stop" position, the "STOP" message flashes and the parameter cannot be modified. 3) Check and adjust the other configuration parameters, as required: Parameter 71 = 1 if reversible heating / cooling floor. Parameter 72 = Simultaneous generator and supplementary heating operation. Parameter 73 = Location of the ambient temperature sensor. Parameter 74 = Heating slope self-adaptation activation. 4) Once the configuration parameters have been verified, disconnect and re-establish the system's power supply to reset the control system. 16

Default configuration - This enables the default values (see list) of all parameters to be reset according to the type of installation. - Procedure: - Set the rotary knob on the control unit to the "Stop" position. - Go to parameter 60. Press the "Z/OK" button; the "init" message is displayed. Note: If this parameter is set in other than the "Stop" position, the word "STOP" flashes and the configuration cannot be launched. - Press and hold the "Z/OK" button for 5 seconds to launch the default configuration. The "init" message flashes. When initialisation is completed, the display returns to parameter 60. Calibration of temperature sensors ("Offset") - The value displayed by certain sensors may be adjusted. To do this, move to the corresponding parameter and enter the desired value (+/- 3 degrees maximum). Mixed Floor + Radiator 2 zones No. Designation Access Range Value / Default Status: 01 Outside temperature D -40 / +90 C 02 Installation return water temperature D -40 / +90 C 03 (not used) 04 Water temperature resulting setpoint, zone 1 D 15 / 55 C 05 Water temperature resulting setpoint, zone 2 D 15 / 80 C 06 Water temperature, zone 1, floor outlet D -40 / +90 C 07 Water temperature, zone 2, radiator outlet (***) D -40 / +90 C 08 Temperature ambiante zone 1 D -40 / +90 C 09 Temperature ambiante zone 2 (***) D -40 / +90 C 10 Generator control output status D 0/1 Read only 11 Generator mode output status (Heating / Cooling) (1 = Heating) (*) D 0/1 12 Supplementary valve opening control output status D 0/1 13 Supplementary valve closing control output status D 0/1 14 Primary circulating pump control output status D 0/1 15 Outlet status, circulator zone 1 D 0/1 16 Outlet status, circulator zone 2 D 0/1 17 Zone 1 valve control output status D -100/0/+100% 18 Zone 2 valve control output status D -100/0/+100% Air temperature settings: 20 Generator shut-down threshold (outside temperature) T -15 / +5 C -5 C 21 Regional min. temperature (outside temperature) T -20 / +5 C -7 C 22 Supplementary authorization threshold (outside temperature) T -5 / +20 C 5 C 23 No heating threshold (outside temperature) T 10 / 25 C 17 C 24 Lowering of ECO temperature (ambiante) T 1 / 6K 2K 25 Anti-freeze ambiance setpoint T 8 / 18 C 12 C Water temperature settings: 28 Water temperature setpoint in "anti-freeze" mode (Floor outgoing line) T 20 / 40 C 25 C 29 Water temperature setpoint in "anti-freeze" mode (Radiator outgoing line) T 20 / 50 C 35 C 30 Heating water max. temperature, zone 1, floor (outgoing line) T 25 / 50 C 40 C 31 Heating water max. temperature, zone 2, radiators (outgoing line) T 25 / 75 C 60 C 32 Heating water min. temperature, zone 1, floor (outgoing line) T 20 / 35 C 25 C 33 Heating water min. temperature, zone 2, radiators (outgoing line) T 20 / 50 C 30 C 34 Zone outgoing line cooling water temperature setpoint (*) T 15 / 25 C 20 C 35 Cooling authorisation threshold (return) (*) T 25 / 50 C 30 C 36 Thermodynamic heating authorization threshold (return) T 10 / 20 C 15 C 37 Floor water outlet max. temperature alarm threshold T 50 / 80 C 55 C 38 Zone valve control proportional strip T 1 / 10K 5K 39 Zone valve control neutral zone T 1 / 3K 1K 40 Supplementary control shift T 1 / 10K 3K Sensor: 50 Outside sensor T + or - 3K 0 51 Zone 1 ambient temperature sensor T + or - 3K 0 52 Zone 2 ambient temperature sensor T + or - 3K 0 53 Installation return water temperature sensor T + or - 3K 0 54 (not used) 55 Zone 1 outgoing water temperature sensor T + or - 3K 0 56 Zone 2 outgoing water temperature sensor T + or - 3K 0 57 (not used) 17

Mixed Floor + Radiator 2 zones (cont'd) No. Designation Access Range Value / Default Miscellaneous and maintenance: 60 Default configuration T Init 61 TYPHONE language selection (1 = F ; 2 = ) T 1 / 2 1 62 TYPHONE access code T 0 / 9999 1234 63 Zone valve action time T 60 / 300 sec. 100 seconds 64 Primary circulating pump control forcing T 0 / 1 0 65 Circulator forcing and zone 1 valve opening T 0 / 1 0 66 Circulator forcing and zone 2 valve opening T 0 / 1 0 67 Generator control forcing T 0 / 1 0 68 Heat / Cool outlet off (1 = Heat) (*) T 0 / 1 0 69 Supplementary valve opening forcing T 0 / 1 0 Configurations: to regulate with 70 Installation type T 1 / 5 1 1 = 1 radiators zone 2 = 1 radiators zone with proportional control valve 3 = 1 floor zone with proportional control valve 4 = 2 mixed zones (floor + radiators) ------------------------------- ----------------------------------- -------------- > 4 5 = 2 floor zones 71 Reversible floor (1 = reversible Heating / Cooling) T 0 / 1 0 72 Simultaneous generator + boiler operation (1 = simultaneous) T 0 / 1 1 73 Remote zone 1 ambient temperature sensor in control box (1 = yes) T 0 / 1 1 74 Slope self-adaptation activation / deactivation (1 = Activated) T 0 / 1 1 Software versions: Read only 80 Control unit T 81 Heating board T 82 Board zone 1 T 83 Board zone 2 T Correction coefficients: Read only 90 Zone 1 self-adaptation correction coefficient (**) T 91 Zone 2 self-adaptation correction coefficient (**) T Correction coefficients: Cooling setpoint zone 1 (*) D 20 / 30 C 25 C Heating setpoint zone 1 Direct 15 / 25 C 20 C Heating setpoint zone 2 access 15 / 25 C 20 C (*) Appears only if reversible floor ( P71 = 1) (**) Does not appear if P74 = 1 (***) Does not appear in cooling mode as it concerns the radiator circuit D = access without password T = access with password 2 Floor zones No. Designation Access Range Value / Default Status: 01 Outside temperature D -40 / +90 C 02 Installation return water temperature D -40 / +90 C 03 (not used) 04 Water temperature resulting setpoint, zone 1 D 15 / 55 C 05 Water temperature resulting setpoint, zone 2 D 15 / 55 C 06 Water temperature, zone 1, floor outlet D -40 / +90 C 07 Water temperature, zone 2, floor outlet D -40 / +90 C 08 Temperature ambiante zone 1 D -40 / +90 C 09 Temperature ambiante zone 2 D -40 / +90 C 10 Generator control output status D 0/1 Read only 11 Generator mode output status (Heating / Cooling) (1 = Heating) (*) D 0/1 12 Supplementary valve opening control output status D 0/1 13 Supplementary valve closing control output status D 0/1 14 Primary circulating pump control output status D 0/1 15 Outlet status, circulator zone 1 D 0/1 16 Outlet status, circulator zone 2 D 0/1 17 Zone 1 valve control output status D -100/0/+100% 18 Zone 2 valve control output status D -100/0/+100% 18

2 Floor zones (cont'd) No. Designation Access Range Value / Default Air temperature settings: 20 Generator shut-down threshold (outside temperature) T -15 / +5 C -15 C 21 Regional min. temperature (outside temperature) T -20 / +5 C -7 C 22 Supplementary authorization threshold (outside temperature) T -5 / +20 C 7 C 23 No heating threshold (outside temperature) T 10 / 25 C 17 C 24 Lowering of ECO temperature (ambiente) T 1 / 6K 2K 25 Anti-freeze ambiance setpoint T 8 / 18 C 12 C Water temperature settings: 29 Water temperature setpoint in "anti-freeze" mode (outgoing) T 20 / 40 C 25 C 30 Heating water max. temperature, zone 1 (outgoing) T 25 / 45 C 35 C 31 Heating water max. temperature, zone 2 (outgoing) T 25 / 45 C 35 C 32 Heating water min. temperature, zone 1 (outgoing) T 20 / 30 C 20 C 33 Heating water min. temperature, zone 2 (outgoing) T 20 / 30 C 20 C 34 Zone outgoing line cooling water temperature (*) T 16 / 25 C 20 C 35 Cooling authorisation threshold (return) (*) T 25 / 50 C 30 C 36 Thermodynamic heating authorization threshold (return) T 10 / 20 C 15 C 37 Floor water outlet max. temperature alarm threshold T 50 / 80 C 55 C 38 Zone valve control proportional strip T 1 / 10K 5K 39 Zone valve control neutral zone T 1 / 3K 1K 40 Supplementary control shift T 1 / 10K 3K Sensor: 50 Outside sensor T + or - 3K 0 51 Zone 1 ambient temperature sensor T + or - 3K 0 52 Zone 2 ambient temperature sensor T + or - 3K 0 53 Installation return water temperature sensor T + or - 3K 0 54 (not used) 55 Zone 1 outgoing water temperature sensor T + or - 3K 0 56 Zone 2 outgoing water temperature sensor T + or - 3K 0 57 (not used) Miscellaneous and maintenance: 60 Default configuration T Init 61 TYPHONE language selection (1 = F ; 2 = ) T 1 / 2 1 62 TYPHONE access code T 0 / 9999 1234 63 Zone valve action time T 60 / 300 sec. 100 seconds 64 Primary circulating pump control forcing T 0 / 1 0 65 Circulator forcing and zone 1 valve opening T 0 / 1 0 66 Circulator forcing and zone 2 valve opening T 0 / 1 0 67 Generator control forcing T 0 / 1 0 68 Heat / Cool outlet off (1 = Heat) (*) T 0 / 1 0 69 Supplementary valve opening forcing T 0 / 1 0 Configuration: To regulate with 70 Installation type T 1 / 5 1 1 = 1 radiators zone 2 = 1 radiators zone with proportional control valve 3 = 1 floor zone with proportional control valve 4 = 2 mixed zones (floor + radiators) 5 = 2 floor zones ----------------------------------------------------------- -------------- ------------------- ---------------> 5 71 Reversible floor (1 = reversible Heating / Cooling) T 0 / 1 0 72 Simultaneous generator + boiler operation (1 = simultaneous) T 0 / 1 1 73 Remote zone 1 ambient temperature sensor in control box (1 = yes) T 0 / 1 1 74 Slope self-adaptation activation / deactivation (1 = Activated) T 0 / 1 1 Software versions: Read only 80 Control unit T 81 Heating board T 82 Board zone 1 T 83 Board zone 2 T Correction coefficients: 90 Zone 1 self-adaptation correction coefficient (**) T Read only 91 Zone 2 self-adaptation correction coefficient (**) T Read only Ambience setpoints: Cooling setpoint zone 1 (*) Heating setpoint zone 1 Cooling setpoint zone 2 (*) Heating setpoint zone 2 D Direct access 20 / 30 C 15 / 25 C 20 / 30 C 15 / 25 C (*) Appears only if reversible floor ( P71 = 1) (**) Does not appear if P74 = 1 D = access without password 19 T = access with password 25 C 20 C 25 C 20 C

8.8 - ALARMS The alarms are indicated by a message flashing alternately on the display. Generator fault (time delay 15') ALARM CODE ACTION RESET Gr (***) In heating mode: Suppression of the heating authorization threshold according to the outside temperature. In Cooling mode: no action Auto Boiler unavailable HE Supplementary valve closure (and suppression of supplementary authorisation) Auto Outside air sensor fault SAE Heating: Operation in Anti-freeze mode (but with no condition on the outside temperature). Cooling: no action Auto Installation return water sensor fault SEin System shut-down Auto Outlet water sensor fault zone 1 SE1 Deactivation, zone 1 (*) (+ system shutdown in cooling mode for 2 Mixed zones application) Auto Outlet water sensor fault zone 2 SE2 Deactivation, zone 2 (*) Auto Ambience sensor fault zone 1 SA1 Deactivation, zone 1 (*) (+ system shutdown in cooling mode for 2 Mixed zones application) Auto Ambience sensor fault zone 2 SA2 Deactivation, zone 2 (*) Auto Communication fault, zone 1 board Cn1 (**) Deactivation, zone 1 (*) (+ system shutdown in cooling mode for 2 Mixed zones application) Auto Communication fault, zone 2 board Cn2 (**) Deactivation, zone 2 (*) (+ system shutdown in cooling mode for 2 Mixed zones application) Auto Communication or system fault Cn System shut-down Auto Supplementary valve or Radiator zone valve open in cooling mode on reversible Floor VA Unit off (in cooling mode) Auto Zone 1 outgoing line water temperature max. fault (adjustable threshold, parameter 37 -Time delay 30") te1 Deactivation, zone 1 (*) (+ system shutdown in cooling mode for 2 Mixed zones application) Manu Zone 2 outgoing line water temperature max. fault, Floor (adjustable threshold, parameter 37 - Time delay 30") te2 Deactivation, zone 2 (*) Manu (*) Zone deactivation = circulator off + valve closed. (**) The sum of Cn1 + Cn2 alarms shuts down the system. (***) Check the nature of the alarm on the generator. Manual resetting by turning the system OFF, once the source of the fault is cleared. Automatic reset: the alarm disappears when the source of the fault is corrected. Note: The alarms are displayed even if the system is shutdown. If several alarms occur simultaneously, the various codes are displayed alternately. 20