Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca Carey J. Simonson, PhD, PEng University of Saskatchewan http://www.engr.usask.ca/dept/mee carey.simonson@usask.ca David A. Torvi, PhD, PEng University of Saskatchewan http://www.engr.usask.ca/dept/mee david.torvi@usask.ca KEYWORDS: HVAC, heat and moisture transfer, experimental testing, radiant ceiling panel, porous membrane, indoor relative humidity, test facility design. SUMMARY: Radiant ceiling panels have been shown to be an effective alternative to all-air systems to maintain the operative temperature in a space. Radiant panels use water flowing through pipes to transfer heat by convection and radiation to maintain the indoor temperature. When radiant panels are used the flow rate of supply air can be drastically reduced as the flow rate only needs to meet ventilation and latent load requirements. This saves energy, capital costs and space as the size of fans and ductwork can be reduced. A disadvantage of using current radiant ceiling panel technology is the lack of control of the latent load in the space. The aim of this research is to create a new ceiling panel that can transfer both heat and moisture to maintain temperature and relative humidity (RH) in a space. The newly designed heat and moisture transfer panel (HAMP) will be constructed from a porous membrane and contain a flowing aqueous salt solution. This will allow for moisture transfer between the panel and the space air, helping to maintain the RH levels in the space. This paper focuses on the design of the new experimental test facility and preliminary results obtained from the experiments. The test facility delivers air at a desired RH past the HAMP. The temperature and RH of the air before and after the HAMP are measured, as well as the temperature of the liquid in the HAMP. Initial tests are performed with stationary water, with and without a porous membrane. The preliminary data presented in this paper show that the test facility is functioning properly and can be used to measure heat and moisture transfer between flowing air and the HAMP. 1. Introduction When designing heating, ventilating and air conditioning (HVAC) equipment for buildings, it is important to consider the comfort of the occupants in the building. Occupant comfort is mainly affected by the operative temperature of the space, but can also be affected by other aspects, such as RH of the air and air velocity. All-air systems supply air that has been heated or cooled, to control the temperature of the space. To meet the ventilation requirements of ASHRAE Standard 62 (2007), a portion of this supply air must come from outdoor air. In some cases, the supply air may consist of only 10-20% outdoor air, while the rest is return air from the building. This mixed air is then heated or cooled to the desired temperature before being supplied to the space by large fans. Heat and moisture are transferred to the space air from the conditioned supply air. These systems can consume large amounts of energy through heating, cooling and fan power. One alternative to an all-air system is radiant panels.
Radiant ceiling panels respond quickly to load changes and are used for both heating and cooling, which makes them ideal for large commercial spaces. The lightweight metal panel is attached to a series of pipes through which heated or chilled water is pumped. The temperature in the space is maintained through heat transfer by a combination of radiation and convection as opposed to convection only, as in all-air systems. Since space heating and cooling is accomplished by transporting water through pipes in the radiant ceiling panel, the amount of air supplied to the space can be reduced to meet ventilation and dehumidification requirements. With a smaller amount of supply air necessary, the size of the ducts and fan used to supply the air can be scaled down. In new constructions, the smaller ducts allow smaller plenums and overall building cost savings. Smaller fans reduce the total fan power, as well as the noise associated with the fan. The use of radiant ceiling panels also reduces drafts in the space because of the lower airflow rates (ASHRAE, 2004). Many researchers have studied the applications of radiant cooling panels. Vangtook and Chirarattananon (2006) performed experiments on a test room equipped with a radiant cooling panel on the ceiling and one on the western wall, located below a window. The results from the experiments were compared with a computer simulation program that was used to calculate comfort levels of the occupants. The results show that a radiant panel can be used to achieve thermal comfort in hot and humid climates. Kim et al. (2005) performed field measurements on an office in Japan. They used a Computational Fluid Dynamics model to analyze the indoor environment of the office for three cases: cooling panel with all-air system for ventilation, all-air cooling system and cooling panel with natural ventilation. In all cases, the latent load was ignored. The results of this research show that more radiant heat is transferred between a cooling panel and a human than an all-air system. They also found that the cooling panel system kept the mean radiant and operative temperatures lower than the all-air system. Imanari et al. (1999) performed experiments to determine the effect of radiant ceiling panels on thermal comfort, compared to an all-air system, in a meeting room. An air-handling unit was used to meet the latent load and provide ventilation during the tests with the ceiling panels. The experiments were performed with human subjects who were present in the room for at least one hour and given a questionnaire to fill out about their comfort. They found that the radiant panels created a more comfortable work place than an all-air system for both genders. They also found that the mean radiant temperature of the space was lower, there was a smaller vertical temperature gradient in the space and the mean air velocity was lower. All of these factors improved the comfort of the occupants and resulted in a smaller percent dissatisfied with the radiant panels. They also performed numerical simulations to determine the energy consumption of the radiant panels. From these simulations, they found that the air transport energy was reduced by 20% and the total energy consumption was reduced by 10%. Brunk (1993) also found that total energy consumption was reduced with the use of radiant ceiling panels, as compared to a variable volume system. It was found that electrical power requirements for fans and pumps decreased by 36%. The total energy cost was reduced by 22% when using radiant panels with displacement ventilation and by 30% when using radiant panels with ceiling-mounted air outlets. The results also showed that cooling ceilings with high radiation effects and low temperature differences between the cooling medium and the cooling surface could provide high indoor comfort levels. Although there are many advantages to using radiant ceiling panels, one major disadvantage is that they only handle the sensible heating and cooling loads. This means that the dehumidification of the space still needs to be controlled with the supply air. This work focuses on the development of a ceiling panel that can transfer latent energy as well as sensible energy. The work presented in this paper is the first phase of this research: the design of a new test facility to measure the heat and moisture transfer across such a panel. The second phase of this project will be to create a numerical model of the panel. This model will then be validated using the experimental results obtained from this testing facility. The final stage of the project is to integrate this model with the commercial building energy software package TRNSYS. TRNSYS will be used to model an office building in order to determine the effect of this panel on the indoor RH, occupant comfort and overall energy consumption. The simulations will be run using weather data for different locations to compare the performance of the panel in different climates. The new heat and moisture transfer panel (HAMP) is similar to existing radiant panels, except that the panel surface will be made of a porous membrane that is permeable to water vapour but impermeable to liquids. The liquid media that will flow over the membrane will be a salt solution. Salt solutions have lower surface RH and
vapour pressure than water at the same temperature. If the vapour pressure of the salt solution is higher than that of the air, moisture will be transferred to the air, and if the vapour pressure of the salt solution is lower, moisture will be removed from the air. This will allow the HAMP to humidify or dehumidify the air. As with the existing panel, temperature of the liquid entering the HAMP can also be controlled. By creating the panel in this manner, both heat and moisture transfer will occur, thus conditioning the air in the space to acceptable temperature and RH levels. 2. Test Facility The test facility that is described here was created to test the HAMP. The main part of the facility is the test section, which consists of an acrylic tray that is 0.23 m by 0.23 m and 0.03 m deep. It can be used with open water (Fig 1a) or with a porous membrane (Fig 1b). There are four baffles attached to the bottom of the tray. The baffles are 0.006 m wide and are the same height as the tray. The baffles ensure that the liquid media flows well through the tray during tests with moving water. They also help with securing the membrane to the tray as the membrane is glued to the top of the tray, as well as the top of the baffles. Airflow Baffles Airflow Water (a) Figure 1. Schematic of the acrylic tray (a) with open water and (b) with a porous membrane. In order to test the HAMP upside down, an acrylic top was created for the tray. Figure 2 shows the tray and top as they will be oriented for (a) flow over the HAMP and (b) flow under the HAMP. The top has the same dimensions as the tray so that the whole section may be turned upside down with ease. This is necessary so that no alterations have to be made to the ductwork between tests. The section is simply turned upside down to test in the other orientation. The tray and the top are fitted together with pins and taped with aluminum tape to ensure that no air or water passes through the seam. The porous membrane is glued to the top of the tray and is pinched between the tray and the top when in use. This ensures the membrane is affixed tightly to the tray and minimizes the deformation of the membrane due to the weight of the water when the HAMP is turned upside down. The test section was insulated with 0.025 m thick insulation. (b) Porous Membrane
(a) Figure 2. Schematic of the acrylic tray and top with airflow (a) over the tray and (b) under the tray. The air that passes over/under the HAMP is compressed air, which is initially dried to approximately 4% RH. The flow rate of the air is controlled by a mass flow controller. The desired flow rate is set by the user on the computer. The compressed air is humidified by passing some of the air through water tanks. By controlling how much air goes through the tanks, and how much is bypassed around the tanks, the RH of the mixed air can be set to the desired level. For the experiments presented here, the entering air was not humidified. Once the air has been conditioned to the desired RH and temperature, it enters the entrance chamber, seen in Figure 3. The entrance chamber is comprised of several parts, all made of galvanized steel. The dimensions of each part are shown in the schematic. The air enters through a hose with a diameter of 0.05 m and then goes through an expansion into a 0.1 m diameter pipe. The pipe is connected to a diffuser with an area ratio of 27.0 and an included angle (2θ) of approximately 10. The diffuser contains three screens located as shown in Figure 3. The placement of each screen was calculated based on equations found in Mehta (1979). The screens have an open area ratio of 0.45. After the diffuser, the air passes into a settling chamber. The settling chamber is filled with coroplast, a corrugated plastic. When several sheets are stacked together, they resemble a honeycomb. Both the screens and the settling chamber are used to help straighten the flow and ensure there is no flow separation in the tunnel. Diffuser Settling Chamber T and RH Sensor (b) Entry Section Screens to test section Contraction Figure 3. Schematic of the entrance chamber, prior to the test section. After leaving the settling chamber, the air enters a contraction to bring the air down to the desired cross-sectional area of 0.15 m high by 0.23 m wide. This height was chosen so that the height of the airflow in the test section would be large enough to resemble the actual situation in the field (a ceiling panel in a room), but small enough so that the temperature and RH gradients across the height are small. This enables the user to take one measurement of the bulk air temperature or RH. The geometry of the entrance chamber was chosen based on guidelines provided by Mehta (1979). After passing through the contraction, the air enters a long straight section, with a hydraulic diameter of 0.18 m. This entry section is used to ensure the flow is fully developed. Based on flat plate boundary layer theory the entry section should be 0.70 m long for laminar flow and 2.4 m long for turbulent flow, to ensure the boundary layers in each direction have merged. This is taken as an approximate value as the boundary layers will develop faster in a rectangular duct than on a flat plate, due to
interference from the other sides and corners. A generally used rule of thumb to ensure fully developed flow in a long straight section is that the length is greater than ten times the hydraulic diameter (Idelchik, 1986). After considering this, the chosen length was deemed adequate. After leaving the entrance chamber, the air enters into the test section, which was described above. Once the air has passed over/under the HAMP it passes into the exit section, shown in Figure 4. This consists of a straight section and a nozzle. The purpose of this section is to mix the air exiting the test section and allow the measurement of the bulk temperature and RH at the end of this section. The nozzle funnels the flow into a jet as it leaves the exit section to prevent any re-circulation of the air. These pieces are also made of galvanized steel. Straight Section from test section T and RH sensor Exit Nozzle Figure 4. Schematic of the exit section of the test facility. The airflow rate is controlled using a Type 1559A Mass-Flo Controller (MKS, Massachusetts, USA), with a range of 23.6 L/s. The controller has an accuracy of ±1.0% of the full scale measurement. The temperature and RH of the air are measured upstream (1.73 m before the test section) and downstream (0.41 m after the test section) using HMP233 sensors (Vaisala, Helsinki, Finland). The sensors use a HUMICAP sensor, which contains a thin polymer film that absorbs water molecules. As water molecules are absorbed, the capacitance changes and the RH is determined. The sensors have a measuring range of -40 C to 80 C and 0-100% RH and an accuracy of ±0.1 C and ±1% RH (for the range 0-90% RH). The RH sensors are calibrated using a humidity generator (Thunder Scientific Corporation, New Mexico, USA) which has an accuracy of ±1% RH. The temperature of the water is measured using five T-type thermocouples. The thermocouples are calibrated using a 9107 dry cell (Hart Scientific, Utah, USA) which has an accuracy of ±0.1 C. All information is collected using a SCXI 1000 chassis (National Instruments, Texas, USA) connected to a 16-bit data acquisition card. The experimental data is recorded using LabView 7.1 (National Instruments), which is a graphical development software package. This program continuously displays measurements and records them to a text file every 10 s. 3. Data Analysis Preliminary experiments were conducted during the commissioning of the test facility. To determine if the facility is functioning properly mass and energy balances will be performed on the test results. If the mass and energy balance within an acceptable margin of error, the facility is working properly. If they do not balance it is possible that the facility contains some leaks. The test section was first tested using a tray full of water, but no membrane. Tests were performed at two different Reynolds numbers (Re, based on hydraulic diameter), 940 and 5240, which result in airflow rates of 2.8 L/s and 13.9 L/s, respectively. Three tests were performed at a Re of 940 and four at a Re of 5240. Two tests were also run with a membrane at a Re of 940. Table 1 shows the time average inlet and outlet air temperature and RH for each of the tests. Figure 5 shows the upstream temperature and RH of the air throughout the experiment, for both Re. The inlet conditions remained relatively constant throughout the tests, with the temperature varying 0.5 C and the RH varying 1% RH.
Table 1. Average temperature and RH Measurements Made During Tests With and Without Membrane. Reynolds Number Test Number Without Membrane Inlet Temp ( C) Inlet RH (% RH) Outlet Temp ( C) Outlet RH (% RH) 940 1 21.0 5.7 20.3 40.1 940 2 21.1 7.2 20.6 41.7 940 3 20.9 5.1 20.6 40.1 5240 1 21.2 5.1 20.4 16.7 5240 2 21.4 4.7 21.0 10.6 5240 3 21.5 4.5 21.0 13.2 5240 4 20.9 5.2 20.6 13.1 With Membrane 940 1 20.0 7.7 19.7 34.4 940 2 19.7 6.9 19.5 32.4 Figure 5. Upstream air temperature and RH for test 1 with Reynolds number of 940 and 5240. The initial temperature of the water in the different channels ranged from 18.4 C to 19.0 C, for a Re of 940 and from 20.3 C to 21.1 C for a Re of 5240. Figure 6 shows the temperature of each thermocouple through the first test, for a Re of 940. The initial temperature difference between the thermocouples decreases as the time increases. Eventually, the temperature of each thermocouple reaches a steady state value of approximately 17.9 C. In the higher Re test, the water reaches a steady state value of 17.3 C. In the test with the membrane, the water reaches a steady state value of 17.0 C. The time that the experiment takes to reach steady state is determined by the temperature of the water. When this temperature stops changing, steady state has been achieved. From these tests it appears that steady state is achieved after approximately 12 hours for the Re, 17 hours for the higher Re and 13 hours for the test with the membrane.
Figure 6. Temperature of the water measured by the five thermocouples, for a Reynolds number of 940. The change in RH across the test section can be seen in Figure 7, for each of the three conditions. The average change in RH throughout the low Re tests is an increase of 34% RH. The high Re tests have a lot of scatter at the beginning, but the average change in RH throughout most of the tests is 7% RH. The average change in RH for the test with the membrane is about 26% RH. The tests with open water resulted in a decrease in the water level of approximately 2mm. When the membrane was attached it was not possible to tell the height of the water, but to fill the tray back up to the level of the membrane required 70 ml of water to be added. It can be seen from the graph that with a low Re the air is able to pick up more moisture than with a high Re. The air picks up less moisture when the membrane is used, then when it is not used, for the same Re. Figure 7. Difference in Relative Humidity across the HAMP for all three test conditions.
To ensure that the facility is working properly mass and energy balances are performed. For the mass to balance, the mass of water removed from the tank (determined by measuring the change in volume) should be equal to the amount of moisture added to the air. The mass balance agrees to within 5% for the tests with Re of 940 and 5240. The mass balance for the membrane tests agrees to within 15%. This is good agreement for the open water tests. The tests with the porous membrane do not agree so well. More work needs to be put into securing the membrane to the tray to ensure no leakage occurs. The energy balance shows that the change in temperature of the airflow corresponds with the phase change energy required to evaporate the water. The energy balance agreed within 5% for all tests. Since the mass and energy balances agree within reasonable error, it can be concluded that the test facility is operating correctly. 4. Conclusions and Future Work This paper outlines the design of a new test facility used to measure the heat and moisture transfer between flowing air and the newly proposed heat and moisture transfer panel. In the facility, air at a known temperature and RH passes over/under the panel. Moisture and heat are transferred between the liquid in the panel and the air stream to change the RH and temperature of the air downstream of the test section. Preliminary tests have been performed in the commissioning of this facility. Air at room temperature and low RH is passed over a tray full of water. As the air passes over the water, moisture is removed and humidifies the air. The temperature of the water drops approximately 2 C throughout the test. When the water reaches a constant temperature, the test has reached steady state conditions. This occurs after 12 hours for Re of 940, after 17 hours for a Re of 5240 and after 13 hours for a Re of 940 when a porous membrane is used. The RH of the air increased an average of 34% RH for the lower Re, an average of 7% RH for the higher Re and an average of 26% RH when a membrane was used. Mass and energy balances were performed and all agreed within reasonable error. This means that the facility is functioning as expected and can be used to further test the HAMP. To determine the heat and moisture transfer coefficients of the HAMP further tests will be run, with a flowing salt solution instead of stationary water. The salt solution will be heated or cooled to simulate both heating and cooling conditions. In these cases more heat transfer is expected than was found in the tests reported here. To date all of the current tests have been run with the HAMP on the bottom of the test section, but future tests will place the HAMP upside down, on the top of the test section, as a ceiling panel would be used. Tests may also be possible in the vertical position to represent a wall panel. After testing is completed, a numerical model of a HAMP will be created and verified with the experimental results obtained. Simulations will be created in TRNSYS to determine the effect of the panel on indoor air RH, occupant comfort and energy consumption. 5. References ASHRAE (2004). ASHRAE Handbook HVAC Systems and Equipment, SI ed., American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, Georgia, USA, Chapter 6. ASHRAE standard 62.1-2007. Ventilation for Acceptable Indoor Air Quality, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, Georgia, USA. Brunk M.F. (1993). Cooling ceilings - an opportunity to reduce energy costs by way of radiant cooling, ASHRAE Trans., Vol. 99, No. 2, 479-487. Idelchik I.E. (1986). Handbook of Hydraulic Resistance, 2 nd ed., Hemisphere Publishing Corporations, New York, New York, USA, Chapter 4. Imanari T., T. Omori and K. Bogaki (1999). Thermal comfort and energy consumption of the radiant ceiling panel system. Comparison with the conventional all-air system, Energy and Buildings, Vol. 30, 167-175. Kim T., S. Kato, S. Murakami and J. Rho (2005). Study on indoor thermal environment of office space controlled by cooling panel system using field measurement and the numerical simulation, Building and Environment, Vol. 40, 301-310. Mehta R.D. (1979). The aerodynamic design of blower tunnels with wide-angle diffusers, Progress in Aerospace Sciences, Vol. 18, 59-120. Vangtook P. and S. Chirarattananon (2006). An experimental investigation of application of radiant cooling in hot humid climate, Energy and Buildings, Vol. 38, 273-285.