Energy Division Heat-shrinkable joints for halogen-free, flame-retardant and fire-resistand cables up to 1 kv

Similar documents
MXSU - Selection table 3-core Kits / X-section

Energy Division

ATUM: General Purpose Thin Wall Tubing - with Adhesive (Black) Medium Wall: MWTM: General Purpose Medium Wall Tubing

Terminations. Energy Division. Return to Contents

Energy Division. CSJT MV cold shrinkable joint for 3-core cables with resin encapsulation

Section 7: Cable Glands & Duct Seals.

RICS. Insulated adapter termination system for SF 6 -insulated switchgear up to 24 kv

Energy Division. CSJR / CSJH Cold shrinkable straight joints for polymeric insulated cables up to 36 kv

Heat-Shrinkable Termination System for Cables up to 36 kv

Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series. Energy Division

BISG II. Bus Insulator Squirrel Guard. This new and improved isolation guard prevents animal-caused outages in electrical substation equipment.

Energy Division. Raychem Insulation Enhancement Systems

Connecting the World of Power ENERGY DIVISION

RICS. Insulated adapter termination system for SF 6 -insulated switchgear up to 24 kv

Section 4: Medium Voltage Terminations - up to 42kV.

Reliable solutions for electrified railway systems

PolyGarde Metal-Oxide Surge Arresters

Raychem heat-shrinkable medium voltage terminations IXSU-F/OXSU-F for indoor and out door applications for polymeric cables up to 42 kv

Section 5: Medium Voltage Joints - up to 42kV

RELIABLE SOLUTIONS FOR ELECTRIFIED RAILWAY SYSTEMS

Section 8: Switchgear Connections (Straight & Elbows)

Insulation and Protection Enhancing the Reliability of Overhead Power Systems

Raychem Raysulate Insulation Enhancement Systems

Product Specification CAT 6 UNSHIELDED PATCH CORDS

ENERGY PRODUCTS DIVISION. Polymeric Surge Arresters Reliable protection for power equipment upto 800kV

Energy Division. Raychem Raysulate Insulation Enhancement Systems

Raychem Elastomeric Medium Voltage Push-on and Cold-shrink Applicable Terminations TFTI/TFTO

WHITE PAPER: IBS & IBSB ADVANCED

TECK-40 Series 1000V Class Splice for 4/C Armored Teck Power Cables

Energy Division. Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series

Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49. Report Number: EDR-5391 Rev. 0 06/15/05. Approved by: Signature: Date:

Lloyd s Register Type Approval System Test Specification Number 3

Traction Cable Radox 3 GKW

Caledonian Flame Retardant Coaxial Cables

PETROCHEMICAL SOLUTIONS

Energy Division. DAH series (IEEE) Distribution metal oxide surge arrester

AFIREFENIX SZ1-K 0,6/1 kv PH120 (AS+)

Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA0 Series, (IEC)

Section 4: Medium Voltage Terminations - up to 42kV

Cable technology for highest safety requirements

CLEARING MISCONCEPTIONS ABOUT LOW-SMOKE, HALOGEN-FREE CABLES

DNVGL-CP-0401 Edition February 2016

INDUSTRY /// RAIL T-CONNECTOR RSTI-68R-HT RSTI-CC-68R-HT RAIL APPROVED T-CONNECTORS FOR ROLLING STOCK- TYPE C INTERFACE

PRODUCT CATALOGUE Norröna

The Quality Connection. BETAflam Fire Resistant Safety Cables

ENERGY PRODUCTS DIVISION. Enhancing the Reliability of Cable Networks. Cable Accessories for upto 245 kv

IEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission

ZH Low Smoke 0-Halogen Flameretardant Identification Sleeves

Custom-designed and standard Multiconductor (Multicore) Cables

Double insulated, electron-beam cross-linked, halogen free photovoltaic wire sunlight resistant. Single conductor, flame retardant insulation.

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

SolderSleeve Insulated Electrical Termination Devices

Qualification Test Report 1/Jul/2005 Rev. A

600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicores)

THE TRUE FIRE SURVIVAL CABLE

Photovoltaic Cables EN H1Z2Z2-K

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

HVS S 15kV Class

High Performance LSZH Fire Resistant Cable

Adhesives Selection Guide

HEAT SHRINK CABLE ACCESSORIES: A 40 YEARS PROVEN TECHNOLOGY FOR APPLICATIONS IN HARSH ENVIRONMENTS

WILDLIFE AND ASSET PROTECTION

Havells Fire Survival Cables

DNVGL-CP-0402 Edition February 2016

Union County Vocational - Technical Schools Scotch Plains, New Jersey

JGK-MS-2/3 Jacketed Concentric Neutral Cable Mid-Span Grounding Kit

Side Entry Insulation Damage Repair Sleeve (SEIDRS) Raychem Devices Products

INTERNATIONAL STANDARD

600/1000V XLPE Insulated, LSZH Sheathed, Double steel tape Armoured Power Cables (3 Cores)

DNVGL-CP-0399 Edition March 2016

Raychem Link Boxes. Cable Services Limited. Powering the UK

PHOTOVOLTAIC CABLES. Photovoltaic Cable 2000V/1500V Photovoltaic Cable 2000V/1000V

CORFLEX. TYPE MC-HL & MV-105 or MC-HL OIL & GAS CABLES

Fire alarm cables. for highest safety requirements TRADITION INNOVATION PASSION

Energy Division. Raychem Cable Accessories for Nuclear Environments

HVS S Splice Series

CABLES FOR ALARM AND SAFETY SYSTEMS

Catalogue Telecommunication Cables INTRODUCCIÓN

INTERNATIONAL STANDARD

Catalogue. Instrumentation & Control Cables

CMZH Low Smoke 0-Halogen Flame- Retardant Mass Transit Tag

Product Data Sheet Trespa HPL Panels

IEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission

Caledonian Fire resistant Coaxial Cables

Shipboard & Offshore Cables

Generation, Assessment

Catalogue Power Cables

DualGuard Fluoropolymer Barrier FRP Duct. Composites USA. Fluoropolymer Barrier FRP Duct. A Critical Process Systems Group Company LISTED

RF one-step BNC/TNC connectors for coaxial cable termination

TYPE APPROVAL CERTIFICATE

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

IEC NORMAS PUBLICADAS. As normas ISO/IEC já estão relacionadas em normas ISO Publicadas

FIREPRO FIRESTOPPING AND PENETRATION SEALS PRODUCT GUIDE

Overmoulded Cable Assembly Selector Guide

Flexible Power Cable DLO

RAIL /// WIRE & CABLE WHERE THE BEST IDEAS IN RAIL BEGIN

Adhesives Selection Guide

Wire and Cable. For more information on these Tyco Electronics products, visit the following website:

Dryflex FLAM. Halogen-Free Flame Retardant TPEs

State of the Art in Splicing and Terminating Power Cables. Patrick Lyons Electric Power Sales, Inc.

Transcription:

Energy Division http://energy.tycoelectronics.com Heat-shrinkable joints for halogen-free, flame-retardant and fire-resistand cables up to 1 kv R

Heat-shrinkable joints for halogen-free, flame-retardant and fire-resistant cables up to 1 kv The choice of suitable materials for electrical systems is an important factor in preventive fire safety measures. In recent years, considerable attention has been paid to the fire risks associated with cable insulation polymers. While high halogen content materials, for example, have been regarded as being barely inflammable, it has been recognized that they may possess undesirable properties such as smoke and acid gas emission in fire conditions. Intensive development work has resulted in a new generation of halogen-free fire-resistant cables. A jointing system meeting comparable requirements is available from Tyco Electronics Energy Division. Flame-retardancy As primary insulation and cable oversheath replacement, we developed a heat-shrinkable material, Zerohal tubing, that is halogen-free and flame-retardant. A range of established tests, such as Limiting Oxygen Index and Temperature Index, have been carried out to assess the flame-retardancy of this material. The results below show that the performance of Zerohal tubing compares favorably with that of modern flame-retardant cable insulations. Absence of halogens Corrosion damage depends on the amount of acid gases generated when a material is burned, and therefore on the level of halogens and other acidic components in the insulation material. Pyrolytic analyses show only trace quantities of these substances in Zerohal tubing. The low toxicity index rating (NES 713) derived from measurements of these and further combustion products provides additional evidence of the material s suitability for jointing cables meeting special requirements of this kind. Photo 1 Public transport systems now make increasing use of halogen-free, flame-retardant and fire-resistant cables and accessories. Photo 2 Raychem joints for halogenfree, fire-resistant cables were developed in the course of the company s experience in supplying jointing systems for special cables used in North Sea oil and gas exploration. Properties of Zerohal tubing Test Method Typical Results Flame Retardancy ASTM D635 burn time 60 secs extent of burn 15 mm Limiting Oxygen Index ASTM D2863 33.0 Temperature Index NES 715 280 C Acid Gas Generation RK 6717C12.14 0.9 % Smoke Index NES 711CI07.01 32 Toxicity Index NES 713 1.6 10 6 10 5 TPE PCP CSP Smoke generation Low smoke generation The optical smoke density produced by Zerohal tubing in fire conditions has been studied over a range of heat fluxes. The graph allows comparision of visibility with that of the smoke from other polymeric compounds. Relative smoke density 10 4 10 3 10 2 10 1 PVC Polyurethane no visibility Zerohal 5 10 15 20 25 30 Time (minutes)

Fire-resistance To withstand temperatures of 1000 C occuring in fires, the Raychem cable joint employs a combination of Zerohal tubing and fire-resistant glass-fibre/silicone sleeves over the connector insulation and the whole joint area. These ensure that electrical insulation is maintained for at least 3 hours during the fire test. This joint construction has been tested in accordance with IEC 60331-21 and VDE 0472-814. An independent report is available on request. Halogen-free fire-resistant cable joint construction 5 6 7 3 4 4 8 2 1 6 7 3 5 1 2 1 halogen free tubings 2 inner fire-barrier sleeves 3 overall fire-barrier sleeve 4 roll springs 5 outer sealing tubing 6 halogen free tubing 7 copper braid 8 sealant Performance in Fire Conditions Test Test Method Result Flame Retardancy in acc. with IEC 60332-1 and pass VDE 0482-265-2-1. (ABS approval Reg.No.84-MU19468) material test on FCSM outer sealing pass tubing in acc. with IEEE 383 and IECA S-19-81 Fire Resistance functional test in acc. with pass IEC 60331-21 and VDE 0472-814 (FMPA report Subj. 1.6-75054)

Design and construction of Raychem fire-resistant joints 3 4 5 Advantages of heat-shrinkable joint design Compact design The use of halogen-free flameretardant material in the form of heatshrinkable tubing leads to a slim and compact joint design. This simplifies installation in confined areas such as tunnels and vertical shafts, and in all locations where space-saving is of importance. Ease of installation As insulation, sealing and outer protection of the joint are provided by heat-shrinkable tubings, there is no mixing or pouring involved in installation. The curing delays and shelf-life restrictions associated with resins are eliminated. Flame-retardant halogen-free cable joints For applications which do not require retention of electrical insulating properties in fire conditions, Raychem halogen-free cable joints are available without glass fibre/silicone sleeves. Ordering information Raychem halogen-free, flame-retardant and fire-resistant joints are available for all common types of shielded and unshielded power and control cable for voltages up to 1 kv. They are supplied in kit form with detailed installation instructions. Please contact your local sales representative for cable joints specific to your application.

6 1 2 1 Connector insulation The heat-shrinkable insulating tubings are of Zerohal (halogen-free), flame-retardant material. The correct insulation thickness round the connectors is provided automatically. 2 Inner fire-barrier sleeves To ensure continued electrical functioning of the joint during fire tests, high-temperature resistant sleeves made of glass-fibre and silicone are employed over each connector area. 3 Cable bedding replacement A tubing of halogen-free material is shrunk over the joint to restore the cable bedding in this area. 4 Shielding Copper mesh wrapped round the joint area provides electrical continuity and restores the functions of the cable shield. 5 Overall fire barrier The joint area is further protected from flames by an overall glassfibre/silicone barrier. The roll springs that secure the ends of the sleeve to the cable oversheath prevent lateral penetration of flames into the joint. 6 Outer protection and sealing To replace the cable oversheath, an outer sleeve is shrunk down over the completed joint. The shrinking action causes sealant applied to the oversheath ends to melt and flow, sealing out moisture.

Minimum performance for Raychem joints for halogen-free, flame-retardant and fire-resistant cables up to 1 kv Test Sequence Result Insulation Resistance between conductor and 1000 MΩ grounded water bath A.C. Voltage Withstand 4 kv for 15 min no breakdown and no flashover Impulse Voltage Withstand 10 positive and 10 negative, 1.2/50 µs, no breakdown and no flashover 8 kv peak, between conductor and grounded water bath Insulation Resistance repeat 1000 MΩ Load Cycling 63 cycles pass 5 h heating, 3 h cooling Conductor temperature: 95 C Thermal Short Circuit 1 s symmetical fault with no visible signs of damage conductor temperature as for cable specification Load Cycling as above with cable in 1 m water, pass oversheath removed Insulation Resistance repeat 1000 MΩ Impulse Voltage Withstand repeat no breakdown and no flashover D.C. Voltage Withstand 10 kv for 5 min no breakdown and no flashover Notes: 1. All voltages are phase to ground. 2.Further details are given in Raychem specification PPS 3013. All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale. ALR, AMP, AXICOM, B&H, Bowthorpe EMP, Dorman Smith, Dulmison, Hellstern, La Prairie, Morlynn, Raychem, and SIMEL are trademarks. Energy Division a pioneer in the development of economical solutions for the electrical power industry. Our product range includes: Cable accessories, connectors & fittings, electrical equipment, instruments, lighting, insulators & insulation enhancement and surge arresters. Tyco Electronics EPP 0205 9/02 For more information and your country contact person, please visit us at: http://energy.tycoelectronics.com Tyco Electronics Raychem GmbH, Energy Division Finsinger Feld 1, 85521 Ottobrunn/Munich, Germany Phone: ++49-89-6089-0, Fax: ++49-89-6096345