SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperClear 45-HS (patent pending)

Similar documents
PART 1 GENERAL 1.01 SUMMARY

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperLite TM I-XL minute SuperLite TM I-XL IGU minute PART 1 GENERAL

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Temperature Rise Door Framing

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Fire Protective

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Fire Protective

SECTION FIRE-RATED GLASS AND FRAME

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

Objectives. To review updated IBC and fire test requirements when designing for life safety.

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation.

ARBOR SERIES DIVISION FLEXIBLE WOOD VENEER WALLCOVERING

ARBOR SERIES WOOD WALLCOVERINGS

ARCHITECTURAL SPECIFICATIONS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES

Fire-Rated Glazing Changes in 2012 International Building Code (IBC)

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

UFGS (June 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

c. Oko-Tex (European environmental health standard)

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

1. Portable fire extinguishers. 2. Fire-protection cabinets for portable fire extinguishers.

SECTION SECURITY TESTING AND COMMISSIONING

.2 Section Waste Management and Disposal..4 Section Electrical General Requirements.

Architectural Specification Sheet

Leading. Click to edit Master subtitle style. 3M Fire Protection Products Awareness & Introduction to 3M Fire Protection Products

WALLCOVERINGS WALLCOVERINGS

SPECIFICATION: ARGONITE Engineered Fire Suppression System

B. Shop Drawings: For fire protection cabinets. Include plans, elevations, sections, details, and attachments to other work.

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

FIRE & LIFE SAFTEY STANDARD

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DESIGN & CONSTRUCTION GUIDELINES

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

A. Curtains: Provide curtain fabrics with the following characteristics:

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION AUTOMATIC TRANSFER SWITCHES

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

SECTION AIR COILS

FIRE SUPPRESSION SPRINKLER SYSTEM

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

ARCHITECT S SPECIFICATIONS For Commercial Vinyl Wallcoverings

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

SECTION GENERATOR PARALLELING CONTROLS

Linear Heat Detection Engineering Specifications

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

SECTION Fire Pumps

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

DIVISION LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM IN EXISTING ASPHALT/CONCRETE

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

SECTION INTRUSION DETECTION SYSTEM

SECTION ELECTRICAL SYSTEMS COMMISSIONING

Design & Construction Standards, Revised January

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER

Product Guide North & South America

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

NATURAL GAS PIPING

D. Reference Standards (Utilize latest editions available):

SECTION ELECTRIC FLOOR HEATING AND SNOW MELTING EQUIPMENT

SECTION ELECTRIC WATER HEATERS

Product Guide Specification

Design & Construction Standards, Revised January

SECTION ENCLOSED CONTROLLERS

CONTENTS AUTOMATIC TRANSFER SWITCHES

ARCHITECT S SPECIFICATIONS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

Emery County Senior Center Green River 06/07

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS

UFGS (August 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Product Guide Specification

SECTION GYPSUM PLASTER

Code Technologies Committee Report Fire Rated Glazing Group A changes: Fire rated glazing

SECTION AIR DUCT ACCESSORIES

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

Chubb Monitoring Solutions

SECTION INTRUSION DETECTION

Medical devices and electromagnetic compatibility. Addressing the requirements of IEC , 4 th Edition

PORTABLE FIRE EXTINGUISHERS

UFGS (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

White Papers: Delayed Egress Hardware

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER TECHNICAL ASSISTANCE FAX:

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

EMERGENCY PHONE: or (651) (24 hours)

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

Transcription:

Welcome to the SAFTIFIRST TM Guide Specification System prepared as an aid to specifiers in preparing written construction documents. For specification assistance with specific product applications, please contact SAFTIFIRST TM. To download an electronic copy, please visit www.safti.com. PART 1 GENERAL 1.01 SUMMARY SPECIFICATION SECTION 08 8810: FIRE RATED GLASS & FRAMING SuperClear 45-HS (patent pending) A. Section Includes: Fire rated glazing 1. SuperClear 45-HS fire protective, safety rated, clear glazing material. 2. Applications of fire rated glazing include: a. Fire rated glazing as vision lites in door assemblies. b. Fire rated glazing as sidelites, windows or transoms in fire rated frames. B. Related Sections: 1. Section 01 3323: Shop Drawings, Product Data and Samples. 2. Section 06 4000: Architectural Woodwork. 3. Section 08 8000: Glazing. 4. Section 08 1110: Steel Doors and Frames. 5. Section 08 1113: Hollow Metal Doors and Frames. 6. Section 08 1400: Wood Doors and Frames. 1.02 REFERENCES A. National Fire Protection Association (NFPA): 1. NFPA 80: Fire Doors and Windows. 2. NFPA 252: Fire Tests of Door Assemblies. 3. NFPA 257: Fire Tests of Window Assemblies. B. Underwriters Laboratories, Inc. (UL): 1. UL 9: Standard for Safety of Fire Tests of Window Assemblies 2. UL 10 B: Standard for Safety of Fire Tests of Door Assemblies. 3. UL 10 C: Standard for Safety of Positive Pressure Tests of Door Assemblies. C. Standard Council of Canada (ULC): 1. ULC Standard CAN4-S104: Fire Tests of Door Assemblies. 2. ULC Standard CAN4-S106: Fire Tests of Window Assemblies D. Consumer Product Safety Commission (CPSC): 1. CPSC 16 CFR 1201: Safety Standard for Architectural Glazing Materials. E. American National Standards Institute (ANSI): 1. ANSI Z91.1: Safety Glazing Materials Used in Buildings Safety Performance Specifications and Methods of Test. F. Canadian General Standards Board (CGSB): 1. CAN/CGSB 12.1: Safety Glazing

G. Glass Association of North America (GANA) 1. GANA Glazing Manual. 2. FGMA Sealant Manual. H. [American Recovery and Reinvestment Act 1. Section 1605, Title XVI Buy American Provision] I. [Insert building code used by Authority Having Jurisdiction] 1.03 SYSTEM DESCRIPTION A. Performance Requirements: Provide a fire rating glazing manufactured, fabricated and installed to maintain performance criteria stated by manufacturer without defects, damage or failure. 1. Fire Rating: 45 minutes with hose stream. 2. Fire protective, safety rated clear glazing tested in accordance with NFPA 80, NFPA 252, NFPA 257, UL 9, UL 10B, UL 10C, CAN/ULC S104 and CAN/ULCS106. 3. Safety Rating: CPSC 16 CFR 1201 Category I and II, ANSI Z79.1 Class A and B and CGSB 12.1 Class A and B. 4. Maximum Sizes: Maximum clear view area for non-temperature rise 45 minute doors is 3,288 sq. in. (33 in width x 99-5/8 in. height). Maximum clear view area for 45 minute sidelites, openings and transoms when ASTM E-119/UL 263/ULC-S101 is not required is 3,880 sq. in. (42-3/4 in. width x 90-3/4 height). 5. Testing Laboratory: Fire test shall be conducted by a nationally recognized independent testing laboratory. B. Listings and Labels: 1. Fire rated glazing shall be under current follow-up service by a nationally recognized independent testing laboratory approved by OSHA and maintain a current listing or certification. Assemblies shall be labeled in accordance with limits of listings. 1.04 SUBMITTALS A. Submit listed submittals in accordance with Conditions of the Contract and Division 1 Submittal Procedure Section. 1. Shop Drawings: Submit shop drawings showing layout, profiles and product components. 2. Samples: Submit 12 x 12 glass samples. 3. Technical Information: Submit latest edition of manufacturer s product data. 1.05 DELIVERY, STORAGE AND HANDLING A. General: Comply with Division 1 Product Requirements Sections. B. Ordering: Comply with manufacturer s ordering instructions and lead-time requirements to avoid construction delays. 2

C. Delivery: Deliver materials to specified destinations in manufacturer s or distributor s packaging undamaged, complete with installation instructions. D. Storage and Protection: Store off ground, under cover, protected from weather and construction activities and at temperature conditions recommended by manufacturer. 1.06 PROJECT CONDITIONS A. Field Measurements: Verify actual measurements for openings by field measurements before fabrication. Show recorded measurements on shop drawings. Coordinate field measurements and fabrication schedule with construction progress to avoid construction delays. 1.07 WARRANTY A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions. B. Manufacturer s Warranty: Submit, for Owner s acceptance, manufacturer s standard warranty document. Manufacturer s warranty is not intended to limit other rights that the Owner may have under the Contract Documents. 1. Warranty Period: Lifetime warranty. PART 2 PRODUCTS 2.01 FIRE RATED GLAZING A. Material: SuperClear 45-HS 45 minute fire and safety rated glazing. B. Manufacturer: SuperClear 45-HS ¾ thick clear specialty fire protective glazing as manufactured and distributed by SAFTIFIRST. 1. Contact: 100 N Hill Drive, Suite 12, Brisbane, CA 94005; Telephone 888.653.3333; Fax 888.653.4444; email info@safti.com; Web site www.safti.com 2. Must be provided by a US manufacturer. Distributors of fire rated glass are not to be considered as manufacturers. C. Design Requirements: 1. Thickness: ¾ (19 mm). 2. Weight: 9 lbs./sq. ft. 3. Sound Transmission Rating: Must meet 37 STC/35 OITC in standard hollow metal frames. Glass and frame must be tested as an assembly. Glass only STC/OITC values are not acceptable. 4. Appearance: clear, wireless and tint-free. 5. Visual Light Transmission: Must meet 83% VLT for standard clear. 6. Fire Rating: 45 minutes with hose stream. 7. Impact Safety Resistance: Must meet CPSC 16 CFR 1201 Category I and II, ANSI Z91.1 Class A and B and CAN/CGSB 12.1 Class A and B. D. Manufacturer s Fire Rated Glazing Material: 3

1. Each piece of fire-rated glazing material shall be labeled with a permanent logo including name of product, manufacturer, testing laboratory, fire rating period and safety glazing standards. 2. Glazing material installed in Hazardous Locations, subject to human impact, shall be certified and permanently labeled as meeting applicable requirements referenced in NFPA 80: a. CPSC 16 CFR 1201, Cat. I or II E. Substitutions: No substitutions allowed. 2.02 MATERIALS A. Glazing Accessories: Manufacturer recommended fire rated glazing accessory as follows: 1. Glazing tape: closed cell PVC foam tape or neoprene tape. 2. Setting blocks: calcium silicate or hardwood. 3. Cleaners, primers, sealers: type recommended by manufacturer of glass and gaskets. 2.03 RELATED PRODUCTS ********************************************************************************************************************************* Note: Basis of design for fire rated framing system is GPX TM Framing as manufactured by SAFTI FIRST TM ********************************************************************************************************************************* A. Glazing shall be installed in an equally rated framing system. 2.04 SOURCE QUALITY A. Obtain fire rated glazing products from a single manufacturer. B. Fabrication Dimensions: Fabricate to approved dimensions. The general contractor shall guarantee dimensions where practicable within required tolerances. PART 3 EXECUTION 3.01 EXAMINATION 3.01 MANUFACTURER S INSTRUCTIONS A. Compliance: Comply with manufacturer s product data including product technical bulletins and installation instructions. 3.02 EXAMINATION A. Site Verification of Conditions: Verify substrate conditions, have been previously installed under other sections, and are acceptable for product installation in accordance with manufacturer s instructions. 3.03 INSTALLATION A. Installation shall be in strict accordance with the fire glazing material manufacturer s 4

specifications. Field cutting or tampering is strictly prohibited. 3.04 CLEANING AND PROTECTION A. Protect glass from contact with contaminating substances resulting from construction operations. Remove such substances by method approved by manufacturer. B. Wash glass on both faces not more than four days prior to date schedule for inspections intended to establish date of Substantial Completion. Wash glass by method recommended by glass manufacturer. C. Remove temporary coverings and protection of adjacent work areas. D. Remove construction debris from project site and legally dispose of debris. END OF SECTION In the interest of continuous improvement of its product line, SAFTIFIRST TM reserves the right to modify its products composition, colors, textures, sizes, and other physical and performance attributes and these guide specifications at any time. SAFTIFIRST TM makes no expressed or implied warranties regarding content, errors, or omissions in the information presented. Specifications modified or rewritten not in conformance with manufacturer s standard processes, products, and procedures may void warranties and related remedies. Last updated Dec 2018. 5