Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Similar documents
CHAPTER 1 INTRODUCTION

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Oyelami S., Bolaji B. O.

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

DEEPAK PALIWAL, S.P.S.RAJPUT

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Department of MCE, Islamic University of Technology 2. Abstract

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Design of LPG Refrigeration System

Pure Butane as Refrigerant in Domestic Refrigerator Freezer

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Study of Behavior of Refrigerant Mixtures in Domestic Refrigerator- Practical Research

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Chapter 10. Refrigeration and Heat Pump Systems

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Design and Fabrication of Liquefied Petroleum Gas Refrigeration System and Comparison with Domestic Refrigerator

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Experimental study of R600a and R436a to replace R134a in a domestic refrigerator and freezer

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

A Comparison Between Refrigerants Used In Air Conditioning

EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R600A & HC MIXTURE)

Thermodynamics I. Refrigeration and Heat Pump Cycles

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

Performance of an Improved Household Refrigerator/Freezer

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

HFCs or the Old Refrigerants - what is the best Choice?

CHAPTER 1 INTRODUCTION

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

LPG Refrigerator. October 2017 IJIRT Volume 4 Issue 5 ISSN:

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Performance Investigation of Domestic Refrigerator Using Pure Hydrocarbons and Blends of Hydrocarbons as Refrigerants

International Engineering Research Journal (IERJ) Special Issue Page , June 2016, ISSN

BUTANE, ISOBUTANE AND THEIR MIXTURES AS AN ALTERANTIVES TO R-134a IN DOMESTIC REFRIGERATOR

A Review Paper on Comparative Study of Household- Refrigerator with Alternative Low Global Warming Potential Refrigerants

Chapter 9. Refrigeration and Liquefaction

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Theoretical analysis of low GWP mixture R600a/ R1234ze as a possible alternative to R600a in domestic refrigerators

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

η second law = Second law efficiency

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

International Journal of Advance Engineering and Research Development

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Refrigerants Retrofit as Alternative for R12 and R134a in Household Refrigerators

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

Chapter 11 REFRIGERATION CYCLES

A Review on selecting an Eco-friendly Refrigerant alternate to R134a in Domestic Refrigerators

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

R-404A Alternative with Low Compressor Discharge Temperature

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Thermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Requirements for Labelling: Labelling of Refrigerant Containers

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Chapter 2. Alternatives to HCFCs and their Characteristics

STUDY AND PERFORMANCE ANALYSIS OF ECO-FRIENDLY REFRIGERANT FOR RETROFITTING R22 IN RESPECT TO BANGLADESH

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

Thermodynamics II Chapter 5 Refrigeration

Transcription:

Energy Conversion and Management 44 (2003) 381 388 www.elsevier.com/locate/enconman Assessment of LPG as a possible alternative to R-12 in domestic refrigerators Bilal A. Akash a, *, Salem A. Said b a Department of Mechanical Engineering, Hashemite University, Zarqa 13115, Jordan b Department of Social Services and Commercial Buildings, P.O. Box 30, Abu Dhabi, United Arab Emirates Received 1 October 2001; accepted 7 February 2002 Abstract In this paper, experimental results on the performance of liquefied petroleum gas (LPG) as a possible substitute for refrigerant R-12 in domestic refrigerators are presented. LPG is obtained from the local market with the composition of about 30% propane, 55% n-butane and 15% iso-butane by mass fraction. The domestic refrigerator used was designed to work on R-12. Various mass charges of 50, 80 and 100 g of LPG were used during this study. The results show that LPG compares very well to R-12. For example, the coefficient of performance was higher for all mass charges at evaporator temperatures lower than 15 C. Overall, it was found that a mass charge of 80 g of LPG had the best results when used in this refrigerator. The condenser was kept at a constant temperature of 47 C. Cooling capacities were obtained. They were in the order of about three- to fourfold higher for LPG than those for R-12. Ó 2002 Elsevier Science Ltd. All rights reserved. Keywords: Domestic refrigerators; Refrigerant R-12; Liquefied petroleum gas; Coefficient of performance 1. Introduction Since the 1930s, chlorofluorocarbons (CFCs) have been widely used in the field of refrigeration due to their favorable characteristics. In particular, they were used for small refrigeration units and domestic refrigerators. Refrigerant R-12 was the most dominant. It was one of the first refrigerants to be developed in the refrigeration industry. It is safe, somewhat inexpensive, nonflammable and very stable. Subsequently, CFCs were found to be the main cause of ozone layer depletion. Also, they were found to cause the greenhouse effect or global warming. The discovery * Corresponding author. Tel.: +962-5-382-6600; fax: +962-5-382-6613. E-mail address: bakash@hotmail.com (B.A. Akash). 0196-8904/02/$ - see front matter Ó 2002 Elsevier Science Ltd. All rights reserved. PII: S0196-8904(02)00065-1

382 B.A. Akash, S.A. Said / Energy Conversion and Management 44 (2003) 381 388 of the ozone hole over the Antarctic led to the Montreal Protocol in 1989 [1]. Therefore, CFCs had to be regulated and banned from the refrigeration industry [2 5]. Hydrochlorofluorocarbons, such as R-22, cause less harm to the ozone layer. They contain less chlorine atoms in their chemical structure than CFCs. However, they still contain chlorine atoms in its chemical structure, which is liberated in the stratosphere, causing ozone depletion potential. They have less ozone depletion potential than CFCs, but they are considered to be harmful as well. They also cause the greenhouse warming effect [3 7]. The global warming potential of R-12 is considered to be 8500 times that of CO 2 over 100 years [1]. Greenhouse gas emissions led to the Kyoto Protocol in 1997 that targets developed countries [8]. Hydrofluorocarbons, such as R-134a, have almost zero ozone depletion potential, since they do not contain chlorine atoms in their chemical structure. Similar to R-12, they are safe, nonflammable and have vapor pressures similar to that of R-12. However, they have lower energy efficiency and are more expensive than R-12. They also have a low negative environmental effect of global warming potential [4,5]. According to Rachidi et al. [2], R-134a presents some inconvenience related to lubricant solubility. They have very high pressure ratios and poor heat transfer at low temperatures. Recently, much attention has been paid to the so-called natural fluids, which are claimed to be more environmentally friendly than synthetic fluids [3 6,9 11]. They are hydrocarbons and their mixtures. They are proposed to be used as refrigerants in domestic refrigerators to replace potentially ozone depleting fluids. They offer other advantages of being very inexpensive and available in large amounts. They are environmentally friendly with zero ozone depletion potential, and they do not cause the greenhouse warming effect. The main disadvantage is that they are highly flammable substances and must be handled with caution. Also, blends or mixtures of some refrigerants can be considered as substitutes or alternatives to existing refrigerants [12]. The objective of this work is to show experimentally that liquefied petroleum gas (LPG) can replace R-12 in domestic refrigerators. It is inexpensive, commercially available in local markets, and it is generally used in gas heaters and cooking stoves. It is a mixture of the following hydrocarbons: pentane, iso-butane and n-butane. 2. Experimental In this study, an ordinary type of domestic dual compartment refrigerator/freezer unit was used. It had a gross capacity of 240 l and was designed to work on R-12 as its refrigerant. The test was conducted initially using 160 g mass charge of R-12. It was then performed using various charges of 50, 80 and 100 g of LPG as the working refrigerant. LPG was commercially available in local markets, and it is generally used as a fuel in gas cooking stoves and domestic gas heaters. It is very inexpensive, comprised of 30% propane, 55% n-butane and 15% iso-butane on a mass basis. When conducting the experiments, pressure gauges were used to record the pressures at both the low and high sides of the compressor. Thermocouples were used at different locations of the cycle in order to record temperatures simultaneously using data acquisition. A schematic diagram of the basic vapor compression refrigeration cycle is shown in Fig. 1. Briefly, the process of refrigeration takes place in the evaporator, by which heat is transferred to the refrigerant causing it to evaporate in the evaporator. Generally, the vapor leaves the

B.A. Akash, S.A. Said / Energy Conversion and Management 44 (2003) 381 388 383 Fig. 1. Schematic diagram of freezer/refrigerator system. evaporator as superheated refrigerant. It passes then through the suction line heat exchanger, gaining more heat before entering the compressor. In the compressor, it is compressed to a higher condensing pressure. Passing through the condenser at a temperature higher than the surroundings, heat is then rejected to the surroundings. At this time, the state of the refrigerant is subcooled in the condenser. It exchanges heat with the vapor leaving the evaporator in the suction line heat exchanger, and it is cooled even further. Finally, the refrigerant is expanded in an adiabatic process, causing a sharp drop in its temperature. It enters the evaporator as saturated liquid at low temperature and pressure, and then the cycle is complete. In order to obtain some ideas about the thermodynamic behavior of LPG, vapor pressure lines were plotted for the gases that comprised our LPG sample as shown in Fig. 2. The gases are propane (R-290), n-butane (R-600), and iso-butane (R-600a). They are compared to the vapor pressure line of R-12. As shown by the figure, the vapor pressures of the three gases are near and surround that of R-12. The vapor pressure line of R-290 is higher than that of R-12. On the other hand, the vapor pressure lines of R-600 and R-600a are lower than that of R-12. Therefore, the vapor pressures of the mixture of three gases, i.e. LPG, are close enough to the range of R-12, and it can be used without making any major modification to the machine. 3. Results and discussion Fig. 3 shows the variation of coefficient of performance (COP) with evaporator temperature for the three mass charges of LPG as compared to R-12. It shows that LPG compares very well to R-12. For example, the values of the COP were higher for all mass charges at evaporator

384 B.A. Akash, S.A. Said / Energy Conversion and Management 44 (2003) 381 388 Fig. 2. Vapor pressure lines of refrigerant R-12, propane (R-290), n-butane (R-600), and iso-butane (R-600a). Fig. 3. Variation of COP with evaporator temperature for R-12 and different charge masses of 50, 80 and 100 g of LPG. temperatures lower than 15 C. At an evaporator temperature of about 10 C, the COP was about 3.4, 2.9 and 2.7 for mass charges of 80, 100 and 50 g of LPG, respectively, whereas the COP for R-12 was about 2.85. The condenser temperature was kept at 47 C. These results are in agreement with those reported in the literature [3 7,9].

B.A. Akash, S.A. Said / Energy Conversion and Management 44 (2003) 381 388 385 Fig. 4. Variation of cooling capacity (in kj/kg) with evaporator temperature for R-12 and different charge masses of 50, 80 and 100 g of LPG. The cooling capacities at various evaporator temperatures are shown in Fig. 4. They are much higher for LPG than for R-12 due to the higher enthalpies of R-290, R-600 and R-600a relative to those of R-12. Their order is in the range of 300 350 kj/kg for the LPG gases and about 110 kj/kg for R-12. Fig. 5 shows the variation of the specific compressor work at various evaporator temperatures. It was higher for LPG than R-12 due to the higher enthalpy values of LPG. In Fig. 5. Variation of compressor work (in kj/kg) with evaporator temperature for R-12 and different charge masses of 50, 80 and 100 g of LPG.

386 B.A. Akash, S.A. Said / Energy Conversion and Management 44 (2003) 381 388 Fig. 6. Variation of refrigerant mass flow rate with evaporator temperature for R-12 and different charge masses of 50, 80 and 100 g of LPG. general, the values were about doubled when LPG was used. The refrigerant mass flow rates were plotted as a function of evaporator temperature. They are presented in Fig. 6. The mass flow rates were much higher for R-12 than LPG (three- to fourfold higher). For example, at an evaporator temperature of 10 C, the mass flow rate was approximately equal to 3 g/s for R-12, whereas it ranges between 0.7 and 1.0 g/s for LPG. The COPs versus different values of refrigerant mass flow Fig. 7. Variation of COP with refrigerant mass flow rate for R-12 and different charge masses of 50, 80 and 100 g of LPG.

B.A. Akash, S.A. Said / Energy Conversion and Management 44 (2003) 381 388 387 Fig. 8. Variation of cooling capacity (in tons of refrigeration) with evaporator temperature for R-12 and different charge masses of 50, 80 and 100 g of LPG. rates are shown in Fig. 7. Again, in general, the mass flow rates are higher for R-12 than for LPG due to the higher enthalpies for LPG than those for R-12. Finally, the cooling capacities in tons of refrigeration are plotted in Fig. 8 for the refrigerants studied. It is clear that LPG is a better refrigerant than R-12 in this manner. The best performance was when 80 g of LPG was used. For example, at an evaporator temperature of 8 C, the cooling capacity was about 0.1 ton of refrigeration for R-12. On the other hand, it was roughly equal to 0.32 ton for 80 g mass charge of LPG, and it was about 0.25 ton for 50 and 100 g mass charges of LPG. 4. Conclusions The performance of LPG as a possible alternative to R-12 was studied experimentally. The refrigerator worked satisfactory with LPG without making any modification to the machine. The COP values were comparable to those of R-12, and in some instances, they were even higher than those of R-12. No operating problems were encountered with the refrigerator compressor and no degradation of lubricating oil was detected. The cooling capacities were higher for LPG than those of R-12. The use of LPG as an alternative to R-12 can contribute to reduction of greenhouse warming and elimination of ozone depletion potential caused by various refrigerants. The only problem that can be associated with LPG is that it is a flammable substance and must be handled with caution. One must remember that most kitchens use LPG in gas cookers. It is considered as the main fuel for combustion in stoves in most countries. Therefore, people are already used to handling LPG with care in domestic usage.

388 B.A. Akash, S.A. Said / Energy Conversion and Management 44 (2003) 381 388 References [1] Aisbett EK, Pham QT. Natural replacements for ozone-depleting refrigerants in eastern and southern Asia. Int J Refrigeration 1998;21(1):18 28. [2] Rachidi T, Bernatchou A, Charia M, Loutfi H. New fluids as substitute refrigerants of R12. Solar Energy Mater Solar Cells 1997;46(4):333 47. [3] Purkayastha B, Bansal PK. An experimental study on HC290 and a commercial liquefied petroleum gas (LPG) mix as suitable replacements for HCFC22. Int J Refrigeration 1998;21(1):3 17. [4] Jung D, Kim CB, Lim BH, Lee HW. Testing of a hydrocarbon mixture in domestic refrigerators. ASHRAE Trans 1996;102:1077 84. [5] Lorentzen G. The use of natural refrigerants: a complete solution to the CFC/HFC predicament. Int J Refrigeration 1995;18:190 7. [6] Alsaad MA, Hammad MA. The application of propane/butane mixture for domestic refrigerators. Appl Thermal Eng 1998;18:911 8. [7] Beyerlein AL, DesMarteau DD, Naik KN, Xie Y. Physical properties of fluorinated propane and butane derivatives and vapor pressure of R-245ca/338mccq mixtures as R-11 alternatives. ASHRAE Trans 1996;101:358 66. [8] Woerdman E. Implementing the Kyoto protocol: why JI and CDM show more promise then international emissions trading. Energy Policy 2000;28:29 38. [9] Hammad MA, Alsaad MA. The use of hydrocarbon mixtures as refrigerants in domestic refrigerators. Appl Thermal Eng 1999;19:1181 9. [10] Liu BY, Tomasek M-L, Radermacher R. Experimental results with hydrocarbon mixtures in domestic refrigerator/ freezers. ASHRAE Trans 1995;101:1415 21. [11] Beyerlein AL, DesMarteau DD, Hwang SH, Smith ND, Joyner PA. Physical properties of fluorinated propane and butane derivatives as alternative refrigerants. ASHRAE Trans 1993;99:368 79. [12] Sami SM, Desjardins DE, Maltais H. Prediction of capillary tubes with alternative refrigerants to CFC-502. Int J Energy Res 2001;25:1249 61.