MASS AND HEAT RECOVERY SYSTEM SALAH MAHMOUD HINDAWI DIRECTOR HINDAWI FOR ENGINEERING SERVICES & CONTRACTING NEW DAMIETTA, EGYPT

Similar documents
Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Redesign of Bennett Hall HVAC System

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

A/C Cooling Load calculation and measurement

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Air Conditioning Clinic

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Dedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Humidity Control & Psychrometrics

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Optimizing Electric Humidifier Operation with an Air Side Economizer

Technical Assignment 3 11/15/04. Executive Summary

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP

Pharmaceutical Facility Design

EarthWise System Seminar

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

Designing Energy Efficient Outdoor Air Systems

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Numerical study of heat pipe application in heat recovery systems

The Temperature and Relative Humidity Control in Cushing Library

Department of Mechanical Engineering ME 322 Mechanical Engineering Thermodynamics

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET

CTI Sponsored Educational Program

ASHRAE Headquarters Building: GSHP vs. VRF systems

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Heat pump and energy recovery systems

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Wall Mounted Air Conditioners with Gas Heat Models AVGA

Explanation of Cooling and Air Conditioning Terminology for IT Professionals

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)


TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

RT-OA TM Rooftop Outdoor-Air (DOAS)

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Industrial Heat Pumped Hot Water

Method to test HVAC equipment at part load conditions

Modular Active. Chilled. Beams

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Trane CDQ Desiccant Dehumidification

Recent Advances in Energy, Environment and Economic Development

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Variable Air Volume with Indoor Air Quality

Computing Services Center

Performance Optimization of the Evaporative Condenser Design

MECCI Engineers. Institute of Engineering Design & Research

Submittal Data Performance Data Electrical Data

Technical Development Program

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

GARCIA GALUSKA DESOUSA Consulting Engineers

Challenges and Methods of Estimating a Conceptual HVAC Design

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

ENERGY RECOVERY HEAT PIPE HEAT EXCHANGERS

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

INSTITUTE OF AERONAUTICAL ENGINEERING

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Presented By: John Dolan, P.E.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Chiller Vs VRF Comparison

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Daikin Blueprint: Delivering Hot Water with a Chiller

Psychrometric Engineering Applications

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Low GWP Refrigerants for Air Conditioning Applications

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

LG VRF Systems. Air Conditioning Technologies

Classic 13 Heat Pumps High Efficiency Vertical Packaged Heat Pumps Models HVPA and HVPSA

Pressure Enthalpy Charts

Transcription:

ESL-IC-10-10-56 MASS AND HEAT RECOVERY SYSTEM SALAH MAHMOUD HINDAWI DIRECTOR HINDAWI FOR ENGINEERING SERVICES & CONTRACTING NEW DAMIETTA, EGYPT ABSTRACT : In the last few years heat recovery was under spot. and in air conditioning fields usually we use heat recovery by different types of heat exchangers. The heat exchanging between the exhaust air from the building with the fresh air to the building ( air to air heat exchanger ). In my papers i use ( water to air heat exchanger ) as a heat recovery. and I use the water as a mass recovery. The source of mass and heat recovery is the condensate water which we were dispose and connect it to the drain lines. THE BENEFIT OF THIS SYSTEM ARE : 1) Using the heat energy from the condensate water to reduce the fresh air temper. In cooling and air conditioning fields. Via heat exchangers ( ENERGY SAVING ). 2) Using the dispose water as a mass flow in different purposes like irrigation systems, W.C. flush thanks systems, etc. ( MASS SAVING ). 3) Saving some of electric power consumption and then less operation costs due to item (1). 4) Reduce the required daily water for irrigation, or flush thanks and then less Operating Costs due to item (2). MASS AND HEAT RECOVER SYSTEM ( MHRS ) A. INTRODUCTION : In the last few years heat recovery was under researches spot. Because of at the end of its application it's reduce the operation cost for the building. we use heat recovery in air conditioning field by different types of heat exchangers between the exhaust air from the building and the fresh air to the building ( air - to air heat exchanger ). In this paper we use ( water - to air heat exchanger ) as a heat recovery and we use the water as a mass recovery. B. MHRS DESCRIPTION : Until now we still dispose the condensate water by free discharge or connect it to the drain network that water carrying heat energy. And in the same time condensate water we can use it again as a mass flow in different uses. Figure (1) showing the mass and heat recovery system (MHRS) layout. This layout can divided to four (4) sections : 1. Mass and heat collection (MHC). 2. Mass and heat storage unit (MHSU). 3. Heat recovery unit (HRU). 4. Mass recovery unit (MRU). - 1 -

ESL-IC-10-10-56-2 -

ESL-IC-10-10-56 For individual description as following : 1) Mass and heat collection (MHC) : When the water or refrigerant in the coil is at a lower temperature than the dew point of the entering air, moisture will be condensate out of the air. As indicated in figure (2). Collection of the condensate water from all air handling units (AHU'S) and fan coil units (FCU'S) by gravity through insulated UPVC pipes network to one main line. Which will go to mass and heat storage unit at the lower level of AHU'S & FCU'S installation. Taking in consideration to extend the highest points of the piping network as a vent. The components of this section are : ( The existing AHU'S & FCU'S - UPVC pipes and its fittings & thermal insulation ). Extend As Vent AHU or FCU ( TYP. ) The amount of condensate water flow can be determine by calculating the total condensate water from AHU'S & FCU'S for one hour. And it can be the same for ( HRU ) pump capacity. It will be more advanced if we use variable speed pump link with the condensate water flow. The components of this section are (condensate water tank pumps control panels with sensors, switches, etc. - piping & fittings ). P.TRAP ( TYP. ) Branch from other AHU'S & FCU'S Main condensate pipe to condensate water tank 3) Heat recovery unit (HRU) : In figure (4) the discharged condensate water from ( MHSU ) to ( water to air heat exchanger ) to reduce the fresh air temperature which will supply by blower to AHU'S & FCU'S. The outlet water will go to the existing building raw water tank. This section can be supplied as a packaged unit from the manufacturer. The section components are ( Coil Blower Casing ) coil and blower design as per building condition. FIGURE - 2 : Mass And Heat Collection 2) Mass and heat storage unit (MHSU) : As indicated in figure (3) the main condensate water pipe from (MHC) will discharge in the condensate water tank which is fitted with float switches for pumps dry running protection and operation control. The pumps will suck the condensate water and discharge to (HRU). Provision for by pass line is required to use it in case of maintenance. By pass line will connect to raw water tank. - 3-4) Mass recover unit (MRU) : In figure (5) the condensate water from (HRU) will feed raw water tank and it will reduce the municipality Fresh Air In

consumption. We recover the condensate water and use it in difft. Purposes. There are tow sets of pumps discharge the water to W. C. flush tanks, irrigation system, etc. The section components are ( raw water tanks pumps control panels with sensors, switches, etc. piping & fittings ). From the above mentioned sections we notice that sections No. 1 & 4 are available and existing in any project or building. Only some additional pipe works. Sections No. 2 & 3 are new and required for mass and heat recovery system. Also there is flexibility in the system. we can use mass recovery only by using the flow rate of condensate water in irrigation or W.C. flush tank systems. and it is easy to install in the existing projects since the initial cost is low. C. SAMPLE PROJECTS : 1) Executive Projects : I have installed condensate water pipe network for one of my previous projects ( 800 R.T. Cooling Capacity ) as a mass recovery on 2000. It was transportation center ( in Riyadh K.S.A ) consist of three (3) buildings. The HVAC system installed in those building is as follows : a. Air cooled chiller ( CH ) 4 NOS. each capacity 210 R.T.. b. Air handling unit (AHU) 16 NOS. different capacities. c. Fan coil unit (FCU) 55 NOS. different capacities. The design conditions were : Entering air conditions : 80 F DB, 68 F WB, 62.1 F DP, 0.012 Ib moisture/ib dry air (HR) & 13.87 F 3 /Ib dry air (v). Leaving air conditions : 60 F DB, 50.2 F WB, 41.5 F DP, 0.0055 Ib moisture/ib dry air (HR) & 13.21 F 3 /Ib dry air (v). Where : DB = Dry bulb temperature. WB = Wet bulb temperature. DP = Dew point temperature. HR T Humidity ratio. V = Specific volume. Condensate Water = Air flow F 3 /m [ HR ( entering ) HR ( leaving ) ] Ib moisture / Ib dry air 1 / V Ib dry air / F 3. = 320000 ( 0.012 0.0055 ) 1 / 13.87 = 149.95 Ib/Min. T 68 kg/min T 68 Liter/M T 17.99 GPM If we consider 8 hours daily working with 70% diversity factor. Total mass recovery = ( Water flow/day) = 68 8 60 0.7 = 22.8 m 3 / day ESL-IC-10-10-56 We have now 22.8 m 3 water per day we connect it to building raw water tank which feed the irrigation system and W.C. flush tanks. 2) Calculated sample project : we will assume 1000 refrigerant ton cooling capacity project. Location : Kuwait, at the Arabic gulf coast. - 4 -

Ambient Conditions : DB = 119.7 F & WB = 89.6 F from ( ASHRAE ) fundamentals handbook 2005 ( Climatic Design Data Tables ). Return Air Condition : DB = 80 F, WB = 68 F, DP = 62,1 F HR = 0.012 Ib. Moisture / Ib Dry air. Considering 400 CFM/R. Ton and 10% fresh air. Total flow = 400 1000 = 400000 CFM. Fresh air = 40000 CFM Out door air ( Fresh air ) at 119.7 F DB and 89.6 F WB is to be mixed with room air ( Return air ) at 80 F DB and 68 F WB the final mixture is to consist of 0.1 fresh air and 0.9 return air. Mixing (DB) Temp. = 0.1 119.7 + 0.9 80 = 83.97 F. From psychometric chart : Entering Mixing (WB) = 70.7 F & DP = 65 F. Entering Mixing (HR) = 0.0131 Ib Moisture / Ib dry air. Entering Mixing (SV) = 13.99 F 3 /Ib dry air. Leaving Conditions : DB = 60 F, WB = 50,2 F, HR = 0.0055 Ib Moisture / Ib dry air. Then : The total mass recovery = ( Water flow / day ) = 105.3 8 60 0.85 = 42962 liters / day = 43 m 3 /day ESL-IC-10-10-56 This amount of water relate to some conditions : 1- Outdoor humidity ( Increase with higher humidity ). 2- Fresh air ( Increase with more fresh air ). 3- Operation condition ( Increase with more room latent heat gain ). 4- Diversity and load demand factors ( Decrease with less than 85% ). Heat Recovery Calculation : The heat exchanger pumps will be capable to discharge the condensate water flow rate. Then the pump capacity = = 27.85 0.85 ( Diversity factor ) = 23.67 GPM Since the dew point temperature for entering air is 65 F. Allow 3 F more for heat gain. Then the condensate water temperature is 68 F. As shown in figure (6) we have cooling media ( Condensate water ) 23.67 GPM & 68 F. Mass Recovery Calculation : Condensate water flow : Air flow [ HR (ent.) HR (lea.) ] 1 / SV = 400000 ( 0.0131 0.005 ) 1 / 13.99 = 231.59 Ib / min = 105.27 kg/min T 105.3 liters/min T 27.85 GPM If we consider 8 hours daily working with 85% diversity. - 5 - And the manufacturer will design heat exchanger ( Heat recovery ) to let the fresh air absorb heat from condensate water. With this condition

( fresh air in 119.7 F D.B fresh air out 90 F D.B ). The total heat absorbed from the condensate water can be determine from this equation : Q ( Btu/hr ) = 500 GPM ΔT = 500 23.67 ( 84 68 ) = 189360 Btu/hr = 15.78 R.T/hr ( heat recovery ) It mean we can give 15.78 R.T/hr to the fresh air. For 8 Hrs/day = 15.78 8 = 126.24 R.T/day The flow amount of fresh air depend on the design of heat exchanger and fresh air in & out temperatures. Now we have in 1000 R.T. cooling load project. 1- Mass recovery as a water: = 43 m 3 /day 2- Heat recovery = 126.24 R.T/day This heat load 126.24 R.T / day can let us save electric power consumption which we were locking to produce this amount of heat load. As following. Electric power saving = = 126.24 1.5 Kw = 189.36 Kw/day. D. Prefer Location : when the water or refrigerant in the coil is at a lower temperature than the dew point temperature of the entering air, moisture will be condensate out of air. we know that. The dew point temperature increase with the higher ( Relative humidity, wet bulb temperature ) there fore water condensation will start early and more. ( There are humidity, less natural soft water and hot weather ). E. Benefit : The installation of heat and mass recovery system give us the following advantage : a) Using the heat energy from the condensate water to reduce the fresh air temperature in cooling and air conditioning fields via heat exchangers ( Energy saving ). b) Using the condensate water as a mass flow in different purposes like irrigation systems, W.C. flush tanks systems & Etc. c) Saving some of electric power consumption and then less operating costs due to item (a). d) Reduce the required daily water need for irrigation & W.C. flush tanks and then less operating costs due to item (b). F. Conclusion & Aim : Using some of mass and energy which were dispose to the waste. We are locking to install the mass and heat recovery system in the suitable projects. Even if it is existing, this system will achieve sustainable energy saving and less operating cost. G. References : ESL-IC-10-10-56 o ASHRAE Hand Books. o 2005 Fundamentals. o 2004 HVAC Systems and Equipment. The areas which we can obtain the best results are in the humidity locations. Specially in Arab gulf countries and similar countries. - 6 -