Experimental Study of Fins Effect on Thermal Performance of HPHX for Air Conditioning System

Similar documents
Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Experimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat Pipe

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Solar Drying Techniques And Performance Analysis: A Review

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Compression of Fins pipe and simple Heat pipe Using CFD

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

Natural Convection Heat Transfer Augmentation from Heat Sinks using Perforated Fins: A Review

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Review of Thermosyphon heat exchanger charged with hybrid nanofluid for waste heat recovery applications

American International Journal of Research in Science, Technology, Engineering & Mathematics

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Mallikarjun 1, Anandkumar S Malipatil 2

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Global Journal of Engineering Science and Research Management

Investigation of Metal and Metal Oxide nanocoating on Fins in HPHE with Silver Water NanoFluid

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India

A study of Transient Performance of A Cascade Heat Pump System

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Experimental Study And CFD Based Simulation of Closed Loop Pulsating Heat Pipe Using of Refrigerants (R-134a)

Performance investigation of Air-conditioning system using ejector as expansion device

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Numerical study of heat pipe application in heat recovery systems

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Design and Development of Water Cooled Condenser for Domestic Refrigerator

American International Journal of Research in Science, Technology, Engineering & Mathematics

EXPERIMENTAL PERFORMANCE ANALYSIS OF SOLAR AIR HEATER WITH THREE DIFFERENT MODIFICATIONS IN ABSORBER PLATE

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Modified Air Cooler with Split Cooling Unit

Experimental Investigation to Assess the Performance of Desiccant Integrated Chilly Dryer

Performance Optimization of the Evaporative Condenser Design

Performance Study of Solar Heat Pipe with Different Working Fluids and Fill Ratios

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Thermal Performance of a Loop Thermosyphon

Recovery Using Heat Pipe Heat Exchanger with Hybrid Nanofluid

Design and Experimental Studies on Modified Solar Dryer

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Operation of a Two-Phase Reverse Loop Thermosyphon

Adsorption refrigeration system using waste heat

LAB EQUIPMENT DETAILS

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

HEAT PIPES

International Journal of Informative & Futuristic Research ISSN (Online):

DESIGN AND FABRICATION OF A PORTABLE REFRIGERATOR BASED ON PELTIER EFFECT

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

HEAT TRANSFER COEFFICIENT ENHANCEMENT IN NATURAL CONVECTION FROM HORIZONTAL RECTANGULAR FIN ARRAYS WITH PERFORATIONS

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

II. OBJECTIVE OF RESEARCH

Analysis of CPU cooling using liquid with different type of heat sinks

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Experimentation of Heat Pipe Used In Nano-Fluids

Design and Development of Combined Direct and Indirect Evaporative Cooling System

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

INTERNATIONAL JOURNAL OF RESEARCH IN AERONAUTICAL AND MECHANICAL ENGINEERING

SCIENCE CHINA Technological Sciences

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

TITLE: Improvement in Heat Transfer Rate and Dynamics of Shrouded Fanned Radiator System

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Performance Analysis of Heat Pipe using Different Screen Mesh Sizes Manikandan.K * 1, Senthilkumar.R 2,

TWO-PHASE MICRO-CHANNEL HEAT SINK FOR SPACE CRAFT THERMAL CONTROL

Enhancement of COP in Vapour Compression Refrigeration System

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Basic CFD model of heat pipe

DESIGN, ANALYSIS AND FABRICATION OF THERMOELECTRIC COOLING AND HEATING SYSTEM FOR WATER DISPENSER

Transcription:

IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 15, Issue 4 Ver. III (Jul. - Aug. 2018), PP 70-78 www.iosrjournals.org Experimental Study of Fins Effect on Thermal Performance of HPHX for Air Conditioning System S.D.Yadav 1, J.A.Kute 2, J.A.Hole 3 1 (ME-Heat Power, Department of Mechanical Engineering, JSPM S RSCOE, Pune), 2 (Research Scholar, DoT, SavitribaiPhule Pune University & Asst. Prof. RSCOE, Pune) 3 (Ph.D.& Associate professor RSCOE,Pune) Corresponding Author: S.D.Yadav Abstract nowadays the use of heat pipes is one of the most effective technique of saving energy & preventing global warming. In heat recovery applications, the heat pipe heat exchangers are used to cool the incoming fresh air in air conditioning systems. Due to increasing in need of HPHx (Heat pipe heat exchanger) in heat recoveryapplication there is a challenge to achieve cost effective solution without compromising on its effectiveness. In this paper the experimentation was carried out to investigate the effect of HPHX on energy recovery in air conditioning system with different array of heat pipes in HPHX. In this experimental work, first one heat pipe was constructed& tested for temperature range 30 to 40ºC with R134a as a working fluid. Then multiple tests were carried out for HPHx without & with fin heat pipe arrangement in HPHx.The series of tests were conducted for multiple values of inlet air velocity from 1 to 5m/s& for different inlet outdoor air temperature varying from 32 to 40ºC based on Pune climatic condition.an experimental results shows that maximum effectiveness can be seen in staggered arrangement of finned pipes than finless pipes. Also results indicates that maximum effectiveness is possible to achieve at minimum velocity of inlet air & goes on increasing as outdoor inlet air temperature increases. This study indicates that due to the addition of fin on heat pipes in HPHx will increased its effectiveness significantly. Index Terms Energy recovery, Heat pipe heat exchanger, air conditioning application,fin geometry, FPI, Effectiveness. ----------------------------------------------------------------------------------------------------------------------------- ---------- Date of Submission: 23-07-2018 Date of acceptance: 06-08-2018 ----------------------------------------------------------------------------------------------------------------------- ---------------- I. Introduction The developing countries like India are indulged to maintain a certain progress rate for which energy is anelementaryfactor. With the rapid development of the economics and the improvement in living standard of ordinary people in India, the use of air-conditioning equipment has been increasing quickly in recent years. The ever increasing energy requirement puts a great burden on the further economic development. The lag between energy supply and demand is increasing every year as power sector is highly capital intensive. So, energy conservation is the approach of regulating and improving energy using systems and procedures to reduce energy requirements per unit of output without affecting socio-economic development [1]. Recently, due to global warming & greenhouse effects, ambient air temperature continuously raising every year. Hence controlling Heating, Ventilation and Air Conditioning (HVAC) system to maintain occupant s indoor thermal comfort is important to energy-efficient buildings and the development of smart cities. For decades, the design of HVAC systems has been focused on minimizing energy waste by enhancing the efficiency in heaters and coolers, or improving insulation of air ducts and exchangers [2]. The use of heat pipes for heat recovery represents an excellent way to a decrease of a waste heat that is rejected to the ambient. Also it has many advantages such as its heat recovery efficiency, lack of moving parts, compactness, light weight, economy, and minimumpressure drop on the air side [3]. Heat pipes applies in various different areas such as in the area of space craft cooling, electrical & electronic equipment cooling, medicine & human body temperature control and as a heat exchanger for heat recovery in air conditioning system. The research based on hphx sapplication shows that the heat transfer rates to the evaporator section of a single heat pipe from the computer simulation is very close to the actual experimental results [4]. Hence the effectiveness of hphx is proven & cross verified. Thanaphol&Chaiyun investigated by their studies the effect of filling ratio of working fluid R134a & length of adiabatic section. The pipe material used was copper. The optimum filling ratio for each adiabatic length is 15% of heat pipe volume[5]e.azad, F.Mohammadieh represents theoretical analysis of multi-stage heat pipe heat recovery system. They have developed the thermal performance & temperature profile in flow direction bothin evaporator& condenser sections. Similarly, they have done a theoretical study on the performance of a circular finned heat pipes in the longitudinal rowsto DOI: 10.9790/1684-1504037078 www.iosrjournals.org 70 Page

forecastits temperature distribution [6]. S.B. Riffat& G. Gan performed the work &represented results of effect of inlet air velocity on effectiveness. Air velocity was found to have a high impact on the effectiveness of heat recovery. The effectiveness decreased with increasing inlet air velocity & effectiveness also affected by shape of fins & pipe arrangement. By using CFD it was found that, for natural ventilation at low velocities the loss of pressure coefficient decreased with increasing air velocity, but the total pressure drop increased with the velocity. From the study it is recommended that, in naturally- ventilated low rise buildings, without the wind effect or solar energy, the design mean air velocity should be less than 1m/s [7]. Some authors represented review documents on HPHX s application, general design procedures, analysis tools based on the thermal network approach. Also this review study discussed about opportunities & challenges related to currenthphx applications. [8] X.Yang, Y.Y.Yan& D. Mullen discussed in their paper the several methods& manufacturing methods to achieve the requirements of lightweight & high performance heat pipes. The application of light weight material helps to reduce 80% the weight of conventional heat pipes. [9]. The research has been done by J.A. Kute to explore the effect of HPHX on energy recovery in HVAC application. Thermosyphon type of heat pipe is investigated for this research. The relative study of inline & staggered arrangement has been carried out for different outdoor temperature and velocity in the article. The study indicates staggered arrangement is more effective than inline based on the thermal performance parameter. [11]. Y.H.Yau [13] carried out experimentation using thermosyphon HPHX with 8 rows with the angle of tilt 300 to examine the influence of condensate forming on the fins of the HPHXs and affecting its effective- Ness. On the basis of available research review, it has been found that experimental study has not been done for finned heat pipes arranged in staggered array used to enhance the performance of HPHx in air conditioning system. Hence this article proposes experimental & comparative study of the thermal performance of the HPHx in both the cases in which, pipes are used with & without fins. Abbreviations HVAC Heating ventilation and air conditioning. HPHX Heat pipe heat exchanger EBR Energy balance ratio FPI Fins Per Inch DBT Dry Bulb Temperature Symbols ṁ Mass flow rate of air (kg/s). T 1DBT of inlet outdoor air before evaporator ( C) T 2 DBT of air after evaporator ( C) T 3 DBT of air before condenser ( C) T 4 DBT of air after condenser ( C) C pcspecific heat of conditioned air at atmospheric pressure at T 4 C(J/kg. C) C pespecific heat of outdoor air at atmospheric pressure at T 1 C(J/kg. C) V Velocity of inlet outdoor air to heat pipe (m/s) Q e Heat absorbed at evaporator zone (W) Q c Heat rejected at condenser zone (W) ε Effectiveness Working of heat pipe: There are three sections of heat pipe, evaporative section, adiabatic section and condenser section as shown in fig.6. Heat gets added to the evaporator section. Due the heat supplied the working fluid present in heat pipe boils and get converted into vapour. As vapour has low density it travels to the condenser section. In condenser thevapour rejects its latent heat and gets condensed into liquid. Due to its weight the liquid moves downward andgets collected in evaporative section. DOI: 10.9790/1684-1504037078 www.iosrjournals.org 71 Page

II. Experimental Apparatus Construction of Test Rig: The experimental set up is as shown in the fig.1. It consists of hphx, air blower, cooling coil, heating coil, sensors to read the temperatures & duct. To minimize the loss of heat to the surroundings by conduction and convection proper insulation is provided to the duct. The ratio of mass flow rate over evaporator & condenser were kept almost constant. To supply the heatto heating coil, wattmeter with desired power ranges with variac for precision control was included to heater circuit. Due to this, the outdoor air with pre-required temperature can be supplied to the evaporator section. For changing inlet air velocity, the another variac control is connected to the air blower. Photograph of actual experimental set up Heat Pipe-Manufacturing & Testing: For HVAC application generally vertically oriented heat pipe is suitable. In this type of pipe, no need to select the wick as these pipes are gravity assisted pipes. Initially, the length of heat pipe, heat pipe material & compatible working fluid were selected. The material of pipe is selected as copper as it is cost effective, thermally conductive& suitable to work at low temperatures. R134a was selected as a working fluid which is ecofriendly. This working fluid filled 60% in the pipe by sealing at one end completely & other end with the non-return valve. The working fluid should wet the pipe internally. Before filling the fluid into the pipe, outgassing is important process. If any gases were present in the pipe prior to filling, they may affect the performance of the heat pipe. The hphx set up is completely sealed properly by insulating material to avoid any kind of leakages. The single heat pipe was tested with the help of thermocouples attached to different sections of heat pipe {i.e. evaporator, adiabatic & condenser}. After testing was done for single heat pipe, the setup of 35 number of heat pipes included in HPHx set-up. DOI: 10.9790/1684-1504037078 www.iosrjournals.org 72 Page

Table. I. Dimensions of HPHx Heat pipe specification Dimension/Details Type of heat pipe Gravity assisted thermosyphon Refrigerant R134a (Tetrafluoroethane) Pipe material Copper Total length of heat pipe 720.0 mm Length of evaporator & condenser section 300.0 mm Length of adiabatic section 120.0 mm Outer diameter 19.1mm Thickness of pipe 1.6 mm Heat capacity per pipe 100 w Working medium air to air hphx Tube pitch ST = 40.0 mm, SL=80.0 mm No. of Rows 7 No. of heat pipes Staggered Array: 35 Fins Selection: The relatively low heat transfer coefficients of flowing cooling air as compared to those of the products to be cooled or condensed may be partly compensated by a surface extension on the air side. This is realized by fin-pipe heat exchanger bundles. The surface extension is optimized on the basis of considerations of economy and manufacture. One criterion for the optimization is the specific performance increase in the heat transfer attainable per cost unit. Fin efficiency mainly depends upon following key parameters: Fin geometry: height, thickness, cross sectional shape Fin material: thermal conductivity coefficient. The thermal rating first requires a reasonable adaptation of the means to be selected to the specified requirement. This implies a certain experience. Shape, size, finning, and fin-tube material must be suitable for the fluid to becooled or condensed and must be adapted to its physical properties. Generally, Fins are provided to increase the effective area for heat transfer. It is found from various studies that with the increase of FPI, surface per unit finned tube increases, but after increasing FPI more than 12, variation in surface per unit-finned tube is gradual. Literature shows that for rectangular plate fins the increase of FPI from 3 to 12 causes the increase of heat transferred about 50% (1.5 times). Moreover, increase of FPI from 12 to 15 causes the increase of heat transferred about 3%. Also, the increase of FPI from 3 to 12 causes only a minor increase in pressure drop about 1%, but there is a sharp increase between FPI=12 and FPI=15. Hence, according to the length of the evaporator & condenser section, rectangular plate fins with 8 FPI are selected for this study. Schematic of fin geometry is shown in Fig.2. DOI: 10.9790/1684-1504037078 www.iosrjournals.org 73 Page

The detailed specification of hphx is shown in table II. Fins specification Fin Material Fin Geometry Rectangular plate dimensions Gap Between Fins Fin Distribution Table. II. Fin specification Dimension/Details Aluminum Rectangular/Circular 40.0*40.0 mm & 80.0*40.0 mm 3.0 mm 8 Fins Per Inch(300 mm of evaporator section & 300 mm of condenser section) Heat pipe arrangement in HPHX: Staggered array of heat pipes without fins: The pipeswere organized in the staggered manner as shown in the Fig.3. According to past study, staggered arrangement shown more effectiveness than inline arrangement [11].In this arrangement, no fins were provided to the pipes. Total 35 number of pipes were organized in 7 number of rows for this arrangement. Fig,3. Staggered array of pipes without fins Staggered array of heat pipes with fins: The pipes were organized in the staggered manner as shown in the Fig.4. in this arrangement rectangular plate fins are provided on the pipes. The circular cut out of 2cm. diameter is taken out from the center of the plate. The heat pipe is passed through the hole of the plate & placed vertically as per shown in the photograph of actual finned pipe arrangement.the evaporator & condenser sections of the heat pipe are responsible for heat transfer, hence fins are provided over the length of evaporator & condenser section, as adiabatic section doesn t involve in any heat exchange activity. Fig,4. Staggered array of pipes with fins For the proper fitment of pipes& to avoid lateral movement of the pipes during working, wooden plates are provided in between the evaporator & condenser section. Due to this adiabatic region becomes isolated & no heat was transferred to that section from either of two ends of the pipe. The assembly of all 35 pipes become immovable & stand straight inside the duct during testing. DOI: 10.9790/1684-1504037078 www.iosrjournals.org 74 Page

Fig.5.Air flow direction over heat pipe array III. Experimental Procedure Following steps has been followed to conduct the experiment for all three set of heat pipe arrangement 1. A series of tests were conductedin the summer season considering Pune city s climatic conditions, where outdoor ambient temperature was 30-36 c. during the day period. The mass flow rate of air passing over evaporator & condenser were kept same. 2. For the decided input conditions first readings have been taken for staggered array heat pipes without fins & repeat the procedure for staggered array of heat pipes with fins. 3. The inlet outdoor temperature was varied in between 30 C and 40 C each step of 2 degrees. (32, 34, 36, 38, 40). The air velocity was varied between 1 to 5m/s, each step of 1.0 m/s (1,2,3,4,5). 4. Temperature & humidity data were collected through data logger during the working of HPHE in an air conditioning application &graphs were plotted IV. Result and Discussion Based on the inlet & outlet temperature of both evaporator & condenser zone, thermal performance of Hphx i.e. heat transfer rate, effectiveness& energy balance ratio was calculated 1. Heat absorbed at evaporator: Qe = ṁ cpe (T1 T2). (1) 2. Heat rejected at condenser: Q c= ṁ cpe(t 4 T 3 ) (2) 3. Thermal effectiveness: Ԑ = Actual Heat Transfer Maximum possible Heat transfer (3) 4. Energy Balance Ratio: EBR = Absorbed heat at evaporator zone Rejected heat at condenser zone (4) DOI: 10.9790/1684-1504037078 www.iosrjournals.org 75 Page

A. Effect of outside inlet air temperature & velocity on thermal performance of hphx without fin: Fig.6. Effectiveness Vs Inlet temperature for Staggered Array of pipes without fins Above fig.6. shows the effectiveness of HPHx is increases as inlet air velocity decreases & inlet outdoor air temperature increases. Fig.7. EBR Vs Inlet temperature for Staggered Array of pipes without fins Fig.7. shows the EBR of HPHx is increases as inlet air velocity & inlet outdoor air temperature increases. The value remains almost constant for inlet air velocity 1 to 5 m/s. B. Effect of outside inlet air temperature & velocity on thermal performance of hphx with fin: Fig.8. Effectiveness Vs Inlet temperature for Staggered Array of pipes with fins Fig.8. shows the effectiveness of HPHx is increases as inlet air velocity decreases & inlet outdoor air temperature increases. DOI: 10.9790/1684-1504037078 www.iosrjournals.org 76 Page

Fig.9.EBR Vs Inlet temperature for Staggered Arrayof pipes with fins Fig.9. shows the EBR of HPHx is increases as inlet air velocity & inlet outdoor air temperature increases. The value remains almost constant for inlet air velocity 1 to 5 m/s. Comparative assessment of Staggered array of heat pipes without & with fins attached arrangement. Fig. 6 & fig. 8depicts drastic variation of with effectiveness across staggered array of heat pipe arrangements in without & with fins where staggered array with fins has higher effectiveness within the range 0.27 to 0.5, than the without finned heat pipe heat exchanger which lies in the range between 0.14 to 0.25. Fig. 7& fig. 9 shows that EBR for three test attached. arrangements remain nearly constant within the range 0.6 to 0.7. Table.III. Comparative assessment of both arrangements Staggered Array Staggered Array Parameters Without fin With fin Total No. of Heat Pipes 35 35 Total No of Fins 0 3948 Max. Effectiveness 0.506 0.357 Max. EBR 0.73 0.72 Table III shows the comparison of different thermal performance & geometric parameters of staggered arrangements of heat pipes without & with fins attached to them. V. Conclusion 1. The effectiveness of HPHX increases with increase in outdoor air temperature while it decreases with increases in inlet air velocity for the staggered array of heat pipes without fins & with fins. The remarkable increment in effectiveness of HPHx has been observed in the second case i.e. when heat pipes are attached with fins as per prediction. The maximum value of effectiveness achieved is for staggered array with fins is having value of 50 to 52 %. Then comparatively less for staggered array without fins up to 25%. 2. Energy Balance Ratio of HPHX slightly increases with increase in outdoor air temperature for all three type of heat pipe array. The EBR value is almost constant for both the arrangementsstated withinthe range of 0.6-0.78. 3.By comparingboth the arrangements& their results obtained by experimentation, it can be concluded that the staggered array of heat pipe with fins attached is most thermally effective than the other two. By considering the no. of fins attached to the heat pipes in the first case, manufacturing cost of the finned pipes is much more than the fin less pipes. So, the only concern of the cost is pertaining to the finned heat pipes. From this comparative study, one can adopt any of these arrangements according to its application in the area of air conditioning system for the provided input conditions. References [1]. Anjna N. Singh, Jagrati Sharma, Energy Conservation in India: Challenges & Achievements, International Journal of Mechanical and Industrial Engineering (IJMIE), ISSN No. 2231 6477, Volume-1, Issue-3, 2012. [2]. Runxin He, Comfort-Aware Building Climate Control Using Distributed-Parameter Models, arxiv:1708.08495v1 [math.oc],28 Aug 2017. [3]. ZhongWei Zhu, HongMing Fan, Cheng Zhang, Experimental investigations on the effectiveness of micro heat pipe array heat exchanger for heat recovery for residential building, Applied Thermal Engineering, 102,pp. 980 988, 2016. DOI: 10.9790/1684-1504037078 www.iosrjournals.org 77 Page

[4]. S.H. Noie-Baghban, G.R. Majideian, Waste heat recovery using heat pipe heat exchanger (HPHE) for surgery rooms in hospitals, Applied Thermal Engineering 20, pp. 1271-1282, 2000. [5]. ThanapholSukchana, ChaiyunJaiboonma, Effect of filling ratios and adiabatic length on thermal efficiency of long heat pipe filled with R 134-a, Energy Procedia, 34, pp. 298-306, 2013. [6]. E. Azad, F. Mohammadieh, F.Moztarzadeh, thermal performance of heat pipe heat recovery system, Heat recovery systems, vol. 5, No. 6, pp. 561-570, 1985. [7]. S.B.Riffat& G. Gan, Determination of effectiveness of heat pipe heat revory for naturally ventilated buildings, Applied Thermal Engineering, vol. 18, Nos. 3-4, pp. 121-130, 1998. [8]. HamidrezaShabgard, Michael J. Allen,NourouddinSharifi, Steven P. Benn, Amir Faghri,Theodore L. Bergman, Heat pipe heat exchangers and heat sinks: Opportunities, challenges,applications, analysis, and state of the art, International Journal of Heat and Mass Transfer 89, pp. 138 158, 2015. [9]. X. Yang, Y.Y. Yan, D. Mullen, Recent developments of lightweight, high performance heat pipes,applied Thermal Engineering, nos. 33-34, pp. 1-14, 2012. [10]. HussamJouhara, Anthony J. Robinson, Experimental investigation of small diameter two-phase closed thermosyphons charged with water, FC-84, FC-77 and FC-3283, Applied Thermal Engineering 30, pp. 201 211, 2010. [11]. J. A. Kute, A. A. Pawar, A. M. Kate, Experimental analysis of performance of HPHX by varying the input parameters for HVAC application,e-issn: 2278-1684, p-issn: 2320-334X, PP.103-108,2015. [12]. Ali FalavandJozaei, Effects of fin per inch on heat transfer and pressure drop of an air cooler with circular and hexagonal fins, Life Science Journal, 10(1), 2013. [13]. Y.H.Yau, Experimental thermal performance study of an inclined heat pipe heat exchanger operated in high humid tropical HVAC systems, International Journal of Refrigeration,30, pp. 1143 1152, 2007 S.D.Yadav "Experimental Study of Fins Effect on Thermal Performance of Hphx for Air Conditioning System. IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE), vol. 15, no. 4, 2018, pp. 70-78. DOI: 10.9790/1684-1504037078 www.iosrjournals.org 78 Page