Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw

Similar documents
Installation, operation and care Wall-mounted electric boiler MP THL nr. - rev 02

LK Electric Boiler - 4,5

MENU. Steamist Digital Sauna Control Models: S170-1 and S Steamist Digital Sauna Control. Contents. 1. Steamist Digital Sauna Control

MENU. Steamist Xenio Sauna Control, Product: 0941 and 0942 Model: S170-1 and S Steamist Xenio Sauna Control. Contents

Installation, operation and maintenance. Accumulator tank. Acc-tank 500 CU. Acc-tank 500 UB ver: Supersedes:

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC CENTRAL HEATING FLOW BOILER

Installation, operation and care. Pellmax UB. Burner not included Replaces:

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Detailed operating instructions

1. Take the hoses and elbow out of the holders, depending on model. max. 100 cm. min. * cm

WATER BOILER METOS MARINE WKI MG MW,

Installer manual ELK 213 Immersion heater

NIBE SPLIT ACVM 270 Air/water heat pump

Sanitary Water Tank INSTALLATION & SVC MANUAL

DIGITAL MODULATING BOILERS

Moisture inside the drum is due to final testing.

FIL-SPL Flow-through heater for central heating USER MANUAL

User Manual 120/240/300 Outdoor Motion Detector

MODEL EH ELECTRIC BOILER OPERATION AND INSTALLATION INSTRUCTIONS

UNDERCOUNTER SERVICE MANUAL. Ecoboiler UC4L 2.4kW Ecoboiler UC10L 2.8kW Ecoboiler UC10L 5.6kW Ecosmart UC4L 2.

MULTI ELEC. Electric Boilers TECHNICAL MANUAL

MANUAL FOR ASSEMBLY AND OPERATION OF ELECTRIC FLOW-THROUGH BOILER/MODULE WITH THREE STAGE ELECTRONIC CONTROL

EUROSTER 2510TX USER MANUAL EUROSTER 2510TX

Detailed operating instructions

MANUAL FOR ASSEMBLY AND OPERATION OF ELECTRIC FLOW-THROUGH BOILER WITH RELAY CONTROL

Multi-Elec COMPACTE BOILER

DS-5C RAIN/SNOW SENSOR CONTROLLER INSTALLATION INSTRUCTIONS

WHE 2.24 / WHE 2.24 FF

MODEL EH ELECTRIC BOILER OPERATION AND INSTALLATION INSTRUCTIONS

s l it l on for Infrared Heaters

CU 300. Installation and operating instructions GRUNDFOS INSTRUCTIONS

Dec Wirsbo CoSy Radio. Installation and Operating Instructions

Installation and maintenance instructions for cabin units type vertical IDAC (V50)

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

HT V2 HT Split

/2010 US/CA

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book

Pump WaterVISE, FloVISE

Constant voltage 3-phase rectifier.

Swedish design and manufacture since 1967

Moisture inside the drum is due to final testing.

Drying Cabinet Installation and Operating Manual

INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER. Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75

KOSPEL S.A. UL. OLCHOWA KOSZALIN

MONITRON II MODEL EH-M2 ELECTRIC BOILER OPERATION AND INSTALLATION INSTRUCTIONS. Four stage electronic control with energy saving and other features.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

KOSPEL S.A KOSZALIN UL. OLCHOWA 1

User Manual. Electric Heating Element MEG DRY MOA REG 2 REG 3

HORIZONTAL COOKING SERIES: 700 / 900 S.A.V MAINTENANCE & AFTER SALES WORK PPS-3WE711911CH

DR. E. HORN GmbH / Schoenaich, Germany

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

For Models FF2310APS, FF2310APW, FF2310APB 55cm FREESTANDING FRIDGE FREEZER. Instruction Manual

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

ST E /ST E / ST E / ST E ST E / ST E / ST E

Cedarbrook Sauna + Steam Family owned and operated since 1971

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

WH-TD20B3E5 WH-TD30B3E5

USER GUIDE LOGIC HEAT H

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

Cooling Unit for Producing Chilled Water. Envicooler. Operation and Maintenance Instructions. Air handling with the focus on LCC

Installation and User Guide Please leave this guide with the end user (for future reference)

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Control solutions Biofloor

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

Operating instructions Page 12

INSTALLATION & TECHNICAL MANUAL

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

OPERATING AND INSTALLATION MANUAL

Spare Parts List. Universal Utensil Washer FV V / 460V / 60HZ 3P / MIKE 2

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

REA 105 Arc Protection Module. Operator s Manual

Hand Dryer Installation & User Manual

4L Instant Water Boiler Instructions for Use

Alpha CombiMax 350 and 600

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Installation, Operation & Maintenance Instructions Annealing Ovens TLD models

Recirculating Cooler SRC14

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

SCHMIDT LED Measured Value Display MD Instructions for Use

TCW 2000 Ice liner refrigerator and freezer PIJ

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

Installation, operation and care Firewood boiler Vedolux 40 UB

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

Instructions for installation and use RE/I. Industrial electric heater for swimming pool

TECHNICAL SPECIFICATION

PRIMUS IMPORTANT. User Manual and Product Specifications. Portable Fridge/Freezer. Part No. PRI18LP - 18 Litre. Read instructions before operation.

Comfort Compact Controller ZG 252N

RE-PR3-E-27 3-Phase Panel Mount 27kW

CU 300 GRUNDFOS INSTRUCTIONS. Installation and operating instructions

AQUARIUS 45 MARINE SERVICE MANUAL

Accumulator tank. 1000, 750 and 500 litres Aqualux Teknik Aqualux UB Aqualux 750 CU

INDUCTION COOKER MODEL: EIC-G1810(BK) Owner s Manual. Please read this manual carefully before operating your set. Retain it for future reference.

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

Trouble Shooting Guide PWA, 3-phase (D10571)

Transcription:

Technical Guide Installation, Operation and Care EP E series 7 step electric boilers 26 and 42 kw Arkelstorpsvägen 88, 291 94 KRISTIANSTAD Tel +46 44-22 63 20, Telefax +46 44-22 63 58 e-mail: info@varmebaronen.se www.varmebaronen.se 01-01-17 ENG THL artnr

2001-01-17 EP E-series Contents: Functions... 2 Technical Details... 3 Installation, General... 4 Ambient temperature Water quality Placement of the boiler Cables and pipes Location of low current cable Safety and supply line Heating Installation... 4 Heating installation, general Flow requirements Recommended flow Pressure drop diagram Open system Closed system; <2.5 bar, <100 kw or <120 C <2.5 bar, <100 kw or <120 C Heating system with VVB Electric and oil-fired boilers in series Electrical Installation... 6 General Supply cable EP 26 E Supply cable EP 42 E Circulation pump External unit Load guard External blocking 0-10Vdc control 0-10Vdc of connected power Settings... 7 Number of power steps Circulation pump Fuse: Element Delayed Switch-on Electrical Diagram EP 26 E... 8 Electrical Diagram EP 42 E... 9 Control Electronics... 10 Control panel... 11 Starting... 11 Check after installation Start Operation & Care... 12 General Venting Overheat protection Excess temperature protection Safety valve Draining Risk for freezing Troubleshooting diagram... 13 Component specification... 14 Heating or industrial process The E series consists of a 26.2 kw and a 42 kw boiler. The boilers can be used for heating waterborne heating systems or for industrial processes. Construction The electric elements are made from stainless steel SS 2353 with a brass head. The pressure vessel is made from steel plating and is approved for 4 bar operational pressure. Connections for supply, safety and return lines and draining valve are at the rear of the boiler. Compact design Despite the compact design, 780 x 280 x 630 mm (h x w x d), there is plenty of room for electrical connections under the lid. Seven power steps The boiler s power output is divided into seven steps that are connected during temperature shortfall. The boiler temperature is adjustable at 20-95 C. The temperature controls adapt the power output to the heating requirements. The power can be limited to four power steps. From a safety perspective the boiler manages zero flow, so it does not need to be equipped with a flow indicator. Functions Load guard Load guard and 35-125 A transformer included. Delayed Switch-on Reconnection after power failure for more than three minutes to be carried out in accordance with the Electricity Producers norms. External control The boiler has a connection for external blocking or power control with a 0-10 Vdc signal. There is a 0-10 Vdc outlet for external display of connected power. Alarm Alarm indicator for overheat is on the front panel, there is also a connection for an external indicator. Outdoor temperature compensation There is an accessory available for outdoor temperature compensation, UTK E, for the control of supply temperature as a function of the outdoor temperature and selected heat curve. -2-

EP E-series EP 26 E 42 E Power 26.25 42 kw Current 37.9 61 A Step size 3.75 6 kw Current/step 5.4 8.7 A Connection cable, max area 16 25* mm 2 Technical Details Common data Voltage 400 3N~ V Frequency 50 Hz Cable fitting Ø 37 mm Water volume 17 litres Testing pressure 5.2 bar Operating pressure 4** bar Max temperature 120 C Operation temperature 20-95 C Pipe connection R 32 external thread 2001-01-17 Dimensions height 775 mm width 280 mm depth 630 mm Weight 50 kg Cladding class IP 24 * For 5-phase cable, dismantle the clamp on the neutral terminal ** Other pressure classes available. We reserve the right to make changes in design without prior notice. Front view, cross section Side view, cross section Rear view EP 26 E 1. Supply / safety pipe R32 external thread. 2. Return pipe R32 external thread. 3. Drainage valve R15. 4. Electric elements 5. Removable ceiling plate for connection space. 20. Cable bushings. 22. Adjustable bolts. Front panel EP 42 E -3-

2001-01-17 Installation EP E-series Ambient temperature To avoid unnecessary wear and tear of electrical components the ambient temperature must not exceed 30 C. Water quality The boiler is designed for non-oxygenated water. For areas with hard water, it is recommended that the water be treated before the boiler and heating system is filled. Hard water causes boiler scale. To avoid corrosion damage to elements and the heating plant, the ph should be as neutral as possible. (Neutral ph = 7) High levels of chloride in the water can cause damage to the stainless elements. If it is not possible to lower the chloride level then copper elements should be used instead. Placement of the boiler The boiler is approved for floor placement in accordance with the high power regulations. Wall brackets are available. Cables and pipes When laying cables and pipes it must be possible after installation to remove the front plate and open the roof plate of the boiler for service work. Placement of low power cable Low power cables must not run parallel with high power cables because induction could affect the low power cable signal. Safety and supply line If an open expansion vessel is not connected to the safety pipe then it must be equipped with automatic venting. Air could collect at the top of the boiler vessel and cause damage to the elements. The safety valve or expansion vessel safety pipe is connected to the supply pipe. Heating Installation Heating installation, general - Installation must be carried out in accordance with the Heating & Hot Water Regulations. - The boiler is mounted horizontally with vertical pipe connections to allow trapped air to escape. Flow requirements The boiler requires a constant and sufficiently large flow to function satisfactorily. If the flow is too low the following problems can occur: - The difference between the temperature setting and actual temperature in the boiler increases. - Unsettled regulation that increases wear and tear of the boiler s relays and contacts, with reduced service life as a result. If the flow is too large the following problems can occur: - Vibrations in the elements resulting in noise and reduced service life. -Unnecessary wear and tear on the system components. Below are the min and max and recommended flow for the boilers. Recommended flow gives a t at 10 C at max power. EP 26 E: min / max: 0.25-2 l/sec, t = 25-3 C recommended: 0.65 l/sec EP 42 E: min / max: 0.4-2 l/sec, t = 25-5 C recommended: 1 l/sec The boilers manage zero flow for safety reasons, but to maintain good function and avoid unnecessary wear and tear on the components, the flow recommendations must be followed. The pressure drop diagram shows the fall in pressure at different flows. The higher the operating temperature and temperature precision, the higher the flow. Pressure drop diagram Pressure drop kpa Flow litre/second -4-

EP E-series Open system The safety pipe must be a continuous, non-closable line rising up to the expansion vessel. The pressure height must exceed the pump s lowest statistical pressure on the suction side. Heating Installation 2001-01-17 Closed system; <2.5 bar, <100 kw and <120 C The safety and venting valves are mounted on the boiler safety pipe. Electric and oil-fired boilers in series If the boiler is dimensioned to 50% of the calculated energy requirements it would manage around 80% of the total energy consumption. When the electric boiler cannot cope with the requirements, the oil-fired boiler goes in and supports or takes over the heating. When the three-way valve H turns off the heat to the heating system (right gate closed), the boiler still has circulation via the pump G. The pump I ensures flow in the heating system through the bypass valve J. With valves E the oil fired boiler can be disconnected from the system and with valves F the electric boiler can be disconnected. >2.5 bar, >100 kw and >120 C Safety valves, emergency safeguard, pressure control and venting valve are mounted on the steam header on the boiler s supply and safety pipe. Heating system with VVB The boiler heats the hot water and heating systems. The systems work independently of each other. The supply temperature to the radiator system is controlled by a three-way valve H. When the heating system does not require any heat, the three-way valve is closed (left gate), the water then only circulates around the heating system. The flow through the boiler is retained by the circulation through the hot water heater. The meaning of the symbols in the above illustration: A Electric boiler J By-pass valve B Closed expansion vessel K Supply pipe C Oil-fired boiler L Return pipe D Safety valve M Air vent E Valve N Emergency protection F Cut-off valve O Pressure control G Circulation pump internal P Open expansion vessel H Three-way valve R Double-cupped VVB I Circulation pump heating Q Steam header -5-

2001-01-17 EP E-series Electrical Installation General - Electrical installation must be carried out under the supervision of a qualified installation engineer. - Installation must be in accordance with the high voltage directives. - The supply cable must be dimensioned in accordance with the high voltage directives. - A multi-polar breaker must be installed ahead of the boiler. - The water and water system must be filled and vented before the power is connected. Supply cable EP 26 E Supply cable, 5-phase, max 16 mm 2 Cu, 50 A fuse, connected to terminal in the boiler. Circulation pump Connecting the circulation pump to the boiler allows you to utilise the pump stop function and you can exercise the pump when not in use. The function can be turned off to provide continuous operation. Max 2 A. PLEASE NOTE, 230V External unit Fused socket for supply to external unit, max 2 A. PLEASE NOTE, 230V External blocking The power can be blocked by an external potential-free switch. An open switch reduces the power in steps. Existing lug is removed. 1 2 3 4 0-10V control The power can be controlled by an external 0-10Vdc signal, which corresponds to 0-100% of the installed power, see below. The lug between 2 and 3 is removed. 1 2 3 4 0-10Vdc GND EP 42 E The supply cable must be PEN or 5- phase of copper, max area 25 mm 2. The phase conductors are connected to a contactor, the earth to a neutral. Load guard Together with the current transformer, the load guard measures the load on the main fuses. The size of the main fuse, 35-125 A, is set on the printed circuit card. The current transformers are positioned on the cables that come from the fuses to be protected, normally the main fuses. 0-10V signal of connected power The boiler s connecting power can be obtained in the form of a 0-10Vdc signal, which corresponds to 0-100% of the installed power, see below. 1 2 3 4 0-10V GND The supply cable must be high voltage insulated, with a minimum area of 0.75 mm 2. Common conductor connected to terminal 4. 1 2 3 4 Installed power Selected number of steps corresponds to installed power. Example: The boiler is set so that the element only uses five output steps, 10.5 kw is then the installed power. At voltage control, 0-10Vdc, 10V is needed for all the five steps to work. The same concerns the voltage signal for the installed power. -6-

EP E-series Number of power steps If the boiler s total power output is not to be utilised it can be limited to min four steps. The number of steps corresponds to the installed power. EP 26 E: 3.8 kw/step EP 42 E: 6 kw/step Circulation pump The pump has two types of operation: 1: Continuous operation. 2: Summer operation / eco function. Means the pump stops eight hours after a power step was last connected. The pump is exercised every twelfth hour. The best function is attained when the boiler is controlled by an outdoor temperature compensator, UTK E. Settings Fuse: The load guard requires information about the size of the main fuse. This adjustment is only necessary if the load guard is to be used. Element The load guard requires information about the size of steps in kw. This parameter is preset at the factory and must not be changed. EP 26 E: 3.8 kw EP 42 E: 6 kw 2001-01-17 Delayed Switch-on According to the Swedish Association of Electricity Producers, only 50% of power output should be connected immediately, the rest must be delayed by one hour. This means that after a power failure longer than three minutes only three of the boiler s power steps are connected directly, the rest are connected in steps, if required, an hour after the power has returned. To test the boiler after it has been shut down for installation or service, the delayed Switch-on can be temporarily disconnected. This is done by pressing the QUICK button and keeping it pressed in until the status indicator glows with a steady light. Settings Number of power steps (1 & 2) OFF ON off on off on off off on on 4 step 5 step 6 step 7 step Circulation pump (3) Main fuse (1-3) off on eco or summer operation continuous operation EP 26 EP 42 off on off on off on off on off off on on off off on on off off off off on on on on 35 A 50 A 63 A 80 A 100 A 125 A 125 A 125 A Element / Step size (4-6) These values must not be changed EP 26 EP 42 off on off on off on off on off off on on off off on on off off off off on on on on 1,0 kw 1,4 kw 1,9 kw 2,1 kw 2,3 kw 3,0 kw 3,8 kw 6,0 kw Delayed Switch-on (7 & 8) off on off on off off on on 0h 1h 2h 2h Supply settings are in bold text. -7-

2001-01-17 EP E-series Electrical Diagram EP 26 E 1 2 4 3 5 6 7 8 9 Power Power group 1 11 Power group 2 Power group 3 12 13 10 Alarm 14 18 15 15 16 16 17 Power group one, 3,75 kw Power group two, 7,5 kw Power group three,15 kw (2 x 7,5 kw) 17 1. Current transformer, common conductor connected to terminal 4. 2. Temperature sensor. 3. Terminal for connection of external blocking, 0-10Vdc control and 0-10Vdc out for connected power output. See electrical installation. 4. Temperature settings, set point 5. Terminal for alarm, circulation pump and voltage supply to external unit. 6A fuse. PLEASE NOTE, 230V 6. Connection for supply cable. 7. Printed circuit card 8. Control breaker. 9. Operating fuse, also fuses the circulation pump and socket for external unit. 10. Indicators for: Operation, lit when there is voltage supply to the boiler. Power groups 1 3, lit when these are connected. Alarm, lit when overheat protection is released. 11. Alarm relay, stops at released excess temperature protection. 12. Overheat protection for power groups one and two. 13. Overheat protection for power group 3. 14. Contactors for power group 3. 15. Electric element for power group one, 3.75 kw. 16. Electric element for power group two, 7.5 kw. 17. Electric element for power group three, 2 x 7.5 kw 18. Plunger tube. -8-

EP E-series Electrical Diagram EP 42 E 2001-01-17 1 2 4 5 6 3 7 10 8 9 11 Power group 3 12 Power 13 Power group 1 16 17 18 19 14 15 Alarm 21 Power group 2 22 25 20 24 23 Power group one, 6 kw Power group two, 12 kw Power group three,24 kw (2 x12 kw) 20 23 24 1. Current transformer, common conductor connected to terminal 4. 2. Temperature sensor. 3. Terminal for connecting external blocking, 0-10Vdc control and 0-10Vdc out for connected power. See electrical installation. 4. Temperature settings, set point 5. Terminal for alarm, circulation pump and voltage supply to external unit. PLEASE NOTE, 230V 6. Connection for supply phase conductors, connected to contactor No. 11. 7. Neutral terminal. 8. Circuit board 9. Control breaker. 10. Operating fuse, also fuses the circulation pump and socket for external unit. 11. Contactors for power group three. 12. Indicator, power group three. 13. Indicator, operation lit when there is voltage supply to the boiler. 14. Indicator, power group one. 15. Indicator, alarm; lit when overheat protection is released. 16. Alarm relay. 17. Overheat protection for power groups one and two. 18. Overheat protection for half of power group three. 19. Overheat protection for half of power group three. 20. Electric element for power group one, 6 kw. 21. Indicator, power group two. 22. Contactors for power group two. 23. Electric element for power group two, 12 kw. 24. Electric element for power group three, 2 x 12 kw 25. Plunger tube. -9-

Control Electronics 2001-01-17 EP E-series 1 Terminal for circulation pump. The pump has two types of operation: 1: Continuous operation. 2: Summer operation / eco function. Means that the pump stops eight hours after a power step was last used. The pump is exercised every twelfth hour. Best function is achieved when an outdoor temperature compensator, UTK E, operates the boiler. Choice is made with the breaker, see item 5. 2 Terminal for power group three. 3 Terminal for power group two. 4 Terminal for power group one. 5 Breaker for setting operating parameters, see Settings 6 Status indicator. Steady glow: Normal operation. Long + a short flash: Delayed Switch-on is blocking the power steps. Long + two short flashes: Load guard, external blocking or 0-10V control limiting the power steps. Long + three short flashes: Damaged temperature sensor or excess temperature. Quick flashes: Quick running of delayed Switchon with the help of QUICK. Off: No power or the set point is lower than 15 C; can occur when a UTK E is connected. 7 Indicator for power group three. 8 Indicator for power group two. 9 Indicator for power group one. 10 QUICK button. Used for temporary disconnection of delayed Switchon and quick connection of the power steps. 11 Temperature and set point settings. Setting range 20-95 C. 12 Terminal for connecting external control units. External blocking can occur via an external potential free contact or with a 0-10Vdc signal, 0-100% of installed power output, permitted number of steps. If the latter is used for regulating the temperature, the boiler s set point should be set at the highest permitted temperature for the system. External operation control, a 0-10Vdc signal, 0-100%, of installed power output obtained from the boiler. 13 Temperature sensor, placed in a plunger tube on the boiler vessel s element base. 14 Current transformers for load guard function. With the help of the current transformers, the load guard measures the load, 35-125A, on the main fuses. At overload, the boiler power is reduced. 5 1 2 3 4 10 11 The power is reconnected when the load has decreased. Temperature control Temperature control regulates the power binarily in seven steps. The connection time between the steps is decided by the temperature difference between the actual value and set point and the actual increase in temperature. When the actual temperature is within ±2 C relative set point there are no changes to the connected power. An outdoor temperature compensator, UTK E, is available, which replaces the boiler s set point with a function that allows the temperature to be decided by the outdoor temperature and the selected heat curve. UTK E provides an improved eco function and frost protection. The excess temperature function immediately breaks all connected power if the boiler temperature exceeds the set point by more than 5 C. When the 6 = Connected power group = Non-connected power group 7 8 9 1 2 3 4 1 2 3 4 1 2 1 2 3 4 12 13 14 excess temperature subsides, the power is reconnected again without the need for manual resetting. There is also a function that checks that the temperature sensor is in one piece. The status indicators blink when any of these functions start. Binary control The boiler regulates the power with binary power steps, which means the various power groups are connected as in the table below. The power for the lit lamps is added up to give the total power. The first power group make up approx. 15% of the total power, the second group approx. 30% and the third approx. 55%. Power step Power group Total power (kw) 1 2 3 EP 26 EP 42 1 3,75 6 2 7,5 12 3 11,25 18 4 15 24 5 18,75 30 6 22,5 36 7 26,25 42-10-

EP E-series Control panel 2001-01-17 Control panel 1. Operation indicator, lit when the boiler is working normally. 2. Control breaker. 3. Indicator for power group one, 15% of the total power. 4. Indicator for power group two, 30% of the total power. 5. Indicator for power group three, 55% of the total power. 6. Temperature and set point settings. 7. Alarm, released overheat protection. 8. Reset overheat protection, EP 42 E only, power groups one and two. 9. Reset overheat protection. EP 26 E: power groups one and two. EP 42 E: half of power group three. 10.Reset overheat protection. EP 26 E: power group three. EP 42 E: half of power group three. 11.Thermometer. 1 2 6 3 7 4 5 8 9 10 11 Starting Check after installation Check there are no tools etc. left inside the boiler s connection area. Ensure that the boiler and heating system is full of water and vented before putting into operation. Start A. A complete inspection of the electrical system is required before starting. B.Put the main breakers and operation breakers in On position. The operation indicator should now be lit and the status indicators on the circuit board should blink. C.Set the required temperature. D.Because the boiler has been without current, only three power steps will be connected. The rest are connected after an hour if so required. The delayed Switch-on is indicated by the status indicator on the circuit board. For checking the boiler s functions, the delayed Switch-on can be disconnected for installation or service. This is done by pressing the QUICK button on the circuit board and keeping it pressed down until the status indicator shines with a steady glow. E.The boiler will now step up the required number of power steps according to the binary control until the temperature coincides with the set value. To reduce step up time, the QUICK button can be kept pressed in until the required number of steps has been reached. Delayed Switch-on According to the Swedish Association of Electricity Producers norms, only 50% of power output should be connected immediately, the rest must be delayed by one hour. This means that after a power failure longer than three minutes, only three of the boiler s power steps are connected directly, the rest are connected in steps, if required, an hour after the power has returned. To test the boiler after it has been shut down for installation or service, the delayed Switch-on can be temporarily disconnected. This is done by pressing in the QUICK button and keeping it pressed in until the status indicator glows with a steady light. -11-

Operation & Care 2001-01-17 EP E-series General Check with the installation engineer that the plant is in full working order after installation. Ask him to show you the functions so you are quite clear about how the plant works. Check the water pressure, there could be air left in the system some time after installation so vent and check the system at least one more time. Venting To quickly remove the oxygen in the fresh water, leave the boiler in operation a few hours with a high operation temperature, 80-90 C. Vent then set the normal operation temperature. Overheat protection The boiler has two respective three overheat protection that releases when the boiler temperature exceeds approx. 100 C. The protection is reset behind screws on the front panel. You can reset when the temperature is under 80 C. Excess temperature protection An excess temperature function compliments the overheat protection. The purpose of the excess temperature protection is to disconnect all power during temporary increases in temperature that could occur due to rapidly reduced water flow through the boiler during pump stop etc. All power steps are immediately disconnected. When the temperature has sunk to the set value, the power is reconnected again in steps without the need to reset. The function comes into play when the boiler temperature exceeds the set value by more than 5 C. Safety valve The safety valve, which is mounted in the heating system together with the closed expansion system, must be regularly exercised about 4 times a year in order to maintain its safety function. Draining The electric element must be turned off before draining the system to avoid damage. Risk for freezing No part of the system is to be turned off during severe cold due to risk for frost damage. Send for an installation engineer if you suspect that a part of the system is frozen. Drain the water if the system is not to be used for some time. -12-

EP E-series Troubleshooting diagram 2001-01-17 PLEASE NOTE. Any work demanding tools must be carried out by an authorised electrical engineer. Begin troubleshooting by checking the status indicators on the circuit board inside the boiler. See page 10, item 6. Causes concerning these indicators are not taken up here. Fault Possible cause Correction: Operation indicator off. Operation indicator on but no heat. Group fuse blown. The boiler does not step up despite the temperature in the boiler being lower than the set value of the thermostat. The boiler has no current. Main and or control breaker off. Operational fuse blown. Indicator lamp broken. Fault in the system electronics. The element is broken. The boiler is step limited. The boiler is controlled by an external 0-10V signal. The outdoor temperature compensator is connected so that the regular thermostat does not control the boiler temperature. The temperature sensor is defective Check the main fuses. Put the breakers into ON position. Delayed Switch-on stops the boiler if it has been without current for more than 3 minutes. Check the location of the short circuit, put right and then reset the fuse. Change the lamp. Change the circuit board. Break the control and working breaker and the operational fuse, then insulation test the elements. To change the element, remove the boiler s bottom front plant and insulation. Disconnect the electrical connections and unscrew the defective elements. A box spanner for removing the elements is available from Värmebaronen. When the new elements are in place, check there are no electric cables touching them. Check the setting, see page 7 Number of power steps. The boiler s set point is too low. Check the UTK E settings Check measure the temperature sensor. PLEASE NOTE. The sensor must not be connected to the circuit board during measuring. The Temperaturgivarens temperature sensor s resistans resistance C kω C kω C kω C kω 0 32,7 25 10,0 50 3,6 75 1,5 5 25,4 30 8,1 55 3,0 80 1,3 10 19,9 35 6,5 60 2,5 85 1,1 15 15,7 40 5,3 65 2,1 90 0,9 20 12,5 45 4,4 70 1,8 95 0,8 Unsettled control, the boiler steps up a number of steps only to immediately step down again. Not enough water flow through the boiler. Check that the circulation pumps and valves are in working order. The flow can be checked in the following way: - Limit the boiler to 4 steps. - Let the boiler s temperature stabilise. - Measure the temperature difference between the flow and return. - Calculate the flow through the boiler in accordance with the following formula. - Check the flow is sufficient on the pressure drop diagram. q = P t x 1,16 q = Water flow in m 3 /hour. P = The boiler s output in kw. t = Temperature difference in C. 1.16 =The heat-absorption quality of the water. For flow in litre per second, multiply q with 1000/3600-13-

2001-01-17 Component Specification EP E-series Pos. Part No. Component Both 26 E 42 E 1 11 00 49 Element 3.75 kw 1 2 11 00 19 Element 7.5 kw 3 1 11 00 16 Element 6 kw 1 2 11 00 44 Element 12 kw 3 3 12 00 20 Overheat protection 100 C 2 3 4 13 00 32 Control switch 2 pol 1 5 16 00 18 Neutral terminal NPF 35 1 5 16 00 20 Earth bar JS 35 1 6 17 00 06 Relay 1-pol vx 1 7 17 00 73 Contactor 100-C30, 230V 1 8 17 00 75 Contactor 100-C43, 230V 1 9 18 00 22 Circuit breaker 1 pol, 6A 1 10 19 00 05 Lamp round 230V, orange, pin 1 11 19 00 06 Lamp round 230V, red, pin 1 12 19 00 08 Lamp round 400V, orange, pin 3 13 21 01 02 Potentiometer OX7E 1 21 02 00 Temperature sensor 1 14 21 02 17 Circuit board OX 7E125 1 24 03 50 Draining valve R15 ext 1 30 00 17 O-ring for element 4 36 00 21 Current transformer 3 15 38 00 03 Thermometer 0-120 C 1 1 2 2 2 15 3 12 10 13 11 4 3 9 7 6 15 13 12 10 14 11 4 EP 26 E 9 7 6 8 5 14 EP 42 E -14-