McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

Similar documents
APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

McQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC)

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)

Multistack Modbus Driver: Standard Unit

Honeywell Modbus Solution: 7800 Series Burner Controller through S7810M Modbus Module

McQuay Microtech III BACnet MS/TP Application 4181 Point Map

APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit

LONWORKS Solution for Orion PT-LON-Link

MicroTech Series 200 Centrifugal Chiller

Open Protocol Data Communications

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

Pneumercator Driver: TMS 2000/3000

MicroTech Series-200 Flooded Screw Chiller

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED

MicroTech Water-Cooled Screw Chiller Controller

GeneSys Air-Cooled Screw Compressor Chiller

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

Air-Cooled Scroll Compressor Chiller

INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER

INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN

Air-Cooled Scroll Compressor Chiller

Water-Cooled Scroll Compressor Chillers

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Pathfinder Air-Cooled Chillers

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

Metasys Integrator McQuay Application

Pathfinder Air-Cooled Chillers

Chapter-8 Capacity Control of Refrigeration Systems

Water-Cooled Scroll Compressor Chillers

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Air-Cooled Scroll Compressor Water Chillers

CONTROLS MANUAL. Touch Pilot Control. 30XA/XAS/XB/XBP/XW 30XA-ZE/XW-ZE AquaForce PUREtec with R-1234ze(E) Operation instructions.

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Air-Cooled Scroll Compressor Water Chillers

Air-Cooled Scroll Compressor Chiller

Engineered for flexibility and performance

Air-Cooled Screw Compressor Chillers

Air-Cooled Scroll Condensing Units

Touch Pilot Control 30XA/XAS/XB/XBP/XW 30XA-ZE/XW-ZE. AquaForce PUREtec with R-1234ze(E) Original document

GeneSys. Air-Cooled Screw Compressor Chillers. Catalog

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Water-Cooled Screw Compressor Chillers

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers

Centrifugal Compressor Water Chillers Catalog 605 Models WSC, WDC, WCC, HSC

Ice Rink (Single and Dual Configurations) Custom Control Features

OPERATING MANUAL Enertronic Control System 2

Centrifugal Compressor Water Chillers THE DISTINCTION SERIES

Call us today! (800)

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Call us today! (800)

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

CONTROLS MANUAL. Touch Pilot Control. 30XA/XAS/XW 30XA-ZE/XW-ZE AquaForce PUREtec with R-1234ze(E) Operation instructions.

Technical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

The McQuay DISTINCTION SERIES. Single/Dual Compressor Centrifugal Chillers. Installation and Maintenance Manual

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Air-cooled chillers with single-screw compressor. Installation, operation and maintenance manual D - KIMAC EN. Original Instructions

Water-Cooled Screw Compressor Chillers

Air-Cooled Scroll Condensing Units

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

PACKAGED AIR COOLED Product Data Catalog

User Guide. Tracer CH530 Control System for Scroll Chillers CGAN/CXAN CGCL CGWH/CCUH CGWN/CCUN RAUL

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

Case 8 Basic Performance of Screw Compressor

Call us today! (800)

Magnitude Frictionless Centrifugal Chillers

NEW CHILLER SCHEDULE

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

POWERS CONTROLS Pneumatic Thermostat Covers

YCIV Hz & Hz

Water-Cooled Screw Compressor Chillers

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Centrifugal Compressor Water Chillers

The Refrigeration Cycle

The McQuay DISTINCTION SERIES. Single/Dual Compressor Centrifugal Chillers. Installation, Operating and Maintenance Manual

Technical Bulletin (TB-0037)

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

The Refrigeration Cycle

Condensing Unit Installation and Operating Instructions

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

Installation Manual IM

Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International

Catalog Water-Cooled Scroll Compressor Chillers

Presented By: John Dolan, P.E.

OPERATING MANUAL Enertronic Control System 2

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Water-Cooled Screw Compressor Chillers

Magnitude Magnetic Bearing Centrifugal Chillers

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

SECTION ROTARY-SCREW WATER CHILLERS

Transcription:

Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV) Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller Point Map, Application 4029. Point Type Description Range/Units a,b,c 1 LAO Address 2 LAO Application 4029 3 LAI Active Setpoint F 4 LAI Actual Capacity % 5 LAI Capacity Limit % 6 LAO Capacity Limit Setpoint % 7 LDO Chiller Enabled Disable/Enable 8 LDI Chiller Limited No/Yes 9 LDI Chiller Remote/Local Remote/Local 10 LAO Chiller Mode 1=Heat 3=Cool 5=Pre-cool 11=Ice 11 LDI Chiller On/Off Off/On 12 LAI Chiller Status 1=Off 2=Start 3=Run 4=Pre-shutdown 5=Service 13 LAI Compressor Discharge Temperature F 14 LAI Compressor Percent RLA % RLA 15 LAI Compressor Run Hours hr 16 LAO Compressor Select 17 LAI Compressor Starts starts 18 LAI Compressor Suction Line Temperature F 19 LAI Condenser Entering Water Temperature F Siemens Building Technologies, Inc. Page 1 of 10

Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller Point Map, Application 4029. (continued) Point Type Description Range/Units a,b,c 20 LAI Condenser Leaving Water Temperature F 21 LDI Condenser Flow Switch Status No Flow/Flow 22 LAI Condenser Pump Run Hours hr 23 LAI Condenser Refrigerant Pressure psi 24 LAI Condenser Saturated Refrigerant Temperature F 25 LDI Condenser Water Pump Status Off/On 26 LAO Cool Setpoint 10 to 120 F -12.2 to 48.9 27 LAI Evaporator Entering Water Temperature F 28 LAI Evaporator Leaving Water Temperature F 29 LDI Evaporator Flow Switch Status No Flow/Flow 30 LAI Compressor Evaporator Leaving Water Temperature F 31 LAI Evaporator Pump Run Hours hr 32 LAI Evaporator Refrigerant Pressure psi 33 LAI Evaporator Saturated Refrigerant Temperature F 34 LDI Evaporator Water Pump Status Off/On 35 LAI Heat Recovery Entering Water Temperature F 36 LAI Heat Recovery Leaving Water Temperature F 37 LAO Heat Setpoint 50 to 120 F 10.0 to 48.9 38 LAO Ice Setpoint 15 to 35 F -9.4 to 1.7 40 LAI Liquid Line Refrigerant Temperature F 41 LAI Oil Feed Pressure psi 42 LAI Oil Feed Temperature F 43 LAI Oil Sump Pressure psi 44 LAI Oil Sump Temperature F 46 LAO Pump Select 47 LAI Warning Alarms SeeTable2 Page 2 of 10 Siemens Building Technologies, Inc.

Table 1. Microtech II Water-Cooled Centrifugal Chiller Controller Point Map, Application 4029. (continued) Point Type Description Range/Units a,b,c 48 LAI Problem Alarms SeeTable2 49 LAI Fault Alarms SeeTable2 50 LDO Clear Alarm No/Yes a Values noted for LDIs and LDOs are in the following format: OFF text/on text. b This column indicates the value/range or engineering units or both if known. c The default English value is not italicized. An italicized entry indicates an SI value. Alarm Messages (Points 47 through 49) Use Table 2 to interpret the Warning (Point 47), Problem (Point 48), and Fault (Point 49) alarm messages. Values 1 through 4 are of a Warning class and apply to Point 47. Values 5 through 50 are of a Problem class and apply to Point 48. Values 52 through 224 are of a Fault class and apply to Point 49. Table 2. Chiller Alarm Values (Points 47, 48, and 49). 1 W NO ACTION Condenser Entering Water Temperature Sensor Failure 2 W NO ACTION Evaporator Entering Water Temperature Sensor Failure 3 W NO ACTION Liquid Line Refrigerant Temperature Sensor Failure 4 W NO ACTION (STOP if Heat) Condenser Leaving Water Temperature Sensor Failure 5 P RESTART DELAYED Power Loss While Running 6 P RESTART DELAYED Power Loss While Running 7 P RESTART DELAYED Power Loss While Running 8 P RESTART DELAYED Power Loss While Running 10 P START INHIBITED Ambient Temperature Low 11 P INHIBIT LOAD Condenser Pressure High 12 P INHIBIT LOAD Condenser Pressure High 13 P INHIBIT LOAD Condenser Pressure High 14 P INHIBIT LOAD Condenser Pressure High 15 P UNLOAD Condenser Pressure High 16 P UNLOAD Condenser Pressure High 17 P UNLOAD Condenser Pressure High 18 P UNLOAD Condenser Pressure High 19 P UNLOAD Condenser Pressure High 20 P CONDENSER PUMP ON Condenser Water Freeze Protection 21 P CONDENSER PUMP ON Condenser Water Freeze Protection Siemens Building Technologies, Inc. Page 3 of 10

24 P PUMP START ATTEMPTED Condenser Pump Failure 25 P PUMP START ATTEMPTED Condenser Pump Failure 26 P LOAD Discharge Temperature High 27 P LOAD Discharge Temperature High 30 P NO EWT RESET Entering Evaporator Temperature Sensor Failure 31 P INHIBIT LOAD Evaporator Pressure Low 32 P INHIBIT LOAD Evaporator Pressure Low 33 P INHIBIT LOAD Evaporator Pressure Low 34 P INHIBIT LOAD Evaporator Pressure Low 35 P INHIBIT LOAD Evaporator Pressure Low 36 P UNLOAD Evaporator Pressure Low 37 P UNLOAD Evaporator Pressure Low 38 P UNLOAD Evaporator Pressure Low 38 P UNLOAD Evaporator Pressure Low 38 P UNLOAD Evaporator Pressure Low 41 P UNLOAD Compressor Motor Current High 42 P UNLOAD Compressor Motor Current High 43 P UNLOAD Compressor Motor Current High 44 P UNLOAD Compressor Motor Current High 45 P EVAPORATOR PUMP ON Evaporator Water Freeze Protection No. 1 46 P EVAPORATOR PUMP ON Evaporator Water Freeze Protection No. 2 49 P PUMP START ATTEMPTED Evaporator Pump Failure 50 P PUMP START ATTEMPTED Evaporator Pump Failure 52 F COMPRESSOR SHUTDOWN Outside Air Temperature Sensor Fault 61 F COMPRESSOR SHUTDOWN Motor Current Low 62 F COMPRESSOR SHUTDOWN Motor Current Low 63 F COMPRESSOR SHUTDOWN Motor Current Low 64 F COMPRESSOR SHUTDOWN Motor Current Low 65 F UNIT SHUTDOWN Motor Protector Trip 66 F COMPRESSOR SHUTDOWN Motor Protector Trip 67 F COMPRESSOR SHUTDOWN Motor Protector Trip 68 F COMPRESSOR SHUTDOWN Motor Temperature High 69 F COMPRESSOR SHUTDOWN Motor Temperature High 70 F COMPRESSOR SHUTDOWN Motor Temperature High Page 4 of 10 Siemens Building Technologies, Inc.

71 F COMPRESSOR SHUTDOWN Motor Temperature High 72 F COMPRESSOR SHUTDOWN Phase Loss 73 F COMPRESSOR SHUTDOWN Phase Loss 74 F COMPRESSOR SHUTDOWN Phase Loss 75 F COMPRESSOR SHUTDOWN Phase Loss 88 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 89 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 90 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 91 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 92 F COMPRESSOR SHUTDOWN Condenser Pressure Sensor Fault 93 F COMPRESSOR SHUTDOWN Condenser Water Flow Loss 94 F COMPRESSOR SHUTDOWN Condenser Pressure High 95 F COMPRESSOR SHUTDOWN Condenser Pressure High 96 F COMPRESSOR SHUTDOWN Condenser Pressure High 97 F COMPRESSOR SHUTDOWN Condenser Pressure High 98 F COMPRESSOR SHUTDOWN Condenser Pressure High 99 F COMPRESSOR OFF Current High with Compressor OFF 100 F COMPRESSOR OFF Current High with Compressor OFF 103 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 104 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 105 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 106 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor Fault 107 F COMPRESSOR SHUTDOWN Discharge Temperature High 108 F COMPRESSOR SHUTDOWN Discharge Temperature High 109 F COMPRESSOR SHUTDOWN Discharge Temperature High 110 F COMPRESSOR SHUTDOWN Discharge Temperature High 111 F COMPRESSOR SHUTDOWN Condenser Entering Water Temperature Sensor Fault 112 F COMPRESSOR SHUTDOWN Evaporator Water Flow Loss 113 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Low (Freeze) Siemens Building Technologies, Inc. Page 5 of 10

114 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 115 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 116 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 117 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 118 F COMPRESSOR SHUTDOWN Evaporator Pressure Low 119 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 120 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 121 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 122 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 123 F COMPRESSOR SHUTDOWN Evaporator Pressure Sensor Fault 124 F COMPRESSOR SHUTDOWN Ground Fault Trip 125 F COMPRESSOR SHUTDOWN Ground Fault Trip 126 F COMPRESSOR SHUTDOWN Ground Fault Trip 127 F COMPRESSOR SHUTDOWN Ground Fault Trip 128 F COMPRESSOR SHUTDOWN Lift Pressure Low 129 F COMPRESSOR SHUTDOWN Lift Pressure Low 130 F COMPRESSOR SHUTDOWN Lift Pressure Low 131 F COMPRESSOR SHUTDOWN Lift Pressure Low 132 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 133 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 134 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 135 F COMPRESSOR SHUTDOWN Liquid Line Pressure Sensor Fault 136 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 137 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 138 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 139 F COMPRESSOR SHUTDOWN Liquid Line Temperature Sensor Fault 140 F UNIT LOCKOUT Number of Allowed Re-starts Exceeded Page 6 of 10 Siemens Building Technologies, Inc.

141 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 142 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 143 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 144 F COMPRESSOR LOCKOUT Number of Allowed Re-starts Exceeded 145 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Sensor Fault 146 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Sensor Fault 147 F COMPRESSOR SHUTDOWN Evaporator Leaving Water Temperature Sensor Fault 150 F UNIT STOP Mechanical High Pressure Trip 151 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 152 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 153 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 154 F COMPRESSOR SHUTDOWN Mechanical High Pressure Trip 155 F COMPRESSOR SHUTDOWN Oil Net Pressure Low 156 F COMPRESSOR SHUTDOWN Oil Net Pressure Low 159 F COMPRESSOR SHUTDOWN Oil Feed Temperature High 160 F COMPRESSOR SHUTDOWN Oil Feed Temperature High 163 F COMPRESSOR SHUTDOWN Oil Feed Temperature Low 164 F COMPRESSOR SHUTDOWN Oil Feed Temperature Low 167 F COMPRESSOR SHUTDOWN Oil Feed Temperature Sensor Fault 168 F COMPRESSOR SHUTDOWN Oil Feed Temperature Sensor Fault 171 F COMPRESSOR SHUTDOWN Oil Level Low 172 F COMPRESSOR SHUTDOWN Oil Level Low 173 F COMPRESSOR SHUTDOWN Oil Level Low 174 F COMPRESSOR SHUTDOWN Oil Level Low 175 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 176 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 177 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 178 F COMPRESSOR SHUTDOWN Oil Filter Delta Pressure High 179 F COMPRESSOR SHUTDOWN Oil Feed Pressure Sensor Fault Siemens Building Technologies, Inc. Page 7 of 10

180 F COMPRESSOR SHUTDOWN Oil Feed Pressure Sensor Fault 183 F COMPRESSOR SHUTDOWN Oil Sump Pressure Sensor Fault 184 F COMPRESSOR SHUTDOWN Oil Sump Pressure Sensor Fault 187 F COMPRESSOR SHUTDOWN Oil Sump Temperature Sensor Fault 188 F COMPRESSOR SHUTDOWN Oil Sump Temperature Sensor Fault 191 F COMPRESSOR SHUTDOWN Starter Fault Compressor 192 F COMPRESSOR SHUTDOWN Starter Fault Compressor 193 F COMPRESSOR SHUTDOWN Starter Fault Compressor 194 F COMPRESSOR SHUTDOWN Starter Fault Compressor 195 F COMPRESSOR SHUTDOWN Starter Fault Compressor 196 F COMPRESSOR SHUTDOWN No Starter Transition 197 F COMPRESSOR SHUTDOWN No Starter Transition 200 F COMPRESSOR START ABORT Oil Pressure Low 201 F COMPRESSOR START ABORT Oil Pressure Low 204 F COMPRESSOR SHUTDOWN Subcooling Low 205 F COMPRESSOR SHUTDOWN Subcooling Low 206 F COMPRESSOR SHUTDOWN Subcooling Low 207 F COMPRESSOR SHUTDOWN Subcooling Low 208 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Running 209 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Running 212 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Starting 213 F COMPRESSOR SHUTDOWN Surge Suction Superheat High-Starting 216 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault 217 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault 218 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault 219 F COMPRESSOR SHUTDOWN Suction Temperature Sensor Fault Page 8 of 10 Siemens Building Technologies, Inc.

220 F COMPRESSOR START ABORT Vanes Open or No Condenser Flow 221 F COMPRESSOR START ABORT Vanes Open or No Condenser Flow 224 F COMPRESSOR SHUTDOWN (Check Chiller Display for Cause) Siemens Building Technologies, Inc. Page 9 of 10

Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. 2004 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. 1000 Deerfield Parkway Country of Origin: US Buffalo Grove, IL 60089-4513 Page 10 of 10 U.S.A.