INSTALLATION MANUAL. Model UAT150CGXY1 UAT180CGXY1 UAT240CGXY1 UAT300CGXY1 UAT150CGXY19 UAT180CGXY19 UAT240CGXY19 UAT300CGXY19.

Similar documents
INSTALLATION MANUAL. Models. English. Deutsch. Français. Nederlands. Español. Italiano. Ελληνικά. Portugues. Русский. Türkçe

INSTALLATION MANUAL AIR COOLED, DUCTED SPLIT TYPE AIR-CONDITIONERS SPLIT TYPE. Part No.:R IM-MHSB-0806-DAIKIN

FWC02AAFNMV1 FWC03AAFNMV1 FWC04AAFNMV1 FWC05AAFNMV1 FWC06AAFNMV1

DAIKIN ROOM AIR CONDITIONER. Operation Manual

DAIKIN ROOM AIR CONDITIONER. Operation Manual. English. Deutsch. Français. Nederlands. Español. Italiano. Ελληνικά. Portugues. Русский.

OPERATION MANUAL. System Inverter Air Conditioners FXNQ20A2VEB FXNQ25A2VEB FXNQ32A2VEB FXNQ40A2VEB FXNQ50A2VEB FXNQ63A2VEB

DUCTED AIR CONDITIONER. Owner s Manual. KD Series KD24. Kaden Owner s Manual 1

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)

Operation manual. Split system air conditioners FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B. Operation manual Split system air conditioners

Split Portable Air Conditioner

General safety precautions English

OPERATION MANUAL. Split series room air conditioners Multi system room air conditioners FDBQ25B7V1

Owner s Manual. Middle Static Pressure Duct Type MEU-18MPH2 MEU-24MPH2 MEU-36MPL2 MEU-48MPL2 MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER

General safety precautions English

General safety precautions English

OPERATING MANUAL AIR CONDITIONER DUCT TYPE. ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

General safety precautions English

OPERATION MANUAL. Split series room air conditioners Multi system room air conditioners FDBQ25B7V1

Operating Instructions Air Conditioner

ULTRA LOW TEMPERATURE FREEZER. User Manual

AIR CONDITIONER OWNER S MANUAL. Please read this manual carefully before operating your set and retain it for future reference.

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G

Model No.: PS08-01 PS10-01 Ref: KY80 KY100

GS-2. Instruction Manual. G-Series Cooler

AIR COOLED MINI CHILLER

WINDOW TYPE ROOM AIR CONDITIONER OPERATION AND INSTALLATION MANUAL

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

USER S MANUAL HSC-14/18/24/24A

OWNER S MANUAL KPD-105 DTN11 KPD-140 DVN11 KPD-140 DTN11 KPD-160 DTN11 KPD-52 DVR11

PORTABLE AIR CONDITIONER (LOCAL)

Owner s Manual Super-Slim Four-Way Cassette

Portable Air Conditioner with Evaporative Technology PE6-10R-03 Operating Instructions. Model No. PE6-10R Soleus Air International

THROUGH-WALL AIR-TO-AIR HEAT PUMP AND AIR CONDITIONER. Instruction Manual. Model AMB-12H

Owner s Manual INVERTER ONE-TWO/ONE-THREE /ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

Operating Instructions

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

Split Air Conditioner

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type) VAM150FC VAM250FC

R410A. AIR CONDITIONER DUCT TYPE / ART Series OPERATING MANUAL. REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A.

Owner s Manual INVERTER ONE-TWO/ONE-THREE /ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

KSD-35 DR11 KUE-35 DVN11

Installation Instructions

Using the Remote Control Unit

OPERATING MANUAL. AIR CONDITIONER Duct Type. Indoor Unit ARTG36LH ARTG45LH ARTG54LH ARTG60LH PART NO KEEP THIS MANUAL FOR FUTURE REFERENCE

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

5) Do not start or stop the unit by inserting or pulling out the power plug.

Operation Manual Portable Room Air Conditioner Models: RPC26WA / RPC35WA / RPC41WA

MODEL: DCB07(2.2kW Cooling / 2.05kW Heating) DCB09(2.6kW Cooling / 2.4kW Heating) DCB14(4.1kW Cooling / 3.6kW Heating) DCB05C(1.

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

R407C TECHNICAL MANUAL. Packaged Air Conditioner Rooftop A series. UATP-A and UATYP-A Series. Cooling only & Heatpump [50Hz]

General safety precautions English

Dual-Hose Portable Air Conditioner User Manual

IMPORTANT INSTRUCTIONS READ & SAVE

Radiant Heater. Instruction Manual QH-200 N13275

Operating Instructions Air Conditioner

AIR CONDITIONER. Please read this owner, s manual carefully before using the air conditioner, and keep this manual for the future reference.

Portable Air Conditioner 6,000 BTU 8,000 BTU 10,000 BTU

AIR CONDITIONER OWNER S MANUAL. Please read this manual carefully before operating your set and retain it for future reference.

Owner s Manual Window Air Conditioner

USER'S MANUAL PGE Single Package Rooftop

Convection Panel Heater

USER MANUAL. Safety Precautions. Unit Specifications and Features. Operating Instructions. Installation Instructions.

OWNER S MANUAL. Portable Air Conditioner. Product defect? Not working properly? DO NOT return this product to the store where you purchased it.

DH 100 P. Always Dry dehumidifier. with. Condensation Removal System

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

Operating Instructions Air Conditioner

Inverter Split-type Room Air Conditioner

GS-1. Instruction Manual. G-Series Cooler. Manual is for the following models: GS-1-N14NF GS-1-N14NG GS-1-N14NI COUNTERTOP COOLER

Indoor Unit (2 Series)

INSTALLATION AND USER MANUAL

2.9kW Portable Air Conditioner

Installation and operation manual

AIR CONDITIONER OWNER S MANUAL. Please read this manual carefully before operating your set and retain it for future reference.

Installation Instructions

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

SYSTEM Inverter Air Conditioners

Quest Power Electric Heat EHS 31 Pro

GDDEM10 DEHUMIDIFIER

10L Dehumidifier. Model Number: LDH V AC 50/60Hz 290W

AIR CONDITIONER ELECTRONIC CONTROL

With Remote Control. English

Si REMOVAL PROCEDURE. 4.0/5.0/5.2/5.8/6.8/7.5 kw Class. Outdoor Unit Inverter Multi Type

1.6kW Window / Wall Air Conditioner

Operating Instructions Air Conditioner

ED-FUW-2014 (50 Hz/60 Hz) Catalogue/Engineering Data. Large-Sized Chilled Water Fan Coil Unit (50/60 Hz) FUW040A DAIKIN INDUSTRIES, LTD.

AIRREX DEHUMIDIFIER ADH-100 USER S MANUAL

Manual is for the following models: G-26 GCG-26 GCG-26-C31N* G-26-C31N* GCG-26-C231N* GCG-26-CA31N* *G,I,M,7,J plug. Instruction Manual.

Portable Air Conditioner User Manual

OPERATING MANUAL AIR CONDITIONER CASSETTE TYPE. AUT Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

HEAT & COOL MODEL (REVERSE CYCLE)

INSTRUCTION MANUAL Water Dispenser

2.9kW Portable Air Conditioner

OPERATION MANUAL. SYSTEM Inverter Air Conditioners FXAQ15PAV1 FXAQ20PAV1 FXAQ25PAV1 FXAQ32PAV1 FXAQ40PAV1 FXAQ50PAV1 FXAQ63PAV1

SLIDER CASEMENT AIR CONDITIONER

Quest Power Electric Heat EHS 62 Pro

11,000 BTU Portable Air Conditioner with dehumidifier & Fan PE4-11R-03 Operating Instructions. Model No. PE4-11R Soleus Air International

Installation Instructions

OPERATION MANUAL. Air Conditioners FXAQ20PV1 FXAQ25PV1 FXAQ32PV1 FXAQ40PV1 FXAQ50PV1 FXAQ63PV1. MODELS Wall-mounted type. English. Deutsch.

General safety precautions English

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY

Transcription:

INSTALLATION MANUAL Installation Manual Rooftop Package Air Conditioner English Model UAT50CGXY UAT80CGXY UAT20CGXY UAT300CGXY UAT50CGXY9 UAT80CGXY9 UAT20CGXY9 UAT300CGXY9 IM-RTC-072(0)-DAIKIN Part No.: R080903790

Model: UAT50C OUTLINE AND DIMENSIONS 855.0 2.0 English 965.0 800.0 82.5 390.0 988.0 50.0 652.0 68.0 652.0 99.0 65.0 652.0 68.0 652.0 25.0 700.0 350.0 50.0 99.0 Original Instruction 630.0 8.0 82.5 CONTROL BOX 25.0 97.0 9.0 800.0 9.0 78.0 CENTER OF GRAVITY Model: UAT80C 830.0 2.0 70.0 965.0 CONTROL BOX 630.0 8.0 65 350.0 50.0 82.5 800.0 82.5 390.0 988.0 25.0 97.0 78.0 50.0 25.0 700.0 9.0 800.0 9.0 CENTER OF GRAVITY

OUTLINE AND DIMENSIONS Model: UAT20C 05.0 58.0 60.0 677.0 076.0 677.0 20.0 20.0 2030.0 8.0 5.0 20.0 9.0 25.0 650.0 38.0 768.0 25.0 56.0 076.0 56.0 98.0 965.0 905.0 7.0 672.0 7.0 6.0 99.0 8.0 690.0 CONTROL BOX 200 768.0 70 8.0 988.0 50.0 25.0 202.0 770.0 58.0 672.0 58.0 CENTER OF GRAVITY Model: UAT300C 07.0 88.0 000.0 CONTROL BOX 230.0 50.0 37.0 770.0 2.0 62.0 20.0 58.0 CENTER OF GRAVITY 2

INSTALLATION MANUAL This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons. This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. English SAFETY PRECAUTIONS! WARNING! CAUTION Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. All field wiring must be installed in accordance with the national wiring regulation. Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram. The unit must be GROUNDED to prevent possible hazard due to insulation failure. All electrical wiring must not touch the refrigerant piping, or any moving parts of the fan motors. Confirm that the unit has been switched OFF before installing or servicing the unit. Disconnect from the main power supply before servicing the air conditioner unit. DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fire hazards. Keep the indoor and outdoor units, power cable and transmission wiring, at least m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than m away}. Please take note of the following important points when installing. Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates around the unit, it may cause fire ignition. Ensure that drainage piping is connected properly. If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture. Do not overcharge the unit. This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor. Ensure that the unit s panel is closed after service or installation. Unsecured panels will cause the unit to operate noisily. Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places. Before turning off the power supply, set the remote controller s ON/OFF switch to the OFF position to prevent the nuisance tripping of the unit. If this is not done, the unit s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user. Do not operate any heating apparatus too close to the air conditioner unit. Don t use joined and twisted wires for incoming power supply. The equipment is not intended for use in a potentially explosive atmosphere. NOTICE Disposal Requirement Dismantling of the unit, treatment of the refrigerant, oil and other parts must be done in accordance with the applicable legislation. 3

REFRIGERANT CIRCUIT DIAGRAM Model: UAT50/80/20/300C No Item Description Compressor 2 High Pressure Switch 3 Access Valve Outdoor Heat Exchanger 5 Indoor Heat Exchanger 6 Filter Dryer 7 Thermal Expansion Valve (TXV) 8 Low Pressure Switch 9 Subcool Circuit (Applicable to UAT50C (only) HEADER IN 3 HEADER 2 3 8 5 HEADER OUT Thermal Expansion Valve Sensor Bulb DISTRIBUTOR 9 3 6 7 Note: UAT50/80/20/300C consists of 2 circuits in the system.

INSTALLATION OF THE UNIT (A) Location For Installation Install the unit in such way that air distributed by the unit cannot be drawn in again (as in the case of short circuit of discharge air). Allow sufficient space for maintenance around the unit. When two or more units are installed in a location, they must be positioned such that one unit will not be taking the discharge air from another unit. Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or air discharge. The location must be well ventilated, so that the unit can draw and distribute plenty of air. The unit is recommended to install in:- A place capable of bearing the weight of the unit and isolating noise and vibration. A place where has adequate drainage. A place where the unit will not be buried in snow. A place where air outlet port is not exposed to strong wind. A place where the air discharge and operating sound level will not annoy the neighbours. The location where it is not accessible by general public. English (B) Duct Construction This unit are equipped with supply and return air openings. Duct connection to the unit should be made with duct flanges and secured directly to the air openings with flexible duct connectors to avoid normal noise transmission. To prevent air leakage, all duct seams should be sealed. Ducts in the spaces that not air-conditioned, must be insulated. Ducts exposed to the outside must be weather proofed. Ducts that entering building through the roof, the entering should be sealed with weather stripping to prevent rain, sand, dust etc, from entering the building. Correct size of filter must be installed at the return air duct. (C) Unit Lifting Holes at corners of the unit base are used for unit lifting purpose. The spreader bar shall be slightly wider than the unit width. The insulation should be added at corners of the chain to prevent the damage of the panel when lifting. Note: Unit shown in diagram is UAT300C. Other models will follow the same method in lifting. Spreader bar Lifting beam Chain! CAUTION Do not install the unit at altitude over 2000m Lifting holes for shackle ( corners) 5

(D) Drain Piping A " MPT condensate drain fitting is provided. The drain pipe can be led out at the front side. The drain pipe must be provided with a trap on the outside of the unit and also installed at an incline for proper drainage, as shown in the right. To prevent condensate formation and leakage, provide the drain pipe with insulation to safeguard against sweating. Upon completion of piping work, check that there is no leakage and that the water drains off properly. The drain piping should have a drain trap. A 70mm B 2C C 2 X ESP C A B Drain piping Drain trap Note: ESP = External Static Pressure Drain trap for condensate The drain pipe should extend below this level. (E) Space Required Around Unit Refer diagram below for the space required around the unit. Note that:- (a) All dimensions shown are in mm. (b) All space value shown are minimum clearance required for the unit. (c) Unit shown in the diagram is UAT300C. Other models shall follow the same clearance. Evaporator coil & motor service, Air filter service 200 Condenser air inlet 200 Condenser air inlet 3000 Condenser air outlet Electrical control circuit service & compressor service Condenser air inlet Evaporator coil, air filter service 200 Condenser air inlet 6

PHYSICAL DATA Description Model UAT50C UAT80C UAT20C UAT300C Refrigerant R22 Refrigerant charge kg.6/.6 6.0/6.0 8.0/8.0 0.6/0.6 Evaporator air flow CFM 600 6500 7900 8700 L/S 27 3068 3728 06 External static pressure mmaq 2.5 5 20 25 Pa 23 7 96 25 Condenser air flow CFM 9900 3800 2230 2500 L/S 672 653 5772 09 Control Mechanical Controller/Sequential Controller Compressor (Type/Quantity) Scroll/2 Air filter (Type/Quantity) Washable Saranet/2 Air filter dimension (L x W x T) mm 895 x 685 x 83 x 760 x 00 x 750 x English ELECTRICAL DATA Description Model UAT50C UAT80C UAT20C UAT300C Power supply V/Ph/Hz 380-5/3N~/50 Max continuous current (Comp) A 20.0/20.0 2.2/2.2 3.0/3.0 2.0/35.0 Full load current (FLA, Comp) A 3.7/3.7 6.8/6.8 22.3/22.3 3.0/25.0 Locked rotor current (LRA, Comp) A 00.0/00.0.0/.0 8.0/8.0 7.0/0.0 *Min. circuit amps, MCA A 8.0 57.0 72.5 85.0 *Max. fuse amps, MFA A 63.0 63.0 80.0 00.0 WIRE CONNECTION All electrical work must be carried out by qualified electrician and accordance with local supply requirement and associate regulation. Before connecting the wire, consult the electric power company of jurisdiction. () The entire wiring diagram of unit a b PE a. Power supply d. Unit c d g e f b. Main switch/fuse (field supply) c. Power supply wiring for unit e. Remote control/thermostat f. Connection wiring for unit & remote controller g. Earth 7

(2) Wiring connection to unit Route the power supply wires and control wire through the holes in the unit. Remove the service panels and connect the units power supply wires to terminal block inside the control box, as shown. Make use of push releasable cable ties which are located at the bottom of control box to hold the power supply wires properly Model: UAT50/80/20/300C Terminal block CONTROL BOX Terminal block Power cable Control wire Note: While installing the circuit breaker onto the unit, make sure that the screws do not damage the components (e.g. coil) inside the unit. (3) Wiring Example And Selection Of Circuit Breaker Model Power cable (mm 2 ) Breaker capacity(a) Over current protection switch (A) Earth cable (mm 2 ) UAT50C 6 8 63 6 UAT80C 25 57 63 25 UAT20C 35 72.5 80 35 UAT300C 35 85 00 35 Note: A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in fixed wiring in accordance with local and national legislation. The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse. Fix the power supply wiring to control module. Connect control wiring to control terminal block through the control box s hole. Earth wiring must be connected. The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in protective tube. 8

N R U S V T W N N F2H N N R S T U V W! WARNING Before working in this unit, isolate it from the power supply. Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate requirement of the local wiring code. English Observe the notes mentioned below when wiring to the terminal block. Precautions to be taken for power supply wiring. (Use a round crimp-style terminal for connection to the terminal block. In case it cannot be used due to unavoidable reasons, be sure to observe the following instruction.)! CAUTION Round crimp-style terminal Stranded wire When connecting the connection wires to the terminal block using a single core wire, be sure to perform curling. Problems with the work may cause heat and fires. Strip wire end to this point. Good Excessive strip length may cause electrical shock or leakage. Wrong Stripping wire at terminal block Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.! WARNING Transmission wire must be routed at least 50mm away from the power cable. Transmission wire should be a shielded wire. () Arrangement of terminal blocks and components for controller are shown as below: (a) Mechanical Control Model : UAT50C L L2 L3 N 3 6 8 5 7 R S T F36A F35A C FZ CZ CZ2 F2H 2 3 5 6 C2 No. Item Description Contactor 2 Capacitor 3 Phase Protector Terminal Block 5 Relay 6 Fuse 7 Transformer 8 Timer 9 Control Module 2 2 9

LIVE OUT FAN 3 OUT FAN OUT FAN 2 OUT FAN NEUTRAL N N F3H R S T U V W 2 6 DS DS3 DS2 DS ROOM 95 98 96 N R ID ID3 ID2 ID N N F2H R S T U V W N N F2H N N F3H R S T U V W OUT FAN 3 OUT FAN OUT FAN 2 OUT FAN NEUTRAL DS DS3 DS2 DS ROOM ID ID3 ID2 ID N N N R S T A U V W A2 LIVE OUT FAN 3 OUT FAN R S T U V W 2 6 OUT FAN 2 OUT FAN NEUTRAL 95 98 96 DS R S T A U V W A2 DS3 DS2 DS ROOM ID ID3 ID2 ID Model : UAT80/20C Model : UAT300C 6 5 8 5 6 8 3 2 5 7 3 7 (b) Sequential Control Model : UAT50C 3 6 5 9 COMP COMP 2 COMP 3 COMP IN FAN HEATER HEATER2 WV WV 2 WV 3 WV LIVE S T F3.5A TRANSFORMER L L2 L3 N C C2 2 2 Model : UAT80/20C 6 9 Model : UAT300C 3 6 5 9 3 5 2 NR S T F3.5A L L2 L3 N RESET TRANSFORMER WV WV 3 WV 2 WV HEATER2 HEATER IN FAN COMP COMP 3 COMP 2 COMP NR S T F3.5A TB2 TRANSFORMER WV WV 3 WV 2 WV HEATER2 HEATER IN FAN COMP COMP 3 COMP 2 COMP L L2 L3 N RESET 0

OPERATING RANGE Ensure the operating temperature is within the allowable range, as stated in diagram below: English Outdoor DB temperature ( C) 5 52 9! CAUTION The use of the air conditioner outside the range of working temperature and humidity can result in serious failure. 9. 23 Indoor WB temperature ( C) PHASE PROTECTOR The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase protector operates, and the unit will not start. This device is located in the control box of the outdoor unit. The following table shows the LED indicator light for phase protector under normal operation and fault conditions. Description LED PW (Red) P_R (Yellow) P_S (Yellow) P_T (Yellow) Actions Normal operation - Reverse phase T phase missing S phase missing R phase missing S &T phase missing + Overload + Sensor missing + Switch off the unit. Check the 3 phase wiring. Switch off the unit. Check the 3 phase wiring. Switch off the unit. Check the 3 phase wiring. Switch off the unit. Check the 3 phase wiring. Switch off the unit. Check the 3 phase wiring. High discharge temperature. Check the refrigerant system. Switch off the unit. Plug in sensor. ON OFF Fast Blink Notes:. + indicates additional functions for PP0 phase protector. 2. When R phase missing, no LED or buzzer will indicate the error, but relay 7 and relay 8 will cut off.! WARNING Trouble shooting must be performed by qualified personnel.

SERVICE AND MAINTENANCE Service Parts Maintenance Procedures Air Filter - Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 0 C) with a neutral cleaning detergent. - Rinse the filter well and dry before placing it back onto the unit. - Do not use gasoline, volatile substances or chemicals to clean the filter. - Clean the filter at least once every 2 weeks or more frequently if neccesary. Air filter position. Unit shown in the diagram is UAT300C. Other models shall follow the same method. Remove filter cover for filter service Air Filter Air Filter TROUBLESHOOTING For any enquiries on spare parts, please contact your authorized dealer. If any malfunction of the air conditioner unit is noted, check the following fault conditions and causes for some simple troubleshooting tips. Problem Causes Action Unit does not run. Power failure. Press the [ON/OFF] after power restore. Compressor does not operate in 3 min after unit has started. Fuse blown or circuit breaker tripped. Power supply wiring phase incorrect. Protection against frequent starting. Replace fuse or reset circuit breaker. Modify the wiring phase. Air flow is low. Filter is filled with dust and dirt. Clean the filter. There are some obstacles at the air inlet or Remove obstacles. outlet of the units. Compressor operate continuously. Dirty air filter. Clean the air filter. Temperature setting too low. Wait for 3 minutes for the compressor to start. Reset the temperature. No cool air delivered. Temperature setting too high. Set the temperature lower. If the fault persists, please call your authorized local dealer/serviceman. 2

MEMO

In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language, the English version of this manual shall prevail. The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior notification. Head offi ce: Umeda Center Bldg., 2--2, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan Zandvoordestraat 300, B-800 Oostende, Belgium P.O.Box 867, Galleries, th Floor, Downtown Jebel Ali, Dubai, UAE.