Standard Devices Electronic Alarm Indication Systems ME 3011b
Before connecting and powering this device, please read carefully the manual, and refer to it whenever you have any doubts. This brochure is subject to changes without previous advice.
Table of Contents Contents Page Operation Principle 4 Technical Data 5 Modularity and Arrangements 6 Dimensions 7 Front Display Engraving Signaling Sequences 9 Special Options 10 e.tool ME 3011-view Visualization via Serial Interface 11 Electronic Alarm Indication Systems ME 3011b 3
Operation Principles The alarm annunciators have the main function of safely signaling critical status of installations, aiming at their integrity. They signal acoustically and optically equipment alarms in a standardized way, within the highest ergonomic and cognitive possible standard. It is recommended, in general, to carry out the direct connection of electric field alarm signals to the annunciator, preventing loops through digital automation and control systems. Thus, the necessary operating safety level is achieved. The maximum alarm signal cable length is 600 m (unshielded) or 1000 m (shielded). These maximum values may be strongly reduced in areas of very high electromagnetic fields, for example in the case of open air cable trays within substations. It is, also, of paramount importance to place the signal cables in trays carrying cables with homogeneous voltages. Placing high and low voltage cables in conjunction within the same cable tray may cause serious annunciator malfunctions or even hardware damages. The ME 3011b annunciator, the new member of Mauell annunciator family, keeps one of the most important characteristics of ME 3010b series, which is the modularity of the alarm windows. The processing fundament of the alarm signs is now carried out through last generation micro controllers, with high performance RISC architecture. So, ME 3011b annunciator incorporates all the advantages of a micro processed system, such as configuration of the annunciators main functions through the front keyboard, or also via configuration software for download. This way, the ME 3011b annunciator provides all conventional functions of alarm announcing together with new and advanced communication function in local network and event recording, among others. These functions will be described in details throughout the manual. Alarm Annunciator ME 3011b 4 Electronic Alarm Indication Systems ME 3011b
Technical Data 1 Supply Voltage 1.1 PS-05 Power Supply Standard 24 Vdc ± 20 % 1.2 PS-02 Power Supply Input 19 to 264 Vdc and/or (Option) 90 to 264 Vac Output 24 Vdc/0.75 A 1.3 Special Option PSFD Power Supply Fault Detector for Vdc and/or Vac Note: All power supplies are integrated into the annunciator 2 Inputs 2.1 Alarm Inputs 4 up to 252 Isolation Optical couplers Input Voltages 24, 4, 60, 110/125 Vdc and 110/127, 220 Vac, ± 20 % Input Current 3 ma (typical) Input Filter lower value = 5 ms, programmable in steps of 2.5 ms 2.2 External Push-Button Station 24 Vdc Isolation Opto couplers Functions Sound Acknowledge (HA) Light Acknowledge (LA) Reset (RE) Light Test / Function Test Sleep Mode (SLM) Keyboard OFF (KBOFF) 2.3 Synchronism with GPS and/or Flashing 24 Vdc Isolation Opto couplers 3 Outputs 3.1 Relays 3 freely programmable relays for various functions, e.g., external buzzer, voltage fault, alarm group, etc 3.2 Sound Indication 90 db / 10 cm, 4 khz 3.3 Repeat relays 1 contact for each alarm point, Note: Field voltages over 125 Vdc or Vac for resistive load. Maximale switching voltage 125 Vdc/250 Vac 4 Interfaces 4.1 Communication Standard RS232TTL bi-directional 4.2 Communication RS232C RS232C bi-directional Option Baud rate: 9600, n,, 1 Protocol: Modbus RTU (Slave) or Modbus RTU (Slave)+TS 4.3 Communication RS 45 bi-directional serial communication (configurable) Baud rate: 110 to 19200 Parity: even, odd or none Stop bit: 1 or 2 Protocol: Modbus RTU (Slave) Event Register (Option) 5.1 Events 1000, with time stemp 5.2 Resolution 1 ms, samples 2.5 ms 5.3 Interfaces Rs232C or RS45 5.4 Protocols Mauell or Modbus RTU (slave) -TS 6 Visualization 6.1 Light Indication Back light Led Special Option Back light available in red, yellow, green white and blue colors 5 mm visible red, yellow and green color leds More than 1 color per annunciator 6.2 Flashing frequency Fast: approx. 1.2 Hz Slow: approx. 0.4 Hz 6.3 Windows Dimension 24 mm x 4 mm Back light White translucent modules Led Gray RAL 7032 polycarbonate modules 7 General 7.1 Alarm sequence ISA 1, 1A, 1B, 2A, 2C, 4A; 4AR others on request 7.2 Environment Operation temperature -20 to 55 C Storage temperature -20 to 0 C Relative Humidity 0 to 95 %, without condensation 7.3 Protection class Front IP41 Enclosure IP30 7.4 Isolation 2 kv, 60Hz, 1 min. in compliance with IEC 255.4 7.5 Terminals Terminal connectors (removable) for cables up to 2.5 mm 2 Electronic Alarm Indication Systems ME 3011b 5
Modularity and Arrangements The minimum configuration possible for the annunciator is a central module with 4 alarm points, and dimension of 2v x 4h or 4v x 2h (see shaded portion on lower right corner of diagram below). Expansion modules can be added to this central unit, with 4 or alarm points each, always in 2v x2h or 2v x 4h modularity basis. So the subsequent configurations are, 12, 16, 20, 24, 2 points and so on, up to a maximum of 252 alarm points. The module arrangement follows the diagram below. Enclosure arrangement Nr. of Points Arrangement 4 2v x 4h 2v x 4h 2v x 6h 6v x 2h 12 4v x 4h 2v x h 16 10v x 2h 2v x 10h 12v x 2h 20 6v x 4h 4v x 6h 2v x 12h 24 14v x 2h 2v x 14h 16v x 2h 2 v x 4h 4v x h 2v x 16h 32 1v x 2h 6v x 6h Nr. of Points Arrangement 20v x 2h 36 10v x 4h 4v x 10h 40 22v x 2h 12v x 4h 44 v x 6h 6v x h 4v x 12h 4 26v x 2h 2v x 2h 52 14v x 4h 4v x 14h 56 10v x 6h 6v x 10h 16v x 4h 60 v x h 4v x 16h 6 1v x 4h 6v x 12h 76 20v x 4h 10v x h Nr. of Points Arrangement 4 22v x 4h 24v x 4h 92 12v x h v x 12h 6v x 16h 10 14v x h 116 10v x 12h 124 16v x h v x 16h 140 1v x h 12v x 12h 156 20v x h 10v x 16h 164 14v x 12h 172 22v x h 1 24v x h 16v x 12h 12v x 16h 212 1v x 12h 220 14v x 16h Nr. of Points Arrangement 236 20v x 12h 252 16v x 16h 6 Electronic Alarm Indication Systems ME 3011b
Dimensions 9.5 L = h x 4 + 24.5 A = v x 24 + 24.5 RUN FA ME 3011 T 114 Cutout Table (height v x width h) mm x mm h (x) Points 2 4 6 10 12 14 16 2-52 x 196-52 x 3-52 x 50-52 x 772 4 100 x 100 100 x 196 100 x 292 100 x 3 100 x 44 100 x 50 100 x 676 100 x 772 6 14 x 100 14 x 196 14 x 292 14 x 3-14 x 50-14 x 772 196 x 100 196 x 196 196 x 292 196 x 3-196 x 50-196 x 772 v 10 244 x 100 244 x 196 244 x 292 244 x 3-244 x 50-244 x 772 (y) 12 292 x 100 292 x 196-292 x 3-292 x 50-292 x 772 14 340 x 100 340 x 196-340 x 3-340 x 50-340 x 772 16 3 x 100 3 x 196-3 x 3-3 x 50-3 x 772 1 436 x 100 436 x 196-436 x 3-436 x 50 - - 20 44 x 100 44 x 196-44 x 3-44 x 50 - - 22-532 x 196-532 x 3-532 x 50 - - 24-50 x 196-50 x 3 - - - - Electronic Alarm Indication Systems ME 3011b 7
Front Display Inscriptions 1 Low Relief Engraving 1.1 Back Light Display LB 24 x 4 White Translucent - Code : 3.53.002 Character height = 3 mm Maximum number of characters per line = 19 Maximum number of lines = 4 24 23 ABCM DRFTG MDMCD ABCM 4 5 5 5 24 23 ABCDEFGHJKLMNOPRSTU ABCDEFGHJKLMMMP ABCDEFGHJKLMM 6 6 5.5 47 4 47 4 1.2 LED Display MK 24 x 4 - RAL 7032 color - Code : 3.52.003 Character height = 3 mm Maximum number of characters per line = 15 Maximum number of lines = 4 24 23.5 ABCDEFGHIJKLMNOP ABCDEFHJKLMM ABCDEFGHJKLMNOP ABCDEFG 4 5 5 5 24 23.5 ABCDEFHJKLMMMP ABCDEFGHJKLMM ABCDEFHJKLMMMP 6 6 6 47 4 47 4 Electronic Alarm Indication Systems ME 3011b
Signaling Sequences The ME 3011b can be configured in order to comply with 16 signaling sequences. Among them the most important are the following: ISA-RP 1.1/(ISA-S1.1) ISA-1/(A), ISA-1A/(A-5), ISA-1B/(A-4), ISA-2A/(R-), ISA-2C/(M), ISA-4A/(F1A), ISA-4AR/(F1M) etc. Other sequences can be implemented on request. ALARM SEQUENCE REF ISA ALARM NORMAL ABNORMAL ACKNOWLEDGE BACK TO BACK TO ACKNOWLEDGE RESET SOUND LIGHT NORMAL NORMAL BEFORE SOUND LIGHT ACKNOWLEDGE ISA 1 (A) ISA 1A (A-5) ISA 1B (A-4) LIGHT SOUND LIGHT SOUND LIGHT SOUND ISA 2A LIGHT F F S F F S (R-) ISA 2C (M)default SOUND LIGHT SOUND PRIMARY SIGNAL SEQUENCE (1 st Event) BACK TO NORMAL REF ALARM NORMAL ABNORMAL ACKNOWLEDGE BACK TO NORMAL BEFORE ACKNOWLEDGE RESET ISA ACKNOWLEDGE INITIAL SUBSEQ INITIAL SUBSEQ INITIAL SUBSEQ INITIAL SUBSEQ INITIAL SUBSEQ ISA 4A Light Sound ISA 4R Light Sound LEGEND F = Fast LED Off Siren = Off LED On S = Slow LED intermittent Siren On Electronic Alarm Indication Systems ME 3011b 9
Special Options 1 Light Display with more than one color In this case, the quantity and position for each color must be requested by the customer. For LED Display up to 3 colors in red, yellow or green For Back Light Display up to 5 colors in red, yellow, green, white or blue 1.1 Back Light Socket In this option, the SMD Back Light LED is socket mounted and plugged on the annunciators PCB. It allows to change the indicating light color for the individual alarm points. The socket Back Light LED must be specified at ordering the annunciator, as a special factory option. 2 - ES-00 Empty Slot If the total alarm points amount of the annunciator enclosure is higher than demanded, it is possible to provide empty slots, each with alarm points. The position of the empty slot is defined due to the physical adress of each module, and must attent to the tables below. The empty slot is always the last, following the pointer direction. The empty slots for Back Light are delivered with the translucent Back Light Display and the LED Version with the RAL 7032 Display. 12 24 1 4 3 2 1 24v x 4h Empty Slot 12 24 2 1 7 6 5 4 3 2 1 24v x h Empty Slot 11 22 92 ES-00 11 22 10 1 ES-00 10 20 4 10 20 172 164 9 1 76 9 1 14 156 16 6 16 140 132 7 14 60 7 14 116 124 6 12 52 6 12 10 100 5 10 44 5 10 4 92 4 36 4 76 6 3 6 2 3 6 52 60 2 4 20 2 4 44 36 1 2 12 4 CM-03 1 2 20 2 12 4 CM-03 10 Electronic Alarm Indication Systems ME 3011b
e.tool ME 3011-view Visualization via Serial Interface The e.tool ME3011-view is a ME3011b dedicated software that allows the visualization of the event registers from up to 10 annunciators in one NET. For more information, please consult our Sales Department at info@mauell.com RS232C (option) with 5, 10 or 15 m cables event recording with 1,0 ms resolution with samples each 2,5 ms enhanced maintenance oriented functions advanced communication protocols TCP/IP interface up to 10 annunciators in one NET Electronic Alarm Indication Systems ME 3011b 11
Representatives Germany Helmut Mauell GmbH Am Rosenhügel 1 7 D-42553 Velbert Tel.: +49 (0)20 53 / 1 30 Fax.: +49 (0)20 53 / 1 36 53 Internet: www.mauell.com E-Mail: info@mauell.com For an up-to-date list of all our representatives and branch offices, please visit our homepage: www.mauell.com Representatives and Branch Offices All Over The World: Abu Dhabi U.A.E. Argentina Austria Belgium Brazil Czech Republic Denmark Finland France Great Britain Hungary Iran Korea Kuwait Netherlands Norway Poland Singapore Spain Sweden Switzerland Turkey USA 05.3011.03E07